Technical content
Advanced Digital Temperature Controller E5AN-H/E5EN-H (96 x 96 mm and 48 x 96 mm) A New High-performance Controller: High Resolution, High Speed, and High Input Accuracy. Logic Operations and Preventive Maintenance Function. Plus Infrared Port on Front Panel.
- High-resolution display with 5 digits/0.01°C display. High-speed sampling cycle of 60 ms. High Accuracy Thermocouple/Pt input: ±0.1% of PV Analog input: ±0.1% FS Universal inputs on all models (thermocouple, PT, or analog input) to handle various sensors with one Controller. Models also available with Remote SP. A PV/SV-status display function can be set to automatically alternate between displaying the status of the Temperature Controller (auto/manual, RUN/STOP, and alarms) and the PV or SV. Flexible contact outputs with logic operations (AND, OR, and delays) set from the Support Software (CX-Thermo Ver. 4.0) Preventive maintenance for relays in the Temperature Controller using a Control Output ON/OFF Counter. Model available with position-proportional control Main I/O Functions 96 × 96 mm E5AN-H 48 × 96 mm E5EN-H Refer to Safety Precautions for E5@N/E5@N-H. Refer to Operation for E5@N/E5@N-H for operating procedures. Auto/manual switching Temperature Controller status display Simple program function Logic operations Control output ON/OFF count alarm PV change rate alarm
- Models available with RS-485, RS-422, or RS-232C communications Event Inputs None Two Four Universal Sensor Inputs Universal thermocouple/ Pt/analog (current/voltage) inputs. Indication Accuracy
- Thermocouple/Pt input: ±0.1% of PV
- Analog input: ±0.1% FS Sampling Period
- 60 ms PF Key (Programmable key function) Auxiliary Outputs Two Three Remote SP Input
- One 3-level Display Simultaneously displays set items, such as the PV, SV, and MV. 5-digit Display with high resolution of 0.01°C Infrared port E5AN-H E5EN-H Computer Support Software CX-Thermo USB Control Output 1 (built-in) SSR outputs Output Unit Relay output Voltage output (for driving SSR) Current output Linear voltage output Control Output 2 (built-in) SSR outputs Output Unit Relay output Voltage output (for driving SSR) Current output Linear voltage output
Note: The Controller can be used for heating/cooling control even if only 1 control output is used. Model Number Structure Model Number Legend Controllers 1. Type H: Advanced 2. Control Mode Blank: Standard or heating/cooling control P: Position-proportional control 3. Control Output 1 A: Control Output Unit R: Relay output S: SSR output 4. Control Output 2 A: Control Output Unit R: Relay output S: SSR output 5. Auxiliary Outputs 2: Two outputs 3: Three outputs 6. Option 1 Blank: None H: Heater burnout/SSR failure/Heater overcurrent detection (CT1) HH: Heater burnout/SSR failure/Heater overcurrent detection (CT2) 7. Option 2 B: Two event inputs BF: Event input + Transfer output 8. Option 3 M: Option Unit can be mounted. 9. Power Supply Voltage Blank: 100 to 240 VAC D: 24 VAC/VDC 10.Case Color Blank: Black W: Silver 11.Terminal Cover -500: With Terminal Cover Option Units 1. Function EN01: RS-232C communications EN02: RS-422 communications EN03: RS-485 communications AKB: Event input Output Units 1. Control Output R: Relay output Q: Voltage output (for driving SSR) Q3: Voltage output (for driving SSR) + 24 VDC (NPN) Q4: Voltage output (for driving SSR) + 24 VDC (PNP) C3: Current output + 4 to 20 mA DC C3D: Current output + 0 to 20 mA DC V34: Linear voltage output + 0 to 10 VDC V35: Linear voltage output + 0 to 5 VDC 2. Version Blank: Available for E5AN-E5EN-H and E5AK/E5EK. N: Available only for E5AN-H/E5EN-H. E5AN-H/E5EN-H Advanced Type 2 control outputs 1 control output 2 auxiliary outputs 2 auxiliary outputs Terminal block Fully universal input 1 23456789 1 1 10 E53-@ 1 2 E53-@@ This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions and other information required for operation before attempting to use the product. E5CN-H/E5AN-H/E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157) E5CN-H/E5AN-H/E5EN-H Digital Controllers Communications Manual Advanced Type (Cat. No. H159)
