Digital Temperature Controller (Simple Type) E5CC-800 (48 × 48 mm) Large White PV Display That’s Easier to Read. Easy to Use, from Model Selection to Setup and Operation. A Complete Range of I/O Capacities, Functions, and Performance. Handles More Applications.
- The white PV display with a height of 15.2 mm improves visibility. Only 48 × 48 mm (C size) and provides five keys. As easy to operate as 48 × 96 mm (E size) models. High-speed sampling at 50 ms. Short body with depth of only 60 mm. Main I/O Functions 48 × 48 mm E5CC Refer to Safety Precautions on page 29. Sensor Input Dual displays: PV/SV 4-digit displays E5CC Thermocouple Pt Universal analog current/voltage input Indication Accuracy Thermocouple input: ±0.3% of PV Pt input: ±0.2% of PV Analog input: ±0.2% of FS Sampling Period 50 ms Control Output 1 Relay output Voltage output (for driving SSR) Current output PF (shift) Key Temperature status display Independent heating and cooling PID control Changed parameter display Display brightness setting Auxiliary Outputs 2
Model Number Legend and Standard Models Model Number Legend E5CC 48x48mm Heating and Cooling Control
- Using Heating and Cooling Control A Control Output Assignment An auxiliary output is used as the cooling control output. B Control If PID control is used, you can set PID control separately for heating and cooling. This allows you to handle control systems with different heating and cooling response characteristics. Optional Products (Order Separately) Terminal Covers Note: The E53-COV10 cannot be used. Refer to page 10 for the mounted dimensions. Waterproof Packing Note: This Waterproof Packing is provided with the Digital Temperature Controller. Current Transformers (CTs) Adapter Note: Use this Adapter when the panel has already been prepared for an E5B@ Controller. Waterproof Cover Note: This Cover complies with IP66 and NEMA 4X waterproofing. Front panel: IP66 protection. Mounting Adapter Note: This Mounting Adapter is provided with the Digital Temperature Controller. Front Covers Control output 1 Auxiliary output Communications Heater burnout Event inputs Power supply voltage Model Relay output Two 100 to 240 VAC E5CC-RX2ASM-800 Voltage output E5CC-QX2ASM-800 Current output E5CC-CX2ASM-800 Relay output
24 VAC/VDC
Voltage output E5CC-QX2DSM-800 Current output E5CC-CX2DSM-800 Relay output One Two 100 to 240 VAC E5CC-RX2ASM-801 Voltage output E5CC-QX2ASM-801 Relay output 24 VAC/VDC E5CC-RX2DSM-801 Voltage output E5CC-QX2DSM-801 Relay output RS-485 100 to 240 VAC E5CC-RX2ASM-802 Voltage output E5CC-QX2ASM-802 Relay output 24 VAC/VDC E5CC-RX2DSM-802 Voltage output E5CC-QX2DSM-802 Current output -T wo 100 to 240 VAC E5CC-CX2ASM-804 Current output 24 VAC/VDC E5CC-CX2DSM-804 Model E53-COV17 E53-COV23 Model Y92S-P8 Hole diameter Model 5.8 mm E54-CT1 12.0 mm E54-CT3 Model Y92F-45 Model Y92A-48N Model Y92F-49 Type Model Hard Front Cover Y92A-48H Soft Front Cover Y92A-48D
Power supply voltage A in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC Operating voltage range 85% to 110% of rated supply voltage Sensor input Models with temperature inputs Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor: 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C Analog input Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V Input impedance Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB/THB.) Control method ON/OFF control or 2-PID control (with auto-tuning) Control output Relay output SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA Voltage output (for driving SSR) Output voltage: 12 VDC ±20% (PNP), max. load current: 21 mA, with short-circuit protection circuit Current output 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000 Auxiliary output Number of outputs 2 Output specifications N.O. relay outputs, 250 VAC, Models with 2 outputs: 3 A (resistive load), Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V Event input Number of inputs 2 or 4 (depends on model) External contact input specifications Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. Current flow: Approx. 7 mA per contact Setting method Digital setting using front panel keys Indication method 11-segment digital display and individual indicators Character height: PV: 15.2 mm, SV: 7.1 mm Multi SP Up to eight set points (SP0 to SP7) can be saved and selected using event inputs, key operations, or serial communications. Other functions Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, 40% AT, 100% AT, MV limiter, input digital filter, self tuning, PV input shift, run/stop, protection functions, extraction of square root, MV change rate limit, temperature status display, moving average of input value, and display brightness setting Ambient operating temperature -10 to 55°C (with no condensation or icing), for 3-year warranty: -10 to 50°C (with no condensation or icing) Ambient operating humidity 25% to 85% Storage temperature -25 to 65°C (with no condensation or icing)
Input Ranges (Universal inputs)
- Thermocouple/Platinum Resistance Thermometer Shaded settings are the default settings. The applicable standards for the input types are as follows: K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 60584-1 JPt100: JIS C 1604-1989, JIS C 1606-1989 L: Fe-CuNi, DIN 43710-1985 Pt100: JIS C 1604-1997, IEC 60751 U: Cu-CuNi, DIN 43710-1985 PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard) W: W5Re/W26Re, ASTM E988-1990
- Analog input Input type Platinum resistance thermometer Thermocouple Infrared temperature sensor Name Pt100 JPt100 K J T E L U N R S B W PLII 10 to 70°C 60 to 120°C 115 to 165°C 140 to 260°C2300 1800 1700 1600 1500 1400 1300 1200 1100 1000 900 800 700 600 500 400 300 200 100 -100 -200 2300 1800 1700 1700 1300 1300 1300 850 850 850 600 500.0 500.0 500.0 400.0 400 400.0 400 400.0 260 120 165 100.0 100.0 90 100 0.0 0.0 00 000000 -200 -199.9 199.9 -200 -200 -199.9 -200 -200 -199.9 -200 Setting number 01234 56789 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 2 4 Input type Current Voltage Input specification 4 to 20 mA 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V Setting range Usable in the following ranges by scaling: -1999 to 9999, -199.9 to 999.9, -19.99 to 99.99 or -1.999 to 9.999 Setting number 25 26 27 28 29 Temperature range (°C)
Each alarm can be independently set to one of the following 19 alarm types. The default is 2: Upper limit. (see note.) Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified. *1 With set values 1, 4 and 5, the upper and lower limit values can be set ndependently for each alarm type, and are expressed as “L” and “H.” *2 Set value: 1, Upper- and lower-limit alarm *3 Set value: 4, Upper- and lower-limit range *4 Set value: 5, Upper- and lower-limit with standby sequence For Upper- and Lower-Limit Alarm Described Above *2 Case 1 and 2 Always OFF when the upper-limit and lower-limit hysteresis overlaps. Case 3: Always OFF *5. Set value: 5, Upper- and lower-limit with standby sequence Always OFF when the upper-limit and lower-limit hysteresis overlaps. *6 Refer to the E5CC/E5EC Digital Controllers User's Manual (Cat. No. H174) for information on the operation of the standby sequence. *7 Refer to the E5CC/E5EC Digital Controllers User's Manual (Cat. No.H174) for information on the loop burnout alarm (LBA). *8 Refer to the E5CC/E5EC Digital Controllers User's Manual (Cat. No. H174) for information on the PV change rate alarm. *9 When heating/cooling control is performed, the MV absolute upper limit alarm functions only for the heating operation and the MV absolute lower limit alarm functions only for the cooling operation. Set value Alarm type Alarm output operation Description of functionWhen alarm value X is positive When alarm value X is negative
0 Alarm function OFF Output OFF No alarm
1 Upper- and lower-limit *1 *2
Set the deviation in the set point by setting the alarm upper limit (H) and alarm lower limit (L). The alarm is ON when the PV is outside this deviation range.
2 Upper-limit
Set the upward deviation in the set point by setting the alarm value (X). The alarm is ON when the PV is higher than the SP by the deviation or more.
3 Lower-limit
Set the downward deviation in the set point by setting the alarm value (X). The alarm is ON when the PV is lower than the SP by the deviation or more.
4 Upper- and lower-limit
range *1 Set the deviation in the set point by setting the alarm upper limit (H) and alarm lower limit (L). The alarm is ON when the PV is inside this deviation range.
5 Upper- and lower-limit with
standby sequence *1 *4 A standby sequence is added to the upper- and lower-limit alarm (1). *6
6 Upper-limit with standby
sequence A standby sequence is added to the upper-limit alarm (2). *6
7 Lower-limit with standby
sequence A standby sequence is added to the lower-limit alarm (3). *6
8 Absolute-value upper-limit The alarm will turn ON if the process value is larger than the
alarm value (X) regardless of the set point.
9 Absolute-value lower-limit The alarm will turn ON if the process value is smaller than the
alarm value (X) regardless of the set point. with standby sequence A standby sequence is added to the absolute-value upper-lim- it alarm (8). *6 with standby sequence A standby sequence is added to the absolute-value lower-limit alarm (9). *6 LBA (alarm 1 type only) -* 7
13 PV change rate alarm - *8
14 SP absolute value
This alarm type turns ON the alarm when the set point (SP) is higher than the alarm value (X).
15 SP absolute value
This alarm type turns ON the alarm when the set point (SP) is smaller than the alarm value (X).
16 MV absolute value
upper limit *9 This alarm type turns ON the alarm when the manipulated variable (MV) is higher than the alarm value (X).
17 MV absolute value
lower limit *9 This alarm type turns ON the alarm when the manipulated variable (MV) is smaller than the alarm value (X). ON OFF PV SP LH SP XON OFF PV SP XON OFF PV SP XON OFF PV SP XON OFF PV SP LHON OFF PV SP LHON OFF PV SP XON OFF PV SP XON OFF PV SP XON OFF PV SP XON OFF PV0 XON OFF PV XON OFF PV0 XON OFF PV XON OFF PV0 XON OFF PV XON OFF PV0 XON OFF PV XON OFF PV XON OFF SP XON OFF SP0 XON OFF SP XON OFF SP0 XON OFF MV XON OFF MV0 XON OFF MV XON OFF MV LH H<0, L>0 SP Case 1 LH H>0, L<0 SP Case 2 LH H<0, L<0 SP L H H<0, L>0 L H H>0, L<0 Case 3 (Always ON) LH H<0, L>0 SP Case 1 LH H>0, L<0 SP Case 2 L H H<0, L<0 SP L L H H<0, L>0 H H>0, L<0 Case 3 (Always OFF)
*1 The indication accuracy of K thermocouples in the -200 to 1300°C range, T and N thermocouples at a temperature of -100°C max., and U and L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°Cmax. is not specified. The indication accuracy of B thermocouples in the 400 to 800°Crange is ±3°C max. The indication accuracy of the R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is ±0.3 of PV or ±3°C, whichever is greater, ±1 digit max. The indication accuracy of PL II thermocouples is ±0.3 of PV or ±2°C, whichever is greater, ±1 digit max. *2 Ambient temperature: -10°C to 23°C to 55°C, Voltage range: -15% to 10% of rated voltage *3 K thermocouple at -100°C max.: ±10°C max. *4 “EU” stands for Engineering Unit and is used as the unit after scaling. For a temperature sensor, the EU is °C or °F. *5 The unit is determined by the setting of the Integral/Derivative Time Unit parameter. *6 Refer to information on maritime standards in Shipping Standards on page 31 for compliance with Lloyd's Standards. Indication accuracy (at the ambient temperature of 23°C) Thermocouple: ( ±0.3% of indicated value or ±1°C, whichever is greater) ±1 digit max. *1 Platinum resistance thermometer: (±0.2% of indicated value or ±0.8°C, whichever is greater) ±1 digit Analog input: ±0.2% FS ±1 digit max. CT input: ±5% FS ±1 digit max. Influence of temperature *2 Thermocouple input (R, S, B, W, PL II): (±1% of PV or ±10°C, whichever is greater) ±1 digit max. Other thermocouple input: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. *3 Platinum resistance thermometer: (±1% of PV or ±2°C, whichever is greater) ±1 digit max. Analog input: (±1%FS) ±1 digit max. CT input: (±5%FS) ±1 digit max. Influence of voltage *2 Input sampling period 50 ms Hysteresis Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) *4 Analog input: 0.01% to 99.99% FS (in units of 0.01% FS) Proportional band (P) Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) *4 Analog input: 0.1% to 999.9% FS (in units of 0.1% FS) Integral time (I) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5 Derivative time (D) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5 Proportional band (P) for cooling Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) *4 Analog input: 0.1% to 999.9% FS (in units of 0.1% FS) Integral time (I) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5 Derivative time (D) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5 Control period 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s) Manual reset value 0.0 to 100.0% (in units of 0.1%) Alarm setting range -1999 to 9999 (decimal point position depends on input type) Affect of signal source resistance Thermocouple: 0.1°C/Ω max. (100 Ωmax.) Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.) Insulation resistance 20 MΩ min. (at 500 VDC) Dielectric strength 2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge) Vibration resistance 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions Malfunction 10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions Destruction Shock resistance 100 m/s2, 3 times each in X, Y, and Z directions Malfunction 300 m/s2, 3 times each in X, Y, and Z directions Weight Controller: Approx. 120 g, Mounting Bracket: Approx. 10 g Degree of protection Front panel: IP66, Rear case: IP20, Terminals: IP00 Memory protection Non-volatile memory (number of writes: 1,000,000 times) Standards Approved standards UL 61010-1, CSA C22.2 No. 611010-1 (evaluated by UL) Conformed standards EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II, Lloyd's standards *6 EMC EMI: EN61326 Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A Noise Terminal Voltage: EN 55011 Group 1, class A EMS: EN 61326 ESD Immunity: EN 61000-4-2 Electromagnetic Field Immunity: EN 61000-4-3 Burst Noise Immunity: EN 61000-4-4 Conducted Disturbance Immunity: EN 61000-4-6 Surge Immunity: EN 61000-4-5 Voltage Dip/Interrupting Immunity: EN 61000-4-11
Communications Specifications * The baud rate, data bit length, stop bit length, and vertical parity can be individually set using the Communications Setting Level. Current Transformer (Order Separately) Ratings Heater Burnout Alarms and SSR Failure Alarms *1 For heater burnout alarms, the heat er current will be measured when the control output is ON, and the output will turn ON if the heater current is lower than the set value (i.e., heater burnout detection current value). *2 For SSR failure alarms, the heat er current will be measured when the control output is OFF, and the output will turn ON if the heater current is higher than the set value (i.e., SSR failure detection current value). *3 The value is 30 ms for a control period of 0.1 s or 0.2 s. *4 The value is 35 ms for a control period of 0.1 s or 0.2 s. Transmission line connection method RS-485: Multipoint Communications RS-485 (two-wire, half duplex) Synchronization method Start-stop synchronization Protocol CompoWay/F, or Modbus Baud rate 19200, 38400, or 57600 bps Transmission code ASCII Data bit length* 7 or 8 bits Stop bit length* 1 or 2 bits Error detection Vertical parity (none, even, odd) Block check character (BCC) with CompoWay/F or CRC-16 Modbus Flow control None Interface RS-485 Retry function None Communications buffer 217 bytes Communications response wait time 0 to 99 ms Default: 20 ms Dielectric strength 1,000 VAC for 1 min Vibration resistance 50 Hz, 98 m/s2 Weight E54-CT1: Approx. 11.5 g, E54-CT3: Approx. 50 g Accessories (E54-CT3 only) Armatures (2) Plugs (2) CT input (for heater current detection) Models with detection for singlephase heaters: One input Models with detection for singlephase or three-phase heaters: Two inputs Maximum heater current 50 A AC Input current indication accuracy ±5% FS ±1 digit max. Heater burnout alarm setting range 0.1 to 49.9 A (in units of 0.1 A) Minimum detection ON time: 100 ms *3 SSR failure alarm setting range *2 0.1 to 49.9 A (in units of 0.1 A) Minimum detection OFF time: 100 ms *4
Electrical Life Expectancy Curve for Relays (Reference Values) External Connections E5CC-800 Note: 1. The application of the terminals depends on the model. 2. Do not wire the terminals that are shown with a gray background. 3. When complying with EMC standards, the cable that connects the sensor must be 30 m or less. If the cable length exceeds 30 m, compliance with EMC standards will not be possible. 4. Connect M3 crimped terminals. 500 300 100 0 12345 6 Switching current (A) E5CC
250 VAC, 30 VDC
(resistive load) cosφ = 1 Life (× 104 operations) The E5CC is set for a K-type thermocouple (input type = 5) by default. An input error (s.err) will occur if the input type setting does not agree with the temperature sensor. Check the input type. Control output 1 Relay output
250 VAC, 3A
(resistive load) Voltage output (for driving SSR)
12 VDC, 21 mA
Load: 500 Ω max. Relay outputs Models with 2 auxiliary outputs: 250 VAC, 3 A (resistive load) 18 12 Pt A B B m V - 5 V 6+ TC I (no polarity) 100 to 240 VAC 24 VAC/VDC Auxiliary outputs 1, 2 Auxiliary output 2 Auxiliary output 1 804 Communications (RS-485), and Event Inputs 3 and 4 801 Event Inputs 1 and 2, and CT1 802 Communications (RS-485), CT1 EV1 EV2 EV3 EV4 CT1 B(+) A(-) RS-485 B(+) A(-) RS-485 CT1 (2) Auxiliary Outputs (3) Input Power Supply(5) Sensor (Temperature/Analog) Input (6) Options Models with
1 Current
1 Relay
(1) Control outputs 1, 2 OUT1 C OUT1 Q OUT1 R Models with 1 Voltage Output (for Driving SSR) RX QX CX Auxiliary outputs 1, 2 Terminal type
Isolation/Insulation Block Diagrams Models with 2 Auxiliary Outputs Nomenclature Communications and event inputs Sensor input and CT input Voltage output (for driving SSR) and current output Relay output Auxiliary output 1 Power supply Auxiliary output 2 : Reinforced insulation : Functional isolation E5CC Top View Level key Temperature unit No.1 display No. 2 display Up key Mode key Shift (PF) key Down key Operation indicators
Dimensions (Unit: mm) Controllers Accessories (Order Separately) 45+0.6 45+0.6 45+0.6 60 min. (48 × number of units - 2.5)+1.0 Group mounting does not allow waterproofing. Panel Cutout Mounted Separately Group Mounted 48 × 48 73.1 Mounting Adapter (Accessory) Terminal Cover (E53-COV17) (Sold separately) 5848.8 Waterproof Packing (Accessory) 44.8 × 44.8 E5CC
- Recommended panel thickness is 1 to 5 mm. Group mounting is not possible in the vertical direction. (Maintain the specified mounting space between Controllers.) To mount the Controller so that it is waterproof, insert the waterproof packing onto the Controller. When two or more Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications. 48.8 9.1 44.8 2 3.8 Terminal Cover (E53-COV23)
- Terminal Covers E53-COV17
- Terminal Covers E53-COV23 (Three Covers provided.)
- Waterproof Packing Y92S-P8 (for DIN 48 × 48) (Provided with the Controller.) Order the Waterproof Packing separately if it becomes lost or damaged. The Waterproof Packing can be used to achieve an IP66 degree of protection. (Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the operating environment. Therefore, periodic replacement is recommended to ensure the level of waterproofing specified in IP66. The time for periodic replacement depends on the operating environment. Be sure to confirm this point at your site. Consider three years a rough standard. OMRON shall not be liable for the level of water resistance if the customer does not perform periodic replacement.) The Waterproof Packing does not need to be attached if a waterproof structure is not required.
- Adapter
- Watertight Cover Y92A-48N
- Mounting Adapter Y92F-49 (Provided with the Controller.)
- Protective Cover Y92A-48D
- Protective Cover Y92A-48H Fixture (Accessory) 69.6 to 77.6 8767 × 67 72 × 72 764.7 72 × 72 48 × 48 Panel (1 to 8 mm) 62.8 To back of the E5CC 2.2 4.7 Y92F-45 Mounted to E5CC Note: 1. Use this Adapter when the Front Panel has already been prepared for the E5B@. 2. Only black is available. 67.6 21.9 14 (2) 79.287.7 Order this Adapter separately if it becomes lost or damaged. This Protective Cover is soft type. It is able to operate the controller with using this cover. This Protective Cover is hard type. Please use it for the mis-operation prevention etc.
- Current Transformers E54-CT3 Accessory A r m a t u r e 15 5.8 dia. 25 3 10.5 2.8 7.5 Two, 3.5 dia. 40 × 40 12 dia. 2.36 dia. Two, M3 (depth: 4) Approx. 3 dia. (22) Approx. 6 dia. Plug Armature Lead E54-CT1 E54-CT3 Connection Example P l u g Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) E54-CT1 Maximum continuous heater current: 50 A (50/60 Hz) Number of windings: 400±2 Winding resistance: 18±2 Ω Thru-current (Io) A (r.m.s.) 1 10 100mA 1 10 100 1,000A 100V Frequency: 50 Hz Distortion factor 10% 100Ω RL=10Ω ∞10 100mV 100μV 1kΩ Output voltage (Eo) V (r.m.s.) Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) E54-CT3 Maximum continuous heater current: 120 A (50/60 Hz) (Maximum continuous heater current for an OMRON Digital Temperature Controller is 50 A.) Number of windings: 400 ±2 Winding resistance: 8±0.8 Ω Thru-current (Io) A (r.m.s.) 1 10 100mA 1 10 100 1,000A 100V Frequency: 50 Hz Distortion factor 10% 1kΩ 100Ω 50Ω RL=10Ω 500Ω ∞10 100mV 100μV Output voltage (Eo) V (r.m.s.)
Digital Temperature Controller (Simple Type) E5EC-800 (48 × 96 mm) Large White PV Display That’s Easier to Read. Easy to Use, from Model Selection to Setup and Operation. A Complete Range of I/O Capacities, Functions, and Performance. Handles More Applications. A white LCD PV display with a height of approx. 18 mm improves visibility. High-speed sampling at 50 ms. Models with up to 2 auxiliary outputs. Short body with depth of only 60 mm. Main I/O Functions 48 × 96 mm E5EC Refer to Safety Precautions on page 29. E5EC 4-digit displays Sensor Input Thermocouple Pt Universal analog current/voltage input Indication Accuracy Thermocouple input: ±0.3% of PV Pt input: ±0.2% of PV Analog input: ±0.2% of FS Sampling Period 50 ms Control Output 1 Relay output Voltage output (for driving SSR) Current output Control Output 2 Relay output Auxiliary Outputs 2 PF (shift) Key Temperature status display Independent heating and cooling PID control Changed parameter display Display brightness setting Dual displays: PV/SV
Model Number Legend and Standard Models Model Number Legend E5EC 48x96mm Heating and Cooling Control l Using Heating and Cooling Control A Control Output Assignment If there is no control output 2, an auxiliary output is used as the cooling control output. If there is a control output 2, the two control outputs are used for heating and cooling. (It does not matter which output is used for heating and which output is used for cooling.) B Control If PID control is used, you can set PID control separately for heating and cooling. This allows you to handle control systems with different heating and cooling response characteristics. Optional Products (Order Separately) Communications Conversion Cable Note: Always use this product together with the E58-CIFQ2. Terminal Covers Waterproof Packing Note: This Waterproof Packing is provided with the Digital Temperature Controller. Waterproof Cover Note: This Cover complies with IP66 and NEMA 4X waterproofing. Front panel: IP66 protection. Front Port Cover Note: This Front Port Cover is provided with the Digital Temperature Controller. Mounting Adapter Note: This Mounting Adapter is provided with the Digital Temperature Controller. Current Transformers (CTs) Control output 1 Control output 2 Auxiliary output Communications Heater burnout Event inputs Power supply voltage Model Relay output - Two -- - 100 to 240 VAC E5EC-RX2ASM-800 Voltage output - E5EC-QX2ASM-800 Current output - E5EC-CX2ASM-800 Relay output Relay output E5EC-RR2ASM-800 Voltage output Relay output E5EC-QR2ASM-800 Current output Relay output E5EC-CR2ASM-800 Relay output - Voltage output - E5EC-QX2DSM-800 Current output - E5EC-CX2DSM-800 Relay output Relay output E5EC-RR2DSM-800 Voltage output Relay output E5EC-QR2DSM-800 Current output Relay output E5EC-CR2DSM-800 Relay output Relay output RS-485 One Two 100 to 240 VAC E5EC-RR2ASM-808 Voltage output Relay output E5EC-QR2ASM-808 Relay output Relay output 24 VAC/VDC E5EC-RR2DSM-808 Voltage output Relay output E5EC-QR2DSM-808 Relay output Relay output - Four 100 to 240 VAC E5EC-RR2ASM-810 Voltage output Relay output E5EC-QR2ASM-810 Relay output Relay output 24 VAC/VDC E5EC-RR2DSM-810 Voltage output Relay output E5EC-QR2DSM-810 Current output Relay output RS-485 - Two 100 to 240 VAC E5EC-CR2ASM-804 Current output Relay output 24 VAC/VDC E5EC-CR2DSM-804 Model E58-CIFQ2-E Model E53-COV24 Model Y92S-P9 Model Y92A-49N Model Y92S-P7 Model Y92F-51 (Two Adapters are included.) Hole diameter Model 5.8 mm E54-CT1 12.0 mm E54-CT3
Power supply voltage A in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC Operating voltage range 85% to 110% of rated supply voltage Sensor input Models with temperature inputs Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor: 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C Analog input Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V Input impedance Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB/THB.) Control method ON/OFF control or 2-PID control (with auto-tuning) Control output Relay output SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA Voltage output (for driving SSR) Output voltage: 12 VDC ±20% (PNP), max. load current: 40 mA, with short-circuit protection circuit (The maximum load current is 21 mA for models with two control outputs.) Current output 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000 Auxiliary output Number of outputs 2 Output specifications N.O. relay outputs, 250 VAC, Models with 2 outputs: 3 A (resistive load), Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V Event input Number of inputs 2 External contact input specifications Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. Current flow: Approx. 7 mA per contact Setting method Digital setting using front panel keys Indication method 11-segment digital display and individual indicators Character height: PV: 18.0 mm, SV: 11.0 mm Multi SP Up to eight set points (SP0 to SP7) can be saved and selected using event inputs, key operations, or serial communications. Bank switching None Other functions Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, 40% AT, 100% AT, MV limiter, input digital filter, self tuning, PV input shift, run/stop, protection functions, ex- traction of square root, MV change rate limit, temperature status display, moving average of input val- ue, and display brightness setting Ambient operating temperature -10 to 55°C (with no condensation or icing), for 3-year warranty: -10 to 50°C (with no condensation or icing) Ambient operating humidity 25% to 85% Storage temperature -25 to 65°C (with no condensation or icing)
Input Ranges (Universal inputs)
- Thermocouple/Platinum Resistance Thermometer Shaded settings are the default settings. The applicable standards for the input types are as follows: K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 60584-1 JPt100: JIS C 1604-1989, JIS C 1606-1989 L: Fe-CuNi, DIN 43710-1985 Pt100: JIS C 1604-1997, IEC 60751 U: Cu-CuNi, DIN 43710-1985 PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard) W: W5Re/W26Re, ASTM E988-1990
- Analog input Input type Platinum resistance thermometer Thermocouple Infrared temperature sensor Name Pt100 JPt100 K J T E L U N R S B W PLII 10 to 70°C 60 to 120°C 115 to 165°C 140 to 260°C2300 1800 1700 1600 1500 1400 1300 1200 1100 1000 900 800 700 600 500 400 300 200 100 -100 -200 2300 1800 1700 1700 1300 1300 1300 850 850 850 600 500.0 500.0 500.0 400.0 400 400.0 400 400.0 260 120 165 100.0 100.0 90 100 0.0 0.0 00 000000 -200 -199.9 -199.9 -200 -200 -199.9 -200 -200 -199.9 -200 Setting range 01234 56789 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 2 4 Input type Current Voltage Input specification 4 to 20 mA 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V Setting range Usable in the following ranges by scaling: -1999 to 9999, -199.9 to 999.9, -19.99 to 99.99 or -1.999 to 9.999 Setting number 25 26 27 28 29 Temperature range (°C)
Each alarm can be independently set to one of the following 19 alarm types. The default is 2: Upper limit. (see note.) Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified. *1 With set values 1, 4 and 5, the upper and lower limit values can be set ndependently for each alarm type, and are expressed as “L” and “H.” *2. Set value: 1, Upper- and lower-limit alarm *3. Set value: 4, Upper- and lower-limit range *4. Set value: 5, Upper- and lower-limit with standby sequence For Upper- and Lower-Limit Alarm Described Above *2 Case 1 and 2 Always OFF when the upper-limit and lower-limit hysteresis overlaps. Case 3: Always OFF *5. Set value: 5, Upper- and lower-limit with standby sequence Always OFF when the upper-limit and lower-limit hysteresis overlaps. *6. Refer to the E5CC/E5EC Digital Controllers User's Manual (Cat. No. H174) for information on the operation of the standby sequence. *7. Refer to the E5CC/E5EC Digital Controllers User's Manual (Cat. No. H174) for information on the PV change rate alarm. *8. Refer to the E5CC/E5EC Digital Controllers User's Manual (Cat. No. H174) for information on the PV change rate alarm. *9. When heating/cooling control is performed, the MV absolute upper limit alarm functions only for the heating operation and the MV absolute lower limit alarm functions only for the cooling operation. Set value Alarm type Alarm output operation Description of functionWhen alarm value X is positive When alarm value X is negative Set the deviation in the set point by setting the alarm upper limit (H) and alarm lower limit (L). The alarm is ON when the PV is outside this deviation range. Set the upward deviation in the set point by setting the alarm value (X). The alarm is ON when the PV is higher than the SP by the deviation or more. Set the downward deviation in the set point by setting the alarm value (X). The alarm is ON when the PV is lower than the SP by the deviation or more. range *1 Set the deviation in the set point by setting the alarm upper limit (H) and alarm lower limit (L). The alarm is ON when the PV is inside this deviation range. standby sequence *1 *4 A standby sequence is added to the upper- and lower-limit alarm (1).*6 sequence A standby sequence is added to the upper-limit alarm (2). *6 sequence A standby sequence is added to the lower-limit alarm (3).*6 alarm value (X) regardless of the set point. alarm value (X) regardless of the set point. with standby sequence A standby sequence is added to the absolute-value upper- limit alarm (8). *6 with standby sequence A standby sequence is added to the absolute-value lower-limit alarm (9). *6 LBA (alarm 1 type only) -* 7 This alarm type turns ON the alarm when the set point (SP) is higher than the alarm value (X). This alarm type turns ON the alarm when the set point (SP) is smaller than the alarm value (X). upper limit *9 This alarm type turns ON the alarm when the manipulated variable (MV) is higher than the alarm value (X). lower limit *9 This alarm type turns ON the alarm when the manipulated variable (MV) is smaller than the alarm value (X). ON OFF PV SP LH SP XON OFF PV SP XON OFF PV SP XON OFF PV SP XON OFF PV SP LHON OFF PV SP LHON OFF PV SP XON OFF PV SP XON OFF PV SP XON OFF PV SP XON OFF PV0 XON OFF PV XON OFF PV0 XON OFF PV XON OFF PV0 XON OFF PV XON OFF PV0 XON OFF PV XON OFF PV XON OFF SP XON OFF SP0 XON OFF SP XON OFF SP0 XON OFF MV XON OFF MV0 XON OFF MV XON OFF MV LH S P Case 1 LHSP Case 2 LHS P LHS P L H SP Case 3 (Always ON) H<0, L<0 H<0, L>0 H>0, L<0 H<0, L>0 H>0, L<0 LH S P Case 1 LHSP Case 2 LHS P L L HS P H SP Case 3 (Always OFF) H<0, L>0 H>0, L<0 H<0, L<0 H<0, L>0 H>0, L<0
*1. The indication accuracy of K thermocouples in the -200 to 1300°C range, T and N thermocouples at a temperature of -100°C max., and U and L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max. is not specified. The indication accuracy of B thermocouples in the 400 to 800°C range is ±3°C max. The indication accuracy of the R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is ±0.3 of PV or ±3°C, whichever is greater, ±1 digit max. The indication accuracy of PL II thermocouples is ±0.3 of PV or ±2°C, whichever is greater, ±1 digit max. *2. Ambient temperature: -10°C to 23°C to 55°C, Voltage range: -15% to 10% of rated voltage *3. K thermocouple at -100°C max.: ±10°C max. *4. “EU” stands for Engineering Unit and is used as the unit af ter scaling. For a temperature sensor, the EU is °C or °F. *5. The unit is determined by the setting of the Integral/Derivative Time Unit parameter. *6. Refer to information on maritime standards in Shipping Standards on page 31 for compliance with Lloyd's Standards. Indication accuracy (at the ambient temperature of 23°C) Thermocouple: (±0.3% of indicated value or ±1°C, whichever is greater) ±1 digit max. *1 Platinum resistance thermometer: (±0.2% of indicated value or ±0.8°C, whichever is greater) ±1 digit Analog input: ±0.2% FS ±1 digit max. CT input: ±5% FS ±1 digit max. Influence of temperature *2 Thermocouple input (R, S, B, W, PL II): (±1% of PV or ±10°C, whichever is greater) ±1 digit max. Other thermocouple input: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. *3 Platinum resistance thermometer: (±1% of PV or ±2°C, whichever is greater) ±1 digit max. Analog input: (±1%FS) ±1 digit max. CT input: (±5% FS) ±1 digit max. Influence of voltage *2 Input sampling period 50ms Hysteresis Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or°F) *4 Analog input: 0.01% to 99.99% FS (in units of 0.01% FS) Proportional band (P) Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) *4 Analog input: 0.1 to 999.9% FS (in units of 0.1% FS) Integral time (I) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5 Derivative time (D) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5 Proportional band (P) for cooling Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) *4 Analog input: 0.1 to 999.9% FS (in units of 0.1% FS) Integral time (I) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5 Derivative time (D) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5 Control period 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s) Manual reset value 0.0 to 100.0% (in units of 0.1%) Alarm setting range -1999 to 9999 (decimal point position depends on input type) Affect of signal source resistance Thermocouple: 0.1°C/Ω max. (100 Ω max.) Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.) Insulation resistance 20 MΩ min. (at 500 VDC) Dielectric strength 2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge) Vibration resistance 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions Malfunction 10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions Destruction resistance 100 m/s2, 3 times each in X, Y, and Z directions Malfunction 300 m/s2, 3 times each in X, Y, and Z directions Weight Controller: Approx. 210 g, Mounting Bracket: Approx. 4 g × 2 Degree of protection Front panel: IP66, Rear case: IP20, Terminals: IP00 Memory protection Non-volatile memory (number of writes: 1,000,000 times) Standards Approved standards UL 61010-1, CSA C22.2 No. 611010-1 (evaluated by UL) Conformed standards EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II, Lloyd's standards *6 EMC EMI EN61326 Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A Noise Terminal Voltage: EN 55011 Group 1, class A EMS: EN 61326 ESD Immunity: EN 61000-4-2 Electromagnetic Field Immunity: EN 61000-4-3 Burst Noise Immunity: EN 61000-4-4 Conducted Disturbance Immunity: EN 61000-4-6 Surge Immunity: EN 61000-4-5 Voltage Dip/Interrupting Immunity: EN 61000-4-11
Communications Specifications * The baud rate, data bit length, stop bit length, and vertical parity can be in- dividually set using the Communications Setting Level. Current Transformer (Order Separately) Ratings Heater Burnout Alarms and SSR Failure Alarms *1. For heater burnout alarms, the heater current will be measured when the control output is ON, and the output will turn ON if the heater current is lower than the set value (i.e., heater burnout detection current value). *2. For SSR failure alarms, the heater current will be measured when the control output is OFF, and the output will turn ON if the heater current is higher than the set value (i.e., SSR failure detection current value). *3. The value is 30 ms for a control period of 0.1 s or 0.2 s. *4. The value is 35 ms for a control period of 0.1 s or 0.2 s. Transmission line connection method RS-485: Multipoint Communications RS-485 (two-wire, half duplex) Synchronization method Start-stop synchronization Protocol CompoWay/F, or Modbus Baud rate 19200, 38400, or 57600 bps Transmission code ASCII Data bit length* 7 or 8 bits Stop bit length* 1 or 2 bits Error detection Vertical parity (none, even, odd) Block check character (BCC) with CompoWay/F or CRC-16 Modbus Flow control None Interface RS-485 Retry function None Communications buffer 217 bytes Communications response wait time 0 to 99 ms Default: 20 ms Dielectric strength 1,000 VAC for 1 min Vibration resistance 50 Hz, 98 m/s2 Weight E54-CT1: Approx. 11.5 g, E54-CT3: Approx. 50 g Accessories (E54-CT3 only) Armatures (2) Plugs (2) CT input (for heater current detection) Models with detection for singlephase heaters: One input Models with detection for singlephase or three-phase heaters: Two inputs Maximum heater current 50 A AC Input current indica- tion accuracy ±5% FS ±1 digit max. Heater burnout alarm setting range 0.1 to 49.9 A (in units of 0.1 A) Minimum detection ON time: 100 ms *3 SSR failure alarm setting range *2 0.1 to 49.9 A (in units of 0.1 A) Minimum detection OFF time: 100 ms *4
Electrical Life Expectancy Curve for Relays (Reference Values) External Connections E5EC-800 Note: 1. The application of the terminals depends on the model. 2. Do not wire the terminals that are shown with a gray background. 3. When complying with EMC standards, the cable that connects the sensor must be 30 m or less. If the cable length exceeds 30 m, compliance with EMC standards will not be possible. 4. Connect M3 crimped terminals. 500 300 100 0 12345 6 Switching current (A) E5EC (resistive load) cosφ = 1 Life (× 104 operations) The E5EC is set for a K-type thermocouple (input type = 5) by default. An input error (s.err) will occur if the input type setting does not agree with the temperature sensor. Check the input type. Relay output
250 VAC, 5 A
(resistive load) Voltage output (for driving SSR)
12 VDC, 40 mA
Control Output 2: 21 mA Current output 0 to 20 mA DC 4 to 20 mA DC Load: 500 Ω max. 175 11 3 100 to 240 VAC V - 23 V 24+ TC 22+ mA- Pt I A B B Auxiliary outputs 1, 2 Auxiliary output 1 Auxiliary output 2 808 Communications, 2 event inputs, and 1 CT input 804 Communications and 2 event inputs EV1 EV2 EV1 EV2 B(+) A(-) RS-485 B(+) A(-) RS-485 CT1 Terminal type Auxiliary outputs 1, 2 Control output 2 Control output 1 Relay output Model with 2 auxiliary outputs: 250 VAC, 3 A (resistive load)Relay output (resistive load) - - (1) Control output Models with (for Driving SSR) Models with Voltage Output (for Driving SSR) and Relay Output Models with 2 Relay Outputs Models with Current Output and Relay Output Models with 1 Current Output RX R R R R Q Q OUT1OUT1OUT1 C C QR RR CR QX CX R (2) Auxiliary Outputs (3) Input Power Supply (6) Options (5) Sensor (Temperature/Analog) Input (no polarity)
Isolation/Insulation Block Diagrams Models with 2 Auxiliary Outputs Nomenclature Communications and event inputs Sensor input and CT input Voltage output (for driving SSR) and current output Relay output Auxiliary output 1 Auxiliary output 2 : Reinforced insulation : Functional isolation Power Supply E5EC Top View Temperature unit Operation indicators Shift (PF) key No.1 display No. 2 display No. 3 display Down key Up key Mode key Level key
Dimensions (Unit: mm) Controllers Mounting Adapter (Accessory) Waterproof Packing (Accessory) 48 60 44 91110 (64) E5EC 92-0.8 92+0.8 45+0.6 120 min. (48 × number of units − 2.5)+1.0 Group mounting does not allow waterproofing. Mounted Separately Group Mounted * Recommended panel thickness is 1 to 8 mm. Group mounting is not possible in the vertical direction. (Maintain the specified mounting space between Controllers.) To mount the Controller so that it is waterproof, insert the waterproof packing onto the Controller. When two or more Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications.
Accessories (Order Separately) 2 3.8
- Terminal Covers E53-COV24 (Three Covers provided.)
- Waterproof Packing Y92S-P9 (for DIN 48 × 96) (Provided with the Controller.) The following degrees of protection apply. The structure is not waterproof for any part for which the degree of protection is not specified or for any part with IP@0 protection. Front panel: IP66, Rear case: IP20, Terminal section: IP00 When waterproofing is required, fit Watertight Packing on the backside of front panel. Keep the Port Cover on the front-panel Setup Tool port of the E5EC securely closed. The degree of protection when the Waterproof Packing is used is IP66. To maintain an IP66 degree of protection, the Waterproof Packed and the Port Cover for the front- panel Setup Tool port must be periodically replaced because they may deteriorate, shrink, or harden depending on the operating environment. The replacement period will vary with the operating environment. Check the required period in the actual application. Use 3 years or sooner as a guideline. If the Waterproof Packing and Port Cover are not periodically replaced, waterproof performance may not be maintained. If a waterproof structure is not required, then the Waterproof Packing does not need to be installed.
- Mounting Adapter Y92F-51 (for DIN 48 × 96) (Two Adapters provided.) One pair is provided with the Controller. Order this Adapter separately if it becomes lost or damaged.
- Current Transformers E54-CT3 Accessory A r m a t u r e 15 5.8 dia. 25 3 10.5 2.8 7.5 Two, 3.5 dia. 40 × 40 12 dia. 2.36 dia. Two, M3 (depth: 4) Approx. 3 dia. (22) Approx. 6 dia. Plug Armature Lead E54-CT1 E54-CT3 Connection Example P l u g Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) E54-CT1 Maximum continuous heater current: 50 A (50/60 Hz) Number of windings: 400 ±2 Winding resistance: 18 ±2 Ω Thru-current (Io) A (r.m.s.) 1 10 100mA 1 10 100 1,000A 100V Frequency: 50 Hz Distortion factor 10% 100Ω RL=10Ω ∞10 100mV 100μV 1kΩ Output voltage (Eo) V (r.m.s.) Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) E54-CT3 Maximum continuous heater current: 120 A (50/60 Hz) (Maximum continuous heater current for an OMRON Digital Temperature Controller is 50 A.) Number of windings: 400 ±2 Winding resistance: 8 ±0.8 Ω Thru-current (Io) A (r.m.s.) 1 10 100mA 1 10 100 1,000A 100V Frequency: 50 Hz Distortion factor 10% 1kΩ 100Ω 50Ω RL=10Ω 500Ω ∞10 100mV 100μV Output voltage (Eo) V (r.m.s.)
This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords. Some parameters are not displayed depending on the protect level setting and the conditions of use. Control stops when you move from the operation level to the initial setting level. *1. To use a key procedure to move to Manual Control Level, set the Auto/Manual Select Addition parameter to ON and set the PF S etting parameter to a-m (Auto/ Manual). *2. The No. 1 display will flash in the middle when the keys are pressed for 1 s or longer. Press O Key once (models with communications only). Communications Setting Level Advanced Function Setting Level Power ON Used to set application functions. Initial Setting Level Operation Level Used to set the input type and other basic settings. Used to set communications. Used for SP, alarm values, and other basic settings and monitoring. Used to change adjustment parameters (PID constants, adjustment sensitivity, etc.). Used to set protection for operations. Press the O Key for at least 1 s. Press the O and M Keys for at least 1 s. Press the O and M Keys for at least 3 s.*2 Press the O Key for at least 3 s.*2 Press the O Key or the S Key for at least 1 s. Only when Manual Mode was used just before power OFF Level changes automatically. Protect Level Manual Control Level Used to set the MV manually. O Key once. O Key once. O Key once. Press the O Key for at least 1 s. Release protection and then enter the password (−169) for the amoV (Move to Advanced Setting Level) parameter. O Key pressed for at least 3 s *2 or S Key pressed for at least 1 s *1 while A-M is displayed Adjustment Level Stopped. