PG.29B.01A.T.U Cutler-Hammer Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications 1
Contents
Electrical Characteristics/ Catalogue Numbers/ Termination Accessories G-Frame, E-Frame, J-Frame, K-Frame, L-Frame, N-Frame, R-Frame, Frame Sizes G through R. . . . 31-32 Accessories and Typical Specifications . . . Inside Back Cover Standards Cutler-Hammer Moulded Case Circuit Breakers are designed to conform with the following international standards: n Australian Standard AS 2184 and AS 3947-2 Moulded Case Circuit Breakers. n British Standards Institution Standard BS 4752: Part 1, Switchgear and Control Gear Part 1, Circuit Breakers. n International Electrotechnical Commission Recommendations IEC 60947.2 Circuit Breakers. n Japanese T-Mark Standard Moulded Case Circuit Breakers. n National Electrical Manufacturers Association Standards Publication No. AB1-1975 Moulded Case Circuit Breakers. n South African Bureau of Standards, Standard SABS 156, Standard Specification for Moulded Case Circuit Breakers. n Swiss Electro-Technical Associa- tion Standard SEV 947.2, Safety Regulations for Circuit Breakers. n Union Technique de l’Electricite Standard NF C 63-120, Low Voltage Switchgear and Control Gear Circuit Breaker Requirements. n Verband Deutscher Elektrotechnike (Association of German Electrical Engineers) Standard VDE 0660, Low Voltage Switchgear and Control Gear, Circuit Breakers. Cutler-Hammer Frame Sizes G through R Global Third Party Certification Certification marks assure product compliance with the total standard via the third party witnessing of tests by globally recognized inde- pendent certification organizations. KEMA is a highly recognized, com- pletely independent international organization that offers certification and inspection facilities for equip- ment in many industries. The KEMA- KEUR mark is the highest certifica- tion an electrical product can receive from KEMA. Our IEC 60947-2 Moulded Case Circuit Breakers are KEMA tested and certified. What does the KEMA-KEUR rating mean for you? It means an inde- pendent testing house. KEMA Regis- tered Quality has tested and certified these products to IEC 60947-2 stand- ards. In addition, KEMA is conduct- ing ongoing follow-up witness test programs to assure IEC 60947-2 compliance to maintain the KEMA Certification mark, KEMA-KEUR has been a well-known and highly respected independent mark for over 70 years, a symbol of quality assurance that enjoys the confi- dence of both manufacturers and consumers. Cutler-Hammer also offers a com- plete line of Moulded Case Circuit Breakers, UL listed in accordance with UL 489 as well as CSA C22.2 No. 5.1 certified are also available. Both UL and CSA are independent third party testing houses that con- tinue to assure that Cutler-Hammer Moulded Case Circuit Breakers meet their exacting standards through regularly scheduled follow-up testing and inspections.
PG.29B.01A.T.U Cutler-Hammer February 2001 Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications The Most Logically Designed Contact Assembly The flexibility and outstanding per- formance characteristics of Cutler- Hammer Circuit Breakers are made possible by one of the most logically designed contact assemblies in circuit breaker history. Based on previously patented Westinghouse contact conductor designs, the Cutler- Hammer contact assembly creates a high-speed “blow-open” action when it confronts the electromechanical forces produced by high-level fault currents. Cutler-Hammer Circuit Breakers are operated by a toggle-type handle that is mechanically trip-free from the handle so that the contacts cannot be held closed against short circuit currents. Tripping due to overload or short circuits is clearly indicated by the position on the handle. This remarkably fast and dependable contact action is designed to enhance safety. Thorough In-Plant Testing The quality, dependability, and relia- bility of every Cutler-Hammer Circuit Breaker is assured by a thorough pro- gram of in-plant testing. Two calibra- tion tests are conducted on every pole of every circuit breaker to verify the trip mechanism, operating mech- anism, continuity, and accuracy. ISO Certification Cutler-Hammer Circuit Breakers are manufactured in ISO certified facilities. More Interrupting Capacity in Less Space Cutler-Hammer Circuit Breakers are physically and electrically inter- changeable with the “Classic” stand- ard line of Westinghouse moulded case circuit breakers. This means Cutler-Hammer Breakers are ideal for upgrading equipment designs and retrofitting existing installations. Current Limiting Characteristics All Cutler-Hammer Circuit Breakers are current limiting because of their high repulsion contact arrangement and incorporation of state-of-the-art arc extinguishing technology. Operating Mechanisms Cutler-Hammer Circuit Breakers have, in their basic version, a toggle handle operating mechanism, which also serves as switching position indicator. As well as ON and OFF, the further position TRIPPED is possible. The toggle handle snaps into the TRIPPED position if the breaker is tripped by one of its overcurrent, short circuit, shunt or undervoltage releases. Before the circuit breaker can be reclosed following a trip-out, the toggle handle must be brought beyond the OFF position (RESET). The circuit breaker can then be reclosed. As an additional switching position indicator for F- to R-Frame circuit breakers, there are two windows on the right and on the left of the toggle handle, in which the switching state is indicated by means of the colours red, green and white corresponding to the ON, OFF and TRIPPED posi- tions respectively. General Information Cutler-Hammer Moulded Case Circuit Breakers provide increased performance in considerably less space than standard circuit breakers or comparable fusible devices. Reduced system costs can also be realized because Cutler-Hammer Circuit Breakers are used in series rated systems, allowing the use of lower interrupting circuit breakers downstream. Cutler-Hammer Circuit Breakers meet applicable IEC 60947-2 stand- ards, have been assigned ultimate and service interrupting ratings per IEC 60947-2, and employ adjustable thermal and adjustable magnetic trips. The Cutler-Hammer family includes seven frame sizes in ratings from 100 to 2500 amperes. Each frame size offers a choice of several inter- rupting capacities up to 100 kA at 415 volts ac (200 kA at 240 volts ac). This provides greater design flexibil- ity than ever before possible while also helping to save space. Cutler-Hammer Circuit Breakers vir- tually eliminate the need for rede- sign and they can be used to replace older circuit breakers in the same panelboards, feeder pillars, busbar trunking tap-offs, individual enclo- sures, machine tool control panels, and motor control centres. In most cases, the same connecting straps, studs, and handle mechanisms can be retained and used. Standard calibration is 40°C. For applications in high ambient temper- ature conditions, 50°C factory cali- bration is available. Cutler-Hammer Circuit Breakers are also provided for dc applications. Interrupting ratings of 35 kA for the 600 ampere frame have been achieved for three-pole breakers in series at 600 volts dc. Cutler-Hammer Frame Sizes G through R Positions of the Toggle Handle Drive OFF RESET ON Tripped
PG.29B.01A.T.U Cutler-Hammer Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications 3 Switchboard Machine Tool Control Panel Busbar Trunking Tap-Off Individual Circuit Breaker Enclosure Panelboard Panelboards As both main and branch circuit pro- tection devices (G-, E-, J-, K-, L- and N-Frames). Feeder Pillars In distribution systems to provide main and branch circuit protection (E-, J-, K-, L-, N- and R-Frames). Switchgear In distribution systems to provide main and branch circuit protection up to 2500 amperes (R-Frame). Busbar Trunking Tap-Offs In busbar trunking tap-offs to provide branch circuit protection (F-Frame); and to provide feeder or branch circuit protection (J-, K- and L-Frames). Individual Enclosures Completely assembled in enclosures to meet specific customer require- ments (G-, E-, J-, K-, L-, N- and R-Frames). Machine Tool Control Panels and Motor Control Centres Applied for specific equipment requirements (G-, E-, J-, K-, and L-Frames). Additional Applications Special versions of each Cutler- Hammer frame are available to provide safe equipment control and protection in mining and other appli- cations. Contact your Cutler-Hammer agent or distributor for additional information. Cutler-Hammer Frame Sizes G through R Frame Continuous Ampere Rating Range Type of Trip Unit Moulded Case SwitchAdjustable Thermal Fixed Magnetic Fixed Thermal Fixed Magnetic Adjustable Thermal Adjustable Magnetic Adjustable Thermal Fixed Magnetic Earth Leakage Digitrip RMS Electronic Trip Units G 16-100 – n ––– n E 16-125 nn ––– n J 125-250 – – nn n K 63-400 – – nnn n L 315-800 – – n nn N 400-1250 –––– nn R 800-2500 –––– nn Typical Cutler-Hammer Applications
PG.29B.01A.T.U Cutler-Hammer February 2001 Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications
Electrical Characteristics
Maximum Rated Current (Amperes) 100 125 250 Breaker Type GWF GWF BE SHE S H Breaker Capacity (kA rms) AC 50-60 Hz IEC 60947-2 220-240 VAC I cu 18 65 25 25 35 85 85 100 100 65 85 100 I cs 9 3 3 2 52 5 3 5 4 34 3 5 05 0 6 5 8 5 1 0 0 380-415 VAC I cu – 25 – 18 25 – 40 – 70 25 40 70 I cs – 13 – 18 25 – 30 – 35 25 40 70 660-690 VAC I cu I cs
250 VDC
À I cu – 1 0 1 01 0 1 0 3 53 5 4 24 2 1 0 2 2 2 2 I cs – 5 10 10 10 35 35 42 42 10 22 22 NEMA 240 VAC 18 65 25 25 35 85 85 100 100 65 85 100
480 VAC – 22 – 18 25 – 35 – 65 25 35 65
Number of Poles 1 2, 3 1 2, 3, 2, 3, 4 1 2, 3, 1 2, 3, 2, 3, 4 Ampere Range 16-125A 16-125A 63-250A Trip Units Interchangeable – – n Built-in nn n Thermal Magnetic Fixed Thermal nn n Adjustable Thermal Fixed nn Magnetic Fixed Fixed Adjustable Solid State rms LS – – – LSI – – – LSG – – – LSIG – – – À 2 poles in series. Not KEMA-KEUR listed. R-frame scheduled for 2001. Not suitable for DC application. 4-pole ground fault not available. Weight (approximate) Kgs. 1-Pole 2-Pole 3-Pole 1-Pole 2-Pole 3-Pole 4-Pole 2-Pole 3-Pole 4-Pole Cutler-Hammer Frame Sizes G through J Dimensions (mm) HW DH W D H W D 2-Pole 50.8 50.8 3-Pole 76.2 76.2 4-Pole – – – 101.6 140 Adjustable Thermal Magnetic Adjustable Thermal Magnetic
PG.29B.01A.T.U Cutler-Hammer Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications 5 Maximum Rated Current (Amperes) 400 630 800 Breaker Type KW HKW KWC À LW HLW LWC À LW Breaker Capacity (kA rms) AC 50-60 Hz IEC 947-2 220-240 VAC I cu 85 100 200 85 100 200 65 I cs 85 100 150 85 100 150 33 380-415 VAC I cu 45 70 100 45 70 100 50 I cs 45 70 75 45 70 75 25 660-690 VAC I cu 20 25 35 20 25 35 20 I cs 10 13 18 10 13 18 10 I cu 10 20 20 20 20 20 20 I cs 51 01 01 01 01 0 1 0 NEMA 240 VAC 65 100 200 65 100 200 65
480 VAC 35 65 100 35 65 100 35
600 VAC 25 35 50 25 35 50 25
Number of Poles 2, 3, 4 2, 3, 4 3 Ampere Range 63-400A 315-630A 700-800A Trip Units Interchangeable nn Built-in nnn Thermal Magnetic Fixed Thermal nnn Adjustable Thermal nn Magnetic Adjustable Adjustable Adjustable Solid State rms LS Standard Standard Standard LSI Optional Optional Optional LSG Optional Optional Optional LSIG Optional Optional Optional À Not KEMA-KEUR listed. R-frame scheduled for 2001. 2 poles in series. Not suitable for DC application. 4-pole ground fault not available. Adjustable Thermal Magnetic Digitrip RMS 310Digitrip RMS 310 Adjustable Thermal Magnetic Cutler-Hammer Frame Sizes K through L Dimensions (mm) HW DH W D 3-Pole 258 140 104 630A = 273 800A = 406 210 104 4-Pole 183 280 Weight (approximate) Kgs. 3-Pole 4-Pole 3-Pole 4-Pole
PG.29B.01A.T.U Cutler-Hammer February 2001 Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications Digitrip RMS 310 Trip Unit Digitrip RMS Trip Units n RMS 610 n RMS 910 Dimensions (mm) HW DH W D 3-Pole 406 210 104 406 394 229 4-Pole 280 508 Weight (approximate) Kgs. 3-Pole 4-Pole 3-Pole 4-Pole 21.3 28.3 47 54 Standard Digitrip RMS 310 Cutler-Hammer Frame Sizes N and R Maximum Rated Current (Amperes) 800, 1250 1600 1600, 2000, 2500 Breaker Type NW HNW NWC À NW RW À RWC À Breaker Capacity (kA rms) AC 50-60 Hz IEC 947-2 220-240 VAC I cu 85 100 200 85 135 200 I cs 85 100 100 85 100 100 380-415 VAC I cu 50 70 100 50 70 100 I cs 50 50 50 50 50 50 660-690 VAC I cu 35 20 25 35 I cs 10 13 18 10 13 18 I cu I cs NEMA 240 VAC 65 100 200 100 125 200
480 VAC 50 65 100 65 65 100
600 VAC 25 35 50 35 50 65
Number of Poles 2, 3, 4 3 3, 4 Ampere Range 400-1250A 1600A 800-2500A Trip Units Interchangeable – – Built-in nn Thermal Magnetic Fixed Thermal – – Adjustable Thermal – – Magnetic – – Solid State rms ˆ LS Standard Standard (LI is Optional in Digitrip 510, 610, 810 and 910) LSI Optional Optional LSG Optional Optional (LIG is Optional in Digitrip 510, 610, 810 and 910) LSIG Optional Optional À Not KEMA-KEUR listed. R-frame scheduled for 2001. IEC 60947-2 H.5 Annex H is not KEMA-KEUR tested. 2 poles in series. ˆ Not suitable for DC application. 4-pole ground fault not available.