Ordering Information
output Control output 1/2 Heater burnout Optional functions ModelEvent inputs Transfer output RSP 1/4 DIN 96 × 96 × 78 (W × H × D) Black 100 to
240 VAC
Control Output Unit × 21 2 4 to 20-mA input E5AN-HAA2HBM-500 SSR outputs × 21 2 4 to 20-mA input E5AN-HSS2HBM-500 Control Output Unit × 22 2 4 to 20-mA output 4 to 20-mA input E5AN-HAA2HHBFM-500 SSR outputs × 22 2 4 to 20-mA output 4 to 20-mA input E5AN-HSS2HHBFM-500 Control Output Unit × 22 4 to 20-mA output 4 to 20-mA input E5AN-HAA3BFM-500 SSR outputs × 22 4 to 20-mA output 4 to 20-mA input E5AN-HSS3BFM-500 Valve 2 Relay outputs × 22 4 to 20-mA input E5AN-HPRR2BM-500 Relay outputs × 22 4 to 20-mA output 4 to 20-mA input E5AN-HPRR2BFM-500
24 VAC/
Control Output Unit × 21 2 4 to 20-mA input E5AN-HAA2HBMD-500 SSR outputs × 21 2 4 to 20-mA input E5AN-HSS2HBMD-500 Control Output Unit × 22 2 4 to 20-mA output 4 to 20-mA input E5AN-HAA2HHBFMD-500 SSR outputs × 22 2 4 to 20-mA output 4 to 20-mA input E5AN-HSS2HHBFMD-500 Control Output Unit × 22 4 to 20-mA output 4 to 20-mA input E5AN-HAA3BFMD-500 SSR outputs × 22 4 to 20-mA output 4 to 20-mA input E5AN-HSS3BFMD-500 Valve 2 Relay outputs × 22 4 to 20-mA input E5AN-HPRR2BMD-500 Relay outputs × 22 4 to 20-mA output 4 to 20-mA input E5AN-HPRR2BFMD-500 Silver 100 to Control Output Unit × 21 2 4 to 20-mA input E5AN-HAA2HBM-W-500 Control Output Unit × 22 2 4 to 20-mA output 4 to 20-mA input E5AN-HAA2HHBFM-W-500 VDC Control Output Unit × 21 2 4 to 20-mA input E5AN-HAA2HBMD-W-500
Accessories (Order Separately) USB-infrared Conversion Cable USB-Serial Conversion Cable Terminal Cover Note: The Terminal Cover comes with the E5CN-@@@-500 models. Waterproof Packing Note: The Waterproof Packing is included with the Controller. Current Transformers (CTs) CX-Thermo Support Software Size Case color Power supply voltage Control method Auxil- iary output Control output 1/2 Heater burn- out Optional Functions ModelEvent inputs Transfer output RSP 1/8 DIN 48 × 96 × 78 (W × H × D) Black 100 to 240 VAC Basic Control Output Unit × 21 2 4 to 20-mA input E5EN-HAA2HBM-500 SSR outputs × 21 2 4 to 20-mA input E5EN-HSS2HBM-500 Control Output Unit × 22 2 4 to 20-mA output 4 to 20-mA input E5EN-HAA2HHBFM-500 SSR outputs × 22 2 4 to 20-mA output 4 to 20-mA input E5EN-HSS2HHBFM-500 Control Output Unit × 22 4 to 20-mA output 4 to 20-mA input E5EN-HAA3BFM-500 SSR outputs × 22 4 to 20-mA output 4 to 20-mA input E5EN-HSS3BFM-500 Valve 2 Relay outputs × 22 4 to 20-mA input E5EN-HPRR2BM-500 Relay outputs × 22 4 to 20-mA output 4 to 20-mA input E5EN-HPRR2BFM-500
24 VAC/VDC
Control Output Unit × 21 2 4 to 20-mA input E5EN-HAA2HBMD-500 SSR outputs × 21 2 4 to 20-mA input E5EN-HSS2HBMD-500 Control Output Unit × 22 2 4 to 20-mA output 4 to 20-mA input E5EN-HAA2HHBFMD-500 SSR outputs × 22 2 4 to 20-mA output 4 to 20-mA input E5EN-HSS2HHBFMD-500 Control Output Unit × 22 4 to 20-mA output 4 to 20-mA input E5EN-HAA3BFMD-500 SSR outputs × 22 4 to 20-mA output 4 to 20-mA input E5EN-HSS3BFMD-500 Valve 2 Relay outputs × 22 4 to 20-mA input E5EN-HPRR2BMD-500 Relay outputs × 22 4 to 20-mA output 4 to 20-mA input E5EN-HPRR2BFMD-500 Silver 100 to 240 VAC Basic 2 Control Output Unit × 21 2 4 to 20-mA input E5EN-HAA2HBM-W-500 Control Output Unit × 22 2 4 to 20-mA output 4 to 20-mA input E5EN-HAA2HHBFM-W-500
24 VAC/VDC Control Output Unit × 21 2 4 to 20-mA
Output unit Model Specifications Relay output E53-RN SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations Voltage output (for driving SSR) E53-QN 12 VDC (PNP), max. load current: 40-mA, with short-circuit protection E53-Q3 24 VDC (NPN), max. load current: 20-mA, with short-circuit protection E53-Q4 24 VDC (PNP), max. load current: 20-mA, with short-circuit protection Current output E53-C3N 4 to 20-mA DC, load: 600 Ω max., resolution: approx. 10,000 E53-C3DN 0 to 20-mA DC, load: 600 Ω max., resolution: approx. 10,000 Linear voltage output E53-V34N 0 to 10 VDC, load: 1 kΩ min., resolution: approx. 10,000 E53-V35N 0 to 5 VDC, load: 1 kΩ min., resolution: approx. 10,000 Model E58-CIFIR Model E58-CIFQ1 Connectable models Model E5AN-H E53-COV16E5EN-H Connectable models Model E5AN-H Y92S-P4 E5EN-H Y92S-P5 Hole diameter Model 5.8 dia. E54-CT1 12.0 dia. E54-CT3 Model EST2-2C-MV4
