02/16/2012 HPL-ED2011 V2.0 EN (UX111) 1 / 4 TIMINGRELAYSETR4-70 Partno. ETR4-70-A Articleno. 031888 Program Range ETR4 timing relay, 22.5 mm wide Basic function Timer relays Function Multi-functional On-delayed Off-delayed Fleeting contact on energization Fleeting contact on de-energization Flashing On- and Off-delayed Pulse forming Pulse generating with connection for potentiometer, and two changeover contacts that can be converted to two timed contacts or one non-delayed contact and one timed contact Conventional thermal current Ith A 6 Time range 0.05 s - 100 h Voltage range ULN V 24 … 240 V AC, 50/60 Hz 24 – 240 V DC Terminal marking according to EN 50042 Terminal marking according to EN 50042 Approbationen UL approval Yes CSA approval Yes Product Standards IEC/EN 60947-…; UL 508; CSA-22.2 No. 14-05; CE marking UL File No. E29184 UL CCN NKCR CSA File No. 12528 CSA Class No. 3211-03 NA Certification UL listed, CSA certified Degree of Protection IEC: IP20, UL/CSA Type: - General Standards Standard IEC/EN 61812 VDE 0435 Lifespan, mechanical AC operated Operations x 106 DC operated Operations x 106 Climatic proofing Damp heat, constant to IEC 60068-2-78 Damp heat, cyclic to IEC 60068-2-30 Ambient temperature °C
02/16/2012 HPL-ED2011 V2.0 EN (UX111) 2 / 4 Ambient temperature, storage °C - 45 - + 60 Open °C - 25 - 60 Enclosed °C - 25 - 45 Mounting position As required Mechanical shock resistance (IEC/EN 60068-2-27) Half-sinusoidal shock, 20 ms g Make contact g 4 Degree of protection Terminals IP20 Weight kg 0.1 Terminal capacities mm2 Solid mm2 1 x (0.75 - 2.5) 2 x (0.75 - 1.5) Flexible with ferrule mm2 1 x (0.75 - 2.5) 2 x (0.75 - 1.5) Solid or stranded AWG 1 x (20 - 14) Contacts Rated impulse withstand voltage Uimp V AC 6000 Overvoltage category/pollution degree III/2 Rated insulation voltage Ui V AC 600 Rated operational voltage Ue V AC 440 Safe isolation to VDE 0106 Part 101 and Part 101/A1 between coil and auxiliary contacts V AC 250 between the auxiliary contacts V AC 250 Making capacity AC-14 cos ϕ = 0.3 440 V A 48 AC-15 cos ϕ = 0.3 220 V A 50 DC-11 L/R - 40 ms x Ie 1.1 Breaking capacity AC-14 cos ϕ = 0.3 440 V A 3 AC-15 cos ϕ = 0.3 220 V A 3 DC-11 L/R - 40 ms x Ie 1.1 Rated operational current Ie A AC--14
440 V Ie A 3
220 V (230 V) Ie A 3
Note Making and breaking conditions to DC13, time constant as stated L/R max. 15 ms A 24 V Ie A 1.5 L/R max. 50 ms A 1.2 Conv. thermal current Ith A 6 Short-circuit rating without welding Note When supplied directly from mains or transformer > 1000 VA Max. fuse, make contacts A gG/ gL Max. fuse, break contacts A gG/ gL max. overcurrent protective device, 220/230 V Type FAZ-B4/1-HI Magnetsystems Voltage tolerance x Uc
02/16/2012 HPL-ED2011 V2.0 EN (UX111) 3 / 4 Pick-up voltage x Us Min. pick-up voltage, AC operated x U c 0.85 Pick-up voltage AC operated, max. x U c 1.1 Pick-up voltage DC operated, min. x Uc 0.7 Max. pick-up voltage, DC operated x Uc 1.1 Power consumption Pick-up AC VA 2 Sealing AC VA 2 Pick-up DC W 1.8 Sealing DC W 1.8 Duty factor % DF 100 Maximum operating frequency Ops/ h 4000 Minimum command time AC ms 50 DC ms 30 Repetition accuracy (deviation) % 0.5 Recovery time (after 100% time delay) ms 70 Contact changeover time tu ms 4 TechnicaldataaccordingtoETIM4.0 Number of outputs, delayed, N/O 0 Remote access possible YES Number of outputs, non-delayed, N/O 0 Function off-delayed YES Outputs, reversible delayed/non-delayed YES Type of electric connection Screw connection Number of outputs, non-delayed, N/C 0 Rated control voltage Us at DC V 240 Clock function, starting with pulse, variable YES Voltage type for actuation AC/DC Function flashing, starting with pulse, fixed time YES Function pulse shaping YES Rated control voltage Us at AC 50HZ V 240 Time range s 360000 Number of outputs, non-delayed, change-over contact 2 With semi-conductor output No Suitable only for remote control No Function flashing starting with pause, fixed time YES Plug-in type on auxiliary contact block No Width mm 23 With plug-in socket No Function fleeting contact on energization YES Function star/delta No Rated control voltage Us at AC 60HZ V 240 Function fleeting contact on de-energization YES Function on-delayed YES Height mm 83 Depth mm 103 Function cyclic starting with pause, variable YES Number of outputs, delayed, N/C 0 Number of outputs, delayed, changeover contact 2
02/16/2012 Eaton Industries GmbH http://www.moeller.net/en © 07/2011 by Eaton Industries GmbH HPL-ED2011 V2.0 EN Dimensions Additionalproductinformation(links) AWA2527-1493 (IL04910002Z) Multi-function relay ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/14930202.pdf