PG.29B.01A.T.U Cutler-Hammer Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications 7 Technical Data G-Frame E125-Frame J250-Frame K-Frame L-Frame N-Frame R-Frame Maximum Rated Current I n Depending on the Version 100A 125A 200/250A 315/400A 500/630/800A 800/1250A 1600/2000/2500A Rated Insulation Voltage U, According to IEC 947-2 Main Conducting Paths Auxiliary Circuits 1-Pole = 250 VAC 2,3-Pole = 415 VAC
690 VAC
750 VAC
Rated Impulse Withstand Voltage U imp Main Conducting Paths Auxiliary Circuits 1-Pole = 4 kV 2,3-Pole = 6 kV 4 kV 6 kV 4 kV 8 kV 4 kV 8 kV 4 kV 8 kV 4 kV 8 kV 4 kV 8 kV 4 kV Rated Operational Voltage U e IEC NEMA
440 VAC
480 VAC
600 VAC
Permissible Ambient Temperature -20 to +70°C -20 to +70°C -20 to +70°C -20 to +70°C -20 to +70°C -5 to +60°C -5 to +60°C Permissible Load for Various Ambient Tempera- tures Close to the Circuit Breaker, Related to the Rated Current of the Circuit Breaker n Circuit Breakers for Plant Protection – At 40°C – At 50°C – At 55°C – At 60°C – At 70°C 100% 96% 93% 91% 86% À 100% 96% 93% 91% 86% 100% 92% 87% 83% 73% À 100% 96% 94% 92% 88% 100% 94% 90% 87% 80% À 100% 96% 93% 90% 85% 100% 92% 87% 84% 75% À 100% 96% 93% 90% 84% 100% 91% 86% 82% 70% 100% 91% 85% 81% 100% 100% 100% 100% n Circuit Breakers for Motor Protection – At 40°C – At 50°C – At 55°C – At 60°C – At 70°C 100% 100% 100% 100% 87% 100% 100% 100% 100% 90% n Circuit Breakers for Starter Combinations and Isolating Circuit Breakers – At 40°C – At 50°C – At 55°C – At 60°C – At 70°C 100% 100% 96% 91% 86% 100% 100% 96% 82% 88% 100% 100% 96% 90% 85% 100% 100% 95% 90% 84% 100% 91% 85% 81% 100% 100% 100% 100% Rated Short Circuit Breaking Capacity (DC) Not for Circuit Breakers for Motor Protection (Time Constant t = 10 rms)
1 Conducting 2 Conducting 3 Conducting
Path Paths in Series Paths in Series For F to L up to:
250 VDC 440 VDC 660 VDC
NEMA (Time Constant t = 8 rms)
1 Conducting 2 Conducting
250 VDC –
– 250 VDC 10 kA (5 rms) 20 kA Max. 10 kA 22 kA 20 kA Max. 10 kA 22 kA 20 kA Max. 10 kA 22 kA 20 kA Max. 10 kA 22 kA Main Switch Characteristics According to IEC 947-2 in Combination with Lockable Rotary Drives – Yes Yes Yes Yes Yes Yes Rated Short Circuit Breaking Capacity According to IEC 947-2 (at AC 50/60 Hz) Rated Short Circuit Breaking Capacity See Table on Pages 4-5-6 Endurance (Operating Cycles) 10,000 10,000 10,000 8,000 8,000 3,000 3,000 Maximum Switching Frequency 300 1/h 300 1/h 240 1/h 240 1/h 240 1/h 60 1/h 20 1/h Conductor Cross Sections and Terminal Types for Main Conductors n Solid or Stranded n Finely Stranded with End Sleeve n Busbar Tightening Torque for Box Terminals Tightening Torque for Busbar Connection Pieces Box Terminals 2.5 to 50 mm 5.1 Nm Box Terminals 2.5 to 95 mm2 2.5 to 50/70 mm2 4/6 Nm 4.5 Nm Box Terminals 50 to 150 mm2 35 to 120 mm2 20 Nm 15 Nm Box Terminals 95 to 240 mm 70 to 150 mm2 42 Nm 30 Nm Flat Bar Terminals 800A 31 Nm 6 Nm Flat Bar Terminals Optional 31 Nm 50 Nm Flat Bar Terminals Optional 37 Nm Conductor Cross Sections for Auxiliary Circuits with Terminal Connection or Terminal Strip n Solid n Finely Stranded with End Sleeve n With Brought-out Cable Ends n Tightening Torque for Fitting Screws 0.75 to 2.5 mm 0.75 to 2.5 mm2 0.75 to 2.5 mm2 0.75 to 2.5 mm2 0.75 to 2.5 mm2 0.75 to 2.5 mm2 0.82 (AWG 18) mm2 0.8 to 1.4 Nm 0.75 to 2.5 mm2 0.75 to 2.5 mm2 0.82 (AWG 18) mm2 0.8 to 1.4 Nm 0.75 to 2.5 mm2 0.75 to 2.5 mm2 0.82 (AWG 18) mm2 0.8 to 1.4 Nm Up to 2x4 mm2 Up to 2x2.5 mm2 0.82 (AWG 18) mm2 0.8 to 1.4 Nm Up to 2x4 mm2 Up to 2x2.5 mm2 0.82 (AWG 18) mm2 0.8 to 1.4 Nm Power Loss per Circuit Breaker at Maximum Rated Current ln (The Power Losses of the Undervoltage Releases (“r” Releases) Must Be Observed if Necessary) at Three-Phase Symmetrical Load) n For Plant Protection n As Isolating Circuit Breaker n For Starter Combinations n For Motor Protection 50 W 40 W 40 W 50 W 50 W 40 W 40 W 50 W 75 W 75 W 45 W 175 W 107 W 107 W 75 W 255 W 160 W 160 W 120 W 87/210 W 87/210 W 220/270/400 W 220/270/400 W Permissible Mounting Position À Thermal overload release set to the lower value. \` Thermal overload release set to the upper value, respecting fixed-setting thermal overload releases. ´ Not suitable for DC switching. Cutler-Hammer Frame Sizes G through R ¡ 90 ¡ 90 ¡ 90
PG.29B.01A.T.U Cutler-Hammer8 February 2001 Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications Technical Data G-Frame E125-Frame J250-Frame K-Frame L-Frame N-Frame R-Frame Auxiliary Switches Rated Thermal Current lth Rated Making Capacity 10A 20A 20A 20A 20A 20A 20A AC (AC-15) – Rated Operational Voltage – Rated Operational Current DC (DC-13) – Rated Operational Voltage – Rated Operational Current Back-up Fuse Miniature Circuit Breaker 240V 230/400/600V 6/3/0.25A 24/125/250V 6/0.5/0.25A 6/4/4A 6/4A 230/400/690V 6/3/0.25A 24/125/240V 6/0.5/0.15A 6/4/4A 6/4A 230/400/690V 6/3/0.25A 24/125/240V 6/0.5/0.15A 6/4/4A 6/4A 230/400/690V 6/3/0.25A 24/125/240V 6/0.5/0.15A 6/4/4A 6/4A 230/400/690V 6/3/0.25A 24/125/240V 6/0.5/0.15A 6/4/4A 6/4A 230/400/690V 6/3/0.25A 24/125/240V 6/0.5/0.15A 6/4/4A 6/4A Releases Undervoltage Releases (“r” Releases) Response Voltage: – Drop (Breaker Tripped) U s – Pickup (Breaker May Be Switched on) Us Power Consumption in Continuous Operation at: – AC 50/60 Hz 12V – AC 50/60 Hz 24V – AC 50/60 Hz 48-60V – AC 50/60 Hz 110-127V – AC 50/60 Hz 208-240V – AC 50/60 Hz 380-500V – DC 12V – DC 24V – DC 48-60V – DC 110-125V – DC 220-250V Maximum Opening Time 35-70% 85-110% 5.3 VA 1.5 VA 1.8 VA 1.4 VA 4.8 VA 50 ms 35-70% 85-110% 0.95 VA 0.72 VA 1.15-1.78 VA 0.96 -1.25 VA 1.28 -1.68 VA 2.2 -3.9 VA 0.88 VA 0.70 VA 1.12-1.76 VA 0.94-1.21 VA 1.45-1.86 VA 50 ms 35-70% 85-110% 1.9 VA 3.9 VA 2.5-3.8 VA 1.8 -2.4 VA 2.7-3.8 VA 3.4-5.8 VA 1.6 W 3.1 W 2.0-3.1 W 1.6-2.2 W 3.1-4 W 50 ms 35-70% 85-110% 1.9 VA 3.9 VA 2.5-3.8 VA 1.8 -2.4 VA 2.7-3.8 VA 3.4-5.8 VA 1.6 W 3.1 W 2.0-3.1 W 1.6-2.2 W 3.1-4 W 50 ms 35-70% 85-110% 1.9 VA 3.9 VA 2.5-3.8 VA 1.8-2.4 VA 2.7-3.8 VA 3.4-5.8 VA 1.6 W 3.1 W 2.0-3.1 W 1.6-2.2 W 3.1-4 W 50 ms 35-70% 85-110% 1.9 VA 2.4 VA 2.3-4.1 VA 3.4-4.2 VA 4.8-6.5 VA 6.8-12.0 VA 2.6 W 3.6 W 3.5 -5.5 W 2.9-3.6 W 4.8-6.3 W 80 ms 35-70% 85-110% 2.9 VA 3.1 VA 3.4-6.0 VA 3.3-3.8 VA 4.2-7.2 VA 3.8 10.0 VA 3.4 W 4.3 W 4.8-7.2 W 3.3-3.8 W 6.6-7.5 W 80 ms Shunt Trips Shunt Trips (“f” Releases) Response Voltage: – Pickup (Breaker Tripped) U s Power Consumption in (Short Time) at: – AC 50/60 Hz 12-24V – AC 50/60 Hz 48-60V – AC 50/60 Hz 48-127V – AC 50/60 Hz 110-240V – AC 50/60 Hz 380-440V – AC 50/60 Hz 380-600V – AC 50/60 Hz 480-600V – DC 12-24V – DC 48-60V – DC 110-125V – DC 220-250V 70-110% 135-500 VA 70-110% 10-41 VA 139-210 VA 83-360 VA 418-1080 VA 29-120 W 475-720 W 99-121 W 0-110% 87-405 VA 710-1105 VA 66-432 VA 127-188 VA 34-60 VA 164-631 W 830-1580 W 112-150 W 40-58 W 70-110% 87-405 VA 710-1105 VA 66-432 VA 127-188 VA 34-60 VA 164-631 W 830-1580 W 112-150 W 40-58 W 70-110% 81-701 VA 58-90 VA 118-665 VA 125-181 VA 43-79 VA 79-1000 W 18-31 W 112-150 W 38-52 W 70-110% 86-631 VA 48-71 VA 81-505 VA 43-68 VA 41-69 VA 46-405 W 58-94 W 74-98 W 38-49 W 70-110% 177-1207 VA 443-731 VA 323-1466 VA 1193-1641 VA 197-312 VA 289-865 W 468-696 W 363-473 W 513-665 W Maximum Load Duration Interrupts Automatically Maximum Opening Time 50 ms 50 ms 50 ms 50 ms 50 ms 62 ms 62 ms Cutler-Hammer Frame Sizes G through R
PG.29B.01A.T.U Cutler-Hammer Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications 9 For 3- and 4-Pole Circuit Breakers Proposed Circuit Maximum Permissible VDC U e Remarks 250 VDC Double-pole switching. If there is no risk of an earth fault, or if any earth fault which occurs is immediately eliminated (earth fault monitoring), the maximum permissible dc voltage can be 600 volts. 440 VDC Double-pole switching (earth system). The earthed pole must always be assigned to the individual conducting path, so that two paths are always in series in the event of an earth fault. 600 VDC Single-pole switching (earthed system). Three conducting paths in series. The earthed pole must be assigned to the nonswitched conducting path. 750 VDC Single-pole switching (earthed system). Four conducting paths in series. The earthed pole must be assigned to the nonswitched conducting path. NSI-5178a M NSI-5179a M NSI-5180 M NSI-5181 M The E- to L-Frame circuit breakers are also suitable for switching dc currents. The N- and R-Frame circuit breakers, FWMP, KWMP, and LWMP circuit breakers for motor protection are not suitable for dc currents due to the solid state overcurrent release system. For switching dc currents, however, the maximum permissible dc voltage per conducting path has to be con- sidered. For voltages higher than 250 volts, the series connection of two or three conducting paths is required. As the current has to flow through all conducting paths so as to maintain the thermal tripping characteristics, the following circuit arrangements are recommended. With dc, the trip values of the instantaneous short circuit release (“n” release) are increased by 30 to 40%. Cutler-Hammer Frame Sizes E through L
PG.29B.01A.T.U Cutler-Hammer10 February 2001 Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications Multi-Function Electronic Trip Units for All Applications Digitrip™ RMS Trip Units True rms Sensing Digitrip RMS Trip Units utilize our proprietary SURE™ Chip and SuRE Plus™ Chip microprocessor-based intelligence to provide true rms sensing, permitting increased accu- racy and reliable system protection. True rms sensing is not susceptible to nuisance tripping when wave- forms containing high harmonic currents are present. Digitrip RMS 310 Digitrip RMS 310 Electronic Trip Units are available with Cutler-Ham- mer Circuit Breakers K-, L-, N- and R-Frames 63 through 2500 amperes. Digitrip RMS 310 Trip Units are available in four styles with either fixed or adjustable rating plugs which establishes the continuous ampere rating of the breaker. Rating Plugs Digitrip RMS 310 Trip Units incor- porate rating plugs that are inter- changeable within a specific circuit breaker frame. This provides the user with versatility when establishing the continuous current rating of a breaker. Rating plugs are frequency sensitive and may be specified for 50 / 60 Hz applications. Both fixed and adjustable rating plugs are avail- able, providing further flexibility when applied to selectively coordi- nated systems. Note: Digitrip RMS rating plugs are not interchangeable with SELTRONIC™ rating plugs. Curve Shaping When selectively coordinated sys- tems are called for, Digitrip RMS 310 will provide a cost-effective solution for a variety of applications. The standard Digitrip RMS 310 includes an adjustable short time pickup setting encompassing an I ramp function which provides the basic LS curve shaping function. The optional Digitrip RMS 310 provides additional flat response short time delay adjustments on an instantaneous setting to provide LSI curve shaping capability. Both Digitrip RMS 310 Trip Units are available with ground fault pickup and flat response ground fault delay which provide the trip unit with full function LSG and LSIG curve shap- ing flexibility. Digitrip RMS 310 Trip Units can effectively coordinate with both sophisticated upstream power breakers as well as downstream thermal magnetic breakers…making Digitrip RMS 310 Trip Units the cost- effective reliable choice for selec- tively coordinated systems. Thermal Memory All Digitrip RMS Trip Units incorpo- rate a long delay and, when ordered with ground, a ground fault thermal memory feature. Thermal memory prevents the system from cumula- tive overheating due to repeated overcurrent events that may occur in quick succession. Digitrip RMS 610 and 910 Digitrip RMS 610, and 910 Trip Units are available with Cutler-Hammer R-Frame Circuit Breakers 800 through 2500 amperes. Digitrip 610 and 910 Trip Units provide unparal- leled system protection with fixed rating plugs to establish the continu- ous ampere rating of the breaker. Curve Shaping Digitrip RMS 610 and 910 Trip Units are available with up to nine curve shaping choices achieved by adjust- ing up to seven switches on the front of the unit for optimum system coor- dination. Maximum curve shaping flexibility is provided by dependent long and short delay adjustments that are long delay pickup (I r) based, depicted on the front of the unit by the blue portion of the time-current curve. Additional coordination capability can be provided by utilizing the short delay and ground fault zone selec- tive interlocking features available on these trip units. R-Frame Digitrip RMS 310, 610 and 910 Trip Units (Noninterchangeable) Cutler-Hammer Frame Sizes K through R
PG.29B.01A.T.U Cutler-Hammer Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications 11 System Diagnostics All four Digitrip RMS models of trip units provide long delay, short delay, instantaneous, and ground fault cause of trip LEDs on the front of the unit. Digitrip RMS 610 and 910 also offer a magnitude of trip information as well as remote signal contacts for improved system diagnostics. System Monitoring Digitrip 610 and 910 Trip Units have the capability to monitor phase currents as well as neutral or ground currents. This information is displayed on a large digital display mounted on the unit. Digitrip RMS 910 Trip Units can also provide the user with power and energy monitoring capability. Peak power demand, present power Cutler-Hammer Frame Size R demand, and total energy as well as forward and reverse energy can be monitored with this unit. Digitrip RMS 910 Trip Units have the additional capability of monitoring line to line voltage as well as system power factor. Both parameters are displayed in the digital display win- dow and are supported by LEDs to indicate which parameter is being displayed. Harmonics Monitoring Digitrip RMS 910 Trip Units are capable of displaying values of cur- rent harmonics in the digital display window. Percentage of harmonic content can be monitored for each phase, neutral or ground, up to the 27th harmonic. Additionally, a total harmonic distortion value can be calculated and displayed. Communications Digitrip RMS 810 and 910 have built-in communications options to allow all protection, monitoring, and control information to be transmitted back to a central location via the Cutler-Hammer PowerNet System. Field Testing Integral field testing capability is provided on all 610 and 910 Trip Units. No additional test set is needed to perform both trip and no trip field testing.
PG.29B.01A.T.U Cutler-Hammer12 February 2001 Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications Digitrip RMS Electronic Trip Unit Selection Guide Digitrip RMS 310 RMS 610 RMS 910 Breaker Type Cutler-Hammer Frame(s) K-, L-, N- and R-Frames R-Frame R-Frame Ampere Rating 70A-2500A 800A-2500A 800A-2500A Interrupting Rating at 415V 35, 70, 100 kA 70, 100 kA 70, 100 kA Trip Unit Sensing rms Sensing Yes Yes Yes Protection and Coordination Protection Ordering Options LS, LSG LSI, LSIG LI, LSI, LIG, LSG, LSIG LI, LS, LSI, LIG, LSG, LSIG Fixed Rating Plug (In) Yes Yes Yes Yes Overtemperature Trip Yes Yes Yes Yes Long Delay Adjustable Rating Plug (In) Yes Yes No No Long Delay Time I2t 12 Seconds 12 Seconds 2-24 Seconds 2-24 Seconds Long Delay Thermal Memory Yes Yes Yes Yes High Load Alarm No No 0.85 x I r 0.85 x Ir Short Delay Short Delay Setting 200-800% x (l n)˜ 200-800% x (ln)˜ 200-600% S1 & S2 x (Ir) 200-600% S1 & S2 x (Ir) Short Delay Time I2t 100 ms No 100-500 ms 100-500 ms Short Delay Time Flat No I-300 ms 100-500 ms 100-500 ms Short Delay Time ZSI No No Yes Yes Instanta- neous Instantaneous Setting No 200-800% x (l n) 200-600% M1 & M2 x (ln) 200-600% M1 & M2 x (ln) Discriminator No No Yes ˆ Yesˆ Instantaneous Override Yes Yes Yes Yes Ground Fault Ground Fault Setting Var/Frame ´ Var/Frame´ 25-100% x (ln)´ 25-100% x (ln)´ Fault Delay I2t No No 100-500 ms 100-500 ms Ground Fault Delay Flat I-500 ms I-500 ms I-500 ms I-500 ms Ground Fault ZSI No No Yes Yes Ground Fault Thermal Memory Yes Yes Yes Yes System Diagnostics Cause of Trip LEDs No No Yes Yes Magnitude of Trip Information No No Yes Yes Remote Signal Contacts No No Yes Yes System Monitoring Digital Display No No Yes Yes Current No No Yes Yes Voltage No No No Yes Power and Energy No \ No\ No Yes Power Quality - Harmonics No No No Yes Power Factor No No No Yes System Communications PowerNet No No No Yes Field Testing Testing MethodÀ Test Set Test Set Integral Integral À Set by adjustable rating plug \` Yes, with addition of Energy Sentinal. ´ Not to exceed 1200A. In = Rating plug rating. Ir = LDPU setting. ˆ LS, LSG only. ˜ 2500A R-frame 200-600% x (In) Cutler-Hammer Frame Sizes K through R
PG.29B.01A.T.U Cutler-Hammer 13Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications À Special 50°C rating available. Order by description. Selection Guide and Ordering Information Maximum Continuous Ampere Rating at 40°C À Standard Interrupting Capacity Catalogue Number U e Maximum 240 VAC U e Maximum 440 VAC 20 kA I cu at 240 VAC 25 kA I cu at 415 VAC Type GWF 1-Pole 2-Pole 3-Pole Fixed Thermal/Fixed Magnetic Circuit Breakers Sealed Breakers with Noninterchangeable Trip Units and Line and Load Terminals 100 GWF1016 GWF1020 GWF1025 GWF1032 GWF1040 GWF1050 GWF1063 GWF1080 GWF1100 GWF2016 GWF2020 GWF2025 GWF2032 GWF2040 GWF2050 GWF2063 GWF2080 GWF2100 GWF3016 GWF3020 GWF3025 GWF3032 GWF3040 GWF3050 GWF3063 GWF3080 GWF3100 Terminals (Factory Fitted Only) Frame Amperes Terminal Type Wire Type Wire Range G 16-100 Pressure Type Copper 2.5-50 Cutler-Hammer Frame Size G, 16-100 Amperes GWF is direct supersedure for GW fixed thermal magnetic breaker.