Power supply voltage No D in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC Operating voltage range 85% to 110% of rated supply voltage Power consumption 100 to 240 VAC: 12 VA 24 VAC/VDC: 8.5 VA (24 VAC)/5.5 W (24 VDC) Sensor input Any of the following can be selected. Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V Input impedance Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB.) Control method ON/OFF control or 2-PID control (with auto-tuning) Control output Relay output Output Unit (Install the Output Unit (sold separately).) Voltage output (for driving SSR) Current output Linear voltage output Built-in SSR output 75 to 250 VAC, 1 A (resistive load) Relay output for position-proportional control Relay output: Open and close: SPST-NO, 250 VAC, 1 A (including in-rush current), electrical life: 100,000 operations min. Potentiometer input: Must be between 100 Ω and 2.5 kΩ for maximum open position. Auxiliary output Number of outputs 2 or 3 max. Output specifications Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA Event input Number of outputs 2 or 4 (with an E53-AKB) External contact input specifications Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. Current flow: Approx. 7 mA per contact Logic operations Number of operations 8 max. Operations
- Logic operation: Any of the following four patterns can be selected. The input status may be inverted. (A and B) or (C and D), (A or C) and (B or D), A or B or C or D, A and B and C and D (A, B, C, and D are four inputs.)
- Delay: ON delay or OFF delay for the results of the logic operation given above. Setting time: 0 to 9999 s or 0 to 9999 min
- Output inversion: Possible Output One work bit per operation Work bit assignment Any of The following can be assigned to up to eight work bits (logic operation results): Event input operations, auxiliary outputs, or control outputs. Transfer outputs Number of outputs 1 max. (Depends on model. Models with transfer output (F in model number) Output specifications Current output: 4 to 20 mA DC, Load: 600 Ω max., Resolution at 4 to 20 mA: Approx. 10,000 RSP input Number of inputs 1 Signal type Current input: 4 to 20 mA (input impedance: 150 Ω ±10%) Analog input scaling Scaling of signal to engineering units (EU) −19,999 to 30,000 (display: 30,000 max.) Accuracy (±0.2% of FS) ±1 digit max. Input sampling period 60 ms Setting method Set digitally using keys on the front panel or by using the RSP input. Indication method 11-segment digital display and individual indicators (7-segments displays also possible) Content of 3-level display: PV/SV/MV, PV/SV/Bank No., or soak time remain Number of digits: 5 for PV and SV, 4 for MV Bank switching Supported (number of banks: 8) Local SP, alarm settings, PID sets (PID constants, MV upper limit, MV lower limit, etc.) Other functions Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout detection, 40% AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop, protection functions, control output ON/OFF counter, extraction of square root, MV change rate limit, PV/SV status display, logic operations, automatic cooling coefficient adjustment Ambient operating temperature −10 to 55°C (with no condensation or icing), for 3-year warranty: −10 to 50°C Ambient operating humidity 25% to 85% Storage temperature −25 to 65°C (with no condensation or icing)
