© 2016 Littelfuse Protection Relays & Controls www.littelfuse.com/ Rev: 1-A-062716 Protection Relays Current Monitoring Relays and Transducers www.littelfuse.com/ecsw ECSW SERIES

Description

The ECSW Series of single-phase, AC window, current sensors includes adjustable overcurrent and undercurrent trip points. Detects locked rotor, jam, loss of load, an open heater or lamp load, a broken belt, or loss of suction. LED’s aid in trip point adjustment and provide fault indication. The built-in toroidal sensor eliminates the need for an external current transformer. The output can be electrically latched after a fault, or automatically reset. Remote resetting of a latched output by removing input voltage. The unit includes switch selectable zero current detection and normally de-energized or energized output operation. Time delays are included to improve operation and eliminate nuisance tripping. Features & Benefits FEATURES BENEFITS Built-in toroidal current sensing Eliminates need to install stand alone current transformer and provides isolation from monitored circuit Encapsulated Protects against shock, vibration, and humidity LED indication Visual indication for trip point adjustment and fault indication Multiple switch selectable features User selectable zero current detection, latched, normally de-energized, or energized output adds application flexibility Adjustable trip delay Eliminates nuisance tripping and prevents rapid cycling Isolated 10A, SPDT output contacts Allows control of loads for AC or DC voltages Operation When the input voltage is applied, sensing delay on startup begins and the output transfers (if normally energized is selected). Upon completion of the startup delay, sensing of the monitored current begins. As long as current is above undercurrent trip point and below the overcurrent trip point (inside the window), the output relay remains in its normal operating condition and both red LED’s are OFF . The green LED glows when the output is energized. If current varies outside the window, the associated red LED glows, and the trip delay begins. If the current remains outside the window for the full Wiring Diagram Current Sensors N/L2 MC = Motor Contactor M = Motor F = Fuses OL = Overload RSW = Reset Switch FSW = Fan or Float Contacts CR = Control Relay CS = Current Sensor MCC = Motor Contactor Coil V = Voltage I> = Adjustable Overcurrent I< = Adjustable Undercurrent W = Monitored Wire ∆T - Adjustable Trip Delay

Ordering Information

MODEL INPUT VOLTAGE TRIP POINT ADJUST. TRIP DELAY SENSING DELAY ON STARTUP CONNECT. ECSW3LABT 24VDC 0.5 - 5A 0.150 - 7s 0.1s Terminal blocks ECSW4HBHT 120VAC 5 - 50A 0.5 - 50s 6s Terminal blocks ECSW4LADT 120VAC 0.5 - 5A 0.150 - 7s 2s Terminal blocks ECSW4LBHT 120VAC 0.5 - 5A 0.5 - 50s 6s Terminal blocks ECSW4MACT 120VAC 2 - 20A 0.150 - 7s 1s Terminal blocks ECSW4MBHT 120VAC 2 - 20A 0.5 - 50s 6s Terminal blocks ECSW4MBGT 120VAC 2 - 20A 0.5 - 50s 5s Terminal blocks ECSW6MBHT 230VAC 2 - 20A 0.5 - 50s 6s Terminal blocks If you don’t find the part you need, call us for a custom product 800-843-8848

© 2016 Littelfuse Protection Relays & Controls www.littelfuse.com/ Rev: 1-A-062716 Protection Relays Current Monitoring Relays and Transducers www.littelfuse.com/ecsw ECSW SERIES trip delay, the relay transfers to fault condition state. If the current returns to normal levels (inside the window) during the trip delay, the red LED goes OFF , the trip delay is reset, and the output remains in the normal condition. Reset: Remove input voltage or open latch switch. If zero current detection is selected, the unit will reset as soon as zero current is detected. Operation With Zero Current Detection Enabled: If the current decreases to zero within the trip delay period, then zero current is viewed as an acceptable current level. The unit’s output remains in its normal operating state. This allows the monitored load to cycle ON and OFF without nuisance tripping the ECSW. Zero current is defined as current flow of less than 250 milliamp-turns. Note: When zero current detect is selected, the latching operation of switch SW2 is canceled; the output will not latch after a fault trip. Notes on Operation 1. There is no hysteresis on the trip points. The overcurrent and undercurrent trip points should be adjusted to provide adequate protection against short cycling. 2. If the upper setpoint is set below the lower setpoint, both red LED’s will glow indicating a setting error. 3. If zero current detection is selected (SW2 ON), and the system is wired to disconnect the monitored load, the system may short cycle. After the unit trips, the load de- energizes, and zero current is detected. The ECSW resets, and the load energizes again immediately and may be short cycled. 4. The sensing delay on start up only occurs when input voltage is applied. When zero current detection is selected, the trip delay must be longer than the duration of the inrush current or the unit will trip on the inrush current. Typical Pump or Fan Protection Circuit Operation Window Current Sensing: With the ECSW connected as shown in the diagram, a load may be monitored and controlled for over and undercurrent. The ECSW Series’ on board CT (CS) may be placed on the line or load side of the contactor. The ECSW selection switches are set for zero current sensing (see Selector Switch SW2) and the output selection is normally de- energized (see Selector Switch SW3). The input voltage (V) is applied to the ECSW continually. As the control switch (FSW) is closed, the input voltage (V) is applied to the motor contactor coil (MCC), and the motor (M) energizes. As long as the current remains below the overcurrent and above the undercurrent trip points, the ECSW’s output contacts remain de-energized. If the load current should rise above or fall below a trip point, for the full trip delay, the normally open (NO) contact will close, energizing the control relay (CR) coil. The CR normally closed contact (CR1) opens and the MCC de-energizes and CR latches on through its normally open contacts (CR2). Reset is accomplished by momentarily opening the normally closed reset switch (RSW). Note: If the current falls to zero within the trip delay, the ECSW remains de-energized. The sensing delay on startup occurs when input voltage is applied therefore trip delay must be longer than the duration of the motor’s inrush current. The external latching relay CR2 is required in this system to prevent rapid cycling. A timer can be added to provide an automatic reset. Selector Switch Not Used Latched Zero I Output - Normally Energized ON OFF SW1 SW2 SW3 Mode Selection Switches SW1 = Latched or Auto reset selector OFF - Automatic reset after a fault ON - Output relay latches after a fault trips the unit SW2 = Zero current detection (below 250 mA) OFF - Zero current detection disabled ON - Zero current detection enabled SW3 = Output during normal operation OFF - Output relay de-energized ON - Output relay energized

© 2016 Littelfuse Protection Relays & Controls www.littelfuse.com/ Rev: 1-A-062716 Protection Relays Current Monitoring Relays and Transducers www.littelfuse.com/ecsw ECSW SERIES Specifications Sensor Type Toroid, through hole wiring for up to #4 AWG (21.1 mm2) THHN wire Mode Over & undercurrent trip points (window current sensing) Trip Point Range 0.5 - 50A in 3 adjustable ranges Tolerance Guaranteed range Maximum Allowable Current Steady - 50A turns; Inrush - 300A turns for 10s Time Point vs Temp. & Voltage ±5% Response Time ≤ 75ms Frequency 45/500 Hz Type of Detection Peak detection Zero Current Detection < 250mA turns typical Time Delay Range 0.15 - 50s in 2 adjustable ranges or 0.1 - 50s fixed Tolerance Adjustable: guaranteed range; Fixed: ±10% Sensing Delay On Start Up Fixed ≅ 0.1 - 6s in 1s increments Tolerance +40% -0% Delay vs. Temp. & Voltage ±15% Input Voltage 24, 120, or 230VAC; 12 or 24VDC Tolerance 12VDC & 24VDC/AC -15% - 20% 120 & 230VAC -20% - 10% AC Line Frequency 50/60 Hz Output Type Electromechanical relay Mode: Switch Selectable ON Energized during normal operation, de-energized after a fault OFF De-energized during normal operation, energizes during a fault Form Isolated, SPDT Rating 10A resistive @ 240VAC; 1/4 hp @ 125VAC; 1/2 hp @ 250VAC Life Mechanical - 1 x 10 6; Electrical - 1 x 10 5 Latch Type Electrical Reset Remove input voltage Function Switch selectable latching function Protection Surge IEEE C62.41-1991 Level A Circuitry Encapsulated Isolation Voltage ≥ 2500V RMS input to output Insulation Resistance ≥ 100 MΩ Mechanical Mounting Surface mount with two #6 (M3.5 x 0.6) screws Dimensions H 88.9 mm (3.5”); W 63.5 mm (2.5”); D 44.5 mm (1.75”) Termination 0.197 in. (5 mm) terminal blocks for up to #12 (3.2 mm2) AWG wire Environmental Operating/Storage Temperature -40° to 60° C/-40° to 85° C Humidity 95% relative, non-condensing Weight ≅ 6.4 oz (181 g)