PG.29B.01A.T.U Cutler-Hammer February 2001 Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications À 16, 32, 63 A are not UL Listed ratings and adjustable thermal not UL listed. Cutler-Hammer Frame Size E, 15-125 Amperes Two-pole E-Frame breakers available June 2001. Selection Guide and Ordering Information Maximum Continuous Ampere Rating at 40°C À IC Rating @ 415/480 V 1-Pole 2-Pole 3-Pole 4-Pole Fixed Thermal Fixed Magnetic Fixed Thermal Fixed Magnetic Fixed Thermal Fixed Magnetic Adjustable Thermal À Fixed Magnetic Thermal Range Fixed Thermal Fixed Magnetic Adjustable Thermal À Fixed Magnetic Thermal Range Complete Circuit Breaker Includes Frame, Trip Unit, Standard Terminals, and Mounting Hardware IEC/CE/UL/CSA 18/18 100 125 125 EGB1015FFG EGB1016FFG EGB1020FFG EGB1025FFG EGB1030FFG EGB1032FFG EGB1035FFG EGB1040FFG EGB1045FFG EGB1050FFG EGB1060FFG EGB1063FFG EGB1070FFG EGB1080FFG EGB1090FFG EGB1100FFG EGB1125FFG EGB2015FFG EGB2016FFG EGB2020FFG EGB2025FFG EGB2030FFG EGB2032FFG EGB2035FFG EGB2040FFG EGB2045FFG EGB2050FFG EGB2060FFG EGB2063FFG EGB2070FFG EGB2080FFG EGB2090FFG EGB2100FFG EGB2125FFG EGB3015FFG EGB3016FFG EGB3020FFG EGB3025FFG EGB3030FFG EGB3032FFG EGB3035FFG EGB3040FFG EGB3045FFG EGB3050FFG EGB3060FFG EGB3063FFG EGB3070FFG EGB3080FFG EGB3090FFG EGB3100FFG EGB3125FFG EGB3125KSG EGB3020AFG EGB3025AFG EGB3032AFG EGB3040AFG EGB3050AFG EGB3063AFG EGB3080AFG EGB3100AFG EGB3125AFG 16-20 20-25 25-32 32-40 40-50 50-63 63-80 80-100 100-125 EGB4015FFG EGB4016FFG EGB4020FFG EGB4025FFG EGB4030FFG EGB4032FFG EGB4035FFG EGB4040FFG EGB4045FFG EGB4050FFG EGB4060FFG EGB4063FFG EGB4070FFG EGB4080FFG EGB4090FFG EGB4100FFG EGB4125FFG EGB4125KSG EGB4020AFG EGB4025AFG EGB4032AFG EGB4040AFG EGB4063AFG EGB4080AFG EGB4100AFG EGB4125AFG 16-20 20-25 25-32 32-40 50-63 63-80 80-100 100-125 IEC/CE/UL/CSA 25/25 100 125 125 EGE2015FFG EGE2016FFG EGE2020FFG EGE2025FFG EGE2030FFG EGE2032FFG EGE2035FFG EGE2040FFG EGE2045FFG EGE2050FFG EGE2060FFG EGE2063FFG EGE2070FFG EGE2080FFG EGE2090FFG EGE2100FFG EGE2125FFG EGE3015FFG EGE3016FFG EGE3020FFG EGE3025FFG EGE3030FFG EGE3032FFG EGE3035FFG EGE3040FFG EGE3045FFG EGE3050FFG EGE3060FFG EGE3063FFG EGE3070FFG EGE3080FFG EGE3090FFG EGE3100FFG EGE3125FFG EGE3125KSG EGE3020AFG EGE3025AFG EGE3032AFG EGE3040AFG EGE3050AFG EGE3063AFG EGE3080AFG EGE3100AFG EGE3125AFG 16-20 20-25 25-32 32-40 40-50 50-63 63-80 80-100 100-125 EGE4015FFG EGE4016FFG EGE4020FFG EGE4025FFG EGE4030FFG EGE4032FFG EGE4035FFG EGE4040FFG EGE4045FFG EGE4050FFG EGE4060FFG EGE4063FFG EGE4070FFG EGE4080FFG EGE4090FFG EGE4100FFG EGE4125FFG EGE4125KSG EGB4020AFG EGB4025AFG EGB4032AFG EGB4040AFG EGB4063AFG EGB4080AFG EGB4100AFG EGB4125AFG 16-20 20-25 25-32 32-40 50-63 63-80 80-100 100-125 IEC/CE/UL/CSA 40/35 100 125 125 EGS1015FFG EGS1016FFG EGS1020FFG EGS1025FFG EGS1030FFG EGS1032FFG EGS1035FFG EGS1040FFG EGS1045FFG EGS1050FFG EGS1060FFG EGS1063FFG EGS1070FFG EGS1080FFG EGS1090FFG EGS1100FFG EGS1125FFG EGS2015FFG EGS2016FFG EGS2020FFG EGS2025FFG EGS2030FFG EGS2032FFG EGS2035FFG EGS2040FFG EGS2045FFG EGS2050FFG EGS2060FFG EGS2063FFG EGS2070FFG EGS2080FFG EGS2090FFG EGS2100FFG EGS2125FFG EGS3015FFG EGS3016FFG EGS3020FFG EGS3025FFG EGS3030FFG EGS3032FFG EGS3035FFG EGS3040FFG EGS3045FFG EGS3050FFG EGS3060FFG EGS3063FFG EGS3070FFG EGS3080FFG EGS3090FFG EGS3100FFG EGS3125FFG EGS3125KSG EGS3020AFG EGS3025AFG EGS3032AFG EGS3040AFG EGS3050AFG EGS3063AFG EGS3080AFG EGS3100AFG EGS3125AFG 16-20 20-25 25-32 32-40 40-50 50-63 63-80 80-100 100-125 EGS4015FFL EGS4016FFL EGS4020FFL EGS4025FFL EGS4030FFL EGS4032FFL EGS4035FFL EGS4040FFL EGS4045FFL EGS4050FFL EGS4060FFL EGS4063FFL EGS4070FFL EGS4080FFL EGS4090FFL EGS4100FFL EGS4125FFL EGS4125KSL EGS4020AFG EGS4025AFG EGS4032AFG EGS4040AFG EGS4063AFG EGS4080AFG EGS4100AFG EGS4125AFG 16-20 20-25 25-32 32-40 50-63 63-80 80-100 100-125 IEC/CE/UL/CSA 70/65 100 125 125 EGH1015FFG EGH1016FFG EGH1020FFG EGH1025FFG EGH1030FFG EGH1032FFG EGH1035FFG EGH1040FFG EGH1045FFG EGH1050FFG EGH1060FFG EGH1063FFG EGH1070FFG EGH1080FFG EGH1090FFG EGH1100FFG EGH1125FFG EGH2015FFG EGH2016FFG EGH2020FFG EGH2025FFG EGH2030FFG EGH2032FFG EGH2035FFG EGH2040FFG EGH2045FFG EGH2050FFG EGH2060FFG EGH2063FFG EGH2070FFG EGH2080FFG EGH2090FFG EGH2100FFG EGH2125FFG EGH3015FFG EGH3016FFG EGH3020FFG EGH3025FFG EGH3030FFG EGH3032FFG EGH3035FFG EGH3040FFG EGH3045FFG EGH3050FFG EGH3060FFG EGH3063FFG EGH3070FFG EGH3080FFG EGH3090FFG EGH3100FFG EGH3125FFG EGH3125KSG EGH3020AFG EGH3025AFG EGH3032AFG EGH3040AFG EGH3050AFG EGH3063AFG EGH3080AFG EGH3100AFG EGH3125AFG 16-20 20-25 25-32 32-40 40-50 50-63 63-80 80-100 100-125 EGH4015FFG EGH4016FFG EGH4020FFG EGH4025FFG EGH4030FFG EGH4032FFG EGH4035FFG EGH4040FFG EGH4045FFG EGH4050FFG EGH4060FFG EGH4063FFG EGH4070FFG EGH4080FFG EGH4090FFG EGH4100FFG EGH4125FFG EGH4125KSG EGH4020AFG EGH4025AFG EGH4032AFG EGH4040AFG EGH4050AFG EGH4063AFG EGH4080AFG EGH4100AFG EGH4125AFG 16-20 20-25 25-32 32-40 40-50 50-63 63-80 80-100 100-125
PG.29B.01A.T.U Cutler-Hammer 15Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications Interphase Barriers The interphase barrier is available for extended insulation between circuit breaker poles. Specify quantity when ordering. Package of 2 Catalogue Number – EFIPBK Control Wire Terminal Kit For use with steel or stainless steel À terminals only. Package of 12 – Priced Individually Catalogue Number – EFCWTK À Standard line and load terminals. Line and Load Terminals E-Frame circuit breakers and moulded case switches have line and load terminals as standard equipment. Selection Guide and Ordering Information Maximum Breaker Amperes Terminal Body Material Wire Type Metric Wire Range mm AWG Wire Range Catalogue Number Package of
3 Terminals
Standard Cu/Al Pressure Type Terminals 125 Steel Cu 2.5-95 #14-3/0 3T125EF À 125 125 Aluminium Aluminium Cu/Al Cu/Al 2.5-50 16-70 #14-1/0 #6-3/0 3TA125EF 3TA150EF Cutler-Hammer Frame Size E, 15-125 Amperes Terminal Shields The terminal shield is available for line terminal areas in 2-, 3-, and 4-pole circuit breakers. Special termi- nal shields are also available for use when an electrical (solenoid) opera- tor is mounted on the circuit breaker. The standard style number by pole for each terminal shield is for a pack- age of 10 and is priced per each package. Special terminal shields are packaged individually. Terminal End Covers The terminal end cover is available for 3-pole circuit breakers only. Two conductor opening sizes are availa- ble. Specify quantity (one per circuit breaker) when ordering. Number of Poles Standard Package of 10 IP30 Protection Catalogue Numbers – Priced Individually
2 EFTS2K
3 EFTS3K
4 EFTS4K
Diameter – mm (Inches) Catalogue Number 6.35 (0.25) EFTC3K 10.41 (0.41) EFTC4K Insert collar enclosing conductor as shown. Locate nut on top of conductor and tighten securely with screw and washer. Caution: Collar must surround conductor. Insert collar enclosing conductor and centre on extrusion. Tighten securely with screw and washer. EF3RTWK 3-Pole – Metric, EF4RTWK 4-Pole – Metric, EF3RTDK 3-Pole – Imperial, EF4RTDK 4-Pole – Imperial Endcap kits are used on E-frame breaker line load to connect bus bar or similar electrical connec- tions. Includes hardware. Catalogue Number Base Mounting Hardware Base mounting hardware is included with a circuit breaker or moulded case switch. (Included with breaker). DIN Rail Adapter Catalogue Number 3- or 4-Pole EF34DIN 3T125EF À 3TA125EF 3TA150EF Endcap Kit
PG.29B.01A.T.U Cutler-Hammer February 2001 Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications Cutler-Hammer Frame Size J, 100-250 Amperes À Change the 4th digit to 8 for adjustable 0-60% neutral protection, 9 for 0-100% neutral protection. IEC-EN 60947-2 only. Use 3-pole MCS. Selection Guide and Ordering Information Maximum Continuous Ampere Rating at 40°C Magnetic Range IC Rating @ 415/480 V 2-Pole 3-Pole 4-Pole À Fixed Thermal Adjustable Magnetic Fixed Thermal Adjustable Magnetic Adjustable Thermal Adjustable Magnetic Thermal Range Fixed Thermal Adjustable Magnetic Adjustable Thermal Adjustable Magnetic Thermal Range Complete Circuit Breaker Includes Frame, Trip Unit, Standard Terminals, and Mounting Hardware IEC/CE/UL/CSA 25/25 100 125 150 160 175 200 225 250 250 315-630 350-700 450-900 500-1000 625-1250 750-1500 800-1600 875-1750 1000-2000 1125-2250 1250-2500 1250-2500 JGE2070FAG JGE2090FAG JGE2100FAG JGE2125FAG JGE2150FAG JGE2175FAG JGE2200FAG JGE2225FAG JGE2250FAG JGE3063FAG JGE3070FAG JGE3090FAG JGE3100FAG JGE3125FAG JGE3150FAG JGE3160FAG JGE3175FAG JGE3200FAG JGE3225FAG JGE3250FAG JGE3250KSG JGE3063AAG JGE3100AAG JGE3125AAG JGE3160AAG JGE3200AAG JGE3250AAG 40-63 63-100 100-125 125-160 160-200 200-250 JGE4063FAG JGE4070FAG JGE4090FAG JGE4100FAG JGE4125FAG JGE4150FAG JGE4160FAG JGE4175FAG JGE4200FAG JGE4225FAG JGE4250FAG JGE4250KSG JGE4063AAG JGE4100AAG JGE4125AAG JGE4160AAG JGE4200AAG JGE4250AAG 40-63 63-100 100-125 125-160 160-200 200-250 IEC/CE/UL/CSA 40/35 100 125 150 160 175 200 225 250 250 315-630 350-700 450-900 500-1000 625-1250 750-1500 800-1600 875-1750 1000-2000 1125-2250 1250-2500 1250-2500 JGS2070FAG JGS2090FAG JGS2100FAG JGS2125FAG JGS2150FAG JGS2175FAG JGS2200FAG JGS2225FAG JGS2250FAG JGS3063FAG JGS3070FAG JGS3090FAG JGS3100FAG JGS3125FAG JGS3150FAG JGS3160FAG JGS3175FAG JGS3200FAG JGS3225FAG JGS3250FAG JGS3250KSG JGS3063AAG JGS3100AAG JGS3125AAG JGS3160AAG JGS3200AAG JGS3250AAG 40-63 63-100 100-125 125-160 160-200 200-250 JGS4063FAG JGS4070FAG JGS4090FAG JGS4100FAG JGS4125FAG JGS4150FAG JGS4160FAG JGS4175FAG JGS4200FAG JGS4225FAG JGS4250FAG JGS4250KSG JGS4063AAG JGS4100AAG JGS4125AAG JGS4160AAG JGS4200AAG JGS4250AAG 40-63 63-100 100-125 125-160 160-200 200-250 IEC/CE/UL/CSA 70/65 100 125 150 160 175 200 225 250 250 315-630 350-700 450-900 500-1000 625-1250 750-1500 800-1600 875-1750 1000-2000 1125-2250 1250-2500 1250-2500 JGH2070FAG JGH2090FAG JGH2100FAG JGH2125FAG JGH2150FAG JGH2175FAG JGH2200FAG JGH2225FAG JGH2250FAG JGH3063FAG JGH3070FAG JGH3090FAG JGH3100FAG JGH3125FAG JGH3150FAG JGH3160FAG JGH3175FAG JGH3200FAG JGH3225FAG JGH3250FAG JGH3250KSG JGH3063AAG JGH3100AAG JGH3125AAG JGH3160AAG JGH3200AAG JGH3250AAG 40-63 63-100 100-125 125-160 160-200 200-250 JGH4063FAG JGH4070FAG JGH4090FAG JGH4100FAG JGH4125FAG JGH4150FAG JGH4160FAG JGH4175FAG JGH4200FAG JGH4225FAG JGH4250FAG JGH4250KSG JGH4063AAG JGH4100AAG JGH4125AAG JGH4160AAG JGH4200AAG JGH4250AAG 40-63 63-100 100-125 125-160 160-200 200-250 Components Frame IEC/CE/UL/CSA 25/25 250 – JGE2250NN JGE3250NN – JGE4250NN – IEC/CE/UL/CSA 40/35 250 – JGS2250NN JGS3250NN – JGS4250NN – IEC/CE/UL/CSA 70/65 250 – JGH2250NN JGH3250NN – JGH4250NN – Trip Unit 100 125 150 160 175 200 225 250 315-630 350-700 450-900 500-1000 625-1250 750-1500 800-1600 875-1750 1000-2000 1125-2250 1250-2500 JT2063FA JT2070FA JT2090FA JT2100FA JT2125FA JT2150FA JT2160FA JT2175FA JT2200FA JT2225FA J2T250FA JT3063FA JT3070FA JT3090FA JT3100FA JT3125FA JT3150FA JT3160FA JT3175FA JT3200FA JT3225FA JT3250FA JT3063AA JT3100AA JT3125AA JT3160AA JT3200AA JT3250AA 40-63 63-100 100-125 125-160 160-200 200-250 JT4063FA JT4070FA JT4090FA JT4100FA JT4125FA JT4150FA JT4160FA JT4175FA JT4200FA JT4225FA JT4250FA JT4063AA JT4100AA JT4125AA JT4160AA JT4200AA JT4250AA 40-63 63-100 100-125 125-160 160-200 200-250
PG.29B.01A.T.U Cutler-Hammer 17Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications Cutler-Hammer Frame Size J250, 63-250 Amperes Endcap Kit Control Wire Terminal Kit Line and Load Terminals J250-Frame circuit breakers include Cu terminals, T250FJ as standard. When optional copper or Cu/1919Al terminals are required, order by catalogue number. Selection Guide and Ordering Information Catalogue Number T250FJ Interphase Barriers Terminal Shields IP30 Location Number of Poles Catalogue Number Package of 10 Line or Load 2, 3 FJTS3K FJTS4K Package of 2 Number of Poles Catalogue Number FJIPBK FJIPBK4 Maximum Breaker Amperes Terminal Body Material Wire Type Metric Wire Range mm AWG Wire Range/ Number Conductors Catalogue Number Standard Pressure Type Terminals
250 Stainless Steel Cu 25-185 4-350/(1) T250FJ
250 Aluminium Cu/Al 25-185 4-350/(1) TA250FJ
À Optional Copper and Cu/Al Pressure Type Terminals
250 Copper Cu/Al 25-185 4-350/(1) TC250FJ
À Base Mounting Hardware Base mounting hardware is included with a circuit breaker or moulded case switch. (Included with breaker). À Individually packed. Standard line and load terminals. TA250FJ TC250FJ Endcap kits are used on J250 Frame breaker line load to connect bus bar or similar electrical connections. Includes hardware. Kit Catalogue Number Number of Poles Catalogue Number Metric Imperial FJ3RTWK FJ4RTWK FJ3RTDK FJ4RTDK For use with aluminium or copper terminals only. Package of 14 - Priced Individually Catalogue Number – FJCWTK
PG.29B.01A.T.U Cutler-Hammer February 2001 Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications Selection Guide and Ordering Information Maximum Continu- ous Ampere Rating at 40°C Number of Poles Thermal Range Magnetic Range Standard Interrupting Capacity Catalogue Number High Interrupting Capacity Catalogue Number Ultra-High Interrupting Capacity Catalogue Number Thermal Magnetic Trip Unit Only For Use with Standard or High or Ultra- High Inter- rupting Frame Adjustable Thermal Adjustable Magnetic Standard Terminals Only Catalogue Number Metric Mounting Hardware Catalogue NumberU e Max. 690 VAC U e Max. 690 VAC U e Max. 690 VAC 45 kA I cu at 415 VAC 70 kA I cu at 415 VAC 100 kA I cu at 415 VAC Factory Assembled Circuit Breaker Consisting of Frame, Trip Unit, and Terminals and Mounting Hardware Frame Only Factory Assembled Circuit Breaker Consisting of Frame, Trip Unit, and Terminals and Mounting Hardware Frame Only Factory Assembled Circuit Breaker Consisting of Frame, Trip Unit, and Terminals and Mounting Hardware Frame Only Adjustable Thermal Magnetic Circuit Breakers with Interchangeable Trip Units Type KW Type HKW Type KWC 200 250 315 400 2-Pole 160-200 200-250 250-315 315-400 1000-2000 1250-2500 1575-3150 2000-4000 KW2200 KW2250 KW2315 KW2400 KW2400F HKW2200 HKW2250 HKW2315 HKW2400 HKW240F KWC2200 KWC2250 KWC2315 KWC2400 KWC2400F KT2200TA KT2250TA KT2315TA KT2400TA TA300KM À TA300KM À TA350KM À TA350KM À BMH3M BMH3M BMH3M BMH3M 200 250 315 400 3-Pole 160-200 200-250 250-315 315-400 1000-2000 1250-2500 1575-3150 2000-4000 KW3200 KW3250 KW3315 KW3400 KW3400F HKW3200 HKW3250 HKW3315 HKW3400 HKW3400F KWC3200 KWC3250 KWC3315 KWC3400 KWC3400F KT3200TA KT3250TA KT3315TA KT3400TA TA300KM À TA300KM À TA350KM À TA350KM À BMH3M BMH3M BMH3M BMH3M 200 250 315 400 315 400 4-Pole 160-200 200-250 250-315 315-400 250-315 315-400 1000-2000 1250-2500 1575-3150 2000-4000 1575-3150 2000-4000 KW4200 KW4250 KW4315 KW4400 KW4315E KW4400E KW4400F HKW4200 HKW4250 HKW4315 HKW4400 HKW4315E HKW4400E HKW4400F KWC4200 KWC4250 KWC4315 KWC4400 KWC4315E KWC4400E KWC4400F KT4200TA KT4250TA KT4315TA KT4400TA KT4315TEA KT4400TEA TA300KM À TA300KM À TA350KM À TA350KMÀ TA350KMÀ TA350KMÀ BMH3M BMH3M BMH3M BMH3M BMH3M BMH3M Adjustable Thermal Magnetic Earth Leakage Circuit Breakers with Line and Load Terminals Included – Type ELKW (Ue Max. 415 VAC) Type ELHKW (Ue Max. 415 VAC) Type ELKWC (Ue Max. 415 VAC) 200 250 315 400 3-Pole 160-200 200-250 250-315 315-400 1000-2000 1250-2500 1575-3150 2000-4000 ELKW3200 ELKW3250 ELKW3315 ELKW3400 – ELHKW3200 ELHKW3250 ELHKW3315 ELHKW3400 – ELKWC3200 ELKWC3250 ELKWC3315 ELKWC3400 – – TA350KM TA350KM TA350KM TA350KM BMH3M BMH3M BMH3M BMH3M 200 250 315 400 4-Pole 160-200 200-250 250-315 315-400 1000-2000 1250-2500 1575-3150 2000-4000 ELKW4200 ELKW4250 ELKW4315 ELKW4400 – ELHKW4200 ELHKW4250 ELHKW4315 ELHKW4400 – ELKWC4200 ELKWC4250 ELKWC4315 ELKWC4400 – – TA350KM TA350KM TA350KM TA350KM BMH3M BMH3M BMH3M BMH3M Moulded Case Switches MCS Only without Line and Load Terminals – Type KW (Ue Max. 690 VAC) Type HKW (Ue Max. 690 VAC) 400 2-Pole 3-Pole 4-Pole – – KW2400KW KW3400KW KW4400KW – HKW2400KW HKW3400KW HKW4400KW – – – – TA350KM À TA350KMÀ TA350KMÀ BMH3M BMH3M BMH3M Electronic Circuit Breakersˆ With Interchangeable Type KES Digitrip RMS Trip Units – Order as Individual Components: Breaker Frame, Trip Unit, Rating Plug, Terminals, Mounting Hardware Maximum Continuous Ampere Rating at 40°C À\` Number of Poles Circuit Breaker Frame Only Catalogue Number Digitrip RMS 310 Trip Unit Only Less Rating Plug Catalogue Number Digitrip RMS 310 Only Rating Plug Order as Individual Component Standard Terminals Only Catalogue Number Metric Mounting Hardware Catalogue NumberStandard Interrupt- ing Capacity High Interrupt- ing Capacity Ultra-High Interrupting Capacity L - Adjustable Long Delay Pickup (By Adjustable Rating Plug) S - Adjustable Short Delay Pickup with Fixed Short Delay Time (I 2t Response) or Adjustable Short Delay Time (Flat Response) I - Adjustable Instantaneous Pickup by Setting Short Delay Time to Instantaneous G - Adjustable Ground Fault Pickup with Adjustable Ground Fault Delay (Flat Response) Fixed Rating Plug Adjustable Rating Plug U e Max. 690 VAC Ampere Rating Catalogue Number Ampere Rating Catalogue Number 45 kA I cu at 415 VAC 70 kA Icu at 415 VAC 100 kA Icu at 415 VAC Type KW Type HKW Type KWC LS LSI LSG LSIG 125 3-Pole KW3400F HKW3400F KWC3400F KES3125LS KES3125LSI KES3125LSG KES3125LSIG 63 100 125 1KES063T 1KES070T 1KES090T 1KES100T 1KES125T Adjustable Settings are: 63/80/ A1KES125T2 TA300KM À TA300KMÀ TA300KMÀ TA300KMÀ TA300KMÀ BMH3M BMH3M BMH3M BMH3M BMH3M
250 KW3400F HKW3400F KWC3400F KES3250LS KES3250LSI KES3250LSG KES3250LSIG 125
Settings are: 125/160/ A2KES250T2 TA300KM À TA300KMÀ TA300KMÀ TA300KMÀ TA300KMÀ BMH3M BMH3M BMH3M BMH3M BMH3M
400 KW3400F HKW3400F KWC3400F KES3400LS KES3400LSI KES3400LSG KES3400LSIG 200
Settings are: 200/250/ A4KES400T2 TA300KM À TA300KMÀ TA300KMÀ TA350KMÀ TA350KMÀ BMH3M BMH3M BMH3M BMH3M BMH3M À Individually packed. \` Special 50ºC rating available. Order by description. ´ 60% protected neutral - left pole ˆ For AC application only. Cutler-Hammer Frame Size K, 63-400 Amperes
PG.29B.01A.T.U Cutler-Hammer 19Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications Handle Extension Not included with breaker. Must be purchased separately. Packaged Individually Catalogue Number – HEX3 Endcap Kit Control Wire Terminal Kit For use with aluminium or copper terminals only. Package of 14 - Priced Individually Catalogue Number – KCWTK Line and Load Terminals K-Frame circuit breakers include Cu/Al terminals as standard. When optional copper or Cu/1919Al terminals are required, order by catalogue number. Selection Guide and Ordering Information Catalogue Number TA300KM, TA300K, T300K TA350KM, TA350K, T350K TA400K, T400K TA401K Number of Poles Description Type of Mounting Catalogue Number Metric Thread 2, 3, 4 M6-0.7 x 38 mm Pan-Head Set screws and Lockwashers Individual 4218B80G14 Imperial Thread 2, 3, 4 0.250-20 x
1.5 Inch
Standard Pressure Type Terminals
225 Aluminium Cu/Al 35-185 3-350/(1) TA300KM À´
400 Aluminium Cu/Al 120-240 250-500/(1) TA350KM À´˜
Optional Copper and Cu/Al Pressure Type Terminals
225 Copper Cu 35-185 3-350/(1) T300K \`´
400 Copper Cu 120-240 250-500/(1) T300K \`´
400 Aluminium Cu/Al 95-120 3/0-250/(2) 2TA400K - 2-Pole Kit \`ˆ
3TA400K - 3-Pole Kit\ˆ 4TA400K - 4-Pole Kit\ˆ
400 Aluminium Cu 95-120 3/0-250/(2) 2T400K - 2-Pole Kit \`ˆ
3T400K - 3-Pole Kit\ˆ 4T400K - 4-Pole Kit\ˆ
400 Aluminium Cu/Al 70-240
2/0-250/(2) or 2/0-500/(1) 2TA401K - 2-Pole Kit\ˆ 3TA401K - 3-Pole Kit\ˆ 4TA401K - 4-Pole Kit\ˆ Base Mounting Hardware Base mounting hardware is included with a circuit breaker or moulded case switch. À Metric hardware. \ Imperial hardware. ´ Individually packed. ˆ TA400K, T400K, and TA401K terminal kits contain one terminal for each pole and one terminal cover. ˜ Standard terminal. Cutler-Hammer Frame Size K, 63-400 Amperes Endcap kits are used on K-Frame breaker line load to connect bus bar or similar electrical connections. Includes hardware. Kit Catalogue Number Metric Imperial KPEKM3 KPEK3 Interphase Barriers Terminal Shields Location Number of Poles Catalogue Number Package of 10 Line End 2, 3 TS33LN TS34LN Load End 3 TS33LD Package of 2 Catalogue Number – IPB3
PG.29B.01A.T.U Cutler-Hammer20 February 2001 Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications À Individually packed. \` Special 50ºC rating available. Order by description. ´ 2TA603KM, 3TA603LDKM and 4TA603LDKM terminal kits contain one ter- minal per each pole and one terminal cover. ˆ 60% protected neutral – left pole ˜ Ampere rating is established by rating plug. ¯ For AC application only. ˘ 3-pole LES trip units are for use in 3-pole frames only. ˙ Trip unit includes unprotected left neutral pole. For 100% protected left pole neutral add “P” to catalogue number, i.e., LES4630LSP. Selection Guide and Ordering Information Maximum Continuous Ampere Rating at 40°C Number of Poles Standard Interrupting Capacity Catalogue Number High Interrupting Capacity Catalogue Number Ultra-High Interrupting Capacity Catalogue Number Thermal Magnetic Trip Unit Only For Use with Standard or High or Ultra-High Interrupting Frame Adjustable Thermal Adjustable Magnetic Standard Terminals Only Catalogue Number Metric Mounting Hardware Catalogue Number U e Max. 690 VAC U e Max. 690 VAC U e Max. 690 VAC 45 kA Icu at 415 VAC 70 kA I cu at 415 VAC 100 kA I cu at 415 VAC Factory Assembled Circuit Breaker Consisting of Frame, Trip Unit, and Terminals Frame Only Factory Assembled Circuit Breaker Consisting of Frame, Trip Unit, and Terminals Frame Only Factory Assembled Circuit Breaker Consisting of Frame, Trip Unit, and Terminals Frame Only Adjustable Thermal Magnetic Circuit Breakers with Interchangeable Trip Units – Type LW Type HLW Type LWC – 315 400 500 630 2-Pole LW2315 LW2400 LW2500 LW2630 LW2630F HLW2315 HLW2400 HLW2500 HLW2630 HLW2630F LWC2315 LWC2400 LWC2500 LWC2630 LWC2630F LT2315TA LT2400TA LT2500TA LT2630TA TA602LDMÀ TA602LDMÀ TA602LDMÀ TA603LDKM´ BMH4M BMH4M BMH4M BMH4M 315 400 500 630 3-Pole LW3315 LW3400 LW3500 LW3630 LW3630F HLW3315 HLW3400 HLW3500 HLW3630 HLW3630F LWC3315 LWC3400 LWC3500 LWC3630 LWC3630F LT3315TA LT3400TA LT3500TA LT3630TA TA602LDMÀ TA602LDMÀ TA602LDMÀ TA603LDKM´ BMH4M BMH4M BMH4M BMH4M 315 400 500 630 500 630 4-Pole LW4315 ˙ LW4400˙ LW4500˙ LW4630˙ LW4500ˆ LW4630ˆ LW4630F HLW4315 HLW4400 HLW4500 HLW4630 HLW4500Eˆ HLW4630Eˆ HLW4630F LWC4315 LWC4400 LWC4500 LWC4630 LWC4500Eˆ LWC4630Eˆ LWC4630F LT4315TA LT4400TA LT4500TA LT4630TA LT4500TAˆ LT4630TAEˆ TA602LDMÀ TA602LDMÀ TA602LDMÀ TA603LDKM´ TA602LDMÀ TA603LDKM´ BMH4M BMH4M BMH4M BMH4M BMH4M BMH4M Thermal Magnetic Fixed Thermal Circuit Breakers with Noninterchangeable Trip Units and Bus Extension – Types LW (Ue Max. 690 VAC, 50 kA lcu @ 415 VAC) 700 800 3-Pole LW3700W LW3800W BMH4M Moulded Case Switches MCS Only without Line and Load Terminals – Type LW (690 VAC Max.) Type HLW (690 VAC Max.) – 630 2-Pole 3-Pole 4-Pole LW2630KW LW3630WK LW4630WK – HLW2630KW HLW3630WK HLW4630WK TA603LDKM´ TA603LDKM´ BMH4M BMH4M BMH4M 800 3-Pole 4-Pole LW3800WK LW4800WK BMH4M Cutler-Hammer Frame Size L, 315-800 Amperes Electronic Circuit Breakers¯ With Interchangeable Type LES Digitrip RMS Trip Units – Order as Individual Components: Breaker Frame, Trip Unit, Rating Plug, Terminals, Mounting Hardware Maximum Continu- ous Ampere Rating at 40°C Number of Poles Circuit Breaker Frame Only Catalogue Number Digitrip RMS 310 Trip Unit Only Less Rating Plug Catalogue Number Digitrip RMS 310 Only Rating Plug Order as Individual Component Standard Terminals Only Catalogue Number Metric Mounting Hardware Cata- logue Number Standard Interrupting Capacity High Interrupt- ing Capacity Ultra-High Interrupt- ing Capacity L - Adjustable Long Delay Pickup (By Adjustable Rating Plug) S - Adjustable Short Delay Pickup with Fixed Short Delay Time (I 2t Response) or Adjustable Short Delay Time (Flat Response) I - Adjustable Instantaneous Pickup by Setting Short Delay Time to Instantaneous G - Adjustable Ground Fault Pickup with Adjustable Ground Fault Delay (Flat Response) Fixed Rating Plug Adjustable Rating Plug 660 VAC Max. Ampere Rating Catalogue Number Ampere Rating Catalogue Number 45 kA I cu at 415 VAC 70 kA Icu at 415 VAC 100 kA Icu at 415 VAC Type LW Type HLW Type LWC LS LSI LSG LSIG 630 3-Pole ˘ LW3630F HLW3630F LWC3630F LES3630LS LES3630LSI LES3630LSG LES3630LSIG 315 350 400 500 630 6LES315T 6LES350T 6LES400T 6LES500T 6LES630T Adjustable Settings are: 315/400/ A6LES630T2 TA602LDMÀ TA602LDMÀ TA602LDMÀ TA603LDKMÀ TA603LDKM´ BMH4M BMH4M BMH4M BMH4M BMH4M 4-Pole˙ LW4630F HLW4630F LWC4630F LES4630LS LES6430LSI LES4630LSG LES4630LSIG 315 350 400 500 630 6LES315T 6LES350T 6LES400T 6LES500T 6LES630T Adjustable Settings are: 315/400/ A6LES630T2 TA602LDMÀ TA602LDMÀ TA602LDMÀ TA603LDKMÀ TA603LDKM´ BMH4M BMH4M BMH4M BMH4M BMH4M Electronic Circuit Breakers Includes Circuit Breaker Frame, Digitrip RMS 310 Electronic Trip Units with Noninterchangeable Adjustable Rating Plug and Bus Extension 800 3-Pole ˘ LW3800T33W LW3800T35W LW3800T35XW Settings are: 400/500/ A8LES800T1 – BMH4M BMH4M BMH4M
PG.29B.01A.T.U Cutler-Hammer 21Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications Circuit Breaker Line Terminal Cover TA401LD or TA603LD Terminal (Step-Type Terminal Requires Terminal Cover and Warning Label. See Inset.) Pan-Head Screws and Lockwashers TA450LD, TA602LD, or T602LD Terminal Pan-Head Screws and Lockwashers (Installed before Cable Clamping Screws) Selection Guide and
Ordering Information
L-Frame circuit breakers include Cu/Al terminals as standard equip- ment. When optional copper termi- nals are required, order by catalogue number. 800 ampere L-Frame circuit breakers include bus extensions only. Maximum Breaker Amperes Terminal Body Material Wire Type Metric Wire Range mm AWG Wire Range / No. Conductors Catalogue Number Standard Cu/Al Pressure Type Terminals
400 Aluminium Cu/AI 120-300 4/0-600 (1) 3TA401LDKM - 3-Pole Kit \`
4TA401LDKM - 4-Pole Kit\`
450 Aluminium Cu/AI 25-95 (2) 4-4/0 (2) TA450LDM À
500 Aluminium Cu/AI 120-150 250-350 (2) TA602LDM À
600 Aluminium Cu/AI 185-240 (2) 400-500 (2) 3TA603LDKM - 3-Pole Kit \`
4TA603LDKM - 4-Pole Kit\` Optional Copper Pressure Type Terminals
600 Copper Copper 120-150 250-350 (2) T602LDM À