Thermocouple/Platinum Resistance Thermometer (Fully Universal Inputs) Input type Platinum resistance thermometer Thermocouple Analog input Name Pt100 JPt100 K J T E L U N R S B W PL II 4 to 20 m A 0 to 20 m A 1 to 0 to 0 to 10 V Temperature range (°C) 2300 1800 1700 1600 1500 1400 1300 1200 1100 1000 900 800 700 600 500 400 300 200 100 −100.0 −200.0 2300.0 Usable in the following ranges by scaling: −19999 to 32400, −1999.9 to 3240.0, −199.99 to 324.00, or −19.999 to 32.400 1800.0 1700.01700.0 1300.0 1300.0 1300.0 850.0 850.0 850.0 600.0 500.0 500.0 500.0 200.00 200.00 200.00 200.00 100.0 100.0 100.0 Setting number 012 2 4 34 5 6 2 1 7 8 2 2 9 1 02 31 11 21 31 41 51 61 71 81 92 02 5 2 6 2 7 2 8 2 9 Shaded settings are the default settings. The applicable standards for the input types are as follows: K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 584-1 L: Fe-CuNi, DIN 43710-1985 U: Cu-CuNi, DIN 43710-1985 W: W5Re/W26Re, ASTM E988-1990 JPt100: JIS C 1604-1989, JIS C 1606-1989 Pt100: JIS C 1604-1997, IEC 751 PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard)
Each alarm can be independently set to one of the following 13 alarm types. The default is 2: Upper limit. Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: For models with heater burnout, SSR failure, and heater overcurrent detection, alarm 1 will be an OR output of the alarm selected from the following alarm types and the alarms for heater burnout, SSR failure, and heater overcurrent. To output only a heater burnout alarm, SSR failure alarm, and heater overcurrent alarm for alarm 1, set the alarm type to 0 (i.e., no alarm function). *1. With set values 1, 4 and 5, the upper and lower limit values can be set independently for each alarm type, and are expressed as “L” and “H.” *2. Set value: 1, Upper- and lower-limit alarm *3. Set value: 4, Upper- and lower-limit range *4. Set value: 5, Upper- and lower-limit with standby sequence For Upper- and Lower-Limit Alarm Described Above
- Case 1 and 2 Always OFF when the upper-limit and lower-limit hysteresis overlaps. Case 3: Always OFF *5. Set value: 5, Upper- and lower-limit with standby sequence Always OFF when the upper-limit and lower-limit hysteresis overlaps. *6. Displayed when there is a remote SP input. *7. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156) for information on the operation of the standby sequence. *8. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156) for information on the loop burnout alarm (LBA). *9. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156) for information on the PV change rate alarm. Set value Alarm type Alarm output operation Description of functionWhen alarm value X is positive When alarm value X is negative
0 Alarm function OFF Output OFF No alarm
1 Upper- and lower-limit *1 *2 Set the deviation in the set point by setting the alarm
upper limit (H) and alarm lower limit (L).
2 Upper-limit Set the upward deviation in the set point by setting
the alarm value (X).
3 Lower-limit Set the downward deviation in the set point by setting
the alarm value (X).
4 Upper- and lower-limit range *1 *3 Set the deviation in the set point by setting the alarm
upper limit (H) and alarm lower limit (L).
5 Upper- and lower-limit with
standby sequence *1 *4 A standby sequence is added to the upper- and lower-limit alarm (1). *7
6 Upper-limit with standby sequence A standby sequence is added to the upper-limit alarm
(2). *7
7 Lower-limit with standby sequence A standby sequence is added to the lower-limit alarm
(3). *7
8 Absolute-value upper-limit The alarm will turn ON if the process value is larger
than the alarm value (X) regardless of the set point.
9 Absolute-value lower-limit The alarm will turn ON if the process value is smaller
than the alarm value (X) regardless of the set point. standby sequence A standby sequence is added to the absolute-value upper-limit alarm (8). *7 standby sequence A standby sequence is added to the absolute-value lower-limit alarm (9). *7
12 LBA (alarm 1 type only) ---
13 PV change rate alarm --- *9
14 RSP absolute value upper limit *6
The alarm turns ON when the remote SP (RSP) is larger than the alarm value (X). This alarm functions in both Local SP and Remote SP Modes.
