Advanced Digital Temperature Controller E5CN-H (48 x 48 mm) A New High-performance Controller: High Resolution, High Speed, and High Input Accuracy. Logic Operations and Preventive Maintenance Function.
- High-resolution display with 5 digits/0.01°C display in a compact Controller (48 x 48 mm). High-speed sampling cycle of 60 ms. High Accuracy Thermocouple/Pt input: ±0.1% of PV Analog input: ±0.1% FS Universal inputs on all models (thermocouple, PT, or analog input) to handle various sensors with one Controller. A PV/SV-status display function can be set to automatically alternate between displaying the status of the Temperature Controller (auto/ manual, RUN/STOP, and alarms) and the PV or SV. Flexible contact outputs with logic operations (AND, OR, and delays) set from the Support Software (CX-Thermo Ver. 4.0) Preventive maintenance for relays in the Temperature Controller using a Control Output ON/OFF Counter. Main I/O Functions 48 × 48 mm E5CN-H Refer to Safety Precautions for E5@N/E5@N-H. Refer to Operation for E5@N/ E5@N-H for operating procedures. Universal Sensor Inputs
- Universal thermocouple/Pt/analog (current/voltage) inputs. Indication Accuracy
- Thermocouple/Pt input: ±0.1% of PV
- Analog input: ±0.1% FS 2-level Display: PV and SV 5-digit Display with high resolution of 0.01°C E5CN-HEvent Inputs
- None
- Two Sampling Period
- 60 ms Control Output 1
- Relay output
- Voltage output (for driving SSR)
- Current output
- Linear voltage output Control Output 2
- None
- Voltage output (for driving SSR) Auxiliary Outputs
- Two
- Auto/manual switching
- Temperature Controller status display
- Simple program function
- Logic operations
- Control output ON/OFF count alarm
- PV change rate alarm
- Models also available with RS-485 or RS-232C communications This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions and other information required for operation before attempting to use the product. E5CN-H/E5AN-H/E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157) E5CN-H/E5AN-H/E5EN-H Digital Controllers Communications Manual Advanced Type (Cat. No. H159)
Note: Models with one control output and models with two control outputs can be used for heating/cooling control. Model Number Structure Model Number Legend Controllers 1. Type H: Advanced 2. Control Output 1 R: Relay output Q: Voltage output (for driving SSR) C: Current output V: Linear voltage output 3. Auxiliary Outputs 2: Two outputs 4. Option 1 M: Option Unit can be mounted. 5. Power Supply Voltage Blank: 100 to 240 VAC D: 24 VAC/VDC 6. Case Color Blank: Black W: Silver 7. Terminal Cover -500: With terminal cover Option Units 1. Applicable Controller CN: E5CN-H or E5CN 2. Function 1 Blank: None Q: Control output 2 (voltage output for driving SSR) P: Power supply for sensor C: Current output 3. Function 2 Blank: None H: Heater burnout/SSR failure/Heater overcurrent detection (CT1) HH: Heater burnout/SSR failure/Heater overcurrent detection (CT2) B: Two event inputs 03: RS-485 communications H03: Heater burnout/SSR failure/Heater overcurrent detection (CT1) + RS-485 communications HB: Heater burnout/SSR failure/Heater overcurrent detection (CT1) + Two event inputs HH03: Heater burnout/SSR failure/Heater overcurrent detection (CT2) + RS-485 communications H01: Heater burnout/SSR failure/Heater overcurrent detection (CT1)/RS-232C communications F: Transfer output BF: Two event inputs/Transfer output 4. Version N2: Available only to models released after January 2008 Note: Not all combinations of function 1 and function 2 specifications are possible for Option Units (E53-@@@@). Terminal blockE5CN-H Advanced Type Fully universal input 2 control outputs 1 control output 2 auxiliary outputs 2 auxiliary outputs 1 2345 6 7 1 234 E53-@@@@
Ordering Information