À Individually packed. \` Terminal kits contain one terminal for each pole and one terminal cover. Terminal Shields Terminal shields provide protection against accidental contact with live line side terminations. Terminal shields are fabricated from high dielectric insulating material and fasten over the front terminal access openings. Small openings in the shields provide limited access to the terminals for tightening connectors. (Field installation only.) Handle Extension Not included with breaker. Must be purchased separately. Keeper Nut Not required on L-Frame. Terminal is threaded. Package of 2 Style Number – 314C420G01 Packaged Individually Catalogue Number – HEX4 Base Mounting Hardware Base mounting hardware is included with a circuit breaker or moulded case switch. Interphase Barriers The interphase barriers provide addi- tional electrical clearance between circuit breaker poles for special termi- nation applications. The barriers are high dielectric insulating plates that are installed in the moulded slots Number of Poles Description Type of Mounting Style Number Metric Thread 2, 3 0.250-20 x Individual 5103A09G01 Imperial Thread 2, 3, 4 0.250-20 x between the terminals. (Field installa- tion only.) Two per package. Endcap Kit Endcap kits are used on L-Frame breaker line load to connect bus bar or similar electrical connections. Includes hardware. Package of 2 Catalogue Number – IPB4 Kit Catalogue Number Metric Imperial KPEKM4 KPEK4 Terminal Cover Warning Label Retainer Screws Cutler-Hammer Frame Size L, 315-800 Amperes
PG.29B.01A.T.U Cutler-Hammer22 February 2001 Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications À For AC use only. \` Special 50ºC rating available. Order by description. ´ For 2-pole applications, use outer poles of 3-pole moulded case switch. ˆ Order rating plug and terminals separately. Selection Guide and Ordering Information Maximum Continuous Ampere Rating at 40°C Number of Poles Circuit Breaker Frame Including Digitrip RMS 310 Electronic Trip Unit Less Rating Plugs and Terminals Order as Individual Component – Catalogue Number ˆ Digitrip RMS 310 Interchangeable Rating Plugs Order as Individual Component L - Adjustable Long Delay Pickup (By Adjustable Rating Plug) S - Adjustable Short Delay Pickup with Fixed Short Delay Time 2t Response) or Adjustable Short Delay Time (Flat Response) I - Adjustable Instantaneous Pickup by Setting Short Delay Time to Instantaneous G -Adjustable Ground Fault Pickup with Adjustable Ground Fault Delay (Flat Response) Fixed Rating Plug Adjustable Rating Plug Ampere Rating Catalogue Number Ampere Rating Catalogue Number – LS LSI LSG LSIG – – – Short Time Range 2-8 x I n 2-8 x In 2-8 x In 2-8 x In Short Time Delay – 0-300 ms – 0-300 ms Ground Fault Pickup – – 200-1200A 200-1200A Ground Fault Delay – – 0-500 ms 0-500 ms Type NW Standard Interrupting Capacity – U e Max. 690 VAC, 50 kA lcu at 415 VAC 800 2-Pole NW2800T33W NW2800T32W NW2800T35W NW2800T36W 400 450 500 550 600 630 700 800 8NES400T 8NES450T 8NES500T 8NES550T 8NES600T 8NES630T 8NES700T 8NES800T Adjustable Settings Are: 400/500/630/800 8NES800T2 3-Pole NW3800T33W NW3800T32W NW3800T35W NW3800T36W 400 450 500 550 600 630 700 800 8NES400T 8NES450T 8NES500T 8NES550T 8NES600T 8NES630T 8NES700T 8NES800T 400/500/630/800 8NES800T2 4-Pole NW4800T33W NW4800T32W – – 400 450 500 550 600 630 700 800 8NES400T 8NES450T 8NES500T 8NES550T 8NES600T 8NES630T 8NES700T 8NES800T 400/500/630/800 8NES800T2 1250 2-Pole NW2125T33W NW2125T32W NW2125T35W NW2125T36W 600 630 700 800 900 1000 1200 1250 12NES600T 12NES630T 12NES700T 12NES800T 12NES900T 12NES1000T 12NES1200T 12NES1250T 630/800/1000/1250 A12NES1250T2 3-Pole NW3125T33W NW3125T32W NW3125T35W NW3125T36W 600 630 700 800 900 1000 1200 1250 12NES600T 12NES630T 12NES700T 12NES800T 12NES900T 12NES1000T 12NES1200T 12NES1250T 630/800/1000/1250 A12NES1250T2 4-Pole NW4125T33W NW4125T32W – – 600 630 700 800 900 1000 1200 1250 12NES600T 12NES630T 12NES700T 12NES800T 12NES900T 12NES1000T 12NES1200T 12NES1250T 630/800/1000/1250 A12NES1250T2 Moulded Case SwitchesÀ´ Ampere Rating Number of Poles Ue Max. 690 VAC Catalogue Number 800 3-Pole 4-Pole NW3800WK NW4800WK MCS Only without Line and Load 1250 3-Pole 4-Pole NW3125WK NW4125WK MCS Only without Line and Load 800 3-Pole 4-Pole HNW3800WK HNW4800WK MCS Only without Line and Load 1250 3-Pole 4-Pole HNW3125WK HNW4125WK MCS Only without Line and Load Cutler-Hammer Frame Size N, 400-1250 Amperes 50 kA at 415 VAC
PG.29B.01A.T.U Cutler-Hammer 23Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications Selection Guide and Ordering Information Maximum Continuous Ampere Rating at 40°C Number of Poles Circuit Breaker Frame Including Digitrip RMS 310 Electronic Trip Unit Less Rating Plugs and Terminals Order as Individual Component – Catalogue Number Digitrip RMS 310 Interchangeable Rating Plugs Order as Individual Component L - Adjustable Long Delay Pickup (By Adjustable Rating Plug) S - Adjustable Short Delay Pickup with Fixed Short Delay Time t Response) or Adjustable Short Delay Time (Flat Response) I - Adjustable Instantaneous Pickup by Setting Short Delay Time to Instantaneous G - Adjustable Ground Fault Pickup with Adjustable Ground Fault Delay (Flat Response) Fixed Rating Plug Adjustable Rating Plug Ampere Rating Catalogue Number Ampere Rating Catalogue Number LS LSI LSG LSIG –– – Short Time Range 2-8 x I n 2-8 x I n 2-8 x I n 2-8 x I n Short Time Delay – 0-300 ms – 0-300 ms Ground Fault Pickup – – 200-1200A 200-1200A Ground Fault Delay – – 0-500 ms 0-500 ms Type HNW Standard Interrupting Capacity – U e Max. 690 VAC, 70 kA I cu at 415 VAC 800 2-Pole HNW2800T33W HNW2800T32W HNW2800T35W HNW2800T36W 400 450 500 550 600 630 700 800 8NES400T 8NES450T 8NES500T 8NES550T 8NES600T 8NES630T 8NES700T 8NES800T Adjustable Settings Are: 400/500/630/800 8NES800T2 3-Pole HNW3800T33W HNW3800T32W HNW3800T35W HNW3800T36W 400 450 500 550 600 630 700 800 8NES400T 8NES450T 8NES500T 8NES550T 8NES600T 8NES630T 8NES700T 8NES800T 400/500/630/800 8NES800T2 4-Pole HNW4800T33W HNW4800T32W – – 400 450 500 550 600 630 700 800 8NES400T 8NES450T 8NES500T 8NES550T 8NES600T 8NES630T 8NES700T 8NES800T 400/500/630/800 8NES800T2 1250 2-Pole HNW2125T33W HNW2125T32W HNW2125T35W HNW2125T36W 600 630 700 800 900 1000 1200 1250 12NES600T 12NES630T 12NES700T 12NES800T 12NES900T 12NES1000T 12NES1200T 12NES1250T 630/800/1000/1250 A12NES1250T2 3-Pole HNW3125T33W HNW3125T32W HNW3125T35W HNW3125T36W 600 630 700 800 900 1000 1200 1250 12NES600T 12NES630T 12NES700T 12NES800T 12NES900T 12NES1000T 12NES1200T 12NES1250T 630/800/1000/1250 A12NES1250T2 4-Pole HNW4125T33W HNW4125T32W – – 600 630 700 800 900 1000 1200 1250 12NES600T 12NES630T 12NES700T 12NES800T 12NES900T 12NES1000T 12NES1200T 12NES1250T 630/800/1000/1250 A12NES1250T2 À For AC use only. Special 50ºC rating available. Order by description. Order rating plug and terminals separately. Cutler-Hammer Frame Size N, 400-1250 Amperes 70 kA at 415 VAC
PG.29B.01A.T.U Cutler-Hammer February 2001 Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications Selection Guide and Ordering Information Maximum Continuous Ampere Rating at 40°C Number of Poles Circuit Breaker Frame Including Digitrip RMS 310 Electronic Trip Unit Less Rating Plugs and Terminals Order as Individual Component – Catalogue Number Digitrip RMS 310 Interchangeable Rating Plugs Order as Individual Component L - Adjustable Long Delay Pickup (By Adjustable Rating Plug) S - Adjustable Short Delay Pickup with Fixed Short Delay Time t Response) or Adjustable Short Delay Time (Flat Response) I - Adjustable Instantaneous Pickup by Setting Short Delay Time to Instantaneous G - Adjustable Ground Fault Pickup with Adjustable Ground Fault Delay (Flat Response) Fixed Rating Plug Adjustable Rating Plug Ampere Rating Catalogue Number Ampere Rating Catalogue Number LS LSI LSG LSIG –– – Short Time Range 2-8 x I n 2-8 x I n 2-8 x I n 2-8 x I n Short Time Delay – 0-300 ms – 0-300 ms Ground Fault Pickup – – 200-1200A 200-1200A Ground Fault Delay – – 0-500 ms 0-500 ms Type NWC Standard Interrupting Capacity – U e Max. 690 VAC, 100 kA I cu at 415 VAC 800 2-Pole NWC2800T33W NWC2800T32W NWC2800T35W NWC2800T36W 400 450 500 550 600 630 700 800 8NES400T 8NES450T 8NES500T 8NES550T 8NES600T 8NES630T 8NES700T 8NES800T Adjustable Settings Are: 400/500/630/800 8NES800T2 3-Pole NWC3800T33W NWC3800T32W NWC3800T35W NWC3800T36W 400 450 500 550 600 630 700 800 8NES400T 8NES450T 8NES500T 8NES550T 8NES600T 8NES630T 8NES700T 8NES800T 400/500/630/800 8NES800T2 4-Pole NWC4800T33W NWC4800T32W – – 400 450 500 550 600 630 700 800 8NES400T 8NES450T 8NES500T 8NES550T 8NES600T 8NES630T 8NES700T 8NES800T 400/500/630/800 8NES800T2 1250 2-Pole NWC2125T33W NWC2125T32W NWC2125T35W NWC2125T36W 600 630 700 800 900 1000 1200 1250 12NES600T 12NES630T 12NES700T 12NES800T 12NES900T 12NES1000T 12NES1200T 12NES1250T 630/800/1000/1250 A12NES1250T2 3-Pole NWC3125T33W NWC3125T32W NWC3125T35W NWC3125T36W 600 630 700 800 900 1000 1200 1250 12NES600T 12NES630T 12NES700T 12NES800T 12NES900T 12NES1000T 12NES1200T 12NES1250T 630/800/1000/1250 A12NES1250T2 4-Pole NWC4125T33W NWC4125T32W – – 600 630 700 800 900 1000 1200 1250 12NES600T 12NES630T 12NES700T 12NES800T 12NES900T 12NES1000T 12NES1200T 12NES1250T 630/800/1000/1250 A12NES1250T2 À For AC use only. Special 50ºC rating available. Order by description. Order rating plug and terminals separately. Cutler-Hammer Frame Size N, 400-1250 Amperes 100 kA
PG.29B.01A.T.U Cutler-Hammer 25Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications Maximum Breaker Amperes Terminal Body Material Wire Type Metric Wire Range mm AWG Wire Number of Conductors Catalogue Number Standard Cu/Al Pressure-Type Terminals
1250 Aluminium Cu/Al 120-300 4/0-500 (3) TA1200NB3M
Optional Copper and Cu/Al Pressure Type Terminals
1250 Copper Copper 95-185 3/0-400 (4) T1200NB3M
Base mounting hardware is included with a circuit breaker or moulded case switch. Keeper Nut Not required on N-Frame. Terminals are threaded. Handle Extension Included with breaker. Additional handle extensions are available. Line and Load Terminals N-Frame circuit breakers include Cu/Al terminals as standard. When optional copper or Cu/Al terminals are required, order by catalogue number. Imperial Thread Number of Poles Description Catalogue Number 2-, 3-, and 4-pole 0.3125-18 x 1.25 Inch Pan-Head Steel Screws and Lock Washers BMH5M Single Handle Extension Catalogue Number – HEX5 Interphase Barriers Catalogue Number – IPB5 Cutler-Hammer Frame Size N, 400-1250 Amperes Selection Guide and Ordering Information Interphase Barriers The interphase barriers provide additional electrical clearance between circuit breaker poles for special termination applications. Barriers are high dielectric insulating plates that are installed in the Moulded slots between the terminals. (Field installation only.)
PG.29B.01A.T.U Cutler-Hammer February 2001 Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications Selection Guide and Ordering Information Maximum Continuous Ampere Rating at 40°C Number of Poles Circuit Breaker Frame Including Digitrip RMS 310 Electronic Trip Unit Less Rating Plugs and Terminals Order as Individual Component – Catalogue Number Digitrip RMS 310 Interchangeable Rating Plugs Order as Individual Component L - Adjustable Long Delay Pickup (By Adjustable Rating Plug) S - Adjustable Short Delay Pickup with Fixed Short Delay Time t Response) or Adjustable Short Delay Time (Flat Response) I - Adjustable Instantaneous Pickup by Setting Short Delay Time to Instantaneous G - Adjustable Ground Fault Pickup with Adjustable Ground Fault Delay (Flat Response) Fixed Rating Plug Adjustable Rating Plug Ampere Rating Catalogue Number Ampere Rating Catalogue Number LS LSI LSG ˆ LSIG –– – Short Time Range 2-8 x I n 2-8 x I n 2-8 x I n 2-8 x I n Short Time Delay – 0-300 ms – 0-300 ms Ground Fault Pickup – – 200-1200A 200-1200A Ground Fault Delay – – 0-500 ms 0-500 ms Type RW with Digitrip 310 Standard Interrupting Capacity – U e Max. 690 VAC, 70 kA I cu at 415 VAC 1600 À 3-Pole RW316T33W RW316T32W RW316T35W RW316T36W 800 1000 1200 1250 1400 1500 1600 16RES08T 16RES10T 16RES12T 16RES125T 16RES14T 16RES15T 16RES16T Adjustable Settings Are: 800/1000/1200/1600 A16RES16T1 800/1000/1250/1600 A16RES16T2
2000 RW320T33W RW320T32W RW320T35W RW320T36W 1000
2500 RW325T33W RW325T32W RW325T35W RW325T36W 1200
À 4-Pole RW416T33W RW416T32W – – 800 1000 1200 1250 1400 1500 1600 16RES08T 16RES10T 16RES12T 16RES125T 16RES14T 16RES15T 16RES16T 800/1000/1200/1600 A16RES16T1 800/1000/1250/1600 A16RES16T2
2000 RW420T33W RW420T32W – – 1000
2500 RW425T33W RW425T32W – – 1200
À For SCR application, use 2000A frame. Special 50ºC rating available. Order by description. Unprotected left pole neutral. Add “P” to catalogue number for 100% protected left pole neutral, add “E” for 60% protected, i.e., “RW416T33PW”, “RW416T33EW”. Cutler-Hammer Frame Size R, 800-2500 Amperes 70 kA at 415 VAC ˆ Ground fault equipped trip units available with remote indicating panel. Add “R” to catalogue number, i.e., “RW316T35RW”. Order rating plug and terminals separately. Mounting hardware not included.
PG.29B.01A.T.U Cutler-Hammer 27Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications À For SCR application, use 2000A frame. Special 50ºC rating available. Order by description. Unprotected left pole neutral. Add “P” to catalogue number for 100% protected left pole neutral, add “E” for 60% protected, i.e., “RW416T33PW”, “RW416T33EW”. Selection Guide and Ordering Information Maximum Continuous Ampere Rating at 40°C Number of Poles Circuit Breaker Frame Including Digitrip RMS 310 Electronic Trip Unit Less Rating Plugs and Terminals Order as Individual Component – Catalogue Number Digitrip RMS 310 Interchangeable Rating Plugs Order as Individual Component L - Adjustable Long Delay Pickup (By Adjustable Rating Plug) S - Adjustable Short Delay Pickup with Fixed Short Delay Time t Response) or Adjustable Short Delay Time (Flat Response) I - Adjustable Instantaneous Pickup by Setting Short Delay Time to Instantaneous G - Adjustable Ground Fault Pickup with Adjustable Ground Fault Delay (Flat Response) Fixed Rating Plug Adjustable Rating Plug Ampere Rating Catalogue Number Ampere Rating Catalogue Number LS LSI LSG ˆ LSIG ˆ __ _ Short Time Range 2-8 x I n 2-8 x I n 2-8 x I n 2-8 x I n Short Time Delay – 0-300 ms – 0-300 ms Ground Fault Pickup – – 200-1200A 200-1200A Ground Fault Delay – – 0-500 ms 0-500 ms Type RWC with Digitrip 310 High Interrupting Capacity – U e Max. 690 VAC, 100 kA I cu at 415 VAC 1600 À 3-Pole RWC316T33W RWC316T32W RWC316T35W RWC316T36W 800 1000 1200 1250 1400 1500 1600 16RES08T 16RES10T 16RES12T 16RES125T 16RES14T 16RES15T 16RES16T Adjustable Settings Are: 800/1000/1200/1600 A16RES16T1 800/1000/1250/1600 A16RES16T2
2000 RWC320T33W RWC320T32W RWC320T35W RWC320T36W 1000
À 4-Pole RWC416T33W RWC416T32W – – 800 1000 1200 1250 1400 1500 1600 16RES08T 16RES10T 16RES12T 16RES125T 16RES14T 16RES15T 16RES16T 800/1000/1200/1600 A16RES16T1 800/1000/1250/1600 A16RES16T2
2000 RWC420T33W RWC420T32W – – 1000
Cutler-Hammer Frame Size R, 800-2500 Amperes 100 kA at 415 VAC ˆ Ground fault equipped trip units available with remote indicating panel. Add “R” to catalogue number, i.e., “RW316T35RW”. Order rating plug and terminals separately. Mounting hardware not included.
PG.29B.01A.T.U Cutler-Hammer February 2001 Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications Selection Guide and Ordering Information Maximum Continuous Ampere Rating at 40°C À Number of Poles Circuit Breaker Frame Including Digitrip 610 and and 910 Electronic Trip Unit Less Rating Plugs and Terminals Order as Individual Component – Catalogue Number Digitrip RMS Interchangeable Rating Plug Order as Individual Component L - Adjustable Long Delay Pickup (I r ) with Adjustable Long Delay Time S - Adjustable Short Delay Pickup with Adjustable Short Delay Time (I t or Flat Response) I - Adjustable Instantaneous Pickup G - Adjustable Ground Fault Pickup with Adjustable Ground Fault Time Delay (I t or Flat Response) Fixed Rating Plug Ampere Rating Catalogue Number LI LS LSI LIG LSG LSIG Long Delay Pickup 0.5-1.0 x I n 0.5-1.0 x I n 0.5-1.0 x I n 0.5-1.0 x I n 0.5-1.0 x I n 0.5-1.0 x I n Long Delay Time 2-24 Seconds 2-24 Seconds 2-24 Seconds 2-24 Seconds 2-24 Seconds 2-24 Seconds Short Time Range 2-6 x I r 2-6 x I r 2-6 x I r 2-6 x I r 2-6 x I r 2-6 x I r Short Time Delay – 100-500 ms 100-500 ms – 100-500 ms 100-500 ms Instantaneous 2-6 x M1 & M2 – 2-6 x M1 & M2 2-6 x M1 & M2 – 2-6 x M1 & M2 Ground Fault Pickup – – – 0.25-1.0 x In 0.25-1.0 x In 0.25-1.0 x In Ground Fault Delay – – – 100-500 ms 100-500 ms 100-500 ms Type RW with Digitrip 610 Standard Interrupting Capacity – U e Max. 690 VAC, 70 kA I cu at 415 VAC 1600 3-Pole RW316T61W RW316T63W RW316T62W RW316T64W RW316T65W RW316T66W 800 1000 1200 1250 1600 RP6R16A080 RP6R16A100 RP6R16A120 RP6R16A125 RP6R16A160
2000 RW320T61W RW320T63W RW320T62W RW320T64W RW320T65W RW320T66W 1000
2500 RW325T61W RW325T63W RW325T62W RW325T64W RW325T65W RW325T66W 1600
Type RWC with Digitrip 610 High Interrupting Capacity – U e Max. 690 VAC, 100 kA I cu at 415 VAC 1600 3-Pole RWC316T61W RWC316T63W RWC316T62W RWC316T64W RWC316T65W RWC316T66W 800 1000 1200 1250 1600 RP6R16A080 RP6R16A100 RP6R16A120 RP6R16A125 RP6R16A160
2000 RWC320T61W RWC320T63W RWC320T62W RWC320T64W RWC320T65W RWC320T66W 1000
Type RW with Digitrip 910 Standard Interrupting Capacity – U e Max. 690 VAC, 70 kA I cu at 415 VAC 1600 3-Pole RW316T91W RW316T93W RW316T92W RW316T94W RW316T95W RW316T96W 800 1000 1200 1250 1600 RP6R16A080 RP6R16A100 RP6R16A120 RP6R16A125 RP6R16A160
2000 RW320T91W RW320T93W RW320T92W RW320T94W RW320T95W RW320T96W 1000
2500 RW325T91W RW325T93W RW325T92W RW325T94W RW325T95W RW325T96W 1600
Type RWC with Digitrip 910 High Interrupting Capacity – U e Max. 690 VAC, 100 kA I cu at 415 VAC 1600 3-Pole RWC316T91W RWC316T93W RWC316T92W RWC316T94W RWC316T95W RWC316T96W 800 1000 1200 1250 1600 RP6R16A080 RP6R16A100 RP6R16A120 RP6R16A125 RP6R16A160
2000 RWC320T91W RWC320T93W RWC320T92W RWC320T94W RWC320T95W RWC320T96W 1000
À Special 50ºC rating available. Order by description. Cutler-Hammer Frame Size R, 800-1250 Amperes 70 kA at 415 VAC and 100 kA at 415 VAC Order rating plug and terminals separately. Mounting hardware not included. Not to exceed 1200A ground fault pick-up.
PG.29B.01A.T.U Cutler-Hammer 29Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications Conductor (Viewed from Front of Circuit Breaker) Conductor (Viewed from Rear of Circuit Breaker and Cut Away for Clarity) Rear Connector (Cu) B2016RD B2016RDL (For 100% Application) (For 1600A and 2000A Frames) Securing Hardware Securing Hardware Cu Only Terminal Catalogue Number T1600RD (For 1600A Frame Only) Al/Cu Terminal Catalogue Number TA1600RD (For 1600A Frame Only) OR Maximum Breaker Amperes Terminal Body Material Wire Type Hardware AWG/kmil Wire Range/Number of Conductors Metric Wire Range mm Catalogue Number Wire Terminals 1600 1600 2000 Aluminium Copper Aluminium Cu/Al Cu Cu/Al English English English 500-1000 (4) 1-600 (4) 2-600 (6) 300-500 50-300 35-300 TA1600RD T1600RD TA2000RD Rear Connectors 2000 2000 2500 Copper Copper Copper English English English B2016RD B2016RDL B2500RD Line and Load Terminals R-Frame circuit breakers have Cu/Al terminals as standard and copper only terminals as an option. Specify if factory installation is required. À Catalogue number includes bus connection, terminals, and hardware for either line side or load side of 3-pole breaker. Base Mounting Hardware Supplied by customer. Single Handle Extension Catalogue Number – HEX6 Handle Extension Included with breaker. Additional handle extensions are available. Selection Guide and Ordering Information RD Rear Connector Exploded View Cutler-Hammer Frame Size R, 800-2500 Amperes Breaker Line/Load Conductors TA2000RDÀ
PG.29B.01A.T.U Cutler-Hammer30 February 2001 Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications À Combination ratings with Cutler-Hammer Freedom® / ADVANTAGE® Control, contact Cutler-Hammer. Selection Guide and Ordering Information Circuit Breakers for Motor Protection Breaker Type Rated Current In Rated Output of 3-Phase Motors À to Be Protected at 50 Hz Setting Current of Inverse-Time Overload Release I r Instantaneous Short Circuit Release I i Trip Class T c Standard Switching Capacity Catalogue Number High Switching Capacity Catalogue Number380/415V Max. kW 500V Max. kW Without Adjustment of the Trip Class, without Phase Unbalance Detection 40 kA at 380/415 VAC 70 kA at 380/415 VAC FWMP FWMP FWMP FWMP 100 160 205 110 110 132 40-80 80-100 100-160 160-205 15 x I r 15 x Ir 15 x Ir 13 x Ir FWMP3080L FWMP3100L FWMP3160L FWMP3205L HFWMP3080L HFWMP3100L HFWMP3160L HFWMP3205L 40 kA at 380/415 VAC KWMP LWMP 315 500 160 250 200 355 160-315 250-500 15 x Ir 15 x Ir KWMP3315W LWMP3500W HKWMP3315W HLWMP3500W With Adjustment of the Trip Class, with Phase Unbalance Detection 35 kA at 380/415 VAC 65 kA at 380/415 VAC FWMP-J FWMP-J FWMP-J FWMP-J 100 160 205 110 110 132 40-80 80-100 100-160 160-205 15 x I r 15 x Ir 15 x Ir 13 x Ir 5/10/15/20 5/10/15/20 5/10/15/20 FWMP3080JL FWMP3100JL FWMP3160JL FWMP3205JL HFWMP3080JL HFWMP3100JL HFWMP3160JL HFWMP3205JL 40 kA at 380/415 VAC KWMP-J LWMP-J 315 500 160 250 200 355 160-315 250-500 15 x Ir 15 x Ir 10/15/20/30 KWMP3315JW LWMP3500JW HKWMP3315JW HLWMP3500JW Motor Circuit Protectors for Combination Starters 35 kA at 380/415 VAC 65 kA at 380/415 VAC À HMCP HMCP HMCP HMCP HMCP HMCP HMCP HMCP HMCP HMCP HMCP HMCP Up to 63 Up to 100 Up to 150 Up to 125 Up to 160 Up to 200 Up to 200 Up to 250 Up to 315 Up to 315 Up to 400 Up to 500 110 160 160 200 250 110 110 132 132 160 200 200 250 355 300-1000 450-1500 750-1500 1000-2000 1125-2250 1250-2500 1500-3000 1750-3500 2000-4000 1800-6000 1800-6000 1800-6000 HMCPE100R3 HMCPJ250C5 HMCPJ250G5 HMCPJ250K5 HMCPJ250L5 HMCPJ250W5 HMCP400N5 HMCP400R5 HMCP400X5 HMCP600L6W HMCP600L6W HMCP600L6W Motor Circuit Protectors
PG.29B.01A.T.U Cutler-Hammer 31Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications Accessory Fit Type Frame G E125 J250 K L N R External Accessory Catalogue Numbers Non-Padlockable Handle Block Field Fitted 1294C01H01 EFHB – LKD3 LKD4 LKD4 – Padlockable Handle Block Field Fitted 223C77G03 EFPHB0FF FJPHB0FF PHB3 – – HLK6 Padlockable Handle Lock Hasp Field Fitted – EFPHL0FF FJPHL0FF PLK3 HLK4 PLK5 – Cylinder Lock Factory Fitted Order by Description Key Interlock Kit (Provision Only) Field Fitted – – KYKFJ KYK3 KYK4 KYK4 KYK6 Slide Bar Interlock – Requires 2 Breakers Field Fitted – – – SBK3 SBK4 SBK5 – Walking Beam Interlock – Requires 2 Breakers Factory Fitted Order by Description Electrical Operator 120 VAC – – – E0P3T07 E0P4T07 E0P5T07 E0P6T08
240 VAC – – – E0P3T11 E0P4T11 E0P5T11 E0P6T11
120 VDC – – – E0P3T07DC E0P4T26 – –
24 VDC – – – MOP3PO3DC E0P4MT21 E0P5T21K E0P6T19K
4 8 V D C ––––– E0P5T22 E0P6T21
125 VDC –––– E0P4T21 E0P5T26 –
Plug-In Adapters\ Field Fitted – 33333 – Rear Connecting Studs\ Field Fitted – 33333 – Handle Mechanism Field Fitted Only\ Flex Shaft 3333333 Rotary 333333 – Slide Plate – – – 3333 Direct 3333333 Test Kit Electronic Portable Test Kit (Digitrip 310 Only) – – – STK2 STK2 STK2 STK2 Special Calibration Special non-UL listed calibrations are available for certain ambient temperatures other than 40ºC and for frequencies other than 50/60 Hz or dc. Reduced interrupting ratings will apply for 400 Hz applications. Selection Guide and Ordering Information 50ºC Calibration À Add suffix “V” to catalogue number for complete breaker when ordering listed ampere ratings for breakers to be used in 50ºC ambients. Contact Cutler-Hammer for availability. Moisture-Fungus Treatment All Cutler-Hammer Circuit Breaker cases are moulded from glass-poly- ester which does not support the growth of fungus. Any parts which are susceptible to the growth of fungus will require special treatment. Order by description. Accessory Frame G E125 J250 K L N R Special Calibration 3333333 Moisture-Fungus Treatment 3333333 À K-, L-, N- and R-Frame breakers equipped with electronic trip units can operate reliably in ambient temperatures of 50ºC. \ Contact Cutler-Hammer for catalogue numbers. Cutler-Hammer Frame Sizes G through R
PG.29B.01A.T.U Cutler-Hammer32 February 2001 Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications Selection Guide and Ordering Information Accessory Pole Location Frame G E125 and J250 K L N R Field Fit Kit Catalogue Numbers Alarm Lockout Make/Break Left – – A1L3LPK A1L4LPK A1L5LPK – Right Factory Fit Only ALM1M1BEPK A1L3RPK A1L4RPK A1L5RPK A1L6RPK
2 Make/2 Break Left – – A2L3LPK A2L4LPK A2L5LPK –
Right – ALM2M2BEPK A2L3RPK A2L4RPK A2L5RPK A2L6RPK Auxiliary Switch 1A, 1B Left – – A1X3PK A1X4PK A1X5LPK – Right Factory Fit Only AUX1A1BPK A1X3PK A1X4PK A1X5RP – 2A, 2B Left – – A2X3PK A2X4PK A2X5LPK – Right Factory Fit Only AUX2A2BPK A2X3PK A2X4PK A2X5RPK A2X6RPK 3A, 3B Left – – A3X3LPK A3X4PK A3X5LPK – Right – – A3X3RPK A3X4PK A3X5RPK – Auxiliary Switch/ Alarm Lockout Left – – AAL3LPK AA114LPK AA115LPK – Right – AUXALRMEPK AAL3RPK AA114RPK AA115RPK – Shunt Trip – StandardÀ
120 VAC Left Factory Fit Only SNT120CPK SNT3P11K SNT4LP11K SNT5LP11K –
Right – – SNT3P11K SNT4RP11K – SNT6P11K
240 VAC Left Factory Fit Only SNT480APK SNT3P11K SNT4LP11K SNT5LP11K –
Right – – SNT3P11K SNT4RP11K – SNT6P11K
24 VDC Left Factory Fit Only SNT060CPK SNT3P04K SNT4LP03K SNT5LP03K –
Right – – SNT3P04K SNT4RP03K – SNT6P03K
48 VDC Left – SNT060CPK SNT3P06K SNT4LP23K SNT5LP23K –
Right – – SNT3P06K SNT4RP23K – SNT6P23K Shunt Trip – Low Energy Left – – LST3LPK LST4LPK LST5LPK – Right – – LST3RPK LST4RPK – LST6RPK Undervoltage Release MechanismÀ
120 VAC Left Factory Fit Only UVR120APK UVH3LP08K UVH4LP08K UVH5LP08K –
Right – – UVH3RP08K UVH4RP08K – UVH6RP08K
240 VAC Left Factory Fit Only UVR480APK UVH3LP11K UVH4LP11K UVH5LP11K –
Right – – UVH3RP11K UVH4RP11R – UVH6RP11K
24 VDC Left – UVR024CPK UVH3LP21K UVH4LP21K UVH5LP21K –
Right – – UVH3RP21K UVH4RP21K – UVH6RP21K
48 VDC Left – UVR048DPK UVH3LP23K UVH4LP23K UVH5LP23K –
Right – – UVH3RP23K UVH4RP23K – UVH6RP23K a b UV Make Break À Shunt trip and undervoltage release can only be mounted in left pole of K- and L-Frame breakers equipped with electronic trip units. ST c Cutler-Hammer Frame Sizes G through R
PG.29B.01A.T.U Cutler-Hammer 33Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications Selection Guide and Ordering Information Handle Mechanisms Overview Handle Mechanisms are used to operate moulded case circuit break- ers, moulded case switches and motor circuit protectors. They are available in three basic configura- tions — Flange Mounted, Through- the-Door and Direct (Close-Coupled) — providing safe, dependable oper- ation and ease of installation. Flange Mounted n Flex Shaft Through-the-Door n Universal Rotary Direct (Close-Coupled) n Universal Direct n Euro IEC n G Direct Handle mechanisms are typically used on enclosed circuit breakers, control panels and motor control centres in many different applica- tions. Cutler-Hammer has a handle mechanism for virtually any need. Flange Mounted Handle Mechanisms Flange Mounted Handle Mecha- nisms mount on the flange of an enclosure door. The Flex Shaft™ is an extra heavy-duty mechanism that includes a flexible shaft in various lengths, 0.9 meters (3 feet) through 3 meters (10 feet) for use with various size enclosures. The Flex Shaft Handle will accept up to three padlock shackles, each with a maximum diameter of 9.5 mm (3/8-inch). Can be used with NEMA 1, 3R and 12 fabricated enclosures. An optional handle is available for Flex Shaft that is suitable for use with NEMA 4 and 4X environments. Flex Shaft comes preset from the factory, requiring only minor field adjustments on installation, which takes about 10 minutes — a signifi- cant time savings compared to installation of other types of flange handle mechanisms. The Flex Shaft mechanism also takes up less interior enclosure space than competitive Flex Shaft™ Handle Mechanisms designs and the handle fits standard flange cutouts. Flex Shaft handle can be remotely mounted from breaker, where an operator can use it by “funnelling” the cable through conduit. Flex Shaft is UL Listed under File E64893 and meets CSA requirements. Flex Shaft Ordering Information Breaker Frame Flexible Shaft Length Meters (Feet) Catalogue Number EF FJ EHMFS03I JHMFS03I EHMFS04I JHMFS04I EHMFS05I JHMFS05I EHMFS06I JHMFS06I EHMFS07I JHMFS07I EHMFS08I JHMFS08I EHMFS09 JHMFS09 EHMFS10 JHMFS10 G K F0S03CI F3S03CI F0S04CI F3S04CI F0S05CI F3S05CI F0S06CI F3S06CI F0S07CI F3S07CI F0S08CI F3S08CI F0S09C F3S09C F0S10C F3S10C L and MDL N R N/A N/A N/A F4S04CI F5S04CI F6S04CI F4S05CI F5S05CI F6S05CI F4S06CI F5S06CI F6S06CI N/A N/A N/A N/A N/A N/A N/A N/A N/A F4S10C F5S10C N/A Note: Type 4/4X handle mechanisms are available. Add Suffix X before the I to complete Catalogue Number. Add Suffix L to complete Catalogue Number for 152.4 mm (6-inch) handle. Original narrow handle design (No C Suffix) is available. Remove C from Catalogue Number. Note: When selecting the length of shaft, ensure minimum bending radius of 101.6 mm (4 inches) is maintained to operate properly. The standard method of shipment includes the mechanism preset at the factory; however, minor field adjustments may be required. Flex Shaft Accessories (E- through R-Frame) Standard Door Hardware (Required Adapter Kit) Latch Panel Height mm (Inches) Catalogue Number 2 point 2 point 3 point Up to 762 (30) Up to 1016 (40) Over 1016 (40) DH1R DH2R DH3R Door Hardware Adapter Kit (Required on Standard Door Hardware) Catalogue Number — AMTDHA Flex Shaft Replacement Door Hardware Kits Breaker Frame Flexible Shaft Catalogue Number F J 5108A56G01 5108A56G02 LONR LH/RH F J K 5108A56G15 5108A56G16 5108A56G17 LONR LH/RH LH/RH F J K 5108A56G18 5108A56G19 5108A56G20 LONR LH/RH LH/RH Door Hardware for Hoffman A – 25 Enclosure À Latch Panel Height mm (Inches) Catalogue Number 2 point 3 point Up to 1016 (40) Over 1016 (40) HDH-2R HDH-3R Flange Mounted Instruction Leaflets Breaker Frame Instruction Leaflet/FRED Number Flex Shaft EF FJ G 29C265 29C518 TBD F J K 15609 15605 15604 L and M N R 15606 15606 15606 À Kit consists of special door hardware and door interlock pin. Available for right hand flange mounting only.
PG.29B.01A.T.U Cutler-Hammer February 2001 Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications Handle Mechanisms Selection Guide and Ordering Information Through-the-Door Handle Mechanisms Rotary The Cutler-Hammer Rotary is suita- ble for use with NEMA 1 and 12 enclosure types. All Rotary handle mechanisms include a handle “Lock Off,” to prevent turning the breaker ON while in the OFF position. All Rotary handles indicate ON/OFF/ Tripped/Reset positions, however, Universal Rotary has the added feature of international markings for ON (I) and OFF (O). Cutler-Hammer Rotary handle is metal, Universal Rotary is made of moulded material. Cutler-Hammer Rotary handle is black and Universal Rotary is available in black or yellow/red. Universal Rotary Ordering Information Shaft Length in mm (Inches) Handle Colour Complete Catalogue Number À Cutler-Hammer Rotary Complete Catalogue Number À IEC IP65 IEC IP66 EF-Frame 152.4 (6) 304.8 (12) 152.4 (6) 304.8 (12) Black Black Red Red EHMVD06B EHMVD12B EHMVD06R EHMVD12R FJ-Frame 152.4 (6) 304.8 (12) 152.4 (6) 304.8 (12) Black Black Red Red FJHMVD06B FJHMVD12B FJHMVD06R FJHMVD12R G-Frame 152.4 (6) 304.8 (12) 152.4 (6) 304.8 (12) Black Black Red Red GHMVD06B GHMVD12B GHMVD06R GHMVD12R F-Frame 152.4 (6) 304.8 (12) 152.4 (6) 304.8 (12) Black Black Red Red FHMVD06B FHMVD12B FHMVD06R FHMVD12R WHM1B06 WHM1B12 WHM1R06 WHM1R12 WHM1B06X WHM1B12X WHM1R06X WHM1R12X J-Frame 152.4 (6) 304.8 (12) 152.4 (6) 304.8 (12) Black Black Red Red JHMVD06B JHMVD12B JHMVD06R JHMVD12R WHM2B06 WHM2B12 WHM2R06 WHM2R12 WHM2B06X WHM2B12X WHM2R06X WHM2R12X K-Frame 152.4 (6) 304.8 (12) 152.4 (6) 304.8 (12) Black Black Red Red KHMVD06B KHMVD12B KHMVD06R KHMVD12R WHM3B06 WHM3B12 WHM3R06 WHM3R12 WHM3B06X WHM3B12X WHM3R06X WHM3R12X L- and MDL-Frames 152.4 (6) 304.8 (12) 152.4 (6) 304.8 (12) Black Black Red Red LHMVD06B LHMVD12B LHMVD06R LHMVD12R WHM4B06 WHM4B12 WHM4R06 WHM4R12 WHM4B06X WHM4B12X WHM4R06X WHM4R12X N-Frame 152.4 (6) 304.8 (12) Black Red HMVD15HB + HMCC5W HMVD15HR + HMCC5W WHM5B06 WHM5R12 WHM5B06X WHM5R12X R-Frame 152.4 (6) 304.8 (12) Black Red HMVD15HB + HMCC6W HMVD15HR + HMCC6W WHM5B06 WHM5R12 WHM5B06X WHM5R12X Through-the-Door Instruction Leaflets/ FRED Number Breaker Frame Cutler-Hammer Rotary Universal Rotary EF FJ 29C517 29C519 G F 15594 29C250 29C250 J K 15599 15600 29C250 29C250 L & MDL N 15601 15602 29C250 À Complete catalogue number includes handle, mechanism, shaft and mounting hardware.
PG.29B.01A.T.U Cutler-Hammer 35Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications Direct (Close-Coupled) Handle Mechanisms Universal Direct Euro IEC Direct G Direct Direct (Close-Coupled) Handle Mech- anisms mount directly to the circuit breaker. They are used in shallow enclosures where the standard variable depth Through-the-Door type mechanism is not practical or cannot be used. They are typically for applications where high volume, standardized enclosures are being fabricated. The Universal Direct handle mecha- nism is designed exclusively for the new Cutler-Hammer E125 and J250 circuit breakers. It is available as standard with a door interlock to prevent opening the enclosure while the circuit breaker is in the ON position. It is also available without a door interlock. Handle Mechanisms Selection Guide and Ordering Information À Suitable for use on 2- or 3-pole G-Frame. Universal Direct Ordering Information Frame Universal Direct Domestic Universal Direct International with Interlock (white) without Interlock (white) without Interlock (charcoal with global label) Catalogue Number EF FJ EHMCCBI JHMCCBI EHMCCB JHMCCB EHMCCR JHMCCR Euro IEC Direct Ordering Information Frame Catalogue Number Black Handle Red Handle K L and M HMCC3B HMCC4B HMCC3R HMCC4R N R HMCC5B HMCC6B HMCC5R HMCC6R G Direct Ordering Information À Frame Catalogue Number Black Handle Yellow Handle with Shroud without Shroud with Shroud without Shroud GD GC HRGCC1S HRGCC1S HRGCC10 HRGCC10 HRGCC3S HRGCC3S HRGCC30 HRGCC30 GHC GMCP HRGCC1S HRGMC1S HRGCC10 HRGMC10 HRGCC3S HRGMC3S HRGCC30 HRGMC30 Direct (Close-Coupled) Instruction Leaflets Frame Instruction Leaflet/FRED Number Universal Direct Euro IEC Direct G Direct EF FJ G 29C255 29C256 15567 F J K 29C288A 29C288A 29C288A L and MDL N R 29C289 29C290 29C291 The Euro IEC Direct handle mecha- nism can be used on F- through R-Frames. G Direct is available with a black or yellow handle, and with or without a shroud. It is suitable for use with NEMA 1 enclosures. It is for use only with the G-Frame (GD, GC, GHC, GMCP). An escutcheon ring and interlock clip are provided as standard. The stand- ard design includes a lock-off feature. The Universal Direct handle mecha- nism is UL 489 listed, IEC 60947-1/2 and meets CSA requirements. The Euro IEC Direct handle mechanism is IEC-240-1. G Direct is UL listed and meets CSA requirements.
PG.29B.01A.T.U Cutler-Hammer February 2001 Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications 2 AS 2 AS 1 AS F-Frame for Motor Protection
4 AUX 4 AUX 4 AUX 4 AUX 4 AUX 4 AUX
U< DI U< DI U< DI U< DI U< DI U< DI U< DI U< DI U< DI
1 AUX
2 AUX
1 AS + 1 AUX
U< 2AS 2AS 2AS U< 2AS 2AS 2AS 2 AS 2 AS 1 AS U< DI = Shunt Trip or Undervoltage Release or DI Module (if Built-In) = Auxiliary Switch AS = Alarm Switch = For R-Frame Circuit Breakers Only Remote Controlled Operating Mechanisms Cutler-Hammer Circuit Breakers (sizes 160 to 2000 amperes) can be equipped with motorized operating mechanisms for remote in-service closing and opening. For normal remote opening, sole- noid operating mechanisms F- and K-Frames are available for circuit breakers and motorized operating mechanisms for J to R (sizes 250 to 2500 amperes) solenoid operating mechanisms and motor operators are always supplied with a locking device for padlocks. This device can be used for electrical and mechanical blocking of the operating mecha- nism. All remote operating mecha- nisms are equipped with a manual actuator for local operation. Alarm Lockout The alarm switches operate when the circuit breaker is tripped by a short circuit or overcurrent, but also when it is tripped by a shunt trip or undervoltage release. Auxiliary Switches Auxiliary switches are used for sig- nalling and control purposes. The various functions of the auxiliary switches (changeover) are shown in the top table to the right. Shunt Trips The shunt trip is used for remote tripping. The coil of the shunt trip is rated only for short-time operation. It is not permissible with the circuit breaker open to apply a continuous opening command to the shunt trip in order to prevent the breaker from closing. This means that interlocking circuits with continuous commands may not be set up with shunt trips. Undervoltage Releases The circuit breaker cannot be closed until the undervoltage release is energized. If the release is not ener- gized, the circuit breaker can only perform an idle switching operation. Frequent idle switching actions should be avoided as they shorten the endurance of the circuit breaker. Possible Equipment of E- and L-Frame Circuit Breakers with Auxiliary and Alarm Switches Selection Guide and Ordering Information Contact making by the auxiliary and alarm switches as a function of the switching position of the circuit breaker OFF RESET ON Tripped Position of the Toggle Handle Drive (Equivalently Applicable for Rotary Drives) Position of the Auxiliary Switch Position of the Alarm Switch Cutler-Hammer Frame Sizes G through R E125 and J250 Auxiliary Switch or Alarm Switch in the Right Pole. E125 and J250 Shunt Trip or UVR in the Left Pole.
PG.29B.01A.T.U Cutler-Hammer 37Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications 100 24 68 101 24 68 102 24 68 103 10000 5000 3000 2000 1000 500 300 200 100 .05 .03 .02 .01 .005 .003 .002 .001 TIME IN SECONDS CURRENT IN MULTIPLES OF In (a) 50-125 Notes: “a” fix ed inverse-time overcurrent release “ b” fix ed electromagnetic release “ c” total operation time “d” in terrupting rating determines end of curve 30-32 15-16 45 (c) (d) Max. Trip Time Min. Trip Time 100 24 6 8 1 0 1 24 6 8 1 0 2 24 6 8 1 0 3 10000 5000 3000 2000 1000 500 300 200 100 .05 .03 .02 .01 .005 .003 .002 .001 TIME IN SECONDS CURRENT IN MULTIPLES OF I n (660/690V) (n) 10XIn (a) (380/415V) (220/240V) 5XIn Notes: “a” thermal overload release “n” instantaneous (electromagnetic) short circuit release 102 24 6 8 1 0 3 24 6 8 1 0 4 24 6 8 1 0 5 10000 5000 3000 2000 1000 500 300 200 100 .05 .03 .02 .01 .005 .003 .002 .001 TIME IN SECONDS CURRENT IN MULTIPLES OF I n Two Poles in Series For IEC Use Only Minimum Trip Time Maximum Trip Time (n) (a) Notes: “a” thermal overload release “n” instantaneous (electromagnetic) short circuit release 100 24 6 8 1 0 1 24 6 8 1 0 2 24 6 8 1 0 3 10000 5000 3000 2000 1000 500 300 200 100 .05 .03 .02 .01 .005 .003 .002 .001 TIME IN SECONDS CURRENT IN MULTIPLES OF I n (660/690V) (n) 10XIn (a) (380/415V) (220/240V) 5XIn Notes: “a” thermal overload release “n” instantaneous (electromagnetic) short circuit release Time-Current Curves Tripping Characteristics The operating values specified for the inverse time overcurrent releases (thermal overload releases, “a” releases) are mean values of the scatter bands of all setting ranges from the cold state and with uniform current loading of the conducting paths. The tripping characteristics of the instantaneous (electromagnetic) short circuit releases (“n” releases) are based on the rated phase current I n which in the case of circuit break- ers with adjustable thermal overload releases is also the upper value of the setting range. With a lower setting current, a correspondingly higher multiple is obtained for the operating current of the “n” release. Individual time-current curves K- and L-Frame Digitrip 310 Electronic Trip Curves are available upon request. Type GWF Tripping characteristics of GWF circuit breakers for plant protection, I cu = 25 kA, “n” release fixed setting n = 500-1300 for breaker 16-63A; 1300-1800 for breaker 70-100A Type J250 Tripping characteristics of J250 circuit breakers for plant protection, I cu = 25/40/70 kA, “n” release adjustable Type KW Tripping characteristics of KW circuit breakers for plant protection, I cu = 45/70 kA, “n” release adjustable Cutler-Hammer Frame Sizes G through K Tripping time characteristics (Thermal Memory) Cold Cold Warm Warm 0 15 min 10 Cooling Down Heating Up Type E125 Tripping characteristics of E125 circuit breakers for plant protection, I cu = 18/25/40/70 kA, “n” release fixed setting n = 500-1300 for breaker 16-63A; 1300-1800 for breaker 70-125A
PG.29B.01A.T.U Cutler-Hammer February 2001 Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications 100 24 6 8 1 0 1 24 6 8 1 0 2 24 6 8 1 0 3 10000 5000 3000 2000 1000 500 300 200 100 .05 .03 .02 .01 .005 .003 .002 .001 TIME IN SECONDS CURRENT IN MULTIPLES OF I n (660/690V) (n) 10XIn (a) (380/415V) (220/240V) 5XIn Notes: “a” thermal overload release “n” instantaneous (electromagnetic) short circuit release 100 24 6 8 1 0 1 24 6 8 1 0 2 24 6 8 1 0 3 10000 5000 3000 2000 1000 500 300 200 100 .05 .03 .02 .01 .005 .003 .002 .001 TIME IN SECONDS CURRENT IN MULTIPLES OF I n (660/690V) (n) 10XIn (a) (380/415V) (220/240V) 5XIn Notes: “a” thermal overload release “n” instantaneous (electromagnetic) short circuit release 100 24 6 8 1 0 1 24 6 8 1 0 2 24 6 8 1 0 3 10000 5000 3000 2000 1000 500 300 200 100 .05 .03 .02 .01 .005 .003 .002 .001 TIME IN SECONDS CURRENT IN MULTIPLES OF I n (660/690V) (n) 10XIn (a) (380/415V) (220/240V) 5XIn Notes: “a” thermal overload release “n” instantaneous (electromagnetic) short circuit release Time-Current Curves Tripping Characteristics The operating values specified for the inverse time overcurrent releases (thermal overload releases, “a” releases) are mean values of the scatter bands of all setting ranges from the cold state and with uniform current loading of the conducting paths. The tripping characteristics of the instantaneous (electromagnetic) short circuit releases (“n” releases) are based on the rated phase current I n which in the case of circuit break- ers with adjustable thermal overload releases is also the upper value of the setting range. With a lower set- ting current, a correspondingly higher multiple is obtained for the operating current of the “n” release. Type LW Tripping characteristics of LW circuit breakers for plant protection, I cu 45/70 kA, “n” release adjustable Type KW Tripping characteristics of KW circuit breakers for plant protection, I cu = 100 kA, “n” release adjustable Type LW Tripping characteristics of LW circuit breakers for plant protection, I cu 100 kA, “n” release adjustable Cutler-Hammer Frame Sizes K through L
PG.29B.01A.T.U Cutler-Hammer 39Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications 12 3 4 5 6 8 1 0 15Xlr 7200 1000 500 200 100 .05 .02 .01 .005 TIME IN SECONDS CURRENT IN MULTIPLES OF I n 1.5 10 15 20 30 40 60 80 100 200kA Setting for ld as Multiples of lr (7X lr Not Shown) 7 X td 300 ms 200 ms 100 ms n s a Notes: Inverse-time overload release “a” lr Set current (adjustable) Short time delayed short circuit release ld Tripping current (adjustable) td Delay time (adjustable) Instantaneous short circuit release “n” li Tripping current (fixed setting) 12 3 4 5 6 8 1 0 15Xlr 7200 1000 500 200 100 .05 .02 .01 .005 TIME IN SECONDS CURRENT IN MULTIPLES OF I n 1.5 10 15 20 30 40 60 80 100 200kA Setting for ld as Multiples of lr (7x lr Not Shown) 7 X Notes: Inverse-time overload release “a” lr Set current (adjustable) Short time delayed short circuit release ld Tripping current (adjustable) td Delay time (adjustable) Instantaneous short circuit release “n” li Tripping current (fixed setting) td 300 ms 200 ms 100 ms n s a Time-Current Curves Type NW Tripping characteristics for NW circuit breakers, I cu 50/70/100 kA, with solid state overcurrent release Working Temperature Range The tolerance bands shown are applicable to an ambient tempera- ture range of -5 to +60°C at the circuit breaker. Working Temperature Range The tolerance bands shown are applicable to an ambient tempera- ture range of -5 to +60°C at the circuit breaker. Type RW Tripping characteristics for RW circuit breakers, I cu 70/100 kA, with solid state overcurrent release Cutler-Hammer Frame Sizes N and R
PG.29B.01A.T.U Cutler-Hammer February 2001 Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications 11 0 100Xle 7200 1000 100 .01 TIME IN SECONDS CURRENT IN MULTIPLES OF I n s Class 30 Type FWMP, KWMP, and LWMP Tripping characteristics for FWMP, KWMP, and LWMP circuit breakers for motor protection with solid state overcurrent releases Time-Current Curves Characteristics of the FWMP, KWMP, and LWMP Circuit Breakers for Motor Protection with Solid State Overcurrent Releases The tripping times of the inverse- time delayed overcurrent releases are only valid for the not preloaded (cold) state. At operating tempera- ture (after load with rated current), the tripping times are reduced to approximately 33%. After an over- current trip, the tripping times are reduced according to the tripping time characteristics (see figure below) so that cooling down for some minutes is required before restarting the motor. During the first minute after tripping, reclosing of the circuit breaker is blocked. Cutler-Hammer Frame Sizes F through L
PG.29B.01A.T.U Cutler-Hammer 41Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications 5 7 10 20 30 50 kA 100 100 I2t VALUE X10 5 SHORT CIRCUIT CURRENT I Srms L A2s K J F 5 7 10 20 30 50 kA 100 100 I2t VALUE X10 6 SHORT CIRCUIT CURRENT I Srms A2s RÀ NÀ Notes: À 50/60 Hz 380/415 VAC \` 50/60 Hz 660/690 VAC 5 7 10 20 30 50 kA 100 200 kA 100 CUT-OFF CURRENT I D SHORT CIRCUIT CURRENT I Srms 0.3 0.2 R N 0.5 cos =0.25 5 7 10 20 30 50 kA 100 100 I2t VALUE X10 5 SHORT CIRCUIT CURRENT I Srms L K J F 5 7 10 20 30 50 kA 100 200 kA 100 CUT-OFF CURRENT I D SHORT CIRCUIT CURRENT I Srms 0.3 0.2 F J K L cos =0.25 0.3 5 7 10 20 30 50 kA 100 200 kA 100 CUT-OFF CURRENT I D SHORT CIRCUIT CURRENT I Srms 0.2 F J K L cos =0.25 Current Limiting Curves Current Limiting Characteristics and Maximum I2t Values Type E/LW Current limiting characteristics for E to LW, 50/60 Hz 380/415 VAC Type E/LW Current limiting characteristics for E to LW, 50/60 Hz 660/690 VAC Type NW/RW Current limiting characteristics for NW to RW, 50/60 Hz 380/415 VAC Type FW/LW Maximum I2t values for FW to LW, 50/60 Hz 380/415 VAC Type FW/LW Maximum I2t values for FW to LW, 50/60 Hz 660/695 VAC Type NW/RW Maximum I2t values for NW to RW Cutler-Hammer Frame Sizes E through R
PG.29B.01A.T.U Cutler-Hammer42 February 2001 Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications Front View 3-PoleFront Cover Cutout Side View 76.20 (3.000) 76.20 (3.000) 56.34 (2.218) 66.67 (2.625) 81.74 (3.218) 123.82 (4.875) Front View 3-PoleFront Cover Cutout Side View 70.35 (2.770) 76.96 (3.03) 139.70 (5.500) (1.850) 33.02 Dia. 22.86 (0.900) 11.94 (0.47) CL 76.20 (3.000) Handle C L Breaker Front View 3-PoleFront Cover Cutout Side View 104.77 (4.125) 4.75 (0.188) R 87.38 (3.440) 177.80 (7.000) 100.38 (3.952) 101.60 (4.000) 77.80 (3.063) 51.99 (2.047) C L Breaker 26.97 (1.062)12.70 (0.500) CLHandle 7.137 (0.281) Front View 3-PoleFront Cover Cutout Side View 139.45 (5.490) 104.00 (4.094) 257.17 (10.125) 151.55 (5.967) 33.35 (1.313) 4.77 (0.188) R 41.66 (1.640) 60.73 (2.391) 66.67 (2.625) 121.46 (4.782) 31.75 (1.250) 8.74 (0.344) R C L Breaker CL Handle Dimensions, mm (inches) E125-Frame J250-Frame K-Frame Cutler-Hammer Frame Sizes G through K G-Frame Dimensions in parentheses in inches.
PG.29B.01A.T.U Cutler-Hammer 43Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications Front View 3-PoleFront Cover Cutout 43.66 (1.719) 63.50 (2.500) R 4.77 (0.188) R 69.90 (2.752) 139.70 (5.500) 184.94 (7.281) 87.32 (3.438) 58.22 (2.292) 33.65 (1.325) 92.48 (3.641) 83.34 (3.281) 142.60 (5.614) 273.10 (10.752) 406.40 (16.00) 38.10 (1.500) CL Handle 209.60 (8.252) 69.90 (2.752) 5.10 R (0.200) 11.10 Dia. (0.437) 381.00 (15.000) 333.00 (13.110) 323.00 (12.716) 12.70 (0.500) 120.30 (4.736) 242.30 (9.539) CL Breaker 44.50 (1.752) Side View 10.00 (0.394) 1 11.10 (4.374) 13.00 (0.512) 24.60 (0.968) 96.80 (3.811) (0.875) CL Bus Ext 234.95 (9.250) CL Breaker Front View 3-PoleFront Cover Cutout 406.40 (16.000) 87.32 (3.438) 6.35 (0.250) R Side View CL Handle 139.68 (5.499) 209.55 (8.250) 43.63 (1.718) 96.77 (3.810) 38.10 (1.500) 161.92 (6.375) 80.94 (3.187) 4.77 (0.188) R 368.30 (14.500) 184.15 (7.250) 129.38 (5.094) 196.85 (7.750) 3.96 R (0.156) Front View 3-PoleFront Cover Cutout CL Breaker 406.40 (16.000) 209.55 (8.250) 393.70 (15.500) 327.81 (12.906) 166.70 (6.563) 246.07 (9.688) 381.00 (15.000)
4 Holes
1 1.12 Dia. (0.438) CL Handle 330.20 (13.000) 2.25 (0.089) Tee Connectors May Be Rotated 90° 171.45 (6.750) 228.60 (9.000) Side View Dimensions, mm (inches) L-Frame 630 (Bus extensions not included) L-Frame 800 N-Frame R-Frame Cutler-Hammer Frame Sizes L through R Dimensions in parentheses in inches.
PG.29B.01A.T.U Cutler-Hammer44 February 2001 Moulded Case Circuit Breakers 16-2500 Amperes for IEC 60947-2 Applications Sales Offices Country Address Office Phone Office Fax Argentina Cutler-Hammer, Inc. Calle Reconquista 656, Piso 13 (1003) Capital Federal – Buenos Aires, Argentina (54-11) 4315-4066 (54-11) 4314-8946 Australia Cutler Hammer Pty Ltd P.O. Box 85 Rosebery, NSW 1445, Australia (61-2) 9693-9333 (61-2) 9693-1258 Brazil Cutler-Hammer, Inc. Eletromar Plant Estrada Velha da PaPavuna, 257 21058-900 Rio de Janeiro-RJ-Brazil (55-21) 865-3912 (55-21) 290-1645 Canada Cutler-Hammer Canada
3228 South Service Road, Box 5040 Station A
Burlington, Ontario L7R 3Y8 (905) 333-6442 (905) 631-4248 Chile Cutler-Hammer, Inc. Neveria 4631, Office 210 /203 Las Condes CP 6761670 Santiago, Chile (56-2) 207-1695 (56-2) 207-1699 China Cutler-Hammer China
193 Su Hong Xi Road, Suzhou Industrial Park
Suzhou, 215021, PRC (86-512) 716-3728 (86-512) 716-9535 Costa Rica Cutler-Hammer, Inc. Industrial Control & Power Distribution Operations-Worldwide Power Distribution Division Apartado Postal 10156
1000 San Jose, Costa Rica
(506) 235-6022 (506) 235-9156 Egypt Cutler-Hammer, Inc. 9, Shehab Street- #11, Mohandessin 12411 Cairo, Egypt (20-2) 338-6170 (20-2) 338-2025 El Salvador Cutler-Hammer, Inc. Centro Comercial Villas Españolas, Local C-1 San Salvador, El Salvador (503) 263-6557 (503) 264-4144 France Cutler-Hammer
11 Rue Chataigneraie
73000 Barberaz, France
(33-4) 79604763 (33-4) 79604766 Germany Eaton GmbH Oranienpassage, 1
57258 Freudenberg, Germany
(49-2734) 4663-0 (49-2734) 4760-5 Guatemala Cutler-Hammer, Inc. Avenida Reforma 7-62 zona 9 Edificio Aristos Reforma, Oficina N°704 Ciudad de Guatemala, Guatemala (502) 362-9168 (502) 385-0343 Honduras Cutler-Hammer, Inc. Honduras Edificio Miramontes Plaza Apart. Hoteles Continental S.A. Segundo nivel, local N°10 Tegucigalpa, Honduras (504) 235-7554 N/A Indonesia Cutler-Hammer Suite 503A Sentra Mulia JI HR Rasuna Said Kav X-6 No.8 Jakarta 12940, Indonesia (62-21) 522-2020 (62-21) 522-2110 Country Address Office Phone Office Fax Jordan Cutler-Hammer, Inc. P.O. Box 510449 Amman 11151, Jordan (962-6) 474-0660 962-6) 744-660 Korea Eaton Limited-Korea 7th Floor, Woo Duk Building 832-2, Yeoksam-dong, Kangnam-ku Seoul, 135-750, Korea (82-2) 557-0313 (82-2) 557-1634 Malaysia Eaton Corporation Regional Office c/o Alpha Executive Business Center
1005 Blk B Level 10 Phileo Tamansara
9 Jin 16/11 Off Jin Tamansara
46350 Petaling Jaya, Selangor, Malaysia
(60-3) 737-2970 (60-3) 737-2960 Mexico Cutler Hammer, Inc. Rojo Gomez 1300 Col. Sn.Miguel Iztapalapa Mexico City DF 09360 Mexico (52-5) 804-8230 (525-5) 804-8232 New Zealand Cutler Hammer P.O. Box 12648 Penrose, Auckland, New Zealand (82-2) 557-0313 (82-2) 557-1634 Nicaragua Cutler-Hammer, Inc. Edificio Ofiplaza El Retiro Modulo N°5-1.1 De los semaforos de la antrada al antiguo, Nejapa Country Club o CAS 200 m al sur Managua, Nicaragua (505) 270-0920 (505) 270-0900 Panama Cutler-Hammer, Inc. Avenida Ricardo J. Alfaro Edifico Plaza Edison, Segundo Nivel, Oficina N°7 Ciudad de Panama, Panama (507) 321-0288 / 0289 (507) 321-0290 Saudi Arabia Cutler-Hammer, Inc. P.O. Box 19651, Riyadh 11445 Kingdom of Saudi Arabia (966-1) 460-2275 (966-1) 460-2991 Singapore Cutler-Hammer Pte Ltd
3 Tai Seng Drive
#03-01 Marconi Building Singapore 535216 (65) 382-7330 (65) 382-7262 Thailand Cutler-Hammer (C-H 1254) Eaton Technologies Limited, 91/1 Chailyo Building, 5th Floor, Rama 1X Road, Huaykwang Bangkok 10320 Thailand (66-2) 643-9504-8 (66-2) 643-9509 United Kingdom Cutler-Hammer Carina, Sunrise Parkway Linford Wood Milton Keynes MK146NR (44-0-1908) 541600 (44-0-1908) 660527 United States Cutler-Hammer, Inc.
1000 Cherrington Way
Pittsburgh, PA 15108 (412) 893-3300 N/A Venezuela Cutler-Hammer, Inc. Avda. Libertador, El Rosal, Edificio Lex, Piso 1 Caracas 1060, Venezuela (58-2) 953-1697 (58-2) 953-2585 / 2841 United Arab Emirates Cutler-Hammer Inc. P.O. Box 9398, Dubai World Trade Centre – Level
10 Dubai, United Arab Emirates
(971-4) 331-3938 (971-4) 332-9239 Cutler-Hammer Sales Offices
The circuit breakers shall meet or exceed all standards as defined in IEC 60947-2. Electrical circuits shall be protected by Cutler-Hammer World Moulded Case Circuit Breakers as manufactured by Cutler-Hammer. Each pole of the one-, two-, and three-pole circuit breakers shall provide complete circuit overcurrrent protection by having inverse time and instantaneous tripping character- istics and, where applicable, be current limiting. The circuit breaker shall be available in interrupting families that provide 35-65-100 kA at 380-415 volts AC. The circuit breakers shall be operated by a toggle-type handle and have a quick-make, quick-break, over-centre switching mechanism that is mechanically trip-free from the handle so that the contacts cannot be closed against short circuit currents. Tripping due to overload or short cir- cuits shall be clearly indicated by the position of the handle. The ON and OFF positions shall be clearly marked on the cover of the circuit breaker along with the international symbols I for ON and O for OFF on the handle, providing positive indication of the circuit breaker contact position. Additionally, a colour-coded indication of the circuit break- er contact position shall be provided: red for ON, green for OFF, and white for TRIPPED. An easily accessible Push-To- Trip button for mechanically exercising the trip unit shall be provided on the cover of each circuit breaker. All poles of a multi-pole circuit breaker shall be so constructed as to ensure simultaneous open, close, and trip operations. Circuit breakers shall be completely enclosed in a high strength glass-polyester case. Noninterchangeable trip circuit breakers shall be factory sealed; interchangeable trip circuit breakers shall have the trip unit sealed to prevent tampering. Ampere ratings shall be clearly visible from the front of the circuit breaker. Con- tacts shall be nonwelding silver alloy. Arc extinction shall be accomplished by means of DE-ION arc extinguishers consisting of metal grids mounted in an insulating support. The minimum interrupting ratings of the circuit breakers shall be at least equal to the available short circuit current at the line terminals. The circuit breakers can be applied in series rated applica- tions and subject to test data verification. Circuit breakers in frame sizes 125 amperes through 250 amperes shall be equipped with thermal-magnetic trip units. Circuit breakers 400 amperes through 2500 ampere frame sizes shall be equipped with electronic trip units that are insensitive to changes in ambient temperature within the normal operating temperature range of the circuit breaker. The 400 ampere and 630 ampere frame sizes shall be designed to accept either thermal-magnetic or electronic interchangeable trip units. Electronic trip units shall be rms sensing type and have unpowered thermal memory. Circuit breaker ratings and modifications shall be indicated on the drawings. Circuit breakers shall be of the inverse time and instan- taneous trip type as provided by thermal-magnetic or electronic trip elements with either standard interrupting, high interrupting, or current limiting characteristics as required. Moulded case circuit interrupters (motor circuit protectors) shall be of the instantaneous (magnetic) only type, providing instantaneous short circuit protection by means of a front adjustable trip unit. Moulded case switches shall be of the same construction as the related listed circuit breaker and equipped with a factory sealed, nonadjustable, high instantaneous only short circuit protection. Moulded case switches shall have no overload or low level fault protection provided and shall be marked with a maximum withstand rating denoting the type and level of upstream protection required. Moulded case switches shall be listed per IEC 60947-2. Internally mounted accessories including alarm (signal)/ lockout switches, auxiliary switches, shunt trips, and undervoltage released mechanisms shall be of the plug-in type and shall be listed for field fitting in circuit breakers which are not factory sealed. Electrical operators for circuit breakers of the 400 ampere frame size and below shall be of the solenoid type with maximum five-cycle closing characteristics. Electrical operators for circuit breaker frame sizes 630 amperes through 2500 amperes shall be of the motor driven type. All electrical operators shall be cover mounted. All electrical operators shall be listed for field installation per IEC 60947-2. Electrical characteristics of accessories shall be as indicated on the drawings. Circuit breakers in the 125 amperes rating shall be sup- plied in one-, two-, three-, and four-pole models, as speci- fied on the drawings. Circuit breakers in ratings of 225 amperes through 1250 amperes shall be supplied in two-, three-, or four-pole models. The 2500 ampere circuit breaker is available in three- and four-pole models as specified on the drawings. Accessory wiring shall be brought out through the side or rear of the circuit breaker, or be connected to a terminal block mounted on the side of the circuit breaker, as specified. The ability to route accessory wiring to the opposite side of the circuit breaker through a trough in the base shall be provided. Circuit breakers shall be provided with uniformly designed nameplates to clearly indicate the type, rating, listing/ recognition/certification marks, accessory details, and other information defined in IEC 60947-2. Typical Specifications for Cutler-Hammer Moulded Case Circuit Breakers