15 RSP absolute value lower limit *
The alarm turns ON when the remote SP (RSP) is smaller than the alarm value (X). This alarm functions in both Local SP and Remote SP Modes. ON OFF SP LH SP XON OFF SP XON OFF SP XON OFF SP XON OFF SP LHON OFF SP LHON OFF SP XON OFF SP XON OFF SP XON OFF SP XON OFF XON OFF XON OFF XON OFF 0 XON OFF XON OFF 0 XON OFF XON OFF 0 XON OFF XON OFF 0 XON OFF XON OFF 0 XON OFF LH H < 0, L > 0 SP Case 1 LH H > 0, L < 0 SP Case 2 LH H < 0, L < 0 SP LH H < 0, L > 0 LH H > 0, L < 0 Case 3 (Always ON) LH H < 0, L > 0 SP Case 1 LH H > 0, L < 0 SP Case 2 LH H < 0, L < 0 SP LH H < 0, L > 0 LH H > 0, L < 0 Case 3 (Always ON)
*1. The indication accuracy of K thermocouples in the −200 to 1300°C range, T and N thermocouples at a temperature of −100°C max., and U and L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max. is not specified. The indication accuracy of B thermocouples in the 400 to 800°C range is ±3°C max. The indication accuracy of the R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is ±0.3% of PV or ±3°C, whichever is greater, ±1 digit max. The indication accuracy of PL II thermocouples is ±0.3% of PV or ±2°C, whichever is greater, ±1 digit max. *2. Ambient temperature: −10°C to 23°C to 55°C, Voltage range: −15% to 10% of rated voltage *3. K thermocouple at −100°C max.: ±10°C max. *4. External communications (RS-232C, RS-485, or RS-422) and cable communications for the Setup Tool can be used at the same time. *5. Refer to information on maritime standards in Safety Precautions for E5@N/E5@N-H for compliance with Lloyd's Standards. Indication accuracy Thermocouple: (±0.1% of indicated value or ±1°C, whichever is greater) ±1 digit max. *1 Platinum resistance thermometer: (±0.1% of indicated value or ±0.5°C, whichever is greater) ±1 digit max. Analog input: ±0.1% FS ±1 digit max. CT input: ±5% FS ±1 digit max. Potentiometer input: ±5% FS ±1 digit max. Transfer output accuracy ±0.3% FS max. Influence of temperature Thermocouple input (R, S, B, W, PL II): (±1% of PV or ±10°C, whichever is greater) ±1 digit max. Other thermocouple input: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. *3 Platinum resistance thermometer: (±1% of PV or ±2°C, whichever is greater) ±1 digit max. Analog input: (±1%FS) ±1 digit max.Influence of voltage *2 Input sampling period 60 ms Hysteresis Temperature input: 0.1 to 3240.0°C or °F (in units of 0.1°C or °F) Analog input: 0.01% to 99.99% FS (in units of 0.01% FS) Proportional band (P) Temperature input: 0.1 to 3240.0°C or °F (in units of 0.1°C or °F) Analog input: 0.1% to 999.9% FS (in units of 0.1% FS) Integral time (I) 0.0 to 3240.0 s (in units of 0.1 s) Derivative time (D) 0.0 to 3240.0 s (in units of 0.1 s) Control period 0.5, 1 to 99 s (in units of 1 s) Manual reset value 0.0 to 100.0% (in units of 0.1%) Alarm setting range −19999 to 32400 (decimal point position depends on input type) Affect of signal source resistance Thermocouple: 0.1°C/Ω max. (100 Ω max.) Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.) Insulation resistance 20 MΩ min. (at 500 VDC) Dielectric strength 2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge) Vibration resistance Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions Destruction 10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions Shock resistance Malfunction 100 m/s2, 3 times each in X, Y, and Z directions Destruction 300 m/s2, 3 times each in X, Y, and Z directions Weight E5AN-H Controller: Approx. 310 g, Mounting Bracket: Approx. 100 g E5EN-H Controller: Approx. 260 g, Mounting Bracket: Approx. 100 g Degree of protection Front panel: IP66, Rear case: IP20, Terminals: IP00 Memory protection Non-volatile memory (number of writes: 1,000,000 times) Setup Tool CX-Thermo version 4.0 or higher Setup Tool port Provided on the bottom of the E5AN-H and E5EN-H. An E58-CIFQ1 USB-Serial Conversion Cable is required to connect the computer to the E5AN-H and E5EN-H. Provided on the front of the E5AN-H and E5EN-H. An E58-CIFIR USB-infrared Conversion Cable is required to connect the computer to the E5AN-H or E5EN-H. *4 Standards Approved standards UL 61010-1, CSA C22.2 No. 1010-1 Conformed standards EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II, Lloyd's standards *5EMC EMI: EN 61326 Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A Noise Terminal Voltage: EN 55011 Group 1, class A EMS: EN 61326 ESD Immunity: EN 61000-4-2 Electromagnetic Field Immunity: EN 61000-4-3 Burst Noise Immunity: EN 61000-4-4 Conducted Disturbance Immunity: EN 61000-4-6 Surge Immunity: EN 61000-4-5 Power Frequency Magnetic Field Immunity: EN 61000-4-8 Voltage Dip/Interrupting Immunity: EN 61000-4-11