One of the following Option Units can be mounted to provide the E5CN with additional functions. Note: These Option Units are applicable only to models released after January 2008. Accessories (Order Separately) USB-Serial Conversion Cable Terminal Cover Note: 1. The Terminal Cover comes with the E5CN-@@@-500 models. 2. The E53-COV10 cannot be used. Waterproof Packing Note: Waterproof Packing is included with the controller only for models with terminal blocks. Current Transformers (CTs) Adapter Note: Use this Adapter when the panel has been previously prepared for the E5B@. Front cover CX-Thermo Support Software Size Case Color Power supply voltage Auxiliary output Control output 1 Model 1/16 DIN 48 × 48 × 78 (W × H × D) Black 100 to 240 VAC 2 Relay output E5CN-HR2M-500 Voltage output (for driving SSR) E5CN-HQ2M-500 Current output E5CN-HC2M-500 Linear voltage output E5CN-HV2M-500
24 VAC/VDC 2
Relay output E5CN-HR2MD-500 Voltage output (for driving SSR) E5CN-HQ2MD-500 Current output E5CN-HC2MD-500 Linear voltage output E5CN-HV2MD-500 Silver 100 to 240 VAC 2 Relay output E5CN-HR2M-W-500 Voltage output (for driving SSR) E5CN-HQ2M-W-500 Current output E5CN-HC2M-W-500 Relay output E5CN-HR2MD-W-500 Voltage output (for driving SSR) E5CN-HQ2MD-W-500 Current output E5CN-HC2MD-W-500 Functions Model Communications RS-485 3-phase heater burnout/SSR failure/ Heater overcurrent detection E53-CNHH03N2 Heater burnout/SSR failure/ Heater overcurrent detection Event inputs E53-CNHBN2 Communications RS-485 Control output 2 (Voltage for driving SSR) E53-CNQ03N2 Communications RS-485 Heater burnout/SSR failure/ Heater overcurrent detection E53-CNH03N2 Communications RS-485 E53-CN03N2 Event inputs E53-CNBN2 Heater burnout/SSR failure/ Heater overcurrent detection Control output 2 (Voltage for driving SSR) E53-CNQHN2 3-phase heater burnout/SSR failure/ Heater overcurrent detection Control output 2 (Voltage for driving SSR) E53-CNQHHN2 Event inputs Control output 2 (Voltage for driving SSR) E53-CNQBN2 Control output 2 (Voltage for driving SSR) Transfer Output E53-CNQFN2 Event inputs Transfer Output E53-CNBFN2 Communications RS-232C Control output 2 (Voltage for driving SSR) E53-CNQ01N2 Communications RS-232C E53-CN01N2 Communications RS-232C Heater burnout/SSR failure/ Heater overcurrent detection E53-CNH01N2 Model E58-CIFQ1 Model E53-COV17 Model Y92S-29 Hole diameter Model 5.8 dia. E54-CT1 12.0 dia. E54-CT3 Connectable models Model Terminal type Y92F-45 Type Model Hard Front Cover Y92A-48B Soft Front Cover Y92A-48D Model EST2-2C-MV4
*For models with current outputs, control output 1 can be used as a transfer output. Power supply voltage No D in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC Operating voltage range 85% to 110% of rated supply voltage Power consumption 100 to 240 VAC: 8.5 VA (max.) (E5CN-HR2 at 100 VAC: 3.0 VA) 24 VAC/VDC: 5.5 VA (24 VAC)/3.5 W (24 VDC) (max.) (E5CN-HR2D at 24 VAC: 2.7 VA) Sensor input Any of the following can be selected (i.e., fully universal input). Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V Input impedance Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB.) Control method ON/OFF control or 2-PID control (with auto-tuning) Control output Relay output SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA Voltage output (for driving SSR) Output voltage: 12 VDC ±15% (PNP), max. load current: 21 mA, with short-circuit protection circuit Current output 4 to 20 mA DC/0 to 20 mA DC, load: 600 Ω max., resolution: approx. 10,000 * Linear voltage output 0 to 10 VDC (load: 1 kΩ min.), Resolution: Approx. 10,000 Auxiliary output Number of outputs 2 max. Output specifications Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA Event input Number of outputs 2 External contact input specifications Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. Current flow: Approx. 7 mA per contact Logic opera- tions Number of operations 8 max. (Combinations can be made using work bits.) Operations
- Logic operation: Any of the following four pattern s can be selected. The input status may be inverted. (A and B) or (C and D), (A or C) and (B or D), A or B or C or D, A and B and C and D (A, B, C, and D are four inputs.)
- Delay: ON delay or OFF delay for the results of the logic operation given above. Setting time: 0 to 9999 s or 0 to 9999 min
- Output inversion: Possible Outputs One work bit per operation Work bit assignments Any of the following can be assigned to up to eight work bits (logic operation results): Event input operations, auxiliary outputs, or control outputs. Transfer outputs Number of outputs 1 max. Output specifications Current output: 4 to 20 mA DC, Load: 600 Ω max., Resolution at 4 to 20 mA: Approx. 10,000 RSP input Not supported Setting method Digital setting using front panel keys Indication method 11-segment digital display and individual indicators (7-segments displays also possible) Character height: PV: 11 mm, SV: 6.5 mm Bank switching Supported (number of banks: 8) Local SP, alarm settings, PID sets (PID constants, MV upper limit, MV lower limit, etc.) Other functions Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout detection, 40% AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop, protection functions, control output ON/OFF counter, extraction of square root, MV change rate limit, PV/SV status display, logic operations, automatic cooling coefficient adjustment Ambient operating temperature −10 to 55°C (with no condensation or icing), for 3-year warranty: −10 to 50°C Ambient operating humidity 25% to 85% Storage temperature −25 to 65°C (with no condensation or icing)
Thermocouple/Platinum Resistance Thermometer/Analog Input (Fully Universal Inputs) Input type Platinum resistance thermometer Thermocouple Analog input Name Pt100 JPt100 K J T E L U N R S B W PL II 4 to 20 mA 0 to 20 mA 1 to 0 to 0 to 10 V Temperature range (°C) 2300 1800 1700 1600 1500 1400 1300 1200 1100 1000 900 800 700 600 500 400 300 200 100 −100 −200 2300.0 Usable in the following ranges by scaling: −19999 to 32400, −1999.9 to 3240.0, −199.99 to 324.00, or −19.999 to 32.400 1800.0 1700.01700.0 1300.0 1300.0 1300.0 850.0 850.0 850.0 600.0 500.0 500.0 500.0 200.00 200.00 200.00 200.00 100.0 100.0 100.0 Setting number 012 2 4 34 5 6 2 1 7 8 2 2 9 1 02 31 11 21 31 41 51 61 71 81 92 02 52 62 72 82 9 Shaded settings are the default settings. The applicable standards for the input types are as follows: K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 584-1 L: Fe-CuNi, DIN 43710-1985 U: Cu-CuNi, DIN 43710-1985 W: W5Re/W26Re, ASTM E988-1990 JPt100: JIS C 1604-1989, JIS C 1606-1989 Pt100: JIS C 1604-1997, IEC 751 PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard)
Each alarm can be independently set to one of the following 13 alarm types. The default is 2: Upper limit. Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: For models with heater burnout, SSR failure, and heater overcurrent detection, alarm 1 will be an OR output of the alarm selected from the following alarm types and the alarms for heater burnout, SSR failure, and heater overcurrent. To output only a heater burnout alarm, SSR failure alarm, and heater overcurrent alarm for alarm 1, set the alarm type to 0 (i.e., no alarm function). *1. With set values 1, 4 and 5, the upper and lower limit values can be set independently for each alarm type, and are expressed as “L” and “H.” *2. Set value: 1, Upper- and lower-limit alarm *3. Set value: 4, Upper- and lower-limit range *4. Set value: 5, Upper- and lower-limit with standby sequence For Upper- and Lower-Limit Alarm Described Above
- Case 1 and 2 Always OFF when the upper-limit and lower-limit hysteresis overlaps. Case 3: Always OFF *5. Set value: 5, Upper- and lower-limit with standby sequence Always OFF when the upper-limit and lower-limit hysteresis overlaps. *6. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156) for information on the operation of the standby sequence. *7. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156) for information on the loop burnout alarm (LBA). *8. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156) for information on the PV change rate alarm. Set value Alarm type Alarm output operation Description of functionWhen alarm value X is positive When alarm value X is negative
0 Alarm function OFF Output OFF No alarm
1 *1 Upper- and lower-limit *2 Set the deviation in the set point by setting the alarm upper limit (H) and alarm lower limit (L).
