V9-T1-5 EATON | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 63
Technical content
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-1 Circuit Protection Circuit Breakers Rotary Disconnect Switches Fuse Blocks and Fuse Holders
1.1 Circuit Breakers
QUICKLAG Type QC Miniature Circuit Breakers—
1.2 Fuse Blocks and Fuse Holders
1.3 Rotary Disconnect Switches
For our complete product offering, see Volume 4—Circuit Protection, CA08100005E and Volume 5—Motor Control and Protection, CA08100006E.
V9-T1-2 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com
1.1 Circuit Protection
Circuit Breaker Selection Guide For our complete product offering, see Volume 4—Circuit Protection, CA08100005E.
Description
Molded Case Circuit Breaker Universal Molded Case Circuit Breakers QUICKLAG® Type QC Miniature Circuit Breakers Page V9-T1-5 Page V9-T1-13 Page V9-T1-19 General Applications Line protection—molded case switch, motor circuit protection (combination tested with Eaton starters and contactors) thermal-magnetic and electronic trip units. Line protection—feeder and branch thermal- magnetic trip unit. Used to provide branch circuit protection in cable-in/out panel or DIN rail mount applications. T echnical Data Maximum current rating 2500A 600A 100A Maximum voltage—AC 690 Vac 480 Vac 240 Vac Maximum voltage—DC 250 Vdc 250 Vdc 80 Vdc Poles 1, 2, 3, 4 1, 2, 3 QC = 1, 2, 3, 4 QCD = 1, 2, 3 QCR/QCF = 1, 2, 3 Max. interrupting capacities See individual catalogs for limitations and back-up protection requirements. Three-pole at 240V E = 200 kA J = 200 kA L = 200 kA Three-pole at 480V E = 100 kA J = 200 kA L = 200 kA Three-pole at 240V G = 25 kA (480/277) F = 25 kA J = 35 kA K = 35 kA L = 35 kA Three-pole at 480V GI = 14 kA (480/277) GD = 22 kA F = 14 kA J = 20 kA K = 20 kA L = 20 kA 65 kA at 240 Vac 5 kA at 80 Vdc Approvals UL ® 489 IEC 60947-2 CE CSA® KEMA-KEUR CCC UL 489CE IEC 60947-2 CE CSA UL 489 CSA 22.2 Environmental Data Humidity Non-condensing 100% relative humidity Non-condensing 100% relative humidity — S h o c k ——— Vibration — — — Operating temperature –20° to 70°C (–4° to 158°F) derating applies –20° to 70°C (–4° to 158°F) derating applies 40°C (104°F) Dielectric strength Below 250A 6 kV Above 250A 8 kV Below 250A 6 kV Above 250A 8 kV 1960 Vac (acc. to UL 489) Insulation resistance 750 Vac 750 Vac — Endurance/life 250A: EG, JG = 8,000 operations 630A: LG = 6,000 operations 250A: Gi = 10,000 operations Fi = 8,000 operations 400A: Ji, Ki, Li = 6,000 operations >10,000 operations Approximate weight E Three-pole—2.88 lbs (1.04 kg) J Three-pole—5.06 lbs (2.30 kg) L Three-pole—12.36 lbs (5.61 kg) G Three-pole—2.10 lbs (0.95 kg) F Three-pole—4.5 lbs (2.0 kg) J Three-pole—12.50 lbs (5.7 kg) K Three-pole—11.50 lbs (5.2 kg) QC Single-pole—0.36 lbs (162.8 g) Two-pole—0.61 lbs (274.9 g) Three-pole—1.14 lbs (518.3 g) QCD Single-pole—0.43 lbs (195.3 g) Two-pole—0.89 lbs (401.9 g) Three-pole—1.34 lbs (605.6 g) QCR Single-pole—0.22 lbs (97.9 g) Two-pole—0.48 lbs (215.8 g) Three-pole—0.70 lbs (315.6 g) QCF Single-pole—0.24 lbs (109.9 g) Two-pole—0.50 lbs (225.2 g) Three-pole—0.74 lbs (335.1 g) Mounting configuration Backpan, plug-in adapter, DIN rail (E) Backpan, DIN rail (G) Panel mount, front mount, 35 mm DIN rail mountable
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-3 1.1Circuit Protection Circuit Breakers Circuit Breaker Selection Guide, continued For our complete product offering, see Volume 4—Circuit Protection, CA08100005E. Miniature Circuit Breakers FAZ UL 1077 Miniature Circuit Breakers— Supplementary Protectors Page V9-T1-25 Page V9-T1-28 General Applications Used to provide branch circuit protection in cable- in/out DIN rail mount applications. Used to provide overcurrent protection where branch protection (for example UL 489 MCCB) is already provided or not required. Replacement for fuses used as supplementary protectors. Te c h n i c a l Da t a Maximum current rating 40A 63A Maximum voltage—AC 480/277 Vac (240/415 Vac IEC) 480/277 Vac Maximum voltage—DC 48 Vdc 65 Vac Single-pole
130 Vac Two-pole
Poles 1, 2, 3 1, 2, 3 Max. interrupting capacities See individual catalogs for limitations and back-up protection requirements. 10 kA UL/CSA; 15 kA IEC/EN 60947-2 IEC 240/415V 10 kA UL/CSA 120V 10 kA 240V 10 kA 277V 6 kA 480V 6 kA Approvals UL 489 CE; IEC/EN 60947-2 CSA 22.2 UL 1077 CE; IEC/EN 60947-2; IEC/EN 60898 CSA 22.2 235 Environmental Data Humidity Acc. IEC 60068-2 (25° to 55°C/ 77° to 131°F, 90–95% RH) Shock Acc. IEC 60068-2-27 (40g half sine wave for 10 ms—3 axes) (15g half sine wave for 20 ms—3 axes) Vibration Acc. to IEC 60068-2-6 5–100 Hz/1.0 mm/0.7g (3 axes) Operating temperature 30°C (86°F) — Dielectric strength 1960 Vac (acc. to UL 489) — Insulation resistance 100M ohms at 500 Vdc — Endurance/life >20,000 operations — Approximate weight Single-pole—0.27 lbs (121.0g) Two-pole—0.53 lbs (242.0g) Three-pole—0.80 lbs (363.0g) Single-pole—0.26 lbs (120.0g) Two-pole—0.54 lbs (244.9g) Three-pole—0.83 lbs (376.5g) Mounting contribution 35 mm DIN rail mountable 35 mm DIN rail mountable
V9-T1-4 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com Circuit Breaker Selection Guide, continued For our complete product offering, see Volume 4—Circuit Protection, CA08100005E. Low Voltage Power Breakers Magnum Low Voltage Power Breakers Page V9-T1-33 Page V9-T1-36 General Applications Solution for where space is at a premium or when equipment dimensions are critical when upgrading or retrofitting current systems. Offering the power and performance of a power breaker in the compact size of a molded case breaker. With its reduced weight and compact dimensions, you can mount two times as many feeder breakers and reduce the overall enclosure density up to 50%. Enables comprehensive solutions to meet and exceed the unique and wide-ranging requirements of today’s global power distribution systems. Designed and engineered for ultimate custom configuration and application flexibility in metal enclosed switchgear and power distribution enclosures. T echnical Data Maximum current rating 630–1600A 800–6300A Maximum voltage—AC 220–690 Vac Up to 690 Vac Maximum voltage—DC — — Poles 3, 4 3, 4 Max. interrupting capacities See individual catalogs for limitations and back-up protection requirements. 65 kAIC at 480 Vac Max. withstand capacities 42 kAIC 200 kA at 480 Vac Max. withstand capacities 100 kAIC CL fuseless 200 kA at 635 Vac with integral limiters Approvals UL 1006 Component UL 489 Component IEC 60947-2 UL 1066 IEC 60947-2 KEMA Environmental Data Humidity — — Shock — — Vibration — — Operating temperature –25° to 70°C –25° to 70°C Dielectric strength — — Insulation resistance — — Endurance/life 10,000 electrical operations 20,000 mechanical operations Approximate weight Three-pole breaker + cassette—85 lbs (39 kg) Three-pole breaker—53 lbs (24 kg) Four-pole breaker + cassette—104 lbs (47 kg) Four-pole breaker—67 lbs (30 kg) Mounting configuration Rear-connected, front-connected, surface mounting, mounting bracket, fixed, drawout breaker with cassette Fixed or drawout with cassette rear-connected, front- connected
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-5 1.1Circuit Protection Circuit Breakers Series G Molded Case Circuit Breakers Features
- Field-fit accessories
- Common accessories through 630A
- Space-saving footprint
- High-performance current limiting designs up to 200 kAIC at 480V
- Global ready: UL, CSA, CE, IEC, KEMA-KEUR listings
- Complete breaker includes frame, trip unit, standard terminals and mounting hardware Catalog Number Selection Series G® Molded Case Circuit Breakers EG Frame Notes 1 Available only as 125 and 160A sizes. 2 Is not UL rated. Frame E Performance 600Y/347 480 415 240 B — 1 81 82 5 E 18 25 25 35 S 22 35 40 85 H 25 65 70 100 C 35 100 100 200 K Molded case switch 1 Standard/Application G = IEC/CE/UL/CSA Amperes 016 2 015 020 025 030 032 2 035 040 045 050 060 063 2 070 080 090 100 110 125 Number of Poles 1 = One 2 = Two 3 = Three 4 = Four—Neutral 0% Protected 7 = Four—Neutral 100% Protected Trip Unit FF = Fixed fixed AF = Adjustable thermal fixed magnetic KS = Molded case switch E G H 3 015 FF G Terminations/Hardware Terminals Mounting Hardware M = Metric end caps E = Imperial end caps G = Line/load standard B = Bolt-on Metric Imperial Metric
V9-T1-6 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com 1 A = Arc reduction, L = Long, S = Short, I = Instantaneous, G = Ground. J G S 3 250 FA G C Frame J Performance 600 480 415 240 E 18 25 25 65 S 18 35 40 85 H 25 65 70 100 C 35 100 100 200 U 50 150 150 200 X 50 200 200 200 K Molded case switch Standard/Application G = IEC/CE/UL/CSA Amperes 050 070 080 090 100 125 150 160 175 200 225 250 Trip Unit AA = Adjustable thermal Adjustable magnetic FA = Fixed thermal Adjustable magnetic KS = Molded case switch 33 = 310+ electronic LS 32 = 310+ electronic LSI 35 = 310+ electronic LSG 36 = 310+ electronic LSIG NN = Frame only (no trip) Terminations/Hardware Terminals Mounting Hardware M = Metric end caps E = Imperial end caps G = Line/load standard Metric Imperial Metric Rating Blank = 80% rated C = 100% rated Number of Poles 2 = Two 3 = Three 4 = Four—Neutral 0% protected 8 = Four—Neutral 0–60% protected 9 = Four—Neutral 100% protected L G S 3 600 FA G C Frame L Performance 600 480 415 240 E 18 35 35 65 S 25 50 50 85 H 35 65 70 100 C 50 100 100 200 U 65 150 150 200 X 65 200 200 200 K Molded case switch Standard/Application G = IEC/CE/UL/CSA Amperes 250 300 350 400 500 600 630 Number of Poles 3 = Three 4 = Four—Neutral 0% protected 6 = Four—Neutral 60% protected 7 = Four—Neutral 100% protected 8 = Four—Neutral 0–60% protected 9 = Four—Neutral 0–100 protected Trip Unit 1 AA = Adjustable thermal Adjustable magnetic FA = Fixed thermal Adjustable magnetic KS = Molded case switch 33 = 310+ electronic LS 32 = 310+ electronic LSI 35 = 310+ electronic LSG 36 = 310+ electronic LSIG 38 = 310+ electronic ALSI 39 = 310+ electronic ALSIG NN = Frame only (no trip) Terminations/Hardware Terminals Mounting Hardware M = Metric end caps E = Imperial end caps G = Line/load standard W = Without terminals Metric Imperial Metric Rating Blank = 80% rated C = 100% rated
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-7 1.1Circuit Protection Circuit Breakers Product Selection Series G Molded Case Circuit Breakers Approximate Dimensions are in Inches EG Frame JG Frame LG Frame Note 1 16, 32, 63A are not UL listed ratings. Maximum Continuous Amperes at 40°C 1 Three-Pole 3.00 W x 5.50 H x 2.99 D Maximum Continuous Amperes at 40°C Three-Pole 3.00 W x 5.50 H x 2.99 D Fixed Thermal Fixed Magnetic Fixed Thermal Fixed Magnetic IC Rating: 25 kAIC at 415 and 480 Vac IC Rating: 70 kAIC at 415 Vac, 65 kAIC at 480 Vac
15 EGE3015FFG 15 EGH3015FFG
20 EGE3020FFG 20 EGH3020FFG
25 EGE3025FFG 25 EGH3025FFG
30 EGE3030FFG 30 EGH3030FFG
35 EGE3035FFG 35 EGH3035FFG
40 EGE3040FFG 40 EGH3040FFG
45 EGE3045FFG 45 EGH3045FFG
50 EGE3050FFG 50 EGH3050FFG
60 EGE3060FFG 60 EGH3060FFG
70 EGE3070FFG 70 EGH3070FFG
80 EGE3080FFG 80 EGH3080FFG
90 EGE3090FFG 90 EGH3090FFG
100 EGE3100FFG 100 EGH3100FFG
125 EGE3125FFG 125 EGH3125FFG
Three-Pole 4.13 W x 7.00 H x 3.57 D Maximum Continuous Amperes Three-Pole 4.13 W x 7.00 H x 3.57 D Magnetic Range Fixed Thermal Adjustable Magnetic Magnetic Range Fixed Thermal Adjustable Magnetic IC Rating: 25 kAIC at 415 and 480 Vac IC Rating: 70 kAIC at 415 Vac, 65 kAIC at 480 Vac 70 350–700 JGE3070FAG 70 350–700 JGH3070FAG 90 450–900 JGE3090FAG 90 450–900 JGH3090FAG 100 500–1000 JGE3100FAG 100 500–1000 JGH3100FAG 125 625–1250 JGE3125FAG 125 625–1250 JGH3125FAG 150 750–1550 JGE3150FAG 150 750–1550 JGH3150FAG 175 875–1750 JGE3175FAG 175 875–1750 JGH3175FAG 200 1000–2000 JGE3200FAG 200 1000–2000 JGH3200FAG 225 1125–2250 JGE3225FAG 225 1125–2250 JGH3225FAG 250 1250–2500 JGE3250FAG 250 1250–2500 JGH3250FAG Ampere Rating Three-Pole 5.48 W x 10.13 H x 4.09 D Ampere Rating Three-Pole 3.00 W x 5.50 H x 2.99 D Fixed Thermal Adjustable Magnetic Fixed Thermal Adjustable Magnetic IC Rating: 35 kAIC at 415 and 480 Vac IC Rating: 70 kAIC at 415 Vac, 65 kAIC at 480 Vac
250 LGE3250FAG 250 LGH3250FAG
300 LGE3300FAG 300 LGH3300FAG
350 LGE3350FAG 350 LGH3350FAG
400 LGE3400FAG 400 LGH3400FAG
500 LGE3500FAG 500 LGH3500FAG
600 LGE3600FAG 600 LGH3600FAG
V9-T1-8 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com Series G Motor Circuit Protector Features
- Instantaneous only protector
- Designed for use in combination with motor starters
- Adjustable to motor FLA
- UL recognized component, File E7819 motor circuit protectors Product Selection Series G Motor Circuit Protectors EG Frame—480 Vac, 600Y/347 Vac Maximum Notes 1 Motor FLA ranges are typical. The corresponding trip setting is at 13 times the minimum FLA value shown. Where a 13 times setti ng is required for an intermediate FLA value, alternate cam settings and/or MCP ratings should be used. 2 For DC applications, actual trip levels are approximately 40% higher than values shown. 3 Settings above 10 x In are for special applications, where the ampere rating of the disconnecting means cannot be less than 115% of the motor full lo ad ampere rating. Continuous Amperes Cam Setting Motor Full Load Current Amperes 1 MCP Trip Setting MCP Catalog Number Continuous Amperes Cam Setting Motor Full Load Current Amperes MCP Trip Setting MCP Catalog Number 3 A 0.69–0.91 9 HMCPE003A0C 50 A 11.5–15.2 150 HMCPE050K2C B 1.1–1.3 15 B 19.2–22.9 250 C 1.6–1.7 21 C 26.9–30.6 350 D 2.0–2.2 27 D 34.6–38.3 450 E 2.3–2.5 30 E 38.4–42.1 500 F 2.6–2.8 33 F 42.2–43.5 550 7 A 1.5–2.0 21 HMCPE007C0C 70 A 16.1–30.6 210 HMCPE070M2C B 2.6–3.1 35 B 26.9–32.2 350 C 3.7–3.9 49 C 37.6–42.9 490 D 4.8–5.2 63 D 48.4–53.7 630 E 5.3–5.7 70 E 53.8–59.1 700 F 5.8–6.1 77 F 59.2–60.9 770 15 A 3.4–4.5 45 HMCPE015E0C 100 A 23.0–30.6 300 HMCPE100R3C B 5.7–6.8 75 B 38.4–46.0 500 C 8.0–9.1 105 C 53.8–61.4 700 D 10.4–11.4 135 D 69.2–76.8 900 E 11.5–12.6 150 E 76.9–84.5 1000 F 12.7–13.0 165 F 84.6–87.0 1100 30 A 3.9–9.1 90 HMCPE030H1C 100 A 38.4–46.0 500 HMCPE100T3C B 11.5–13.7 150 B 57.6–65.2 750 C 16.1–18.3 210 C 76.9–84.5 1000 D 20.7–22.9 270 D 3 1250 E 23.0–25.2 300 E 3 1375 F 25.3–26.1 330 F 3 1500