USB-Serial Conversion Cable Note: A driver must be installed in the personal computer. Refer to installation information in the operation manual for the Conversion Cable. Communications Specifications * The baud rate, data bit length, stop bit length, and vertical parity can be individually set using the Communications Setting Level. Current Transformer (Order Separately) Ratings USB-Infrared Conversion Cable Note: A driver must be installed in the personal computer. Refer to installation information in the operation manual for the Conversion Cable. Heater Burnout Alarms, SSR Failure Alarms, and Heater Overcurrent Alarms *1. For heater burnout alarms, the heater current will be measured when the control output is ON, and the output assigned to the alarm 1 function will turn ON if the heater current is lower than the set value (i.e., heater burnout detection current value). *2. For SSR failure alarms, the heater current will be measured when the control output is OFF, and the output assigned to the alarm 1 function will turn ON if the heater current is higher than the set value (i.e., SSR failure detection current value). *3. For heater overcurrent alarms, the heater current will be measured when the control output is ON, and the output assigned to the alarm 1 function will turn ON if the heater current is higher than the set value (i.e., heater overcurrent detection current value). Applicable OS Windows 2000, XP, or Vista Applicable software CX-Thermo version 4 or higher Applicable models E5AN/E5EN/E5CN/E5CN-U/ E5AN-H/E5EN-H/E5CN-H/E5GN USB interface standard Conforms to USB Specification 1.1. DTE speed 38400 bps Connector specifications Computer: USB (type A plug) Temperature Controller: Setup Tool port (on bottom of Controller) Power supply Bus power (Supplied from USB host controller.) Power supply voltage 5 VDC Current consumption 70 mA Ambient operating temperature 0 to 55°C (with no condensation or icing) Ambient operating humidity 10% to 80% Storage temperature −20 to 60°C (with no condensation or icing) Storage humidity 10% to 80% Altitude 2,000 m max. Weight Approx. 100 g Transmission line connection method RS-485, RS-422: Multipoint RS-232C: Point-to-point Communications RS-485 (two-wire, half duplex) RS-422 (four-wire, half duplex) or RS-232C Synchronization method Start-stop synchronization Protocol CompoWay/F, SYSWAY, or Modbus Baud rate 1200, 2400, 4800, 9600, 19200, 38400, or 57600 bps Transmission code ASCII (CompoWay/F, SYSWAY) RTU (Modbus) Data bit length * 7 or 8 bits Stop bit length * 1 or 2 bits Error detection Vertical parity (none, even, odd) Frame check sequence (FCS) with SYSWAY Block check character (BCC) with CompoWay/F or CRC-16 Modbus Flow control None Interface RS-485, RS-422, or RS-232C Retry function None Communications buffer 217 bytes Communications response wait time 0 to 99 ms Default: 20 ms Dielectric strength 1,000 VAC for 1 min Vibration resistance 50 Hz, 98 m/s2 Weight E54-CT1: Approx. 11.5 g, E54-CT3: Approx. 50 g Accessories (E54-CT3 only) Armatures (2) Plugs (2) Applicable OS Windows 2000, XP, or Vista Applicable software CX-Thermo version 4.0 or higher Applicable models E5AN-H/E5EN-H USB interface standard Conforms to USB Specification 1.1. DTE speed 38400 bps Connector specifications Computer: USB (type A plug) Temperature Controller: Infrared port (on front of Controller) Power supply Bus power (Supplied from USB host controller.) Power supply voltage 5 VDC Current consumption 80 mA Ambient operating temperature 0 to 55°C (with no condensation or icing) Ambient operating humidity 10% to 80% Storage temperature −20 to 60°C (with no condensation or icing) Storage humidity 10% to 80% Altitude 2,000 m max. Weight Approx. 130 g (with mounting adaptor) CT input (for heater current detection) Models with detection for single-phase heaters: One input Models with detection for single-phase or three-phase heaters: Two inputs Maximum heater current 50 A AC Input current indication accuracy ±5% FS ±1 digit max. Heater burnout alarm setting range *1 0.1 to 49.9 A (in units of 0.1 A) Minimum detection ON time: 100 ms SSR failure alarm setting range *2 0.1 to 49.9 A (in units of 0.1 A) Minimum detection OFF time: 100 ms Heater overcurrent alarm setting range *3 0.1 to 49.9 A (in units of 0.1 A) Minimum detection ON time: 100 ms