2 Upper-limit Set the upward deviation in the set point by setting
the alarm value (X).
3 Lower-limit Set the downward deviation in the set point by setting
the alarm value (X). 4 *1 Upper- and lower-limit range *3 Set the deviation in the set point by setting the alarm upper limit (H) and alarm lower limit (L). 5 *1 Upper- and lower-limit with standby sequence *4 A standby sequence is added to the upper- and lower-limit alarm (1). *6
6 Upper-limit with standby sequence A standby sequence is added to the upper-limit alarm
(2). *6
7 Lower-limit with standby sequence A standby sequence is added to the lower-limit alarm
(3). *6
8 Absolute-value upper-limit The alarm will turn ON if the process value is larger
than the alarm value (X) regardless of the set point.
9 Absolute-value lower-limit The alarm will turn ON if the process value is smaller
than the alarm value (X) regardless of the set point. standby sequence A standby sequence is added to the absolute-value upper-limit alarm (8). *6 standby sequence A standby sequence is added to the absolute-value lower-limit alarm (9). *6
12 LBA (alarm 1 type only) ---
13 PV change rate alarm --- *8
H < 0, L > 0 SP Case 1 LH H > 0, L < 0 SP Case 2 LH H < 0, L < 0 SP LH H < 0, L > 0 LH H > 0, L < 0 Case 3 (Always ON) LH S P Case 1 LHSP Case 2 LHS P L L HS P HSP Case 3 (Always OFF) H < 0, L > 0 H > 0, L < 0 H < 0, L < 0 H < 0, L > 0 H > 0, L < 0
*1. The indication accuracy of K thermocouples in the −200 to 1300°C range, T and N thermocouples at a temperature of −100°C max., and U and L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max. is not specified. The indication accuracy of B thermocouples in the 400 to 800°C range is ±3°C max. The indication accuracy of the R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is ±0.3 of PV or ±3°C, whichever is greater, ±1 digit max. The indication accuracy of PL II thermocouples is ±0.3 of PV or ±2°C, whichever is greater, ±1 digit max. *2. Ambient temperature: −10°C to 23°C to 55°C, Voltage range: −15% to 10% of rated voltage *3. K thermocouple at −100°C max.: ±10°C max. *4. External communications (RS-232C or RS-485) and cable communications for the Setup Tool can be used at the same time. *5. Refer to information on maritime standards in Safety Precautions for E5@N/E5@N-H for compliance with Lloyd's Standards. Indication accuracy Thermocouple: (±0.1% of indicated value or ±1°C, whichever is greater) ±1 digit max. *1 Platinum resistance thermometer: (±0.1% of indicated value or ±0.5°C, whichever is greater) ±1 digit max. Analog input: ±0.1% FS ±1 digit max. CT input: ±5% FS ±1 digit max. Transfer output accuracy ±0.3% FS max. Influence of temperature Thermocouple input (R, S, B, W, PLII): (±1% of PV or ±10°C, whichever is greater) ±1 digit max. Other thermocouple input: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. *3 Platinum resistance thermometer: (±1% of PV or ±2°C, whichever is greater) ±1 digit max. Analog input: (±1%FS) ±1 digit max.Influence of voltage *2 Input sampling period 60 ms Hysteresis Temperature input: 0.1 to 3240.0°C or °F (in units of 0.1°C or °F) Analog input: 0.01% to 99.99% FS (in units of 0.01% FS) Proportional band (P) Temperature input: 0.1 to 3240.0°C or °F (in units of 0.1 °C or °F) Analog input: 0.1% to 999.9% FS (in units of 0.1% FS) Integral time (I) 0.0 to 3240.0 s (in units of 0.1 s) Derivative time (D) 0.0 to 3240.0 s (in units of 0.1 s) Control period 0.5, 1 to 99 s (in units of 1 s) Manual reset value 0.0 to 100.0% (in units of 0.1%) Alarm setting range −19999 to 32400 (decimal point position depends on input type) Affect of signal source resistance Thermocouple: 0.1°C/Ω max. (100 Ω max.) Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.) Insulation resistance 20 MΩ min. (at 500 VDC) Dielectric strength 2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge) Vibration resistance Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions Destruction 10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions Shock resistance Malfunction 100 m/s2, 3 times each in X, Y, and Z directions Destruction 300 m/s2, 3 times each in X, Y, and Z directions Weight Controller: Approx. 