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-9 1.1Circuit Protection Circuit Breakers JG Frame—600 Vac Maximum, 250 Vdc Maximum LG Frame—600 Vac Maximum, 250 Vdc Maximum Continuous Amperes MCP Trip Range Amperes MCP Catalog Number 250 500–1000 HMCPJ250D5L 625–1250 HMCPJ250F5L 750–1500 HMCPJ250G5L 875–1750 HMCPJ250J5L 1000–2000 HMCPJ250K5L 1125–2250 HMCPJ250L5L 1250–2500 HMCPJ250W5L Continuous Amperes MCP Trip Range Amperes MCP Catalog Number 600 1250–2500 HMCPL600L6G 1500–3000 HMCPL600N6G 1750–3500 HMCPL600R6G 2000–4000 HMCPL600X6G 2250–4500 HMCPL600Y6G 2500–5000 HMCPL600P6G 3000–6000 HMCPL600M6G
V9-T1-10 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com Series G Motor Protector Breakers Features
- Eliminates need for separate overload relay
- Can be used with contactor to eliminate need for overload relay and still create manual motor control
- Meets requirement for motor branch protection, including:
- Disconnecting means
- Branch circuit short-circuit protection
- Overload protection
- UL 489 listed, IEC 60947-02 rated
- Phase unbalance, phase loss protection and high load alarm
- Optional pre-detection trip relay Product Selection Series G Motor Protector Breakers For pre-trip alarm option, order Style Number 5721B31G02. JG Frame Motor Protector Circuit Breakers, 250A Maximum Rated Current LG Frame Motor Protector Circuit Breakers, 630A Maximum Rated Current Note 1 630A is not a UL listed rating. 600A is the maximum UL or CSA rating for LG breaker. Continuous Amperes 35 kAIC Catalog Number 65 kAIC Catalog Number
50 JGMPS050G JGMPH050G
100 JGMPS100G JGMPH100G
160 JGMPS160G JGMPH160G
250 JGMPS250G JGMPH250G
250 LGMPS250G LGMPH250G
400 LGMPS400G LGMPH400G
600 LGMPS600G LGMPH600G
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-11 1.1Circuit Protection Circuit Breakers Accessories Field Fit Kit Catalog Numbers Multiwire Connectors Ordering Information (Package of 3) High SCCR ratings are available for Power Distribution blocks with Series G MCCBs. See Ta b 6. T erminal Shields Interphase Barriers (Package of 2) Flex Shaft Handle Mechanisms Universal Direct Handle Mechanisms Notes 1 Part number for JG and LG is ALM1M1BJPK. 2 Part number for JG and LG is ALM2M2BJPK. 3 Part number for JG and LG is AUXALRMJPK. 4 110–125 Vdc, 50/60 Hz. 5 380–600 Vdc, 50/60 Hz. Description Pole Location Frame— EG, JG and LG Alarm Lockout Make/break Right ALM1M1BEPK 1 2 make/2 break Right ALM2M2BEPK 2 Auxiliary Switch 1A, 1B Right AUX1A1BPK 2A, 2B Right AUX2A2BPK Auxiliary Switch/Alarm Lockout —R i g h t AUXALRMEPK 3 Shunt T rip—Standard
120 Vac Left SNT120CPK 4
240 Vac Left SNT120CPK 4
12 Vdc Left SNT012CPK
24 Vdc Left SNT060CPK
48 Vdc Left SNT060CPK
380–600 Vac Left SNT480CPK 5 Undervoltage Release Mechanism 110–127 Vac Left UVR120APK 208–240 Vac Left UVR240APK
24 Vac Left UVR024APK
24 Vdc Left UVR024DPK
48–60 Vdc Left UVR048DPK
12 Vac/Vdc Left UVR012CPK
48–60 Vac Left UVR048APK
120 Vdc Left UVR125DPK
220–250 Vdc Left UVR250DPK 380–500 Vac Left UVR480APK 525–600 Vac Left UVR600APK Maximum Amperes Wires per Terminal Wire Size Range AWG Cu Frame Kit Catalog Number 125 3 14–2 EG 3TA125E3K 125 6 14–6 EG 3TA125E6K 250 3 14–2 JG 3TA250FJ3 250 6 14–6 JG 3TA250FJ6 Alarm Lockout Auxiliary Switch Shunt Trip Undervoltage Release Mechanism Location Number of Poles Frame IP30 Protection Catalog Number Line 3 EG EFTS3K Line 4 EG EFTS4K Line or load 2, 3 JG FJTS3K Line or load 4 JG FJTS4K Number of Poles Frame Catalog Number 3 or 4 EG EIPBK 3J G FJIPBK 4J G FJIPBK4 3 or 4 LG IPB3 Flexible Shaft Length in ft (m) Breaker Frame 4 (1.2) Catalog Number 7 (2.1) Catalog Number EG EHMFS04 EHMFS07 JG JHMFS04 JHMFS07 LG LHMFS04 LHMFS07 Frame With Interlock Catalog Number Without Interlock Catalog Number Black Handle Color EG EHMCCBI EHMCCB JG JHMCCBI JHMCCB LG LHMCCBI LHMCCB Red Handle Color EG EHMCCRI EHMCCR JG JHMCCRI JHMCCR LG LHMCCRI LHMCCR Flex Shaft Handles Universal Direct Handle Mechanism
V9-T1-12 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com High Performance Rotary Handle Mechanisms (Complete Kit Includes Handle, Shaft and Mechanism) External Accessories Notes 1 Compatible with three-pole and four-pole EG breakers only. 2 Provision only. 3 See Volume 4—Circuit Protection, CA08100005E, Tab 2, for bolt projection dimensions. 4 Castell bolt mounting hole must be 10 mm. 5 Requires two breakers. Color Rating Type UL IP EG Frame 1 Catalog Number JG Frame Catalog Number LG Frame Catalog Number Black/blue 1/12/3R 20/54/55 EGHMVD06B JGHMVD06B LGHMVD06B EGHMVD12B JGHMVD12B LGHMVD12B EGHMVD24B JGHMVD24B LGHMVD24B Red/yellow 1/12/3R 20/54/55 EGHMVD06R JGHMVD06R LGHMVD06R EGHMVD12R JGHMVD12R LGHMVD12R EGHMVD24R JGHMVD24R LGHMVD24R Black/blue 4/4X 66 EGHMVD06BX JGHMVD06BX LGHMVD06BX EGHMVD12BX JGHMVD12BX LGHMVD12BX EGHMVD24BX JGHMVD24BX LGHMVD24BX Red/yellow 4/4X 66 EGHMVD06RX JGHMVD06RX LGHMVD06RX EGHMVD12RX JGHMVD12RX LGHMVD12RX EGHMVD24RX JGHMVD24RX LGHMVD24RX Description Fit Type Frame EG JG LG Non-padlockable handle block Field EFHB — — Padlockable handle block Field EFPHB — — Padlockable handle block off-only Field EFPHBOFF FJPHBOFF LBHPOFF Padlockable handle lock hasp Field EFPHL FJPHL LPHL Padlockable handle lock hasp off-only Field EFPHLOFF FJPHLOFF LPHLOFF Kirk key interlock kit 23 Field — KYKJG KYKLG Castell key interlock kit 34 Field — CTKJG CTKLG Slide bar interlock 5 Field EFSBI FJSBI LGSBI Walking beam interlock Three-pole EG3WBI JG3WBI LG3WBI Four-pole EG4WBI JG4WBI LG4WBI
125 Vdc MOPEG240C MOPJG240C MOPLG240C
Plug-in adapters Three-pole PAD3E PAD3J PAD3L Four-pole PAD4E PAD4J PAD4L Rear connecting studs Field EFRCSDL FJRCSDL 3P–LRCS3WK EFRCSDS FJRCSDS 4P–LRCS4WK EFRCSWL FJRCSWL — EFRCSWS FJRCSWS — Rotary Handle Mechanisms
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-13 1.1Circuit Protection Circuit Breakers Universal Molded Case Circuit Breakers Features
- Universal design for both NEMA® (UL 489) and IEC (IEC 947-2) standards
- Suitable for 50°C application
- Factory-sealed thermal magnetic trip unit
- Standard interrupting ratings
- Includes mounting hardware and terminals Catalog Number Selection Universal Molded Case Circuit Breakers Universal Molded Case Frame Size Gi = Gi Frame Fi = Fi Frame Ji = Ji Frame Ki = Ki Frame Li = Li Frame Number of Poles Gi Frame 1 = Single-pole 2 = Two-pole 3 = Three-pole Fi Frame 2 = Two-pole 3 = Three-pole Ji Frame 3 = Three-pole Ki Frame 3 = Three-pole Li Frame 3 = Three-pole Ampere Rating Gi Frame 015 = 15 amp 020 = 20 amp 030 = 30 amp 040 = 40 amp 050 = 50 amp 060 = 60 amp 070 = 70 amp 080 = 80 amp 100 = 100 amp 125 = 125 amp Fi Frame 015 = 15 amp 020 = 20 amp 030 = 30 amp 040 = 40 amp 050 = 50 amp 060 = 60 amp 070 = 70 amp 080 = 80 amp 100 = 100 amp 125 = 125 amp 150 = 150 amp 160 = 160 amp 175 = 175 amp 200 = 200 amp 225 = 225 amp Ji Frame 250 = 250 amp Ki Frame 300 = 300 amp 350 = 350 amp 400 = 400 amp Li Frame 500 = 500 amp 600 = 600 amp 630 = 630 amp G 2 070i
V9-T1-14 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com Universal Molded Case Circuit Breakers Three-Pole Approximate Dimensions are in Inches Universal G Frame Universal F Frame Universal J Frame Universal K Frame Universal L Frame Note 1 Metric mounting hardware. Description Amperes Catalog Number 1
3 W x 4-7/8 H x 2-13/16 D (optional DIN rail kit available
catalog number GDIN, package of ten)
15 Gi3015
20 Gi3020
25 Gi3025
30 Gi3030
35 Gi3035
40 Gi3040
45 Gi3045
50 Gi3050
60 Gi3060
4-1/8 W x 6 H x 3-3/8 D 15 Fi3015L
20 Fi3020L
30 Fi3030L
35 Fi3035L
40 Fi3040L
50 Fi3050L
60 Fi3060L
70 Fi3070L
80 Fi3080L
90 Fi3090L
100 Fi3100L
125 Fi3125L
150 Fi3150L
175 Fi3175L
200 Fi3200L
225 Fi3225L
Voltage Interrupting Rating 380–415 18/5K 480/277 14K Voltage Interrupting Rating 415 18/9K 480 20K Description Amperes Catalog Number 1 4-1/8 W x 10 H x 4-1/16 D 225 Ji3225L
250 Ji3250L
5-1/2 W x 10-1/8 H x 4-1/16 D 300 Ki3300L
350 Ki3350L
400 Ki3400L
8-1/4 W x 10-3/4 H x 4.37 D 500 Li3500
600 Li3600
Voltage Interrupting Rating 415 25/13K 480 20K Voltage Interrupting Rating 415 25/13K 480 20K Voltage Interrupting Rating 415 25/13K 480 20K
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-15 1.1Circuit Protection Circuit Breakers Accessories Internal Accessories Auxiliary Switch (Right-Pole Mounted) Bell Alarm (Right-Pole Mounted) Shunt Trip (Left-Pole Mounted) UVR (Left-Pole Mounted) Add This Suffix to Catalog NumberConfiguration Add This Suffix to Catalog Number Configuration Add This Suffix to Catalog Number Voltage Range Voltage Range Add This Suffix to Catalog Number Universal G Frame 1NO/1NC A3 1 make/1 break B3 24 Vac S7 24 Vac 50/60 Hz T2 2NO/2NC A6 120 Vac S1 48 Vac 50/60 Hz T3 If both an auxiliary switch and bell alarm are required, add B13 to the catalog number (right-pole mounted). Auxiliary switch and bell alarm are 240V rated.
240 Vac S2 60 Vac 50/60 Hz T4
12 Vdc S3 120 Vac 50/60 Hz T1
24 Vdc S4 240 Vac 50/60 Hz T8
220 Vac 50 Hz T7
440 Vac 50 Hz T11
480 Vac 60 Hz T12
1NO/1NC A06 1 make/1 break B06 12–24 Vac/Vdc S02 12 Vac U02 2NO/2NC A13 48–127 Vac or 48–60 Vdc S06 24 Vac U06 If both an auxiliary switch and bell alarm are required, add C05 to the catalog number (right-pole mounted). Auxiliary switch and bell alarm are 600V rated.
48 Vac/Vdc U38
208–380 Vac or 110–127 Vdc S10 110–127 Vac U14 208–240 Vac U18 415–600 Vac or 220–250 Vdc S14 380–480 Vac U22 525–600 Vac U26
12 Vdc U30
24 Vdc U34
125 Vdc U42
220–250 Vdc U46 Universal J Frame 1NO/1NC A06 1 make/1 break B06 12–24 Vac/Vdc S42 12 Vac U06
2 NO/2NC A13 48–60 Vac/Vdc S50 24 Vac
If both an auxiliary switch and bell alarm are required, add CO5 to the catalog number (right-pole mounted). Auxiliary switch and bell alarm are 600V rated. 110–240 Vac or 110–125 Vdc S10 48–60 Vac U14 110–127 Vac U18 380–440 Vac or 220–50 Vdc S14 208–240 Vac U22 380–480 Vac U26 480–600 Vac S18 12 Vdc T02
24 Vdc T06
48–60 Vdc T10 110–125 Vdc T14 220–250 Vdc T18
V9-T1-16 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com Internal Accessories, continued Auxiliary Switch (Right-Pole Mounted) Bell Alarm (Right-Pole Mounted) Shunt Trip (Left-Pole Mounted) UVR (Left-Pole Mounted) Add This Suffix to Catalog NumberConfiguration Add This Suffix to Catalog Number Configuration Add This Suffix to Catalog Number Voltage Range Voltage Range Add This Suffix to Catalog Number Universal K Frame 1NO/1NC A06 1 make/1 break B06 12–24 Vac/Vdc S42 12 Vac U06 2NO/2NC A13 48–60 Vac/Vdc S50 24 Vac U10 If both an auxiliary switch and bell alarm are required, add CO5 to the catalog number (right-pole mounted). Auxiliary switch and bell alarm are 600V rated. 110–240 Vac or 110–125 Vdc S10 48–60 Vac U14 110–127 Vac U18 380–440 Vac or 220–250 Vdc S14 208–240 Vac U22 380–480 Vac U26 480–600 Vac S18 12 Vdc T02 48–60 Vdc T10 110–125 Vdc T14 220–250 Vdc T18 Universal L Frame 1NO/1NC A06 1 make/1 break B06 12–24 Vac/Vdc S02 12 Vac U06 2NO/2NC A13 48–60 Vdc S06 24 Vac U10 If both an auxiliary switch and bell alarm are required, add CO5 to the catalog number (right-pole mounted). Auxiliary switch and bell alarm are 600V rated. 48–60 Vac S86 48–60 Vac U14 110–240 Vac S10 110–127 Vac U18 110–125 Vdc S42 208–240 Vac U22 380–440 Vac or 220–250 Vdc S14 380–480 Vac U26
12 Vdc T02
480–600 Vac S18 24 Vdc T06 48–60 Vdc T10 110–125 Vdc T14 220–250 Vdc T18
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-17 1.1Circuit Protection Circuit Breakers Handle Mechanisms Note 1 Only available as complete handle mechanism. Parts not sold separately. Type 1/12 Universal Rotary Ordering Information 1 Shaft Length in Inches (mm) Handle Color Complete Catalog Number Flange Flex Shaft Type 1, 3R, 12 Versions Universal G Frame 6 (152.4) Black GHMVD06B 3-ft length; order F0S03C 12 (304.8) Black GHMVD12B 4-ft length; order F0S04C 6 (152.4) Red GHMVD06R 5-ft length; order F0S05C 12 (304.8) Red GHMVD12R 6-ft length; order F0S06C Universal F Frame 6 (152.4) Black FHMVD06B 3-ft length; order F1S03C 12 (304.8) Black FHMVD12B 4-ft length; order F1S04C 6 (152.4) Red FHMVD06R 5-ft length; order F1S05C 12 (304.8) Red FHMVD12R 6-ft length; order F1S06C 7-ft length; order F1S07C 8-ft length; order F1S08C 9-ft length; order F1S09C 10-ft length; order F1S10C Universal J Frame 6 (152.4) Black JHMVD06B 3-ft length; order F2S03C 12 (304.8) Black JHMVD12B 4-ft length; order F2S04C 6 (152.4) Red JHMVD06R 5-ft length; order F2S05C 12 (304.8) Red JHMVD12R 6-ft length; order F2S06C 7-ft length; order F2S07C 8-ft length; order F2S08C 9-ft length; order F2S09C 10-ft length; order F2S10C Universal K Frame 6 (152.4) Black KHMVD06B 3-ft length; order F3S03C 12 (304.8) Black KHMVD12B 4-ft length; order F3S04C 6 (152.4) Red KHMVD06R 5-ft length; order F3S05C 12 (304.8) Red KHMVD12R 6-ft length; order F3S06C 7-ft length; order F3S07C 8-ft length; order F3S08C 9-ft length; order F3S09C 10-ft length; order F3S10C Handle Mechanisms
V9-T1-18 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com Terminals and Termination Accessory Devices Universal G Frame Universal F Frame Universal J Frame Universal K Frame Universal L Frame Terminals (Included with Breaker) Optional Multiwire Lugs (Load End Only) 15–20 A 25–100A Three-Hole Version Six-Hole Version 14–2 AWG Cu/Al 10–1/0 AWG Cu/Al (3) 14–2 AWG Order 3TA100G3K (6) 14–6 AWG Order 3TA100G6K2.5–4 mm2 Cu/Al 4–50 mm 2 Cu/Al Terminals (Included with Breaker) Optional Multiwire Lugs (Load End Only) 10–20A 25–100A 110–225A Three-Hole Version Six-Hole Version 14–10 AWG Cu/Al 14–1/0 AWG Cu/Al 4–4/0 AWG Cu/Al (3) 14–2 AWG Order 3TA150F3K (6) 14–6 AWG Order 3TA150F6K2.5–4 mm2 Cu/Al 2.5–50 mm 2 Cu/Al 25–95 mm 2 Cu/Al Terminals (Included with Breaker) Optional Multiwire Lugs (Load End Only) 70–250A Three-Hole Version Six-Hole Version 4–350 kcmil AWG Cu/Al (3) 14–2 AWG Order 3TA250J3K (6) 14–6 AWG Order 3TA250J6K25–150 mm2 Cu/Al Terminals (Included with Breaker) Optional Multiwire Lugs (Load End Only) 300–350A 400A Three-Hole Version Six-Hole Version 250–500 kcmil AWG Cu/Al 3/0–200 (2) AWG Cu/Al (3) 12–2/0 AWG Order 3TA400K3K (6) 14–2/0 AWG Order 3TA400K6K120–240 mm2 Cu/Al 95–120 mm 2 Cu/Al Terminals (Included with Breaker) Optional Multiwire Lugs (Load End Only) 500A 600A Three-Hole Version Six-Hole Version (2) 250–300 kcmil Cu/Al (2) 400–500 kcmil Cu/Al — — 120–150 mm2 Cu/Al 185–250 mm 2 Cu/Al Terminal/Termination Devices
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-19 1.1Circuit Protection Circuit Breakers QUICKLAG Type QC Miniature Circuit Breakers—Cable-In/Cable-Out Type QC Features For Cable-In/Cable-Out Panel Mount Applications
- Single-, two-, three- and four-pole options
- Built and listed to UL 489
- All products UL and CSA listed
- All products 10–100A are HACR rated Catalog Number Selection QUICKLAG Type QC Miniature Circuit Breakers—Cable-In/Cable-Out Type QC T ype QC Miniature Circuit Breakers Product Selection QUICKLAG T ype QC 10,000 Ampere I.C. Thermal-Magnetic Breakers Note: For non-automatic switches, see Volume 4—Circuit Protection, CA08100005E, Tab 1 . Notes 1 Switching duty rated for 120 Vac fluorescent light applications only. 2 For special low-magnetic breaker, order QC1015L1 or QC1020L1. Continuous Ampere Rating at 40ºC Single-Pole, 120/240 Vac Catalog Number Two-Pole, 120/240 Vac Catalog Number Three-Pole, 240 Vac Catalog Number
10 QC1010 QC2010 —
15 QC1015 12 QC2015 QC3015H
20 QC1020 12 QC2020 QC3020H
30 QC1030 QC2030 QC3030H
40 QC1040 QC2040 QC3040H
50 QC1050 QC2050 QC3050H
60 — QC2060 QC3060H 70 — QC2070 QC3070H
100 QC1100 QC2100 QC3100H
QC = QC breaker Ampere Rating 010 = 10 amp 015 = 15 amp 020 = 20 amp 025 = 25 amp 030 = 30 amp 035 = 35 amp 040 = 40 amp 045 = 45 amp 050 = 50 amp 055 = 55 amp 060 = 60 amp 070 = 70 amp 080 = 80 amp 090 = 90 amp 100 = 100 amp Construction H = 240V (two-, three- and four-pole only) QC 3 020 H Number of Poles 1 = Single-pole 2 = Two-pole 3 = Three-pole 4 = Four-pole
V9-T1-20 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com QUICKLAG Type QC Miniature Circuit Breakers—Cable-In/Cable-Out Type QCD Features For Cable-In/Cable-Out DIN rail Mount HVAC Applications
- Single-, two- and three-pole options
- Modular construction
- DIN mounted (symmetrical rail 35 in x 7 .5 in DIN/EN 50 022)
- Flexible power feed connection: wire size, position
- Same breaker size for entire rating range
- Field-mountable accessories: finger-shroud proof, quick connect terminals, jumper units Catalog Number Selection QUICKLAG T ype QC Miniature Circuit Breakers—Cable-In/Cable-Out T ype QCD Product Selection QUICKLAG T ype QCD 10,000 Ampere I.C. Thermal-Magnetic Breakers Continuous Ampere Rating at 40ºC Single-Pole, 120/240 Vac Catalog Number Two-Pole, 120/240 Vac Catalog Number Three-Pole, 240 Vac Catalog Number
10 QCD1010 QCD2010 —
15 QCD1015 QCD2015 QCD3015H
20 QCD1020 QCD2020 QCD3020H
30 QCD1030 QCD2030 QCD3030H
40 QCD1040 QCD2040 QCD3040H
50 QCD1050 QCD2050 QCD3050H
60 QCD1060 QCD2060 QCD3060H
70 — QCD2070 QCD3070H 100 — QCD2100 QCD3100H Breaker Type QCD = QCD breaker Ampere Rating 010 = 10 amp 015 = 15 amp 020 = 20 amp 025 = 25 amp 030 = 30 amp 035 = 35 amp 040 = 40 amp 045 = 45 amp 050 = 50 amp 055 = 55 amp 060 = 60 amp 070 = 70 amp 080 = 80 amp 090 = 90 amp 100 = 100 amp Construction H = 240V (two- and three-pole only) QCD 3 020 H Number of Poles 1 = Single-pole 2 = Two-pole 3 = Three-pole
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-21 1.1Circuit Protection Circuit Breakers QUICKLAG Type QC Miniature Circuit Breakers—Cable-In/Cable-Out 1/2-Inch Wide Types QCR, QCF
Features
When Space is at a Premium
- QCR: For DIN rail mount cable-in/cable-out applications
- QCF: For front-mount through-the-door cable-in/cable-out
applications
- 1/2 in (12.7 mm) wide per pole
- Three-position handle: ON, tripped (center), OFF
- Thermal-magnetic protection
- Single-, two- and three-pole
- 10 kAIC at 120/240 Vac, 10–60A
- 10 kAIC at 240 Vac, 10–30A Catalog Number Selection QUICKLAG T ype QC Miniature Circuit Breakers—Cable-In/Cable-Out 1/2-Inch Wide T ypes QCR, QCF Product Selection QUICKLAG T ype QCR Breakers 10 kAIC QUICKLAG T ype QCF Breakers 10 kAIC Interrupting Ratings 1234 Interrupting Ratings 123 Notes 1 Standard breaker terminals are box type lugs. 2 Breakers with “T” catalog number suffix are suitable for line and load side ring terminal connection (#10-32 plus/minus termina l screw provided). 3 Breakers with “P” catalog number suffix are suitable for terminating two 10 AWG quick-connect type terminals per phase on break er load side. 4 Breakers with shunt trip (extra pole required on breaker right-hand side) are available on single-, two- and three-pole. 5 All 15 and 20A single-pole breakers are SWD (switching duty) rated for fluorescent lighting applications. 6 60/75°C Cu/Al wire on all ratings except 60A, which requires Cu only conductor. Continuous Ampere Rating at 40ºC Single-Pole 120/240 Vac Catalog Number Two-Pole 120/240 Vac Catalog Number Three-Pole
240 Vac
at 40ºC Single-Pole 120/240 Vac Catalog Number Two-Pole 120/240 Vac Catalog Number Three-Pole
10 QCR1010 QCR2010 — 10 QCF1010 QCF2010 —
QCR1010T QCR2010T — QCF1010T QCF2010T —
15 QCR1015 5 QCR2015 QCR3015H 15 QCF1015 5 QCF2015 QCF3015H
QCR1015T 5 QCR2015T QCR3015HT — — QCF3015HT
20 QCR1020 5 QCR2020 QCR3020H 20 QCF1020 5 QCF2020 QCF3020H
QCR1020T 5 QCR2020T QCR3020HT — — QCF3020HT
25 QCR1025 QCR2025 QCR3025H 25 QCF1025 QCF2025 QCF3025H
— — QCR3025HT — — QCF3025HT
30 QCR1030 QCR2030 QCR3030H 30 QCF1030 QCF2030 QCF3030H
— — QCR3030HT — — QCF3030HT
35 QCR1035 QCR2035 — 40 QCF1040 QCF2040 —
40 QCR1040 QCR2040 — 50 QCF1050 QCF2050 —
45 QCR1045 QCR2045 — 60 6 QCF1060 QCF2060 —
50 QCR1050 QCR2050 —
55 QCR1055 — —
60 6 QCR1060 QCR2060 — Breaker Type QCR = QCD Breaker (rear mount) QCF = QCF Breaker (front mount) Ampere Rating 010 = 10 amp 015 = 15 amp 020 = 20 amp 025 = 25 amp 030 = 30 amp 035 = 35 amp 040 = 40 amp 045 = 45 amp 050 = 50 amp 055 = 55 amp 060 = 60 amp Construction/Terminals H = 240V (two- and three-pole only) T = Ring or spade terminals (10–30A only) QCR 1 020 T Number of Poles 1 = Single-pole 2 = Two-pole 3 = Three-pole
V9-T1-22 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com Description Catalog Number Steel mounting clip mounts QCR breaker if individual mounting is required. Quantity two required for single- and two-pole and four required for three-pole breakers. QCRMTGFT Removable padlock device for single-pole QCR or QCF breaker. QCRFPL1P Removable padlock device for multi-pole QCR or QCF breaker. QCRFPLMP Padlock bracket assembly for QCR or QCF single- or multi-pole breakers (OFF only). QCRFLOFF Padlock bracket for QCR, lock-off only. QCRPLOFF QUICKLAG Type C Spacer QCRSPACER QCR and QCF ring or spade lug terminals (10–30A ratings only). Factory installed line and load side terminals each equipped with a #10-32 screw suitable for terminating one 10 AWG wire with insulated ring or spade type terminal as shown. Suffix “T” QUICKLAG Type C Spacer QCR and QCF Ring or Spade Lug Terminals
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-23 1.1Circuit Protection Circuit Breakers QUICKLAG Type QC Miniature Circuit Breakers—Cable-In/Cable-Out 1/2-Inch Wide Types QCGF, QCGFEP For Cable-In/Cable-Out Panel-Mount Applications
- QUICKLAG ground fault circuit breakers, Class A GFCI:
- Built and tested to UL 943
- 5 mA trip sensitivity
- QUICKLAG ground fault equipment protectors:
- Built and tested to UL 1053
- 30 mA trip sensitivity
- All products UL and CSA listed Catalog Number Selection QUICKLAG T ype QC Miniature Circuit Breakers— Cable-In/Cable-Out Ground Fault and Equipment Protector T ypes QCGF , QCGFEP Product Selection T ypes QCGF and QCGFEP Thermal-Magnetic Breakers Continuous Ampere Rating at 40ºC Single-Pole, 120/240 Vac Catalog Number Two-Pole, 120/240 Vac Catalog Number Ground Fault Circuit Breakers—5 mA Sensitivity QUICKLAG T ype: QCGF 10,000 Ampere I.C.
15 QCGF1015 QCGF2015
20 QCGF1020 QCGF2020
30 QCGF1030 QCGF2030
40 QCGF1040 QCGF2040
50 — QCGF2050 Ground Fault Equipment Protectors—30 mA Sensitivity QUICKLAG T ype: QCGFEP 10,000 Ampere I.C.
15 QCGFEP1015 QCGFEP2015
20 QCGFEP1020 QCGFEP2020
30 QCGFEP1030 QCGFEP2030
40 QCGFEP1040 QCGFEP2040
50 — QCGFEP2050 Breaker Type QCGF = QC ground fault circuit protector QCGFEP = QC ground fault equipment protector Ampere Rating 015 = 15 amp 020 = 20 amp 025 = 25 amp 030 = 30 amp 040 = 40 amp 050 = 50 amp QCGFEP 1 020 Number of Poles 1 = Single-pole 2 = Two-pole
V9-T1-24 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com T ype QC Miniature Circuit Breakers Notes 1 See Page V9-T1-22 for QCR and QCF accessories. 2 Can lock in ON or OFF position. 3 Suitable for ground fault breakers. Accessory 1 Description Catalog Number Handle locks: Non-padlockable 2 QUICKLAG type P , B, C—single-pole QL1NPL QUICKLAG type P , B, C—two-, three-pole QL23NPL Handle locks: Padlockable QUICKLAG type P , B, C—single-pole QL1PL QUICKLAG type C—single-, two-, three-pole QC123PL QUICKLAG type C—single-, two-, three-pole (off only) QCD123PLOFF Handle tie QUICKLAG handle tie—single-pole QL1HT QUICKLAG handle tie—three-pole QL3HT Mounting hardware QUICKLAG type C face mounting clip QCFCLIP QUICKLAG type C face mounting plate—single-pole QC1FP QUICKLAG type C face mounting plate —two-pole QC2FP QUICKLAG type C face mounting plate —three-pole QC3FP QUICKLAG type C face mounting plate and lock-off (off only)—two-pole 3 QC2FPLOFF QUICKLAG type C face mounting plate and lock-off (off only)—three-pole QC3FPLOFF QUICKLAG type C base mounting clamp QCBCLIP QUICKLAG base mounting plate—six poles total QC6BP QUICKLAG type C base mounting plate, six-poles total— heavy-duty screw-secured QC6BPS QUICKLAG type C (QCD) two-way jumper unit with cover QCDJ2 QUICKLAG type C (QCD) four-way jumper unit with cover QCDJ4 QUICKLAG type C (QCD) six-way jumper unit with cover QCDJ6 QUICKLAG type C (QCD) two-way jumper unit, no cover QCDJ2T QUICKLAG type C (QCD) four-way jumper unit, no cover QCDJ4T QUICKLAG type C (QCD) six-way jumper unit, no cover QCDJ6T QUICKLAG type QCD finger protection attachment QCDFP QUICKLAG type C DIN rail adapter QCDINADAPT Handle Locks Handle Tie Hardware
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-25 1.1Circuit Protection Circuit Breakers FAZ-NA UL 489 Circuit Breakers Features
- UL 489 listed DIN rail mounted miniature circuit breakers up to 40A current rating
- Current limiting design provides fast short-circuit interruption that reduces let-through energy
- Thermal-magnetic overcurrent protection
- Three levels of short-circuit protection, categorized by B, C and D curves
- Ring-tongue terminals available
- Complete line of accessories Catalog Number Selection FAZ-NA UL 489 Circuit Breakers FAZ-NA UL 489 Notes 1 In = Rated current for instantaneous trip characteristics. 2 B curve starts at 1 ampere. Breaker Family FAZ = FAZ UL circuit breaker Ampere Rating 2 0.5 =0 . 5 A 1 =1 A 1.5 =1 . 5 A 2 =2 A 3 =3 A 4 =4 A 5 =5 A 6 =6 A 7 =7 A 8 =8 A 10 = 10A 13 = 13A 15 = 15A 16 = 16A 20 = 20A 25 = 25A 30 = 30A 32 = 32A 35 = 32A 40 = 40A Trip Characteristics 1 B = 3–5X In C = 5–10X In D = 10–20X In Number of Poles 1 = Single-pole 2 = Two-pole 3 = Three-pole Single Package SP = Single package for C and D curve single-pole only Blank = Standard packaging Terminal NA = UL 489 branch circuit with screw terminals RT = UL 489 branch circuit with ring tongue terminals DC = UL 489 branch circuit at 125 Vdc per pole FAZ C 6 / 1 NA SP
V9-T1-26 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com FAZ-NA UL 489 Circuit Breakers—10 kAIC, 14 kAIC B Curve (15–25A) FAZ-RT UL 489 Circuit Breakers with Ring-T ongue T erminals—10 kAIC, 14 kAIC B Curve (15–25A) FAZ-NA UL 489 Circuit Breakers—10 kAIC, 14 kAIC C Curve (15–25A) FAZ-RT UL 489 Circuit Breakers with Ring-T ongue T erminals—10 kAIC, 14 kAIC C Curve (15–25A) Notes 1 Two-piece order. Quantities of two per box. 2 240 Vac rated only. 3 Option for single packaging on single-pole C and D curves only; add suffix SP when ordering. Amperes Single-Pole 1 Catalog Number Two-Pole Catalog Number Three-Pole Catalog Number B Curve (3–5X In Current Rating)
1 FAZ-B1/1-NA FAZ-B1/2-NA FAZ-B1/3-NA
1.5 FAZ-B1.5/1-NA FAZ-B1.5/2-NA FAZ-B1.5/3-NA
2 FAZ-B2/1-NA FAZ-B2/2-NA FAZ-B2/3-NA
3 FAZ-B3/1-NA FAZ-B3/2-NA FAZ-B3/3-NA
4 FAZ-B4/1-NA FAZ-B4/2-NA FAZ-B4/3-NA
5 FAZ-B5/1-NA FAZ-B5/2-NA FAZ-B5/3-NA
6 FAZ-B6/1-NA FAZ-B6/2-NA FAZ-B6/3-NA
7 FAZ-B7/1-NA FAZ-B7/2-NA FAZ-B7/3-NA
8 FAZ-B8/1-NA FAZ-B8/2-NA FAZ-B8/3-NA
10 FAZ-B10/1-NA FAZ-B10/2-NA FAZ-B10/3-NA
13 FAZ-B13/1-NA FAZ-B13/2-NA FAZ-B13/3-NA
15 FAZ-B15/1-NA FAZ-B15/2-NA FAZ-B15/3-NA
16 FAZ-B16/1-NA FAZ-B16/2-NA FAZ-B16/3-NA
20 FAZ-B20/1-NA FAZ-B20/2-NA FAZ-B20/3-NA
25 FAZ-B25/1-NA FAZ-B25/2-NA FAZ-B25/3-NA
30 FAZ-B30/1-NA FAZ-B30/2-NA FAZ-B30/3-NA
32 FAZ-B32/1-NA FAZ-B32/2-NA FAZ-B32/3-NA
35 2 FAZ-B35/1-NA FAZ-B35/2-NA FAZ-B35/3-NA 40 2 FAZ-B40/1-NA FAZ-B40/2-NA FAZ-B40/3-NA Amperes Single-Pole 1 Catalog Number Two-Pole Catalog Number Three-Pole Catalog Number B Curve with Ring-T ongue T erminals (3–5X In Current Rating)
1 FAZ-B1/1-RT FAZ-B1/2-RT FAZ-B1/3-RT
1.5 FAZ-B1.5/1-RT FAZ-B1.5/2-RT FAZ-B1.5/3-RT
2 FAZ-B2/1-RT FAZ-B2/2-RT FAZ-B2/3-RT
3 FAZ-B3/1-RT FAZ-B3/2-RT FAZ-B3/3-RT
4 FAZ-B4/1-RT FAZ-B4/2-RT FAZ-B4/3-RT
5 FAZ-B5/1-RT FAZ-B5/2-RT FAZ-B5/3-RT
6 FAZ-B6/1-RT FAZ-B6/2-RT FAZ-B6/3-RT
7 FAZ-B7/1-RT FAZ-B7/2-RT FAZ-B7/3-RT
8 FAZ-B8/1-RT FAZ-B8/2-RT FAZ-B8/3-RT
10 FAZ-B10/1-RT FAZ-B10/2-RT FAZ-B10/3-RT
13 FAZ-B13/1-RT FAZ-B13/2-RT FAZ-B13/3-RT
15 FAZ-B15/1-RT FAZ-B15/2-RT FAZ-B15/3-RT
16 FAZ-B16/1-RT FAZ-B16/2-RT FAZ-B16/3-RT
20 FAZ-B20/1-RT FAZ-B20/2-RT FAZ-B20/3-RT
25 FAZ-B25/1-RT FAZ-B25/2-RT FAZ-B25/3-RT
30 FAZ-B30/1-RT FAZ-B30/2-RT FAZ-B30/3-RT
32 FAZ-B32/1-RT FAZ-B32/2-RT FAZ-B32/3-RT
35 2 FAZ-B35/1-RT FAZ-B35/2-RT FAZ-B35/3-RT 40 2 FAZ-B40/1-RT FAZ-B40/2-RT FAZ-B40/3-RT Amperes Single-Pole 3 Catalog Number Two-Pole Catalog Number Three-Pole Catalog Number C Curve (5–10X In Current Rating) 0.5 FAZ-C0.5/1-NA-SP FAZ-C0.5/2-NA FAZ-C0.5/3-NA
1 FAZ-C1/1-NA-SP FAZ-C1/2-NA FAZ-C1/3-NA
1.5 FAZ-C1.5/1-NA-SP FAZ-C1.5/2-NA FAZ-C1.5/3-NA
2 FAZ-C2/1-NA-SP FAZ-C2/2-NA FAZ-C2/3-NA
3 FAZ-C3/1-NA-SP FAZ-C3/2-NA FAZ-C3/3-NA
4 FAZ-C4/1-NA-SP FAZ-C4/2-NA FAZ-C4/3-NA
5 FAZ-C5/1-NA-SP FAZ-C5/2-NA FAZ-C5/3-NA
6 FAZ-C6/1-NA-SP FAZ-C6/2-NA FAZ-C6/3-NA
7 FAZ-C7/1-NA-SP FAZ-C7/2-NA FAZ-C7/3-NA
8 FAZ-C8/1-NA-SP FAZ-C8/2-NA FAZ-C8/3-NA
10 FAZ-C10/1-NA-SP FAZ-C10/2-NA FAZ-C10/3-NA
13 FAZ-C13/1-NA-SP FAZ-C13/2-NA FAZ-C13/3-NA
15 FAZ-C15/1-NA-SP FAZ-C15/2-NA FAZ-C15/3-NA
16 FAZ-C16/1-NA-SP FAZ-C16/2-NA FAZ-C16/3-NA
20 FAZ-C20/1-NA-SP FAZ-C20/2-NA FAZ-C20/3-NA
25 FAZ-C25/1-NA-SP FAZ-C25/2-NA FAZ-C25/3-NA
30 FAZ-C30/1-NA-SP FAZ-C30/2-NA FAZ-C30/3-NA
32 FAZ-C32/1-NA-SP FAZ-C32/2-NA FAZ-C32/3-NA
35 2 FAZ-C35/1-NA-SP FAZ-C35/2-NA FAZ-C35/3-NA 40 2 FAZ-C40/1-NA-SP FAZ-C40/2-NA FAZ-C40/3-NA Amperes Single-Pole 3 Catalog Number Two-Pole Catalog Number Three-Pole Catalog Number C Curve with Ring-T ongue T erminals (5–10X In Current Rating) 0.5 FAZ-C0.5/1-RT-SP FAZ-C0.5/2-RT FAZ-C0.5/3-RT
1 FAZ-C1/1-RT-SP FAZ-C1/2-RT FAZ-C1/3-RT
1.5 FAZ-C1.5/1-RT-SP FAZ-C1.5/2-RT FAZ-C1.5/3-RT
2 FAZ-C2/1-RT-SP FAZ-C2/2-RT FAZ-C2/3-RT
3 FAZ-C3/1-RT-SP FAZ-C3/2-RT FAZ-C3/3-RT
4 FAZ-C4/1-RT-SP FAZ-C4/2-RT FAZ-C4/3-RT
5 FAZ-C5/1-RT-SP FAZ-C5/2-RT FAZ-C5/3-RT
6 FAZ-C6/1-RT-SP FAZ-C6/2-RT FAZ-C6/3-RT
7 FAZ-C7/1-RT-SP FAZ-C7/2-RT FAZ-C7/3-RT
8 FAZ-C8/1-RT-SP FAZ-C8/2-RT FAZ-C8/3-RT
10 FAZ-C10/1-RT-SP FAZ-C10/2-RT FAZ-C10/3-RT
13 FAZ-C13/1-RT-SP FAZ-C13/2-RT FAZ-C13/3-RT
15 FAZ-C15/1-RT-SP FAZ-C15/2-RT FAZ-C15/3-RT
16 FAZ-C16/1-RT-SP FAZ-C16/2-RT FAZ-C16/3-RT
20 FAZ-C20/1-RT-SP FAZ-C20/2-RT FAZ-C20/3-RT
25 FAZ-C25/1-RT-SP FAZ-C25/2-RT FAZ-C25/3-RT
30 FAZ-C30/1-RT-SP FAZ-C30/2-RT FAZ-C30/3-RT
32 FAZ-C32/1-RT-SP FAZ-C32/2-RT FAZ-C32/3-RT
35 2 FAZ-C35/1-RT-SP FAZ-C35/2-RT FAZ-C35/3-RT 40 2 FAZ-C40/1-RT-SP FAZ-C40/2-RT FAZ-C40/3-RT
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-27 1.1Circuit Protection Circuit Breakers FAZ-NA UL 489 Circuit Breakers—10 kAIC, 14 kAIC D Curve (13–20A) FAZ-RT UL 489 Circuit Breakers with Ring-T ongue T erminals—10 kAIC, 14 kAIC D Curve (13–20A) FAZ-NA-DC UL 489 Circuit Breakers—10 kAIC at
125 Vdc Per Pole
1 Option for single packaging on single-pole C and D curves only; add suffix SP when ordering. 2 240 Vac rated only. 3 Option for single packaging on single-pole C curves only; add suffix SP when ordering. Amperes Single-Pole 1 Catalog Number Two-Pole Catalog Number Three-Pole Catalog Number D Curve (10–20X In Current Rating) 0.5 FAZ-D0.5/1-NA-SP FAZ-D0.5/2-NA FAZ-D0.5/3-NA
1 FAZ-D1/1-NA-SP FAZ-D1/2-NA FAZ-D1/3-NA
1.5 FAZ-D1.5/1-NA-SP FAZ-D1.5/2-NA FAZ-D1.5/3-NA
2 FAZ-D2/1-NA-SP FAZ-D2/2-NA FAZ-D2/3-NA
3 FAZ-D3/1-NA-SP FAZ-D3/2-NA FAZ-D3/3-NA
4 FAZ-D4/1-NA-SP FAZ-D4/2-NA FAZ-D4/3-NA
5 FAZ-D5/1-NA-SP FAZ-D5/2-NA FAZ-D5/3-NA
6 FAZ-D6/1-NA-SP FAZ-D6/2-NA FAZ-D6/3-NA
7 FAZ-D7/1-NA-SP FAZ-D7/2-NA FAZ-D7/3-NA
8 FAZ-D8/1-NA-SP FAZ-D8/2-NA FAZ-D8/3-NA
10 FAZ-D10/1-NA-SP FAZ-D10/2-NA FAZ-D10/3-NA
13 FAZ-D13/1-NA-SP FAZ-D13/2-NA FAZ-D13/3-NA
15 FAZ-D15/1-NA-SP FAZ-D15/2-NA FAZ-D15/3-NA
16 FAZ-D16/1-NA-SP FAZ-D16/2-NA FAZ-D16/3-NA
20 FAZ-D20/1-NA-SP FAZ-D20/2-NA FAZ-D20/3-NA
25 FAZ-D25/1-NA-SP FAZ-D25/2-NA FAZ-D25/3-NA
30 FAZ-D30/1-NA-SP FAZ-D30/2-NA FAZ-D30/3-NA
32 FAZ-D32/1-NA-SP FAZ-D32/2-NA FAZ-D32/3-NA
35 2 FAZ-D35/1-NA-SP FAZ-D35/2-NA FAZ-D35/3-NA 40 2 FAZ-D40/1-NA-SP FAZ-D40/2-NA FAZ-D40/3-NA Amperes Single-Pole 1 Catalog Number Two-Pole Catalog Number Three-Pole Catalog Number D Curve with Ring-T ongue T erminals (10–20X In Current Rating) 0.5 FAZ-D0.5/1-RT-SP FAZ-D0.5/2-RT FAZ-D0.5/3-RT
1 FAZ-D1/1-RT-SP FAZ-D1/2-RT FAZ-D1/3-RT
1.5 FAZ-D1.5/1-RT-SP FAZ-D1.5/2-RT FAZ-D1.5/3-RT
2 FAZ-D2/1-RT-SP FAZ-D2/2-RT FAZ-D2/3-RT
3 FAZ-D3/1-RT-SP FAZ-D3/2-RT FAZ-D3/3-RT
4 FAZ-D4/1-RT-SP FAZ-D4/2-RT FAZ-D4/3-RT
5 FAZ-D5/1-RT-SP FAZ-D5/2-RT FAZ-D5/3-RT
6 FAZ-D6/1-RT-SP FAZ-D6/2-RT FAZ-D6/3-RT
7 FAZ-D7/1-RT-SP FAZ-D7/2-RT FAZ-D7/3-RT
8 FAZ-D8/1-RT-SP FAZ-D8/2-RT FAZ-D8/3-RT
10 FAZ-D10/1-RT-SP FAZ-D10/2-RT FAZ-D10/3-RT
13 FAZ-D13/1-RT-SP FAZ-D13/2-RT FAZ-D13/3-RT
15 FAZ-D15/1-RT-SP FAZ-D15/2-RT FAZ-D15/3-RT
16 FAZ-D16/1-RT-SP FAZ-D16/2-RT FAZ-D16/3-RT
20 FAZ-D20/1-RT-SP FAZ-D20/2-RT FAZ-D20/3-RT
25 FAZ-D25/1-RT-SP FAZ-D25/2-RT FAZ-D25/3-RT
30 FAZ-D30/1-RT-SP FAZ-D30/2-RT FAZ-D30/3-RT
32 FAZ-D32/1-RT-SP FAZ-D32/2-RT FAZ-D32/3-RT
35 2 FAZ-D35/1-RT-SP FAZ-D35/2-RT FAZ-D35/3-RT 40 2 FAZ-D40/1-RT-SP FAZ-C40/2-RT FAZ-D40/3-RT Amperes Single-Pole 3 Catalog Number Two-Pole Catalog Number C Curve (5–10X In Current Rating)
2 FAZ-C2/1-NA-DC-SP FAZ-C2/2-NA-DC
3 FAZ-C3/1-NA-DC-SP FAZ-C3/2-NA-DC
4 FAZ-C4/1-NA-DC-SP FAZ-C4/2-NA-DC
5 FAZ-C5/1-NA-DC-SP FAZ-C5/2-NA-DC
6 FAZ-C6/1-NA-DC-SP FAZ-C6/2-NA-DC
7 FAZ-C7/1-NA-DC-SP FAZ-C7/2-NA-DC
8 FAZ-C8/1-NA-DC-SP FAZ-C8/2-NA-DC
10 FAZ-C10/1-NA-DC-SP FAZ-C10/2-NA-DC
13 FAZ-C13/1-NA-DC-SP FAZ-C13/2-NA-DC
15 FAZ-C15/1-NA-DC-SP FAZ-C15/2-NA-DC
16 FAZ-C16/1-NA-DC-SP FAZ-C16/2-NA-DC
20 FAZ-C20/1-NA-DC-SP FAZ-C20/2-NA-DC
25 FAZ-C25/1-NA-DC-SP FAZ-C25/2-NA-DC
30 FAZ-C30/1-NA-DC-SP FAZ-C30/2-NA-DC
32 FAZ-C32/1-NA-DC-SP FAZ-C32/2-NA-DC
35 FAZ-C35/1-NA-DC-SP FAZ-C35/2-NA-DC
40 FAZ-C40/1-NA-DC-SP FAZ-C40/2-NA-DC
V9-T1-28 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com FAZ UL 1077 Circuit Breakers Features
- UL 1077 recognized DIN rail mounted supplemental protectors up to 63A
- Current limiting design provides fast short-circuit interruption that reduces let-through energy
- Thermal-magnetic overcurrent protection
- Three levels of short-circuit protection, categorized by B, C and D curves
- Ideal replacement for fuses that are applied as supplemental protection
- Complete line of accessories Catalog Number Selection FAZ UL 1077 Circuit Breakers FAZ UL 1077 Note 1 In = Rated current for instantaneous trip characteristics. Breaker Family FAZ = Supplementary protector Ampere Rating 0.5 =0 . 5 A 1 =1 A 2 =2 A 3 =3 A 4 =4 A 5 =5 A 6 =6 A 7 =7 A 8 =8 A 10 =1 0 A 13 = 13A 15 = 15A 16 = 16A 20 = 20A 25 = 25A 30 = 30A 32 = 32A 40 = 40A 50 = 50A 63 = 63A Trip Characteristics 1 B = 3–5X In C = 5–10X In D = 10–20X In K = 8–12X In S = 13–17X In Z = 2–3X In Number of Poles 1 = Single-pole 2 = Two-pole 3 = Three-pole 4 = Single-pole 1N = Single-pole + neutral 3N = Three-pole + neutral Single Package SP = Single packaging of single- pole curve B, C and D for select amperes only Blank = Standard packaging FAZ C 6 / 1 SP
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-29 1.1Circuit Protection Circuit Breakers Product Selection B Curve (3–5X In Current Rating)—Designed for Resistive or Slightly Inductive Loads 1 B Curve (3–5X In Current Rating)—Designed for Resistive or Slightly Inductive Loads, continued 1 Notes
1 In North America, these switches are UL recognized and CSA Certified as supplementary
protection devices. Per the intent of NEC (National Electrical Code), Article 240, and CEC (Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to provide overcurrent protection within an appliance or other electrical equipment where branch circuit overcurrent protection is already provided, or is not required.
2 Option for single packaging on single-pole B, C and D curves only; add suffix SP when
ordering. Amperes Single-Pole 2 Catalog Number Two-Pole Catalog Number Three-Pole Catalog Number
1 FAZ-B1/1-SP FAZ-B1/2 FAZ-B1/3
2 FAZ-B2/1-SP FAZ-B2/2 FAZ-B2/3
3 FAZ-B3/1-SP FAZ-B3/2 FAZ-B3/3
4 FAZ-B4/1-SP FAZ-B4/2 FAZ-B4/3
5 FAZ-B5/1-SP FAZ-B5/2 FAZ-B5/3
6 FAZ-B6/1-SP FAZ-B6/2 FAZ-B6/3
7 FAZ-B7/1-SP FAZ-B7/2 FAZ-B7/3
8 FAZ-B8/1-SP FAZ-B8/2 FAZ-B8/3
10 FAZ-B10/1-SP FAZ-B10/2 FAZ-B10/3
12 FAZ-B12/1-SP FAZ-B12/2 FAZ-B12/3
13 FAZ-B13/1-SP FAZ-B13/2 FAZ-B13/3
15 FAZ-B15/1-SP FAZ-B15/2 FAZ-B15/3
16 FAZ-B16/1-SP FAZ-B16/2 FAZ-B16/3
20 FAZ-B20/1-SP FAZ-B20/2 FAZ-B20/3
25 FAZ-B25/1-SP FAZ-B25/2 FAZ-B25/3
30 FAZ-B30/1-SP FAZ-B30/2 FAZ-B30/3
32 FAZ-B32/1-SP FAZ-B32/2 FAZ-B32/3
40 FAZ-B40/1-SP FAZ-B40/2 FAZ-B40/3
50 FAZ-B50/1-SP FAZ-B50/2 FAZ-B50/3
63 FAZ-B63/1-SP FAZ-B63/2 FAZ-B63/3
+ Neutral Three-Pole + Neutral
1 FAZ-B1/4 FAZ-B1/1N FAZ-B1/3N
2 FAZ-B2/4 FAZ-B2/1N FAZ-B2/3N
3 FAZ-B3/4 FAZ-B3/1N FAZ-B3/3N
4 FAZ-B4/4 FAZ-B4/1N FAZ-B4/3N
5 FAZ-B5/4 FAZ-B5/1N FAZ-B5/3N
6 FAZ-B6/4 FAZ-B6/1N FAZ-B6/3N
7 FAZ-B7/4 FAZ-B7/1N FAZ-B7/3N
8 FAZ-B8/4 FAZ-B8/1N FAZ-B8/3N
10 FAZ-B10/4 FAZ-B10/1N FAZ-B10/3N
12 FAZ-B12/4 FAZ-B12/1N FAZ-B12/3N
13 FAZ-B13/4 FAZ-B13/1N FAZ-B13/3N
15 FAZ-B15/4 FAZ-B15/1N FAZ-B15/3N
16 FAZ-B16/4 FAZ-B16/1N FAZ-B16/3N
20 FAZ-B20/4 FAZ-B20/1N FAZ-B20/3N
25 FAZ-B25/4 FAZ-B25/1N FAZ-B25/3N
30 FAZ-B30/4 FAZ-B30/1N FAZ-B30/3N
32 FAZ-B32/4 FAZ-B32/1N FAZ-B32/3N
40 FAZ-B40/4 FAZ-B40/1N FAZ-B40/3N
50 FAZ-B50/4 FAZ-B50/1N FAZ-B50/3N
63 FAZ-B63/4 FAZ-B63/1N FAZ-B63/3N
V9-T1-30 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com C Curve (5–10X In Current Rating)—Designed Inductive Loads 1 C Curve (5–10X In Current Rating)—Designed Inductive Loads, continued 1 Notes protection devices. Per the intent of NEC (National Electrical Code), Article 240, and CEC (Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to provide overcurrent protection within an appliance or other electrical equipment where branch circuit overcurrent protection is already provided, or is not required. ordering. Amperes Single-Pole 2 Catalog Number Two-Pole Catalog Number Three-Pole Catalog Number 0.5 FAZ-C0.5/1-SP FAZ-C0.5/2 FAZ-C0.5/3
1 FAZ-C1/1-SP FAZ-C1/2 FAZ-C1/3
1.6 FAZ-C1.6/1-SP FAZ-C1.6/2 FAZ-C1.6/3
2 FAZ-C2/1-SP FAZ-C2/2 FAZ-C2/3
3 FAZ-C3/1-SP FAZ-C3/2 FAZ-C3/3
4 FAZ-C4/1-SP FAZ-C4/2 FAZ-C4/3
5 FAZ-C5/1-SP FAZ-C5/2 FAZ-C5/3
6 FAZ-C6/1-SP FAZ-C6/2 FAZ-C6/3
7 FAZ-C7/1-SP FAZ-C7/2 FAZ-C7/3
8 FAZ-C8/1-SP FAZ-C8/2 FAZ-C8/3
10 FAZ-C10/1-SP FAZ-C10/2 FAZ-C10/3
13 FAZ-C13/1-SP FAZ-C13/2 FAZ-C13/3
15 FAZ-C15/1-SP FAZ-C15/2 FAZ-C15/3
16 FAZ-C16/1-SP FAZ-C16/2 FAZ-C16/3
20 FAZ-C20/1-SP FAZ-C20/2 FAZ-C20/3
25 FAZ-C25/1-SP FAZ-C25/2 FAZ-C25/3
30 FAZ-C30/1-SP FAZ-C30/2 FAZ-C30/3
32 FAZ-C32/1-SP FAZ-C32/2 FAZ-C32/3
40 FAZ-C40/1-SP FAZ-C40/2 FAZ-C40/3
50 FAZ-C50/1-SP FAZ-C50/2 FAZ-C50/3
63 FAZ-C63/1-SP FAZ-C63/2 FAZ-C63/3
+ Neutral Three-Pole + Neutral 0.5 FAZ-C0.5/4 FAZ-C0.5/1N FAZ-C0.5/3N
1 FAZ-C1/4 FAZ-C1/1N FAZ-C1/3N
1.6 FAZ-C1.6/4 FAZ-C1.6/1N FAZ-C1.6/3N
2 FAZ-C2/4 FAZ-C2/1N FAZ-C2/3N
3 FAZ-C3/4 FAZ-C3/1N FAZ-C3/3N
4 FAZ-C4/4 FAZ-C4/1N FAZ-C4/3N
5 FAZ-C5/4 FAZ-C5/1N FAZ-C5/3N
6 FAZ-C6/4 FAZ-C6/1N FAZ-C6/3N
7 FAZ-C7/4 FAZ-C7/1N FAZ-C7/3N
8 FAZ-C8/4 FAZ-C8/1N FAZ-C8/3N
10 FAZ-C10/4 FAZ-C10/1N FAZ-C10/3N
13 FAZ-C13/4 FAZ-C13/1N FAZ-C13/3N
15 FAZ-C15/4 FAZ-C15/1N FAZ-C15/3N
16 FAZ-C16/4 FAZ-C16/1N FAZ-C16/3N
20 FAZ-C20/4 FAZ-C20/1N FAZ-C20/3N
25 FAZ-C25/4 FAZ-C25/1N FAZ-C25/3N
30 FAZ-C30/4 FAZ-C30/1N FAZ-C30/3N
32 FAZ-C32/4 FAZ-C32/1N FAZ-C32/3N
40 FAZ-C40/4 FAZ-C40/1N FAZ-C40/3N
50 FAZ-C50/4 FAZ-C50/1N FAZ-C50/3N
63 FAZ-C63/4 FAZ-C63/1N FAZ-C63/3N
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-31 1.1Circuit Protection Circuit Breakers D Curve (10–20X In Current Rating)—Designed for Inductive Loads 1 D Curve (10–20X In Current Rating)—Designed for Inductive Loads, continued 1 Notes protection devices. Per the intent of NEC (National Electrical Code), Article 240, and CEC (Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to provide overcurrent protection within an appliance or other electrical equipment where branch circuit overcurrent protection is already provided, or is not required. ordering. 3 IEC 60947-2 only. Amperes Single-Pole 2 Catalog Number Two-Pole Catalog Number Three-Pole Catalog Number 0.5 FAZ-D0.5/1-SP FAZ-D0.5/2 FAZ-D0.5/3
1 FAZ-D1/1-SP FAZ-D1/2 FAZ-D1/3
2 FAZ-D2/1-SP FAZ-D2/2 FAZ-D2/3
3 FAZ-D3/1-SP FAZ-D3/2 FAZ-D3/3
4 FAZ-D4/1-SP FAZ-D4/2 FAZ-D4/3
5 FAZ-D5/1-SP FAZ-D5/2 FAZ-D5/3
6 FAZ-D6/1-SP FAZ-D6/2 FAZ-D6/3
7 FAZ-D7/1-SP FAZ-D7/2 FAZ-D7/3
8 FAZ-D8/1-SP FAZ-D8/2 FAZ-D8/3
10 FAZ-D10/1-SP FAZ-D10/2 FAZ-D10/3
13 FAZ-D13/1-SP FAZ-D13/2 FAZ-D13/3
15 FAZ-D15/1-SP FAZ-D15/2 FAZ-D15/3
16 FAZ-D16/1-SP FAZ-D16/2 FAZ-D16/3
20 FAZ-D20/1-SP FAZ-D20/2 FAZ-D20/3
25 FAZ-D25/1-SP FAZ-D25/2 FAZ-D25/3
30 FAZ-D30/1-SP FAZ-D30/2 FAZ-D30/3
32 FAZ-D32/1-SP FAZ-D32/2 FAZ-D32/3
40 FAZ-D40/1-SP FAZ-D40/2 FAZ-D40/3
50 3 FAZ-D50/1-SP FAZ-D50/2 FAZ-D50/3 63 3 FAZ-D63/1-SP FAZ-D63/2 FAZ-D63/3 Amperes Four-Pole Single-Pole + Neutral Three-Pole + Neutral 0.5 FAZ-D0.5/4 FAZ-D0.5/1N FAZ-D0.5/3N
1 FAZ-D1/4 FAZ-D1/1N FAZ-D1/3N
2 FAZ-D2/4 FAZ-D2/1N FAZ-D2/3N
3 FAZ-D3/4 FAZ-D3/1N FAZ-D3/3N
4 FAZ-D4/4 FAZ-D4/1N FAZ-D4/3N
5 FAZ-D5/4 FAZ-D5/1N FAZ-D5/3N
6 FAZ-D6/4 FAZ-D6/1N FAZ-D6/3N
7 FAZ-D7/4 FAZ-D7/1N FAZ-D7/3N
8 FAZ-D8/4 FAZ-D8/1N FAZ-D8/3N
10 FAZ-D10/4 FAZ-D10/1N FAZ-D10/3N
13 FAZ-D13/4 FAZ-D13/1N FAZ-D13/3N
15 FAZ-D15/4 FAZ-D15/1N FAZ-D15/3N
16 FAZ-D16/4 FAZ-D16/1N FAZ-D16/3N
20 FAZ-D20/4 FAZ-D20/1N FAZ-D20/3N
25 FAZ-D25/4 FAZ-D25/1N FAZ-D25/3N
30 FAZ-D30/4 FAZ-D30/1N FAZ-D30/3N
32 FAZ-D32/4 FAZ-D32/1N FAZ-D32/3N
40 FAZ-D40/4 FAZ-D40/1N FAZ-D40/3N
50 3 FAZ-D50/4 FAZ-D50/1N FAZ-D50/3N 63 3 FAZ-D63/4 FAZ-D63/1N FAZ-D63/3N