Electrical Life Expectancy Curve for Relays (Reference Values) SSR Outputs (OUT1/OUT2) Ratings
- Rated load voltage: 75 to 250 VAC
- Rated load current: 1 A (resistive load) Note: 1. The load current must be within the derating curve. 2. There is no zero-cross function. Derating Curve for SSR Outputs (Reference Values) Condition A: SSR outputs 100% ON Condition B: SSR outputs 50% ON with 2-s control cycle 500 300 100 0 12345 6 E5AN-H/E5EN-H
250 VAC, 30 VDC
(resistive load) cosφ = 1 Switching current (A) Life (× 104 operations) 1.5 1.25 0.75 0.5 0.25 −10 0 10 20 30 40 50 55 45 60 Ambient temperature (°C) Load current I (A) OUT1/OUT2 Condition A Condition B
Control output 1 and control output 2 are functionally isolated from the internal circuits. Note: Wire all voltage input terminals correctly. The Controller may fail if voltage input terminals are wired incorrectly. Potentiometer RDB RDA SG SDB SDA 4 to 20 mA DC (Load: 600 Ω max.) 4 to 20 mA DC 100 to 240 VAC 24 VAC/VDC (no polarity) Input power supply Control output 1 B V mA Control output 2 CT2 CT1 EV1 EV2 CT2 DO NOT USE DO NOT USE DO NOT USE B A C W O DO NOT USE DO NOT USE DO NOT USE DO NOT USE Event Inputs EV1 EV2 Event Inputs Communications B (+) A (−) DO NOT USE B (+) A (−) E53-EN03 RS-485 E53-EN01 RS-232C SD RD SG DO NOT USE DO NOT USE E53-AKB E53-EN02 RS-422 Control Output Unit Control outputs 1, 2 Refer to page 4 SSR Outputs 75 to 250 VAC, 1 A (resistive load) Models with Position- proportional Control Relay output
250 VAC, 1 A
(including inrush current) Control outputs 1, 2 Relay output SPST-NO,
250 VAC, 3 A
(resistive load) Auxiliary outputs 1, 2, 3 A heater burnout alarm, SSR failure, heater overcurrent alarm, input alarm, or Remote SP Input Error is sent to the output to which the alarm 1 function is assigned. Auxiliary output 3 EV4 EV3 − + Output unit Output unit Control Output Unit SSR SSR SSR Outputs Open Closed Models with Position- proportional Control Event input/ Transfer output/ Remote SP Remote SP input DO NOT USE Transfer output Input power supply Input power supply Input power supply Auxiliary output 2 Auxiliary output 1 Auxiliary output 2 Auxiliary output 1 Auxiliary output 2 Auxiliary output 1 Auxiliary output 2 Auxiliary output 1 Relay output SPDT, 250 VAC, 3 A (resistive load) Auxiliary output 3 The Temperature Controller is set for a K-type thermocouple (input type = 5) by default. An input error (s.err) will occur if the input type setting does not agree with the temperature sensor. Check the input type. Option UnitsControllers
Dimensions (Unit: mm) PFA/M SUB3 HA SUB2 OUT2 OUT1 CMW RSP STOP MANU SUB1 MV SV PV Ir E5AN-H Operation indicators No.1 display No.2 display No.3 display Up Key Down Key Temperature unit Mode KeyLevel Key Programmable Function Key/ Auto/Manual Key E5AN-H E5EN-H Ir PF A/M MV SV PV SUB2 SUB3 STOPOUT1 RSP MANUCMWOUT2 SUB1 HA E5EN-H Operation indicators Temperature unit Operation indicators Mode Key Level Key No.1 display No.2 display No.3 display Up Key Down Key Programmable Function Key/ Auto/Manual Key Mounting Bracket (Accessory) Waterproof Packing (Accessory) Terminal Cover (E53-COV16) (Accessory) Crimp terminal size: M3.5 96 × 96 112 91 79.26 92+0.8 92+0.8 92+0.8 0 (96 × number of units − 3.5)+1.0 120 min. Group mounting does not allow waterproofing. Mounted Separately Group Mounted *
- Recommended panel thickness is 1 to 8m m .
- Group mounting is not possible in the vertical direction. (Maintain the specified mounting space between Controllers.)
- To mount the Controller so that it is waterproof, insert the waterproof packing onto the Controller.
