Differential Pressure Sensor EE600
v1.9 / Modification rights reserved | 2 EE600 The EE600 is dedicated for reliable measurement of differential pressure in HVAC, building automation and filter monitoring applications. The multi-range device is suitable for air as well as all non-flammable and non-aggressive gases. Optionally, the sensor is available with auto-zero function. Measurement Performance The EE600 is available with full scale 1 000 Pa (4 inch WC) and 10 000 Pa (40 inch WC) and offers an outstanding accuracy of ±0.5 % full scale. The piezoresistive, no flow-through pressure sensing element stands for outstanding long- term stability. Analogue and Digital Outputs The measured data is available on the analogue voltage and current output or on the RS485 interface with Modbus RTU or BACnet MS/TP protocol. Functional and Robust The IP65 / NEMA 4X enclosure minimizes installation costs. External mounting holes allow for installation with closed cover, the electronics are thus protected against construction site damage and pollution. Configurable and Adjustable The setup can be easily performed with DIP switches on the electronics board (EE600 with analogue output) or with an optional adapter and the free PCS10 Product Configuration Software. The setup includes measuring range, output signal, response time, displayed units and backlight. The auto-zero interval can be set with the PCS10 The EE600 can be set up for volume flow or air velocity measurement, as well as for filter monitoring or level indication. A zero point and span adjustment can be easily performed with push buttons on the electronics board. Differential Pressure Sensor EE600 with backlit display EE600 without display
v1.9 / Modification rights reserved | 3
Features
Configurable and Adjustable ▪ Measuring range ▪ Output signal ▪ Response time ▪ Displayed units and backlight ▪ Zero point and span adjustment Enclosure ▪ IP65 / NEMA 4X protection rating ▪ Bayonet screws - opened / closed with a ¼ rotationExternal Mounting Holes ▪ Mounting with closed cover ▪ Electronics protected against construction site pollution ▪ Easy and fast mounting Multi-range (Analogue Output) ▪ 0…250 / 500 / 750 / 1 000 Pa ▪ 0…2 500 / 5 000 / 7 500 / 10 000 Pa Knockout for ½" Conduit Fitting (US) Test Report According DIN EN 10204-2.2 Accuracy ▪ ±0.5 % FS Service Interface for Configuration ▪ Measurands - Differential pressure ∆p - Volume flow V' (k-Factor input) - Air velocity v (k-Factor input) ▪ Application setting - Filter monitoring - Level indicator ▪ Auto-zero interval (optional)
v1.9 / Modification rights reserved | 4 Dimensions Pressure fittings Ø5 (0.2) + high pressure - low pressure Pressure connection set is included in the scope of supply. FOR CONDUIT INSTALLATION CABLE GLAND M16x1.5 80.6 5 (0.2) (1.81) (3.17) (0.2) (3.54) Values in mm (inch)
v1.9 / Modification rights reserved | 5 Technical Data Calculated measurands Unit Level Indicator LI cm inch Volume flow V' m3/h l/s m3/s ft3/min Air velocity v m/s ft/min Filter contamination level FCL % Differential Pressure (∆p) Measurement principle Piezoresistive, no flow-through Measuring range Analogue output selectable with DIP switches 1) With PCS10 0...250 / 500 / 750 / 1 000 Pa 0...2 500 / 5 000 / 7 500 / 10 000 Pa Configurable within max. measuring range Accuracy @ 20 °C (68 °F), incl. hysteresis, non-linearity and repeatability ±0.5 % FS FS = full scale (1 000 Pa or 10 000 Pa) Temperature dependency, typ. <0.03 % from FS/K Response time t 90 Analogue output 1) Digital interface 2) 50 ms / 500 ms / 2 s / 4 s selectable with DIP switches Configurable in the range from 0.05 to 30 s with PCS10 Configurable in the range from 0.5 to 30 s with PCS10 Auto-zero interval 24 h (factory setting) Configurable between 10 min and 7 days with PCS10. Can be deactivated. Long-term stability <0.5 % FS/year Overload limits 1 000 Pa FS 10 000 Pa FS ±10 000 Pa ±80 000 Pa 1) Factory setup analogue output: measurement range 0...100 % FS; response time t 90: 50 ms; displayed unit: Pa; display backlight: on; analogue outputs: 0 - 10 V and 4 - 20 mA. Other ranges upon request. 2) Factory setup RS485: response time t 90: 500 ms; displayed unit: Pa; display backlight: on Measurands