V9-T1-32 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com FAZ UL 1077 Auxiliary Contacts FAZ UL 1077 Busbar System Pin T ype Incoming Supply T erminals Pin T ype Incoming Supply T erminals—Single-Phase Only Protective Accessories Bus Incoming Supply T erminals Busbar End Cap Notes 1 Voltage of FAZ-NA circuit breaker is limited to 300V with this auxiliary contact installed. 2 Do not cut commoning link. 3 A maximum of three commoning links may be used in conjunction. Each breaker connected to the commoning link must have the same number of poles for proper use. 4 Not for use with ring-tongue circuit breakers. 5 Bus may be center fed for high current capacity. Description Catalog Number Two-pole contact or auxiliary contact/trip indicating contact Z-NHK 1 Auxiliary contact Z-IHK-NA Shunt trip 110–415 Vac FAZ-XAA-NA110-415VAC Shunt trip 12–110 Vac FAZ-XAA-NA12-110VAC Padlock hasp IS/SPE-1TE Busbar—single-pole, 6 terminals 2345 Z-SV/UL-16/1P-1TE/6 Busbar—single-pole, 12 terminals 2345 Z-SV/UL-16/1P-1TE/12 Busbar—single-pole, 18 terminals 2345 Z-SV/UL-16/1P-1TE/18 Busbar—two-pole, 6 terminals 2345 Z-SV/UL-16/2P-2TE/6 Busbar—two-pole, 12 terminals 2345 Z-SV/UL-16/2P-2TE/12 Busbar—two-pole, 18 terminals 2345 Z-SV/UL-16/2P-2TE/18 Busbar—three-pole, 6 terminals 2345 Z-SV/UL-16/3P-3TE/6 Busbar—three-pole, 12 terminals 2345 Z-SV/UL-16/3P-3TE/12 Busbar—three-pole, 18 terminals 2345 Z-SV/UL-16/3P-3TE/18 Three-pole busbar shroud ZV-BS-UL Extension terminal—35 mm2 (2–14 AWG) Z-EK/35/UL Bus connector—conductors up to 50 mm2 (~1/0 AWG) Z-EB/50/UL Standard Auxiliary Contacts 1NO/1NC Installs on left side of FAZ or shunt trip Max. one per FAZ (1077) device Switches when FAZ is tripped electrically or manually
230 Vac FAZ-XHIN11
Installs on left side of FAZ or shunt trip Max. one per FAZ (1077) device Switches when FAZ is tripped electrically or manually
230 Vac FAZ-XHINW1
Auxiliary/T rip Indicating Contact Small selector screw changes mode Two Form C (changeover) contacts Installs on left side of FAZ or shunt trip Auxiliary contacts switch when FAZ is tripped electrically or manually Trip indicating contact switches only when FAZ is tripped electrically
230 Vac FAZ-XAM002
Prevents FAZ from operating unless voltage is present Installs on left side of FAZ Includes test button
115 Vac FAZ-XUA(115VAC)
230 Vac FAZ-XUA(230VAC)
400 Vac FAZ-XUA(400VAC)
Installs on left side of FAZ 12–110 Vac 12–60 Vdc FAZ-XAA-C-12-110VAC 110–415 Vac 110–230 Vdc FAZ-XAA-C-110-415VAC Rated Operational Current Number of Poles per Device Number of Terminals Catalog Number 5 Without Auxiliary Contacts 80A 1 57 BB-UL-18/1P-1M/57 25 6 BB-UL-18/2P-2M/56 35 7 BB-UL-18/3P-3M/57 100A 1 57 BB-UL-25/1P-1M/57 25 6 BB-UL-25/2P-2M/56 35 7 BB-UL-25/3P-3M/57 Auxiliary/T rip Indicating Contacts 80A 1 37 BB-UL-18/1P-1,5M/37 24 6 BB-UL-18/2P+AS-2,5M/46 34 8 BB-UL-18/3P+AS-3,5M/48 100A 1 37 BB-UL-25/1P-1,5M/37 24 6 BB-UL-25/2P+AS-2,5M/46 34 8 BB-UL-25/3P+AS-3,5M/48 Description Catalog Number Accommodates conductors from 6–35 mm 2/#10–2 AWG 4–5.5 Nm/35–50 lb-in / Two- and three-pole BB-UL-TEP/35 Description Catalog Number Accommodates conductors from 6–35 mm2/#10–2 AWG 4–5.5 Nm/35–50 lb-in BB-UL-TEPA/35 Description Catalog Number For covering unused terminals BB-IP/5 Prevents reactivation of the device during maintenance Holds one padlock IS/SPE-1TE Description Catalog Number 50 mm2 #14–1 AWG
75 Deg wire
115 A/Y , 480V UL
160 A/Y 690V IEC
Description Poles Catalog Number Install after cutting busbar Protects end of busbar 2 and 3 BB-UL-EC/3
1 BB-UL-EC/1
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-33 1.1Circuit Protection Circuit Breakers Series NRX Low Voltage Power Breakers Features
- Rogowski coil does not saturate like iron core sensors, and one sensor accommodates 200–1600A range. Never change a sensor, and NO CTs are required
- Tension clamp secondary terminals—10A continuous rating at 600V meets UL/CSA/RoHS and UL -94 V0. Mounted directly to fixed breaker or drawout cassette they reduce wiring and provide clean, organized wiring schemes
- Breaker mounted communication modules for INCOM™, Modbus ® and PROFIBUS® mount directly to the cassette, reducing the space and room required for communication capability
- With the patent pending simple design of the fold-up cassette, all items in a cassette are replaceable without removing the cassette from the cell
- Plug-and-play accessories—no special tools needed. Accessories come with plug and wires ready to install Series NRX™ Low Voltage Power Breakers
V9-T1-34 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com Series NRX Power Breakers (Exclusionary Rules Apply) Note 1 Contact Eaton for available voltages. Not all voltages are currently available. Breaker Frame Size N = Type NF, 630–1600A, (70 mm pole spacing) Standard, Mechanism, Device S = UL 1066, stored energy, power breaker X = UL 489, stored energy, insulated case breaker E = IEC 60947-2, stored energy, air breaker Fault Current Rating S4 = 42 kA at 480 Vac UL or 415 Vac IEC S5 = 50 kA at 480 Vac UL or 415 Vac IEC S6 = 65 kA at 480 Vac UL or 415 Vac IEC Frame Rating (Amperes) 07 = 630 (IEC only) 08 = 800 10 = 1000 (IEC only) 12 = 1200 (UL only) 13 = 1250 (IEC only) 16 = 1600 (On NF: IEC only) Poles, Phasing 3 = Three-pole, ABC 4 = Four-pole, NABC Mounting Configuration W = Drawout B = Fixed mount rear connect, mounting bracket, with secondary terminal row R = Fixed mount rear connect, surface mount, with secondary terminal row T = Fixed mount front connect, surface mount, cable connect, with secondary terminal row F = Fixed mount front connect, mounting bracket, bus connect, with secondary terminal row S = Fixed mount front connect, surface mount, bus connect, with secondary terminal row Trip Unit 52 = 520 LSI, no ZSI 53 = 520 LSI, with ZSI 5G = 520 LSIG, no ZSI 5H = 520 LSIG, with ZSI M2 = 520M LSI, no ZSI, 24 Vdc M3 = 520M LSI, with ZSI, 24 Vdc MA = 520M LSIA, no ZSI, 24 Vdc MB = 520M LSIA, with ZSI, 24 Vdc MG = 520M LSIG, no ZSI, 24 Vdc MH = 520M LSIG, with ZSI, 24 Vdc R2 = 520M LSI, no ZSI, 24 Vdc, with Arcflash Reduction Maintenance System™ R3 = 520M LSI, with ZSI, 24 Vdc, with Arcflash Reduction Maintenance System RA = 520M LSIA, no ZSI, 24 Vdc, with Arcflash Reduction Maintenance System RB = 520M LSIA, with ZSI, 24 Vdc, with Arcflash Reduction Maintenance System RG = 520M LSIG, no ZSI, 24 Vdc, with Arcflash Reduction Maintenance System RH = 520M LSIG, with ZSI, 24 Vdc, with Arcflash Reduction Maintenance System SW = Non-auto switch Rating Plug (Amperes) 1 = 200 2 = 250 3 = 300 4 = 400 5 = 500 6 = 600 7 = 630 8 = 800 A = 1000 B = 1200 C = 1250 D = 1600 Shunt Trip 1 N = No shunt trip A = 110–127 Vac/Vdc R = 208–240 Vac/Vdc L = 24 Vdc H = 48 Vdc Motor Operator 1 M = Manually operated B = 110–125 Vac W = 110–125 Vdc T = 208–250 Vac P = 220–250 Vdc L = 24 Vdc H = 48 Vdc Spring Release, Latch Check Switch 1 N = No spring release, no LCS A = 110–127 Vac/Vdc, no LCS R = 208–240 Vac/Vdc, no LCS N S S6 08 3 W 52 8 A B A N 4 X N D X UVR, Second Shunt Trip 1 N = None A = 110–125 Vac/Vdc UVR R = 220–250 Vac/Vdc UVR 1 = 110–127 Vac/Vdc second shunt trip 2 = 208–240 Vac/Vdc second shunt trip Auxiliary, Switches, Label Language 1 E = No auxiliary switches, no label (parent) 2 = 2 Form C, English 4 = 4 Form C, English Trip Indicator and Bell Alarm/OTS, Secondary Terminal Blocks 1 N = No indicator, no OTS, secondary terminal blocks per breaker options X = Trip indicator provided, no OTS, secondary terminal blocks per breaker options Z = Trip indicator provided, 2 Form C OTS, secondary terminal blocks per breaker options M = Interlock trip indicator provided, no OTS, secondary terminal blocks per breaker options Y = Trip indicator provided, 2 Form C OTS, secondary terminal blocks per breaker options 1 = No indicator, no OTS, full complement secondary terminal blocks 2 = Trip indicator, no OTS, full complement secondary terminal blocks 3 = Trip indicator provided, 2 Form C OTS, full complement secondary terminal blocks 4 = Interlock trip indicator provided, no OTS, full complement secondary terminal blocks 5 = Interlock trip indicator provided, 2 Form C, full complement secondary terminal blocks Future Use X = All product Drawout Breaker Shipping, Fixed Breaker Terminals, Door Frame Kit D = Drawout (or parent) breaker shipping alone, without door frame kit C = Drawout breaker in cassette, no shutters, no terminals, with door frame kit K = Fixed breaker, no adapters, rear connector, with door frame kit, with mounting feet, with door frame kit A = Terminal adapters for rear connect, short vertical/horizontal, with door frame kit E = Terminal adapters for rear connect, long vertical/horizontal, with door frame kit F = Terminal adapters for rear connect, with mounting feet, short vertical/horizontal, with door frame kit H = Terminal adapters for rear connect, with mounting feet, long vertical/horizontal, with door frame kit 1 = Drawout breaker in cassette, no shutters, short vertical/horizontal, with door frame kit 2 = Drawout breaker in cassette, no shutters, long vertical/horizontal, with door frame kit 4 = Drawout breaker in cassette, with shutters, short vertical/horizontal, with door frame kit 5 = Drawout breaker in cassette, with shutters, long vertical/horizontal, with door frame kit 9 = Drawout breaker in cassette, with shutters, no terminals, with door frame kit Padlock Provisions, Key Lock Provisions, Operations Counter 1 N = No PB covers, none, no counter
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-35 1.1Circuit Protection Circuit Breakers Catalog Number Selection Series NRX Cassettes Product Selection Series NRX Low Voltage Power Breakers Notes 1 See Page V9-T1-34 for cassette selection for drawout breakers. 2 See selection above for accessories in positions 12–20. Breaker Frame Industry Standard Fault Current Rating (kAIC) Frame Rating in Amperes Poles Mounting Trip Unit Rating Plug Part Number 2 N UL 1066 42 800 3 Drawout 1 520 LSI (No ZSI) 800 NSS4083W528 N UL 1066 42 800 4 Fixed 520 LSI (No ZSI) 800 NSS4084B528 N UL 1066 50 800 3 Drawout 1 520 LSI (No ZSI) 800 NSS5083W528 N UL 1066 50 800 4 Fixed 520 LSI (No ZSI) 800 NSS5084B528 N UL 1066 65 800 3 Drawout 1 520 LSI (No ZSI) 800 NSS6083W528 N UL 1066 65 800 3 Fixed 520 LSI (No ZSI) 800 NSS6083B528 N UL 1066 65 800 4 Drawout 1 520 LSI (No ZSI) 800 NSS6084W528 N UL 1066 65 800 4 Fixed 520 LSI (No ZSI) 800 NSS6084B528 N UL 489 42 800 3 Drawout 1 520 LSI (No ZSI) 800 NXS4083W528 N UL 489 42 1200 4 Drawout 1 520 LSI (No ZSI) 1200 NXS4124W52B N UL 489 50 800 3 Fixed 520 LSI (No ZSI) 800 NXS5083B528 N UL 489 50 1200 4 Fixed 520 LSI (No ZSI) 1200 NXS5124B528 N UL 489 65 800 3 Drawout 1 520 LSI (No ZSI) 800 NXS6083W528 N UL 489 65 800 4 Fixed 520 LSI (No ZSI) 800 NSS6084B528 N UL 489 65 1200 3 Drawout 1 520 LSI (No ZSI) 1200 NXS6123W52B N UL 489 65 1200 4 Fixed 520 LSI (No ZSI) 1200 NXS6124B52B N IEC 42 630 3 Drawout 1 520 LSI (No ZSI) 630 NES4073W527 N IEC 42 1600 4 Drawout 1 520 LSI (No ZSI) 1600 NES4164W52D N IEC 50 630 3 Fixed 520 LSI (No ZSI) 630 NES5073B527 N IEC 50 1600 4 Fixed 520 LSI (No ZSI) 1600 NES5164B52D N IEC 65 630 3 Drawout 1 520 LSI (No ZSI) 630 NES6073W527 N IEC 65 800 4 Fixed 520 LSI (No ZSI) 800 NES6084B528 N IEC 65 1250 3 Fixed 520 LSI (No ZSI) 1250 NES6133B52C N IEC 65 1600 4 Drawout 1 520 LSI (No ZSI) 1600 NES6164W52D Poles and Phasing (Facing Front of Breaker) 3 = Three-pole ABC 4 = Four-pole NABC Continuous Ampere Range 08 = 800A (UL 1066) 12 = 800–1200A (UL 489) 16 = 630–1600A (IEC) Arc Hood A = Arc hood installed (default) TOC Switches (Truck Operated Cell) N = Not included (default) Cassette Family and Breaker Frame NS = UL 1066 N Frame NX = UL 489 N Frame NE = IEC N Frame Load Terminal Connections F = With flat tapped pads only G = With vertical/horizontal bus adapter kit (short style) H = With front-connected kit N = No cassette stabs (interunit only) Future N = None Future N = None Cassette Shipping C = Cassette only B = Breaker shipped in cassette Shutters N = Not included (default) S = Included NX 12 3 F A B N S N N N C Secondary Contact Terminals Installed N = None B = Breaker defined, when breaker ships in cassette F = Full complement C = Common options when cassette ships alone Door Frame Gasket and Rejection Kits B = Door kit included (default), with rejection kit
V9-T1-36 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com Magnum Low Voltage Power Breakers Features
- Rated up to 6300A with interrupting ratings up to 200 kAIC and withstand ratings up to 100 kAIC
- Magnum® DS is UL 1066 listed for one-half second short-time withstand rating, and rated for 30 cycles. It is a switchgear class product to meet UL 1558 switchgear standards
- Magnum SB is a UL 1066 listed product with one-half second short-time withstand rating at three cycles to meet switchboard class product specifications, such as UL 891
- Magnum DS MDDX is the highest interrupting performance in a non-current limiting breaker construction rated up to 200 kAIC with 100 kAIC short-time withstand
- The Magnum DS, Magnum SB and Magnum IEC lines all offer the smallest double narrow 4000A frame available Magnum Low Voltage Power Breakers
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-37 1.1Circuit Protection Circuit Breakers Catalog Number Selection Magnum ANSI/UL Low Voltage Power Breakers Breaker Type MD = Magnum DS SB = Magnum switchboard Frame Type S = Standard or double N = Narrow D = Double (MDDX only) Interrupting/ Withstand Rating 4 = 42 5 = 50 6 = 65 8 = 85 C = 100 E = 150 (DSE) X = 200 (DSX) L = 200 (DSL) Poles and Neutral (Facing Front of Breaker) 3 = Three-pole 4 = Four-pole, neutral left MD S 4 12 3 V E A 06 MU A W C H N E H K L A X Continuous Amperes and Phasing (Facing Front of Breaker) 08 = 800 ABC 12 = 1200 ABC 16 = 1600 ABC 20 = 2000 ABC 25 = 2500 ABC 30 = 3000 ABC 32 = 3200 ABC or ABCABC 3N = 3200 AABBCC 4N = 4000 AABBCC 5N = 5000 AABBCC 6N = 6000 AABBCC 40 = 4000 ABCABC 50 = 5000 ABCABC 60 = 6000 ABCABC Mounting Configuration and Load Terminals H = Fixed horizontal V = Fixed vertical L = Drawout (MDN) W = Drawout (MDS) Nameplate Language E = English A = Spanish Current Limiter Selection A =N o n - D S L (no limiter) D =M A 2 5 0 E =M A 3 0 0 F =M A 4 0 0 G =M A 6 0 0 H = MA800 K = MB1200 L = MB1600 M = MB2000 N = MD2500 P = MD3000 Sensor and Rating Plug Rating NN = None 01 = 100 02 = 200 05 = 250 03 = 300 04 = 400 06 = 600 08 = 800 10 = 1000 12 = 1200 13 = 1250 16 = 1600 20 = 2000 25 = 2500 30 = 3000 32 = 3200 40 = 4000 50 = 5000 60 = 6000 Trip Unit and Protection (and External Control Voltage When Required) NN = Non-automatic (no trip unit) 22 = 220 + LI 52 = 520 LSI 5G = 520 LSIG M2 = 520M LSI MT = 520M LSI (24/48 Vdc) MU = 520M LSI (120 Vac) MV = 520M LSI (240 Vac) MQ = 520M LSI (125 Vac) MG = 520M LSIG MH = 520M LSIG (24/48 Vdc) MM = 520M LSIG (120 Vac) MN = 520 LSIG (240 Vac) MX = 520M LSIG (125 Vac) ME = 520M LSIA (24/48 Vdc) MC = 520 LSIA (120 Vac) MF = 520M LSIA (240 Vac) MZ = 520M LSIA (125 Vac) CT = 520MC LSI (24/48 Vdc) CU = 520MC LSI (120 Vac) CV = 520MC LSI (240 Vac) CQ = 520MC LSI (125 Vac) CH = 520MC LSIG (24/48 Vdc) CM = 520MC LSIG (120 Vac) CN = 520MC LSIG (240 Vac) CX = 520MC LSIG (125 Vac) CE = 520MC LSIA (24/48 Vdc) CC = 520MC LSIA (120 Vac) CF = 520MC LSIA (240 Vac) CY = 520MC LSIA (125 Vac) 1A = 1150 LSI (24/48 Vdc) 1C = 1150 LSI (120 Vac) 1E = 1150 LSI (240 Vac) 1Q = 1150 LSI (125 Vac) 1F = 1150 LSIG (24/48 Vdc) 1G = 1150 LSIG (120 Vac) 1H = 1150 LSIG (240 Vac) 1X = 1150 LSIG (125 Vac) 1J = 1150 LSIA (24/48 Vdc) 1K = 1150 LSIA (120 Vac) 1M = 1150 LSIA (240 Vac) 1Y = 1150 LSIA (125 Vac) Shunt Trip (ST) N = None A = 110–127 Vac/Vdc R = 208–240 Vac/Vdc C = 24 Vdc H = 48 Vdc Motor Operator M = Manual operated N = 110–125 Vac W = 110–125 Vdc T = 220–250 Vdc P = 220–240 Vac L = 24 Vdc K = 48 Vdc Spring Release Device (SRD) N = None A = 110–127 Vac/Vdc R = 208–240 Vac/Vdc C = 24 Vdc H = 48 Vdc Undervoltage Release (UVR) or 2nd Shunt Trip (ST) N = None A = UVR (110–127 Vac) R = UVR (208–240 Vac) C = UVR (24 Vdc) H = UVR (48 Vdc) E = UVR (110–125 Vdc) F = UVR (220–250 Vdc) J = UVR (480 Vac) K = UVR (600 Vac) 1 = 2nd ST (110–127 Vac/Vdc) 2 = 2nd ST (208–240 Vac/Vdc) 3 = 2nd ST (24 Vdc) 4 = 2nd ST (48 Vdc) Bell Alarms Switch (OTS) with 2a/2b Contacts and/or Mechanical Trip Indicator OTS 2a/2b Trip Indicator E = N = Y = No OTS No OTS With OTS No indicator With indicator With indicator Auxiliary Switch N = None 2 = 2A/2B 4 = 4A/4B 6 = 6A/6B Padlock Provisions for Blocking Close and/or Open ACB Manual Pushbuttons N = None M = Metal (block close and open) P = Plastic (block close and open) C = Metal (block close only) H = Plastic (block close only) S = Metal swbd lock-off (block close, depress open) Operations Counter and/or Keylock Provisions Counter Keylock Provisions N = K = C = R = A = Y = L = H = No counter No counter No counter No counter Counter Counter Counter Counter No lock Kirk lock Castell lock Ronis lock No lock Kirk lock Castell lock Ronis lock Latch Check Switch/Trip Unit Metering Voltage Connection for Digitrip 1150 Trip Unit Latch Check Switch
1150 Voltage
N = M = L = Y = C = D = None None LCS wired to SRD LCS wired to SRD LCS wired external LCS wired external Upper terminals Lower terminals Upper terminals Lower terminals Upper terminals Lower terminals Breaker Shipping Options and Instructions A = Fixed breaker alone with door kit F = Fixed breaker alone without door kit A = Drawout breaker alone without door frame kit C = Drawout breaker in cassette (unwired) P = Drawout breaker in cassette (prewired) S = Drawout breaker in cassette (shutters) W = Drawout breaker in cassette (prewired and shutters) Double frame drawout breakers ship without cassette drawout. ACBs ship in narrow and universal cassettes only. Frame Use X = All breakers
V9-T1-38 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com Magnum ANSI/UL Low Voltage Air Circuit Breaker Cassettes Cassette Family M = Standard or double frame L = Narrow frame S = SB standard or double frame T = SB narrow frame Continuous Amperes 16 = Up to 1600A 20 = Up to 2000A 32 = 2500 to 3200A 40 = 4000A 50 = 5000A Poles 3 = Three-pole 4 = Four-pole Cassette Frame and Rear Terminals P = Basic cassette (without vertical bus stabs) C = Basic cassette with stabs (with vertical bus stab kit) H = Narrow frame cassette (with horizontal terminal pads) U = Universal cassette (with universal terminal pads) Future Use E = SB cassette (150 kAIC) N = Cassettes (up to 100 kA) L = MDSL cassettes (200 kA) X = MDSX cassettes (200 kA) D = MDDX breaker Arc Hood A = Arc hood installed Door Frame and Gasket Kit DN = Door frame and gasket kit included XN = Door frame and gasket kit not included Cassette Shipping CA = Cassette only BA = Breaker shipped in cassette Cassette Wiring N = Unwired W = Cassettes wired Future Use NNN = All cassettes Shutters N = No shutters S = Shutters installed M E 32 3 C A DN N NNN W C
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-39 1.1Circuit Protection Circuit Breakers Magnum IEC Low Voltage Air Circuit Breakers Auxiliary Switch N = None 2 = 2A/2B 4 = 4A/4B 6 = 6A/6B Breaker Frame I = Standard or double N = Narrow K = Special
1100 Vac ACB
Sensor and Rating Plug Rating NN = None 02 = 200 05 = 250 03 = 300 04 = 400 06 = 600 07 = 630 08 = 800 10 = 1000 12 = 1200 13 = 1250 16 = 1600 20 = 2000 25 = 2500 30 = 3000 32 = 3200 40 = 4000 50 = 5000 63 = 6300 Nameplate Language E = English A = Spanish Poles and Neutral (Facing Front of Breaker) 3 = Three 4 = Four (neutral left) R = Four (reserved for neutral right) Future Use X = All ACBs ACB Shipping Instructions A = Fixed ACB with door kit F = Fixed ACB without door kit A = D/O ACB only without door kit C = D/O ACB in cassette (unwired) P = D/O ACB in cassette (prewired) S = D/O ACB in cassette (shutters) W = D/O ACB in cassette (prewired and shutters) Double frame D/O ACBs ship without cassette Shunt Trip Attachment (STA) N = None A = 110–127 Vac R = 208–240 Vac C = 24 Vdc H = 48 Vdc Bell Alarms Switch (OTS) with 2a/2b Contacts and/or Mechanical Trip Indicator OTS 2a/2b Trip Indicator E = N = Y = No OTS No OTS With OT No indicator With indicator With indicator Operations Counter and/or Keylock Provisions Counter Keylock Provisions N = K = C = R = A = T = L = H = No counter No counter No counter No counter Counter Counter Counter Counter No lock Kirk lock Castell lock Ronis lock No lock Kirk lock Castell lock Ronis lock MW I 4 08 3 H E A–0 2 22 A M A A 2 E M K L A X Motor Operator M = Manual operated N = 110–125 Vac W = 110–125 Vdc T = 220–250 Vdc P = 220–250 Vac L = 24 Vdc K = 48 Vdc Spring Release Device (SRD) N = None A = 110–127 Vac/Vdc R = 208–240 Vac/Vdc C = 24 Vdc H = 48 Vdc Undervoltage Release (UVR) or 2nd Shunt Trip Attachment (STA) N = None A = 110–127 Vac R = 208–240 Vac C = 24 Vdc H = 48 Vdc E = 110–125 Vdc F = 220–250 Vdc G = 32 Vdc X = 380–415 Vac J = 480 Vac K = 600 Vac 1 = 2nd STA (110–127 Vac/Vdc) 2 = 2nd STA (208–250 Vac/Vdc) 3 = 2nd STA (24 Vdc) 4 = 2nd STA (48 Vdc) Continuous Amperes and Phasing (Facing Front of Breaker) 08 = 800 ABC 10 = 1000 ABC 12 = 1250 ABC 16 = 1600 ABC 20 = 2000 ABC 25 = 2500 ABC 32 = 3200 ABC 4N = 4000 AABBCC 5N = 5000 AABBCC 6N = 6300 AABBCC 40 = 4000 ABCABC 50 = 5000 ABCABC 60 = 6300 ABCABC Mounting Configuration and Load Terminals H = Fixed horizontal V = Fixed vertical L = Drawout horizontal Latch Checking Switch/Trip Unit Metering Voltage Connection for Digitrip 1150 Trip Unit Latch Check Switch N = M = L = Y = C = D = None None LCS wired to SRD LCS wired to SRD LCS wired external LCS wired external Upper terminals Lower terminals Upper terminals Lower terminals Upper terminals Lower terminals Trip Unit Protection, (and External Control Voltage When Required) NN = Non-automatic (no trip unit) 22 = 220 LI 52 = 520 LSI 5W = 520i LSIG M2 = 520M LSI MT = 520M LSI (24–48 Vdc) MU = 520M LSI (120 Vac) MV = 520M LSI (240 Vac) MW = 520Mi LSIG MJ = 520Mi LSIG (24–48 Vdc) MK = 520Mi LSIG (120 Vac) ML = 520Mi LSIG (240 Vac) ME = 520M LSIA (24–48 Vdc) MC = 520M LSIA (120 Vac) MF = 520M LSIA (240 Vac) CT = 520MC LSI CU = 520MC LSI CV = 520MC LSI CE = 520MC LSIA CC = 520MC LSIA CF = 520MC LSIA CJ = 520MCi LSIG CK = 520MCi LSIG CL = 520MCi LSIG 1W = 1150i LSI (24–48 Vdc) 1N = 1150i LSI (120 Vac) 1P = 1150i LSI (240 Vac) 1R = 1150i LSIG/A (24–48 Vdc) 1S = 1150i LSIG/A (120 Vac) 1T = 1150i LSIG/A (240 Vac) Interrupting ICU 4 = 40 kA 5 = 50 kA 6 = 65 kA 8 = 85 kA C = 100 kA 2 = 25 kA (1100 Vac MWK) Padlock Provisions for Blocking Close and/or Open ACB Manual Pushbuttons N = None M = Metal (block close and open) P = Plastic (block close and open) C = Metal (block close only) H = Plastic (block close only)
V9-T1-40 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com Magnum IEC Low Voltage Air Circuit Breaker Cassettes Continuous Amperes 20 = Up to 2000A 32 = 2500–3000A 40 = 4000A 63 = 5000–6300A Arc Hood A = Arc hood for 690 Vac K = Arc hood for 1100 Vac Future Use N = All cassettes Rear Terminals H = Horizontal stabs (upper and lower terminals) Cassette Family E = Standard or double frame IEC (690 and 1100 Vac) N = Narrow frame IEC Poles 3 = Three-pole 4 = Four-pole Cassette Wiring N = Unwired W = Cassette wired Cassette Wiring C = Cassette only E N 20 3 H A N N N N N N N C Future Use N = All cassettes Door Frame and Gasket Kit X = Door frame and gasket kit included D = Door frame and gasket kit not included Future Use N = All cassettes Shutters N = No shutters S = Shutters installed Future Use N = All cassettes Future Use N = All cassettes
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-41 1.1Circuit Protection Circuit Breakers Product Selection Magnum DS Switchgear Class UL 1066 Low Voltage Power Circuit Breakers Notes 1 Interrupting ratings shown based on breaker equipped with integral Digitrip RMS trip unit. Interruption ratings for non-automatic breakers are equal to the published short time current rating. These interruption ratings are based on the standard duty cycle consisting of an open operation, a 15-second interval and a close-open operation, in succession, with delayed tripping in case of short-delay devices. The standard duty cycle for short time ratings consists of maintaining the rated current for two periods of 1/2 seconds each, with a 15-second interval of zero current between the two periods. 2 See Page V9-T1-40 for selection of trip unit and accessories. See Page V9-T1-40 for cassette selection for drawout breakers. 3 Magnum MDSL current limiting power circuit breaker with integral current limiters. Current limiter selected determines short ti me and maximum instantaneous trip rating. Maximum voltage rating is 600 Vac. 4 Product to be tested. Contact Eaton for product rating. 5 Magnum MDSX current limiting power circuit breaker with fast opening contacts. 6 Contact Eaton for availability. 7 Breaker applied in a tested fan-cooled enclosure. Frame Type RMS Symmetrical Current Ratings kA 50/60 Hz 1 Short Time Current Rating Frame AmperesInterrupting at 254 Vac Interrupting at 508 Vac Interrupting at 635 Vac Breaker Type 2 N a r r o w 4 24 24 24 2 8 0 0 MDN-408 50 50 50 50 MDN-508 65 65 65 65 MDN-608 100 100 65 20 MDN-C08 Standard 42 42 42 42 800 MDS-408 65 65 65 65 MDS-608 85 85 85 85 MDS-808 100 100 100 85 MDS-C08 200 200 200 — MDS-L08 3 200 200 4 30 MDS-X08 56 N a r r o w 4 24 24 24 2 1 6 0 0 MDN-416 50 50 50 50 MDN-516 65 65 65 65 MDN-616 100 100 65 30 MDN-C16 Standard 65 65 65 65 1600 MDS-616 85 85 85 85 MDS-816 100 100 100 85 MDS-C16 200 200 200 — MDS-L16 3 200 200 4 30 MDS-X16 5 N a r r o w 6 56 56 56 5 2 0 0 0 MDN-620 100 100 65 35 MDN-C20 Standard 65 65 65 65 2000 MDS-620 85 85 85 85 MDS-820 100 100 100 85 MDS-C20 200 200 200 — MDS-L20 3 200 200 4 30 MDS-X20 5 65 65 65 65 3200 MDS-632 85 85 85 85 MDS-832 100 100 100 85 MDS-C32 Double 200 200 4 50 3200 MDS-X32 5 Double (N) 85 85 4 85 4000 MDN-840 100 100 4 100 MDN-C40 D o u b l e 8 58 58 58 5 4 0 0 0 MDS-840 100 100 100 100 MDS-C40 200 200 4 50 MDS-X40 5 200 200 4 100 4000 MDD-X40 85 85 85 85 5000 MDS-850 100 100 100 100 MDS-C50 200 200 4 50 MDS-X50 57 200 200 4 100 MDD-X50 100 100 100 100 6000 MDS-C60 7 200 200 4 100 MDD-X60
V9-T1-42 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com Magnum SB Switchboard Class UL 1066 Insulated Case Low Voltage Power Circuit Breakers Notes 1 Interrupting ratings shown based on breaker equipped with integral Digitrip RMS trip unit. Interruption ratings for non-automatic breakers are equal to the published short time current rating. These interruption ratings are based on the standard duty cycle consisting of an open oper ation, a 15-second interval and a close-open operation, in succession, with delayed tripping in case of short-delay devices. The standard duty cycle for sh ort time ratings consists of maintaining the rated current for two periods of 1/2 seconds each, with a 15-second interval of zero current between the two pe riods. 2 Product to be tested. Contact Eaton for product rating. 3 Magnum SBSE current limiting power circuit breaker with fast opening contacts. 4 Breaker applied in a tested fan-cooled enclosure. Frame Type RMS Symmetrical Current Ratings kA 50/60 Hz 1 Short Time Current Rating Frame AmperesInterrupting at 254 Vac Interrupting at 508 Vac Interrupting at 635 Vac Breaker Type 2 N a r r o w 5 05 03 52 0 8 0 0 SBN-508 65 65 42 20 SBN-608 100 100 65 20 SBN-C08 Standard 65 65 65 20 800 SBS-608 100 100 85 20 SBS-C08 200 150 2 30 SBS-E08 3 N a r r o w 5 05 03 52 5 1 2 0 0 SBN-512 65 65 42 25 SBN-612 100 100 65 25 SBN-C12 Standard 65 65 65 25 1200 SBS-612 100 100 85 25 SBS-C12 200 150 2 30 SBS-E12 3 N a r r o w 5 05 03 53 0 1 6 0 0 SBN-516 65 65 42 30 SBN-616 100 100 65 30 SBN-C16 Standard 65 65 65 30 1600 SBS-616 100 100 85 30 SBS-C16 200 150 2 30 SBS-E16 3 N a r r o w 6 56 56 53 5 2 0 0 0 SBN-620 100 100 65 35 SBN-C20 Standard 65 65 65 35 2000 SBS-620 100 100 85 35 SBS-C20 200 150 2 30 SBS-E20 3 65 65 65 45 2500 SBS-625 100 100 85 45 SBS-C25 Double 200 150 2 50 SBS-E25 3 Standard 65 65 65 50 3000 SBS-630 100 100 85 50 SBS-C30 Double 200 150 2 50 SBS-E30 3 Double (N) 85 85 3 85 4000 SBN-840 100 100 3 100 SBN-C40 D o u b l e 8 58 58 58 5 SBS-840 100 100 100 100 SBS-C40 200 150 2 50 SBS-E40 3 85 85 85 85 5000 SBS-850 100 100 100 100 SBS-C50 200 150 2 50 SBS-E50 34 100 100 100 100 6000 SBS-C60 4
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-43 1.1Circuit Protection Circuit Breakers Magnum IEC 60947-2 Rated Low Voltage Air Circuit Breakers Note 1 Interrupting ratings shown based on breaker equipped with integral Digitrip RMS trip unit. Interruption ratings for non-automat ic breakers are equal to the published breaker Icw rating. rms Symmetrical Current Ratings kA 1 Fixed Internal Inst. Trip Available Current Sensor and Rating Plugs for Digitrip RMS Trip Unit (Establishes Breaker In Rating) Frame Amperes Breaker Type Frame Type Interrupting at
240 Vac ICU = ICS
440 Vac I
CU = ICS Interrupting at
690 Vac I
CU = ICS Withstand Rating I CW 1-Sec/3-Sec
800 MWN-408 Narrow 40 40 40 40/— — 200, 250, 300, 400, 630, 800
M W N - 5 0 8 N a r r o w 5 05 05 05 0 / — — M W N - 6 0 8 N a r r o w 6 56 56 56 5 / 4 0 — MWI-608 Standard 65 65 65 65/— — MWI-808 Standard 85 85 85 85/65 — MWI-C08 Standard 100 100 85 85/65 85
1000 MWN-410 Narrow 40 40 40 40/— — 200, 250, 300, 400, 630, 800, 1000
M W N - 5 1 0 N a r r o w 5 05 05 05 0 / — — M W N - 6 1 0 N a r r o w 6 56 56 56 5 / 4 0 — MWI-610 Standard 65 65 65 65/— — MWI-810 Standard 85 85 85 85/65 — MWI-C10 Standard 100 100 85 85/65 85
1250 MWN-412 Narrow 40 40 40 40/— — 200, 250, 300, 400, 630, 800, 1000, 1250
M W N - 5 1 2 N a r r o w 5 05 05 05 0 / — — M W N - 6 1 2 N a r r o w 6 56 56 56 5 / 4 0 — MWI-612 Standard 65 65 65 65/— — MWI-812 Standard 85 85 85 85/65 — MWI-C12 Standard 100 100 85 85/65 85
1600 MWN-516 Narrow 50 50 50 50/— — 200, 250, 300, 400, 630, 800, 1000, 1250,
1600M W N - 6 1 6 N a r r o w 6 56 56 56 5 / 4 0 — MWI-616 Standard 65 65 65 65/— — MWI-816 Standard 85 85 85 85/65 — MWI-C16 Standard 100 100 85 85/65 85
2000 MWN-520 Narrow 50 50 50 50/30 — 200, 250, 300, 400, 630, 800, 1000, 1250,
1600, 2000M W N - 6 2 0 N a r r o w 6 56 56 56 5 / 4 0 — MWI-620 Standard 65 65 65 65/50 — MWI-820 Standard 85 85 85 85/65 — MWI-C20 Standard 100 100 85 85/65 85
2500 MWI-625 Standard 65 65 65 65/— — 200, 250, 300, 400, 630, 800, 1000, 1250,
1600, 2000, 2500MWI-825 Standard 85 85 85 85/65 — MWI-C25 Standard 100 100 85 85/65 85
3200 MWI-632 Standard 65 65 65 65/50 — 200, 250, 300, 400, 630, 800, 1000, 1250,
1600, 2000, 2500, 3200MWI-832 Standard 85 85 85 85/65 — MWI-C32 Standard 100 100 85 85/65 85
4000 MWI-64N Double 65 65 65 65/— — 2000, 2500, 3200, 4000
M W I - 8 4 N D o u b l e 8 58 58 58 5 / — — MWI-C4N Double 100 100 100 100/— —
5000 MWI-85N Double 85 85 85 85/— — 2500, 3200, 4000, 5000
MWI-C5N Double 100 100 100 100/— —
6300 MWI-86N Double 85 85 85 85/— — 3200, 4000, 5000, 6300
MWI-C6N Double 100 100 100 100/— —
V9-T1-44 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com
1.2 Circuit Protection
Fuse Blocks and Fuse Holders Product Overview Fuse Blocks and Fuse Holders For our complete product offering, see Volume 4—Circuit Protection, CA08100005E. Description C350 Series Page V9-T1-45 T echnical Data Number of poles Up to 3 Mounting 35 mm flat or 32 mm asymmetrical DIN rail (with optional adapter) Terminal ratings 600V, 30A Housing construction Thermoplastic UL 94VO flammability rating Clip/terminal construction Tin-plated copper alloy Screw/pressure plate construction Zinc-plated steel Dielectric strength 1200V Approvals UL, CSA
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-45 1.2Circuit Protection Fuse Blocks and Fuse Holders C350 Series Fuse Blocks and Fuse Holders Features
- Space-saving design
- Rated 600V , 30A
- UL approved for motor loads Product Selection C350 Series Fuse Blocks and Fuse Holders Wire Termination Number of Poles 250V 600V 30A Catalog Number Carton Qty. 60A Catalog Number Carton Qty. 30A Catalog Number Carton Qty. 60A Catalog Number Carton Qty. Class H Fuse Holders Single collar (box lug)—sized to ampere rating
1 W231HA 10 W261HA 10 W631HA 10 W661HA 1
2 W232HA 5 W262HA 5 W632HA 5 W662HA 1
3 W233HA 5 W263HA 5 W633HA 1 W663HA 2
Combination of double quick-connect, 20A max., and binding head screw, #10 max., Cu/Al Combination of double quick-connect, 20A max., and pressure plate screw, #10 max., Cu only Class R Fuse Holders Single collar (box lug)—sized to ampere rating
1 WR231HA 10 — — WR631HA 10 — —
3 WR233HA 5 WR263HA 1 WR633HA 5 WR663HA 5
Combination of double quick-connect, 20A max., and binding head screw, #10 max., Cu/Al Combination of double quick-connect, 20A max., and pressure plate screw, #10 max., Cu only Class R Fuse Holder, T ype WRR Control T ransformer Fuse Block Combination of double quick-connect, 20A max., and pressure plate screw, #14–#10 Cu only
V9-T1-46 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com
1.3 Circuit Protection
Rotary Disconnect Switches Open Rotary Disconnects Product Overview Rotary Disconnect Switch Selection Guide Note
1 Q4 2010
Non-Fusible 16–80A R9 Series Non-Fusible 30–100A Compact R9 Series Non-Fusible 100–1200A Page V9-T1-48 Page V9-T1-50 Page V9-T1-52 Product Description R5 Series (UL 508 listed) products are manually operated modular switches. Load break switching and isolation provide safety solutions for any low voltage circuit, particularly for machine and control circuits. The R5 Series products are manual motor controllers suitable as motor disconnect. The R9 Series (UL 98 listed) non-fusible 30–100A compact range ensures making or breaking on load and safety isolation for low voltage electrical circuits, particularly for machine control circuits up to 600V. The R9 Series (UL 98 listed) non-fusible 100–1200A are manually operated multipole load-break switches. Quick-make, quick-break design provides safety isolation for any low voltage circuit. Approvals UL 508 listed, Guide NLRV , File E165150 CSA C22.2 No.14, File 217736 IEC 60947-3, EN 60947-3 CCC UL 98, File E222859 CSA 22.2 No. 4, File 217736 IEC 60947-3 EN 60947-3 UL 98, File E222859 CSA 22.2 No. 4, File 217736 IEC 60947-3 EN 60947-3 Fusible 30–800A R9 Series DC Rated Disconnects Manual Transfer Switches Page V9-T1-54 Page V9-T1-59 Page V9-T1-60 Product Description R9 Series (UL 98 listed) Fusible 30–800A manual operated multi-pole fusible disconnect switches use double break contacts per pole that ensure complete isolation of the fuse when the switch is in the OFF position. When installed with fuses, they provide protection for low voltage electrical installations against short circuit and overload. UL listed disconnect switches 600 Vdc for photovoltaic applications 100 to 400A R9 Series (UL 98 listed) DC rated disconnects are manually operated multi-pole load break switches. They provide safety isolation for any low voltage circuit in a photovoltaic application. R9 Series (UL 98 listed) non-fusible disconnects are heavy-duty manual transfer switches, they transfer load manually between two low voltage circuits and provide safety disconnection. These switches are extremely durable and are tested and approved for use in the most demanding applications as resistive load or total system applications. Approvals UL 98, File E222859 for 30 to 800A ratings UL 489, File E305341 for H Frame switches CSA 22.2 No. 4, File 217736 CSA 22.2 No. 5, File 217736, H Frame only IEC 60947-1, EN 60947-1 IEC 60947-3, EN 60947-3 CE mark NFPA ® 79 UL 98, cULus®, File E222859 CSA 22.2 No. 4, File 217736 1 IEC 60947-3 EN 60947-3 IEC 60-364-7-712 (Rules for the installations and sites special—photovoltaic applications) UL 98, cULus, File E222859 UL 1008 (2011) CSA 22.2 No. 4, File 217736 IEC 60947-3 EN 60947-3
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-47 1.3Circuit Protection Rotary Disconnect Switches Catalog Number Selection Disconnects External Handles Shafts Notes 1 HV at the end of some catalog numbers indicates use with H and V switches only. Not all handles are designed to go with all disconnects. Consult specific section of the catalog for available options. 2 H at the end of some catalog numbers indicates use with H Frame switches only. Not all shafts are designed to go with all discon nects. Consult specific section of the catalog for available options. UL Listing R5 = UL 508 R9 = UL 98 R4 = UL 489 R5 A 3 016 U Frame Designation A = UL 508 (16–40A) B = UL 508 (60–80A) C = UL 98 Non-fusible (30–100A modular) V = UL 98 Non-fusible (60–100A visible blade) D = UL 98 Non-fusible (100–200A) E = UL 98 Non-fusible (400A) F = UL 98 Non-fusible (600A) G = UL 98 Non-fusible (800–1200A) H = UL 489 Fusible (30A compact) I = UL 98 Fusible (30A) J = UL 98 Fusible (30–60A) K = UL 98 Fusible (60–100A) L = UL 98 Fusible (200A) M = UL 98 Fusible (400A) N = UL 98 Fusible (600–800A) Phase 2 = Two-pole 3 = Three-pole 4 = Four-pole Ampere Rating 016 =1 6 A 025 =2 5 A 030 =3 0 A 040 =4 0 A 060 =6 0 A 080 =8 0 A 100 = 100A 200 = 200A 400 = 400A 600 = 600A 800 = 800A 1000 = 1000A 1200 = 1200A Protection U = Non-fusible F = Fusible Fuse Type Accepted CC = Class CC J = Class J L = Class L Blank = Non-fusible device SH B 00 4X F Handle Type SH = Selector handle PH = Pistol handle Color B = Black/blue R = Red/yellow Size (Smallest to Largest) 00 = S i z e 0 0 0 = Size 0 1 = Size 1 2 = Size 2 3 = S i z e 3 4 = S i z e 4 NEMA Type Rating 12 = Type 1, 3R, 12 4X = Type 4, 4X Operation F = Front S = Right side Blank = Front or right side Additional Features 1 T = Test position function Blank = No test function Product Type SF = Shaft Length 55 =5 5 m m 90 =9 0 m m 150 =1 5 0 m m 200 =2 0 0 m m 320 =3 2 0 m m 400 =4 0 0 m m 500 =5 0 0 m m Applicable Handle Type SH = Selector handle PH = Pistol handle Shaft Cross Section 5x5 = 5 mm x 5 mm 6x6 = 6 mm x 6 mm 10x10 = 10 mm x 10 mm 12x12 = 12 mm x 12 mm 15x12 = 15 mm x 12 mm Additional Features 2 SF 150 SH 5X5
V9-T1-48 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com Rotary Disconnect Switches R5 Series Non-Fusible 16–80A Features
- Up to 65 kAIC short-circuit rating
- Direct or external operation
- Compact footprint
- DIN rail or base mount
- Wide range of accessories
- Modular design
- Padlockable design (direct, toggle and external handles) R5 Series Non-Fusible 16–80A Product Identification
1 External front handle
2 Shaft extension for external handle
3 Direct handle
4 Auxiliary contacts
5 Switched fourth-pole module
6 Terminal shroud
Note: For further details, please see the installation instructions supplied with each device.
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-49 1.3Circuit Protection Rotary Disconnect Switches Product Selection R5 Series Accessories Notes 1 Toggle version includes direct handle. 2 Available Q2 2011. 3 Includes shaft and accessory cap. Ampere Rating Three-Pole Toggle Switch Only 1 Three-Pole Rotary Switch Only Direct Handle Front and Right External Handle SH00 (Choose One) Front and Right External Handle SH0 (Choose One) Three-Position Front External Handle SH00 (Black) 2 Shaft for SH0 and SH00—5 x 5 mm— In (mm) 16 — R5A3016U DHR5 SH00 Black 3R, 12 SHB00N12 SH00 Red 3R, 12 SHR00N12 SH00 Black 4, 4X SHB00N4X SH00 Red 4, 4X SHR00N4X SH0 Black 3R, 12 SHB0N12 SH0 Red 3R, 12 SHR0N12 SH0 Black 4, 4X SHB0N4X SH0 Red 4, 4X SHR0N4X SH00 4, 4X I–0–II Open transition SHB00MTSOT SH00 4, 4X I–I+II–II Closed transition SHB00MTSCT 2.20 (55.5) SF55SH5X5 3.50 (90.0) SF90SH5X5 5.90 (150.0) SF150SH5X5 7.90 (200.0) SF200SH5X5 12.60 (320.0) SF320SH5X5 25 — R5A3025U
30 T5A3030U R5A3030U
40 T5A3040U R5A3040U
60 T5B3060U R5B3060U
80 T5B3080U R5B3080U
+ ++ Switch body Direct handle Switch body Shaft External handle+ + + Direct Operation External Operation Ampere Rating Switched Fourth-Pole Module Unswitched Neutral Module Auxiliary Contacts (Choose One) Terminal Shrouds Conversion Kit (Choose One) 2 Door Mounting Kit
16 S4PR516 UNMR5A 1NO + 1NC
I–0–II MTSCKR5OT Changeover switch Closed transition I–I+II–II MTSCKR5CT DMK
25 S4PR525
30 S4PR530
40 S4PR540
60 S4PR560
2 UNMR5B 1P
80 S4PR580 2
V9-T1-50 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com Rotary Disconnect Switches Non-Fusible 30–100A Compact Features
- Rating three-pole from 30A to 100A
- Direct or external operation handle (padlockable in ON position)
- Double breaking per phase
- Small footprint R9 Series Non-Fusible 30–100A Compact Product Identification
1 Direct handle
2 Door interlocked external handle
3 Shaft extension
4 Terminal shrouds
5 Unswitched neutral pole
6 Switch body
7 Switched fourth-pole module
8 Modular type auxiliary contacts
Note: For further details, please see the installation instructions supplied with each device. 5 6
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-51 1.3Circuit Protection Rotary Disconnect Switches Product Selection R9 Series 30–100A Ampere Rating (Frame) Number of Poles Switch Body Only Direct Handle Front and Right External Handle SH00 (Choose One) Front and Right External Handle SH0 (Choose One) Shaft for SH0 and SH00 Handles— In (mm) (Choose One) Switched Fourth-Pole Module Unswitched Neutral Module Auxiliary Contacts (Choose One) Terminal Shrouds (Choose One) (C Frame)
3 R9C3030U DHR9 SH00
3R, 12 SHB00N12 SH00 Red 3R, 12 SHR00N12 SH00 Black 4, 4X SHB00N4X SH00 Red 4 4X SHR00N4X SH0 Black 3R, 12 SHB0N12 SH0 Red 3R, 12 SHR0N12 SH0 Black 4, 4X SHB0N4X SH0 Red 4 4X SHR0N4X 2.20 (55.5) SF55SH5X5 3.50 (90.0) SF90SH5X5 5.91 (150.0) SF150SH5X5 7.87 (200.0) SF200SH5X5 12.60 (320.0) SF320SH5X5 S4PR930 Neutral UNMR9C 1NO + 1NC AC1NONC 2NO AC2N TS1R9 TS3R9CV (C Frame)
3 R9C3060U S4PR960
(C Frame)
3 R9C3100U S4PR9100
+ ++ Switch body Direct handle Switch body Shaft External handle+ + + Direct Operation External Operation
V9-T1-52 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com Rotary Disconnect Switches Non-Fusible 100–1200A Features
- High thermal and dynamic withstand ratings
- Arduous categories of applications
- High electrical and mechanical endurances R9 Series Non-Fusible 100–1200A Product Identification
2 Shaft extensions for external handle
3 Configurable U-type ACs, for pre-break and signalling or TEST
4 Terminal Screens
Note: For further details, please see the installation instructions supplied with each device.
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-53 1.3Circuit Protection Rotary Disconnect Switches Product Selection R9 Series Non-Fusible 100–1200A Notes 1 Top (line side) supplied as standard. 2 Auxiliary contact requires holder (catalog number ACHFG) when used on F and G Frame switches (non-fusible 600–1200A). 3 Each catalog number is for line or load side. For both line and load, please order two sets. Ampere Rating (Frame) Number of Poles Switch Body Only Direct Handle Door Interlocked External Pistol Handle (Choose One) Shaft Extensions for External Handle— In (mm) (Choose One) Auxiliary Contacts Terminal Screens (Choose One) Terminal Lugs 100 (D Frame)
3 R9D3100U DHR9DE Size 2, Black
1, 3R, 12 Defeatable PHB2N12F Size 2, Red 1, 3R, 12 Defeatable PHR2N12F Size 2, Black 4, 4X Defeatable PHB2N4XF Size 2, Red 4, 4X Defeatable PHR2N4XF 7.90 (200.0) SF200PH10X10 12.60 (320.0) SF320PH10X10 15.70 (400.0) SF400PH10X10 19.70 (500.0) SF500PH10X10 1NO + 1NC AC1N0NCDE AC1N0NCDELL 2NO + 2NC AC2N0NCDE AC2N0NCDELL 3-pole, Line side only TS3R9DT 3-pole, Load side only TS3R9DB 4-pole, Line or load side TS4R9DTB LK3R9DL
4 R9D4100U LK4R9DL
(D Frame)
3 R9D3200U LK3R9DL
4 R9D4200U LK4R9DL
(E Frame)
3 R9E3400U 3-pole, Line side only
3-pole, Load side only TS3R9EB 4-pole, Line or load side TS4R9ETB LK3R9EM
4 R9E4400U LK4R9EM
(F Frame)
3 R9F3600U DHR9FG Size 3, Black
4, 4X Defeatable PHB3N4XF Size 3, Red 4, 4X Defeatable PHR3N4XF Size 4, Black 4, 4X Defeatable PHB4N4XF Size 4, Red 4, 4X Defeatable PHR4N4XF 7.90 (200.0) SF200PH15X12 12.60 (320.0) SF320PH15X12 1.70 (400.0) SF400PH15X12 19.7 (500.0) SF500PH15X12 1NO AC U Type AC1N0R9 1NC AC U Type AC1NCR9 2 TS3R9F 1 LK3R9FN
4 R9F4600U TS4R9F 1 LK4R9FN
(G Frame)
3 R9G3800U TS3R9G 1 LK6R9G
LK8R9G 4 R9G4800U TS4R9G 1 1000 (G Frame)
3 R9G31000U
4 R9G41000U
(G Frame)
3 R9G31200U
4 R9G41200U
+ ++ Switch body Direct handle Switch body Shaft External handle+ + + Direct Operation External Operation
V9-T1-54 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com Rotary Disconnect Switches Fusible 30–800A
- Load break functionality
- Double break contacts
- Up to 200 kA short-circuit rating with Class CC, J or L fuses
- Compact footprints
- Defeatable pistol handles automatically re-latch when the panel door is closed
- Front or right side operation
- NFPA 79 compliant kits
- Two-, three- and four-pole devices R9 Series Fusible 30–800A R9 Fusible 30A/CC and 30A/J (H Frame)— Direct and External Operation Product Identification
1 External front handles
2 Direct handle
3 Shaft extensions for external handles
4 Configurable U Type ACs, for pre-break and signaling or TEST
R9 Fusible 30A/J–800A/L (I–N Frames)— Direct and External Operation Product Identification
2 External right side handle (not applicable for N Frame 600/800A)
4 Shaft extensions for external handles
5 Configurable U Type ACs, for pre-break and signaling or TEST
6 Side auxiliary contacts
7 Terminal shrouds
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-55 1.3Circuit Protection Rotary Disconnect Switches Product Selection Front and Right Side Operation Note 1 100 kA short-circuit rating. Ampere Rating (Frame) (Fuse Class) Number of Poles Switch Body Only Direct Handle External Selector Handle (Choose One) Shaft Extension for Selector Handle Only (Choose One) External Front Pistol Handle External Right Side Pistol Handle Compact (H Frame) (CC)
3 R4H3030FCC DHR9HC Black
1,3R,12 SHB0N12HV Red 1,3R,12 SHR0N12HV Black 4,4X SHB0N4XHV Red 4,4X SHR0N4XHV 7.90 (200.0) SF200SH5X5H Black 1,3R,12 PHB1N12F Red 1,3R,12 PHR1N12F Black 4,4X PHB1N4XF Red 4,4X PHR1N4XF Black 4,4X (w/ TEST Position) PHB1N4XFT Red 4,4X (w/ TEST Position) PHR1N4XFT (H Frame) (CC) 3 + switched neutral R4H3030FCCSN 12.60 320.0) SF320SH5X5H Compact (H Frame) (J) 3 R4H3030FJ DHR9HJ 15.70 (400.0) SF400SH5X5H (H Frame) (J) 3 + switched neutral R4H3030FJSN (I Frame) (CC)
3 R9I3030FCC DHR9J2M ——
4 R9I4030FCC
(J Frame) (J)
2 R9J2030FJ Black
4, 4X PHB1N4XS Red 4, 4X PHR1N4XS
3 R9J3030FJ
4 R9J4030FJ
(J Frame) (J)
2 R9J2060FJ
3 R9J3060FJ
4 R9J4060FJ
+ ++ Switch body Direct handle Switch body Shaft External handle+ + + Direct Operation External Operation
V9-T1-56 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com Rotary Disconnect Switches Front and Right Side Operation, continued Note 1 100 kA short-circuit rating. Ampere Rating (Frame) (Fuse Class) Number of Poles Switch Body Only Shaft Extensions for Pistol Handle Only In (mm) (Choose One) NFPA
79 Kit
(Choose One) S Type Auxiliary Contacts (Choose One) Terminal Shrouds Compact (H Frame) (CC) 3 R4H3030FCC 7.90 (200.0) SF200PH5X5 12.60 (320.0) SF320PH5X5 15.70 (400.0) SF400PH5X5 NFPA79H 1 AC NO AC1NOR9 1 AC NC AC1NCR — Integral to switch (H Frame) (CC) 3 + switched neutral R4H3030FCCSN Compact (H Frame) (J)
3 R4H3030FJ
(H Frame) (J) 3 + switched neutral R4H3030FJSN (I Frame) (CC) 3 R9I3030FCC 7.90 (200.0) SF200PH10X10 12.60 (320.0) SF320PH10X10 15.70 (400.0) SF400PH10X10 19.70 (500.0) SF500PH10X10 NFPA79JKL 1 AC NO + NC AC1NO1NCJ2N 2 AC NO + NC AC2NO2NCJ2N 1 AC NO + NC w/ TEST AC1NO1NCJ2NT 2 AC NO + NC w/ TEST AC2NO2NCJ2NT (J Frame) (J)
2 R9J2030FJ
(J Frame) (J)
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-57 1.3Circuit Protection Rotary Disconnect Switches Front and Right Side Operation, continued Note 1 200 kA short-circuit rating. Ampere Rating (Frame) (Fuse Class) Number of Poles Switch Body Only Direct Handle (Black) External Front Pistol Handle (Choose One) External Right Side Pistol Handle (Choose One) 60 1 (K Frame) (J)
2 R9K2060FJ DHR9J2M Black
1,3R,12 PHB2N12F Red 1,3R,12 PHR2N12F Black 4,4X PHB2N4XF Red 4,4X PHR2N4XF Black 4,4X (w/ TEST Position) PHB2N4XFT Red 4,4X (w/ TEST Position) PHR2N4XFT Black 4, 4X PHB2N4XS Red 4, 4X PHR2N4XS
3 R9K3060FJ
4 R9K4060FJ
(K Frame) (J)
2 R9K2100FJ
3 R9K3100FJ
4 R9K4100FJ
(L Frame) (J)
2 R9L2200FJ
3 R9L3200FJ
4 R9L4200FJ
(M Frame) (J)
3 R9M3400FJ —
4 R9M4400FJ
(N Frame) (J)
2 R9N2600FJ DHR9N Black
4, 4X PHB3N4XF Red 4,4X PHR3N4XF
3 R9N3600FJ
4 R9N4600FJ
(N Frame) (L)
2 R9N2800FL
3 R9N3800FL
4 R9N4800FL
V9-T1-58 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com Rotary Disconnect Switches Front and Right Side Operation, continued Note 1 200 kA short-circuit rating. Ampere Rating (Frame) (Fuse Class) Number of Poles Switch Body Only Shaft Extensions for External Handle In (mm) (Choose One) NFPA (Choose One) Auxiliary Contacts (Choose One) Terminal Shrouds 60 1 (K Frame) (J) 2 R9K2060FJ 7.90 (200.0) Pistol SF200PH10X10 12.60 (320.0) Pistol SF320PH10X10 15.70 (400.0) Pistol SF400PH10X10 19.70 (500.0) Pistol SF500PH10X10 NFPA79JKL 1 AC NO AC1NOR9 1 AC NC AC1NCR9 1 AC NO + NC AC1NO1NCJ2N 2 AC NO + NC AC2NO2NCJ2N 1 AC NO + NC w/ TEST AC1NO1NCJ2NT 2 AC NO + NC w/ TEST AC2NO2NCJ2NT Integral to switch (K Frame) (J) (L Frame) (J)
2 R9L2200FJ TSR9L2
3 R9L3200FJ TSR9L3
4 R9L4200FJ TSR9L4
(M Frame) (J)
3 R9M3400FJ TSR9M3
4 R9M4400FJ TSR9M4
(N Frame) (J) 2 R9N2600FJ 7.90 (200.0) Pistol SF200PH12X12 12.60 (320.0) Pistol SF320PH12X12 15.70 (400.0) Pistol SF400PH12X12 19.70 (500.0) Pistol SF500PH12X12 NFPA79N 1 AC NO + NC AC1NO1NCJ2N 2 AC NO + NC AC2NO2NCJ2N TSR9N2
3 R9N3600FJ TSR9N3
4 R9N4600FJ TSR9N4
(N Frame) (L)
2 R9N2800FL TSR9N2
4 R9N4800FL TSR9N4
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-59 1.3Circuit Protection Rotary Disconnect Switches DC Rated Disconnects Features
- Switching technology
- Up to 600 Vdc according to UL 98/CSA
- Up to 1000 Vdc according to IEC 947-3 R9 Series DC Rated Disconnects Product Selection Front Operation—Three- and Four-Pole Notes 1 Defeatable handle. 2 Top (line side). 3 Bottom (load side). 4 Top or bottom (line or load side). Ampere Rating Number of Poles Switch Body Direct Handle External Handle (Choose One) Shaft for External Handle In (mm) (Choose One) Auxiliary Contacts (Choose One) Terminals Shroud Terminal Lugs Jumpers for Connecting Poles in Series 100 3 R9D3100UDC DHR9DE S2 Type Black 1, 3R, 12 PHB2N12F Red/Yellow 1, 3R, 12 1 PHR2N12F Black 4, 4X 1 PHB2N4XF Red/Yellow 4, 4X 1 PHR2N4XF 7.90 (200.0) SF200PH10X10 12.60 (320.0) SF320PH10X10 15.7 0 (400.0) SF400PH10X10 C Type 1st Contact NO+NC AC1NONCDE C Type 2nd Contact NO+NC AC2NONCDE TS3R9DT 3P 3 TS3R9DB TS4R9DTB 3P 4 LK3R9DL 4P 4 LK4R9DL 2 pieces DCJUMPD2 3 pieces DCJUMPD3
4 R9D4100UDC
4 R9D4200UDC
4 R9E4400UDC
+ ++ Switch body Direct handle Switch body Shaft External handle+ + +
V9-T1-60 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com Rotary Disconnect Switches Manual Transfer Switches
- Three load break positions (I, 0, II)
- On load switching
- Direct or external handle
- 480 Vac total system
- 600 Vac resistive load Manual Transfer Switches Product Identification
3 Shaft extension for external handle
4 Pre-break ACs (standard on 600–1200A)
5 Terminal Screen
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-61 1.3Circuit Protection Rotary Disconnect Switches Product Selection Manual T ransfer Switches—UL 98 Standard 1 Notes 1 All ratings, 100–1200A, are UL 98 listed. Switches are to be UL 1008 listed in 2011. 2 Line or load (top or bottom); for both line and load, order two kits. 3 Low level auxiliary contact—gold plated for minimal resistance—for PLC applications. Ampere Rating Number of Poles Switch Body Only 1 Direct Handle (Black) External Three- Position Handle (Choose One) Shaft Extensions for External Handle In (mm) (Choose One) Bridging Bars Auxiliary Contacts Terminal Screens 100 3 RMTS3100U DHMTSSL Size 2, Black I–0–II Type 4/4X PHB2N4X3P Size 2, Red I–0–II Type 4/4X PHR2N4X3P 7.90 (200.6) SF200PH10X10 12.60 (320.0) SF320PH10X10 15.70 (398.8) SF400PH10X10 BB3P200 BB4P200 NO/NC AC1NONCMTS400 Low level AC1NONCMTS400LL 3 TS3MTS200TB TS4MTS200TB
4 RMTS4100U
4 RMTS4200U
400 3 RMTS3400U Size 3, Black I–0–II Type 4/4X PHB3N4X3P Size 3, Red I–0–II Type 4/4X PHR3N4X3P 7.90 (200.6) SF200PH15X12 12.60 (320.0) SF320PH15X12 15.70 (398.8) SF400PH15X12 BB3P400 BB4P400 TS3MTS400TB TS4MTS400TB
4 RMTS4400U
600 3 RMTS3600U DHMTSDL Size 4, Black I–0–II Type 4/4X PHB4N4X3P Size 4, Red I–0–II Type 4/4X PHR4N4X3P BB3P600 BB4P600 NO/NC contact standard TS3MTS600 TS4MTS600
4 RMTS4600U
800 3 RMTS3800U DHMTSDLM 3P BB3P1200 BB4P1200 TS3MTS1200 TS4MTS1200
4 RMTS4800U
4 RMTS41200U
+ ++ Switch body Direct handle Switch body Shaft External handle+ + + Direct Operation External Operation
V9-T1-62 Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com Rotary Disconnect Switches Enclosed Rotary Disconnects
- Padlockable in the OFF position (up to three padlocks) to meet OSHA lockout requirements
- Available in 16–80A ratings
- 600 Vac, three- and four-pole non-fusible device
- Rated for making and breaking loads
- Accepts auxiliary contacts; capability to signal PLC controllers
- Ground lug connection provided
- Possibility of adding one power pole and one auxiliary contact
- NEMA Type 1, 3R, 12, 4, 4X
- 65kAIC rating when applied downstream from appropriate fusing Enclosed Rotary Disconnects Provide users with the ability to lock directly wired motor loads in the OFF position to comply with OSHA lockout/ tagout regulations. Also for machine applications that require compact, economical disconnect switches. Enclosed rotary disconnect switches allow safe control and safe disconnect of any motor application. Open rotary disconnects can be found on Pages V9-T1-46 to V9-T1-61 and full information in Volume 5, Motor Control and Protection, CA08100006E, Tab 8.
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—February 2014 www.eaton.com V9-T1-63 1.3Circuit Protection Rotary Disconnect Switches Product Selection Enclosed Rotary Non-Fusible Accessories for Enclosed Rotary Disconnects 56 Notes 1 For CSA listed switches, add prefix letter “C” to the front of the catalog number. 2 NEMA Type 12 enclosures (16–80A) can be field modified to meet NEMA Type 3R rainproof requirements when a factory-provided drain hole is opened. 3 YR suffix indicates Yellow cover with Red handle. For Gray cover with Black handle, replace “YR” with “GB.” For Gray cover with Red handle, replace “YR” with “GR.” 4 cULus only. 5 Ordered and shipped as separate components—not integral to enclosed device. 6 Enclosed disconnects can accept one power pole, neutral or up to two auxiliary contacts (one mounted on either side of switch). 7 Available 2011. Contact the Safety Switch Flex Center (1-888-329-9272) for factory-installed accessories or other special modifications. Ampere Rating Maximum Horsepower Ratings NEMA 1 1 Enclosure Indoor NEMA 12 1 2 Enclosure Dust-Tight/ Rainproof NEMA 4X 1 Enclosure Corrosion-Resistant, Stainless Steel NEMA 4X 1 Enclosure Corrosion-Resistant, Non-Metallic NEMA 4X Enclosure Polycarbonate- Non-MetallicThree-Phase AC 208V 240V 480V 600V Catalog Number Catalog Number Ca talog Number Catalog Number Catalog Number Three-Pole, 600 Vac 1 6 351 0 1 0 ER53016UG ER53016UD ER53016UW ER53016UX — 25 7-1/2 7-1/2 15 20 ER53025UG ER53025UD ER53025UW ER53025UX — 30 7-1/2 7-1/2 15 20 ER53030UG ER53030UD ER53030UW ER53030UX ER53030UPYR 34 40 7-1/2 7-1/2 20 25 ER53040UG ER53040UD ER53040UW ER53040UX — 60 15 15 30 30 ER53060UG ER53060UD ER53060UW ER53060UX ER53060UPYR 34 80 15 20 40 40 ER53080UG ER53080UD ER53080UW ER53080UX — Four-Pole, 600 Vac 1 6 351 0 1 0 ER54016UG ER54016UD ER54016UW ER54016UX — 25 7-1/2 7-1/2 15 20 ER54025UG ER54025UD ER54025UW ER54025UX — 30 7-1/2 7-1/2 20 25 ER54030UG ER54030UD ER54030UW ER54030UX — 40 7-1/2 7-1/2 20 25 ER54040UG ER54040UD ER54040UW ER54040UX — Disconnect Ampere Rating Switched Fourth Pole Unswitched Neutral Pole Auxiliary Contacts (Choose One) Terminal Shrouds