- When two or more Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications. E5AN-H *Group mounting is not possible if an SSR output is used for control output 1 or 2 and the E53-C3N or E53-C3DN Output Unit is used. For these combinations, maintain the following mounting space between Controllers. 92+0.8 92+0.8 110 min. 120 min.
(Accessory) Waterproof Packing (Accessory) Terminal Cover (E53-COV16) (Accessory) Crimp terminal size: M3.5 96 112 79.26 E5EN-H 92+0.8 92+0.8 45+0.6 120 min. (48 × number of units − 2.5)+1.0 Group mounting does not allow waterproofing. Mounted Separately Group Mounted *
- Recommended panel thickness is 1 to 8 mm.
- Group mounting is not possible in the vertical direction. (Maintain the specified mounting space between Controllers.)
- When two or more Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications. *Group mounting is not possible if an SSR output is used for control output 1 or 2 and the E53-C3N or E53-C3DN Output Unit is used. For these combinations, maintain the following mounting space between Controllers. 45+0.6 60 min. 120 min. 92+0.8
Accessories (Order Separately) (2,000) 54 4.6 dia. 35.8 17.8 USB connector (type A plug) LED indicator: RD LED indicator: SD USB-Infrared Conversion Cable E58-CIFIR USB-Infrared Conversion Cable 99.2 18.5 23.1 (75) 21.8 Mounting Adapter (Accessory) With Mounting Adapter Connected Mounting Adapter (2,100) 250 1,765 USB connector (type A plug) Serial connectorLED indicator: RD LED indicator: SD USB-Serial Conversion Cable E58-CIFQ1 Terminal Covers E53-COV16 (Six Covers provided.) 1.2 3.2 44.8
Y92S-P4 (for DIN 96 × 96) Order the Waterproof Packing separately if it becomes lost or damaged. The Waterproof Packing can be used to achieve an IP66 degree of protection. (Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the operating environment. Therefore, periodic replacement is recommended to ensure the level of waterproofing specified in IP66. The time for periodic replacement depends on the operating environment. Be sure to confirm this point at your site. Consider one year a rough standard. OMRON shall not be liable for the level of water resistance if the customer does not perform periodic replacement.) The Waterproof Packing does not need to be attached if a waterproof structure is not required. Y92S-P5 (for DIN 48 × 96) E54-CT3 Accessory
- Armature 15 5.8 dia. 25 3 10.5 2.8 7.5 Two, 3.5 dia. 40 × 40 12 dia. 2.36 dia. Two, M3 (depth 4) Approx. 3 dia. (22) Approx. 6 dia. Plug Armature Lead E54-CT1 E54-CT3 Connection Example
- Plug E54-CT1 Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) Maximum continuous heater current: 50 A (50/60 Hz) Number of windings: 400±2 Winding resistance: 18±2 Ω Thru-current (Io) A (r.m.s.) 1 10 100 mA 1 10 100 1,000 A Output voltage (Eo) V (r.m.s.)
100 V 50 Hz
factor 10% 100 Ω RL = 10 Ω ∞10 100 mV 100 µV 1 kΩ E54-CT3 Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) Maximum continuous heater current: 120 A (50/60 Hz) (Maximum continuous heater current for an OMRON Temperature Controller is 50 A.) Number of windings: 400±2 Winding resistance: 8±0.8 Ω 1 kΩ 100 Ω 50 Ω RL = 10 Ω 500 Ω Distor- tion factor 10% Thru-current (Io) A (r.m.s.) 1 10 100 mA 1 10 100 1,000 A Output voltage (Eo) V (r.m.s.) 100 µV
Read and Understand This Catalog Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranty and Limitations of Liability WARRANTY OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED. LIMITATIONS OF LIABILITY OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY. In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR. Application Considerations SUITABILITY FOR USE OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the products. At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product, machine, system, or other application or use. The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
- Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
- Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations.
- Systems, machines, and equipment that could present a risk to life or property. Please know and observe all prohibitions of use applicable to the products. NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. PROGRAMMABLE PRODUCTS OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof. Disclaimers CHANGE IN SPECIFICATIONS Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual specifications of purchased products. DIMENSIONS AND WEIGHTS Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown. PERFORMANCE DATA Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability. ERRORS AND OMISSIONS The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical, or proofreading errors, or omissions. 2009.11 In the interest of product improvement, specifications are subject to change without notice. OMRON Corporation Industrial Automation Company http://www.ia.omron.com/ (c)Copyright OMRON Corporation 2009 All Right Reserved.