v1.9 / Modification rights reserved | 6 Technical Data Outputs Analogue Analogue output 1) 0 - 5 V or 0 - 10 V -1 mA < IL < 1 mA IL = load current and 0 - 20 mA or 4 - 20 mA (3-wire) RL ≤ 500 Ω RL = load resistor 1) Voltage and current output signals available simultaneously at the spring loaded terminals. Settings selectable with DIP switches. Factory setup analogue outputs: measurement range 0...100 % FS; response time t 90: 50 ms; displayed unit: Pa; display backlight: on; analogue outputs: 0 - 10 V and 4 - 20 mA. Other ranges upon request. Digital Digital interface RS485 (EE600 = 1/2 unit load) Protocol Factory settings Supported Baud rates Data types for measuring values Modbus RTU Baud rate see order information, parity even, 1 stop bit, Modbus address 43 9 600, 19 200 and 38 400 FLOAT32 and INT16 Protocol Factory settings Supported Baud rates BACnet MS/TP Baud rate see order information, BACnet address 43 9 600, 19 200, 38 400, 57 600 and 76 800 Power supply class III USA & Canada: Class 2 supply necessary, max. voltage 30 V DC 15 - 35 V DC or 24 V AC ±20 % Current consumption, typ. @ 0 Pa (0 psi) / 24 V DC Analogue output Digital interface Without display 23 mA 8 mA Display with backlight 49 mA 29 mA Electrical connection Analogue output Digital interface Spring-loaded terminals, max. 1.5 mm 2 (AWG16) Screw terminals, max. 2.5 mm 2 (AWG14) Cable gland M16x1.5 Display Graphic, with backlight Selectable units on display with Analogue output via DIP switch Analogue output and digital interface via PCS10 Pa, kPa, mbar, mm H 2O Pa, kPa, mbar, mm H 2O, inch WC, m 3/h, m3/s, ft3/min, l/s m/s, ft/min, % Humidity range 0...95 %RH, non-condensing Temperature range Operation Storage Enclosure Material Protection rating Polycarbonate, UL94 V-0 (with display UL94 HB) approved IP65 / NEMA 4X Electromagnetic compatibility EN 61326-1 EN 61326-2-3 Industrial environment FCC Part15 Class A ICES-003 Class A Shock and vibration Tested according to EN 60068-2-64 and EN 60068-2-27 Conformity General
v1.9 / Modification rights reserved | 7 Ordering Guide Feature Description Code Hardware configuration EE600- Output Analogue (voltage and current output) A7 RS485 J3 Display Without display No code Display with backlight D2 Auto-zero Without auto-zero No code Auto-zero AF8 Software setup Protocol Modbus RTU2) P1 BACnet MS/TP 3) P3 Baud rate 9 600 BD5 19 200 BD6 38 400 BD7 57 600 (for BACnet MS/TP only) BD8 76 800 (for BACnet MS/TP only) BD9 1) Measuring ranges 0...25 % / 50 % / 75 % / 100 % FS, selectable with DIP switches at analogue output or PCS10. 2) Factory setting: Even parity, 1 stop bit; Modbus Map and communication setting: See User Manual and Modbus Application Note at www.epluse.com/ee600. 3) Factory setting: No parity, 1 stop bit; Product Implementation Conformance Statement (PICS) available at www.epluse.com/ee600. Configurability Device DIP switches PCS10 Analogue output without auto-zero Analogue output with auto-zero Digital interface without auto-zero Digital interface with auto-zero Configuration options see above or manual at www.epluse.com/ee600. Technical Data
v1.9 / Modification rights reserved | 8 Accessories For further information see datasheet Accessories. Accessories Code Pressure connection set, 2 m (6.6 ft) PVC hose with two ABS pressure connection nipples (included in the scope of supply) HA011304 USB configuration adapter HA011066 E+E Product Configuration Software (Free download: www.epluse.com/pcs10) PCS10 Order Examples EE600-HV52A7 Feature Code Description Output A7 Analogue (voltage and current output) Display No code Without display Auto-zero No code Without auto-zero EE600-HV53J3D2AF8P1BD5 Feature Code Description Output J3 RS485 Display D2 Display with backlight Auto-zero AF8 Auto-zero Protocol P1 Modbus RTU Baud rate BD5 9 600
Company Headquarters & Production Site E+E Elektronik Ges.m.b.H. Langwiesen 7
4209 Engerwitzdorf | Austria
info@epluse.com www.epluse.com Subsidiaries E+E Sensor Technology (Shanghai) Co., Ltd. T +86 21 6117 6129 info@epluse.cn E+E Elektronik France SARL T +33 4 74 72 35 82 info.fr@epluse.com E+E Elektronik Deutschland GmbH T +49 6171 69411-0 info.de@epluse.com E+E Elektronik India Private Limited T +91 990 440 5400 info.in@epluse.com E+E Elektronik Italia S.R.L. T +39 02 2707 86 36 info.it@epluse.com E+E Korea Co., Ltd. T +82 31 732 6050 info.kr@epluse.com E+E Elektronik Corporation T +1 847 490 0520 info.us@epluse.com Version v1.9 | 11-2022 Modification rights reserved