150 g, Mounting Bracket: Approx. 10 g Degree of protection Front panel: IP66, Rear case: IP20, Terminals: IP00 Memory protection Non-volatile memory (number of writes: 1,000,000 times) Setup Tool CX-Thermo version 4.0 or higher Setup Tool port Provided on the bottom of the E5CN-H. Use this port to connect a computer to the E5CN-H. An E58-CIFQ1 USB-Serial Conversion Cable is required to connect the computer to the E5CN-H. *4 Standards Approved standards UL 61010-1, CSA C22.2 No. 1010-1 Conformed standards EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II, Lloyd's standards *5EMC EMI: EN 61326 Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A Noise Terminal Voltage: EN 55011 Group 1, class A EMS: EN 61326 ESD Immunity: EN 61000-4-2 Electromagnetic Field Immunity: EN 61000-4-3 Burst Noise Immunity: EN 61000-4-4 Conducted Disturbance Immunity: EN 61000-4-6 Surge Immunity: EN 61000-4-5 Power Frequency Magnetic Field Immunity: EN 61000-4-8 Voltage Dip/Interrupting Immunity: EN 61000-4-11
USB-Serial Conversion Cable Note: A driver must be installed in the personal computer. Refer to installation information in the operation manual for the Conversion Cable. Communications Specifications * The baud rate, data bit length, stop bit length, and vertical parity can be individually set using the Communications Setting Level. Current Transformer (Order Separately) Ratings Heater Burnout Alarms, SSR Failure Alarms, and Heater Overcurrent Alarms *1. For heater burnout alarms, the heater current will be measured when the control output is ON, and the output assigned to the alarm 1 function will turn ON if the heater current is lower than the set value (i.e., heater burnout detection current value). *2. For SSR failure alarms, the heater current will be measured when the control output is OFF, and the output assigned to the alarm 1 function will turn ON if the heater current is higher than the set value (i.e., SSR failure detection current value). *3. For heater overcurrent alarms, the heater current will be measured when the control output is ON, and the output assigned to the alarm 1 function will turn ON if the heater current is higher than the set value (i.e., heater overcurrent detection current value). Electrical Life Expectancy Curve for Relays (Reference Values) Applicable OS Windows 2000, XP, or Vista Applicable software CX-Thermo version 4 or higher Applicable models E5AN/E5EN/E5CN/E5CN-U/ E5AN-H/E5EN-H/E5CN-H/E5GN USB interface standard Conforms to USB Specification 1.1. DTE speed 38400 bps Connector specifications Computer: USB (type A plug) Temperature Controller: Setup Tool port (on bottom of Controller) Power supply Bus power (Supplied from USB host controller.) Power supply voltage 5 VDC Current consumption 70 mA Ambient operating temperature 0 to 55°C (with no condensation or icing) Ambient operating humidity 10% to 80% Storage temperature −20 to 60°C (with no condensation or icing) Storage humidity 10% to 80% Altitude 2,000 m max. Weight Approx. 100 g Transmission line connection method RS-485: Multipoint RS-232C: Point-to-point Communications RS-485 (two-wire, half duplex)/RS-232C Synchronization method Start-stop synchronization Protocol CompoWay/F, SYSWAY, or Modbus Baud rate 1200, 2400, 4800, 9600, 19200, 38400, or 57600 bps Transmission code ASCII (CompoWay/F, SYSWAY) RTU (Modbus) Data bit length * 7 or 8 bits Stop bit length * 1 or 2 bits Error detection Vertical parity (none, even, odd) Frame check sequence (FCS) with SYSWAY Block check character (BCC) with CompoWay/F or CRC-16 Modbus Flow control None Interface RS-485, RS-232C Retry function None Communications buffer 217 bytes Communications response wait time 0 to 99 ms Default: 20 ms Dielectric strength 1,000 VAC for 1 min Vibration resistance 50 Hz, 98 m/s2 Weight E54-CT1: Approx. 11.5 g, E54-CT3: Approx. 50 g Accessories (E54-CT3 only) Armatures (2) Plugs (2) CT input (for heater current detection) Models with detection for single- phase heaters: One input Models with detection for single- phase or three-phase heaters: Two inputs Maximum heater current 50 A AC Input current indication accuracy ±5% FS ±1 digit max. Heater burnout alarm setting range *1 0.1 to 49.9 A (in units of 0.1 A) Minimum detection ON time: 100 ms SSR failure alarm setting range *2 0.1 to 49.9 A (in units of 0.1 A) Minimum detection OFF time: 100 ms Heater overcurrent alarm setting range *3 0.1 to 49.9 A (in units of 0.1 A) Minimum detection ON time: 100 ms 500 300 100 01 2 3 4 56 E5CN-H
250 VAC, 30 VDC
(resistive load) cosφ = 1 Switching current (A) Life (× 104 operations)
- A voltage output (control output, for driving SSR) is not electrically insulated from the internal circuits. When using a grounding thermocouple, do not connect any of the control output terminals to ground. If the control output terminals are connected to ground, errors will occur in the measured temperature values as a result of leakage current. Controllers Note: Wire all voltage input terminals correctly. The Controller may fail if voltage input terminals are wired incorrectly. Control output 1 A B B Control output 1 V DO NOT USE DO NOT USE DO NOT USE mA Auxiliary outputs (relay outputs) Input power supply Auxiliary outputs (relay outputs)
250 VAC, 3 A
(resistive load)
- 100 to 240 VAC
- 24 VAC/VDC (no polarity) Auxiliary output 2 Auxiliary output 1 Relay output
(resistive load) Voltage output (for driving SSR)
12 VDC, 21 mA
Load 1 kΩ min. Current output 0 to 20 mA DC 4 to 20 mA DC Load 600 Ω max. A heater burnout alarm, SSR failure, heater overcurrent alarm, or input alarm is sent to the output to which the alarm 1 function is assigned. RS-232C CT1 CT1 CT1 Communications (RS-232) and CT CT2 CT1 Control Output 2 and CT2 Control Output 2 and Transfer Output EV1 EV2 Event Inputs E53-CNBN2 E53-CNQHHN2 CT1 Control Output 2 and CT E53-CNQHN2 E53-CN03N2 E53-CNQ03N2 E53-CNH03N2 E53-CNHH03N2 E53-CNQFN2 E53-CN01N2 E53-CNH01N2 E53-CNQ01N2 E53-CNQBN2 E53-CNHBN2 E53-CNBFN2 SD RS-232C RD SG SD RD SG RS-232C Communications (RS-232) SD RD SG RS-485 Communications (RS-485) and CT CT2 CT1 RS-485 Communications (RS-485) and CT2 Communications (RS-232) and Control Output 2 RS-485 Communications (RS-485) and Control Output 2 RS-485 Communications (RS-485) EV1 EV2 Event Inputs and Control Output 2 EV1 EV2 Event Inputs and CT EV1 EV2 Event Inputs and Transfer Output Transfer output DO NOT USE DO NOT USE DO NOT USE DO NOT USE DO NOT USE DO NOT USE DO NOT USE DO NOT USE DO NOT USE DO NOT USE DO NOT USE 4 to 20 mA DC (Load 600 Ω max.) 4 to 20 mA DC (Load 600 Ω max.) B (+) A (−) B (+) A (−) B (+) A (−) B (+) A (−) Control output 2
12 VDC 21 mA
Transfer output Control output 2 The Temperature Controller is set for a K-type thermocouple (input type = 5) by default. An input error (s.err) will occur if the input type setting does not agree with the temperature sensor. Check the input type. Option Units
Dimensions (Unit: mm) Accessories (Order Separately) USB-Serial Conversion Cable E5CN-H E5CN-H SUB1 OUT1 OUT2 STOP CWM MANU SUB2 SUB3 HA Level Key Temperature unit No. 1 display No. 2 display Up Key Mode Key Down Key Operation indicators 45+0.6 45+0.6 45+0.6 60 min. (48 × number of units − 2.5)+1.0 Group mounting does not allow waterproofing. Panel Cutout Mounted Separately Group Mounted 48 × 48 44.8 × 44.8 48.8 1.5 Terminal Cover (E53-COV17) (Accessory) Mounting Adapter (Accessory) Waterproof Packing (Accessory) E5CN-H
- Recommended panel thickness is 1 to 5m m . Group mounting is not possible in the vertical direction. (Maintain the specified mounting space between Controllers.) To mount the Controller so that it is waterproof, insert the waterproof packing onto the Controller. When two or more Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications. Note: The terminal block cannot be removed. (2,100) 250 1,765 USB connector (type A plug) Serial connectorLED indicator (RD) LED indicator (SD) E58-CIFQ1
48.8 9.1 Terminal Cover E53-COV17 Waterproof Packing Y92S-29 (for DIN 48 × 48) Order the Waterproof Packing separately if it becomes lost or damaged. The Waterproof Packing can be used to achieve an IP66 degree of protection. (Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the operating environment. Therefore, periodic replacement is recommended to ensure the level of waterproofing specified in IP66. The time for periodic replacement depends on the operating environment. Be sure to confirm this point at your site. Consider one year a rough standard. OMRON shall not be liable for the level of water resistance if the customer does not perform periodic replacement.) The Waterproof Packing does not need to be attached if a waterproof structure is not required. Note: The E53-COV10 can not be used. E54-CT3 Accessory
- Armature 15 5.8 dia. 25 3 10.5 2.8 7.5 Two, 3.5 dia. 40 × 40 12 dia. 2.36 dia. Two, M3 (depth: 4) Approx. 3 dia. (22) Approx. 6 dia. Plug Armature Lead E54-CT1 E54-CT3 Connection Example
- Plug E54-CT1 Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) Maximum continuous heater current: 50 A (50/60 Hz) Number of windings: 400±2 Winding resistance: 18±2 Ω Thru-current (Io) A (r.m.s.) 1 10 100 mA 1 10 100 1,000 A Output voltage (Eo) V (r.m.s.)
100 V 50 Hz
factor 10% 100 Ω RL = 10 Ω ∞10 100 mV 100 µV 1 kΩ E54-CT3 Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) Maximum continuous heater current: 120 A (50/60 Hz) (Maximum continuous heater current for an OMRON Temperature Controller is 50 A.) Number of windings: 400±2 Winding resistance: 8±0.8 Ω 1 kΩ 100 Ω 50 Ω RL = 10 Ω 500 Ω Distor- tion factor 10% Thru-current (Io) A (r.m.s.) 1 10 100 mA 1 10 100 1,000 A Output voltage (Eo) V (r.m.s.) 100 µV
Fixture (Accessory) 69.6 to 77.6 8767 × 67 72 × 72 764.7 72 × 72 48 × 48 Panel (1 to 8 mm) 77.3 (to back of E5CN-H) 2.2 4.7 Y92F-45 Mounted to E5CN-H Note: 1. Use this Adapter when the panel has already been prepared for the E5B@. 2. The Adapter is available only in black.
Read and Understand This Catalog Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranty and Limitations of Liability WARRANTY OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED. LIMITATIONS OF LIABILITY OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY. In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR. Application Considerations SUITABILITY FOR USE OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the products. At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product, machine, system, or other application or use. The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
- Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
- Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations.
- Systems, machines, and equipment that could present a risk to life or property. Please know and observe all prohibitions of use applicable to the products. NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. PROGRAMMABLE PRODUCTS OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof. Disclaimers CHANGE IN SPECIFICATIONS Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual specifications of purchased products. DIMENSIONS AND WEIGHTS Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown. PERFORMANCE DATA Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability. ERRORS AND OMISSIONS The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical, or proofreading errors, or omissions. 2009.11 In the interest of product improvement, specifications are subject to change without notice. OMRON Corporation Industrial Automation Company http://www.ia.omron.com/ (c)Copyright OMRON Corporation 2009 All Right Reserved.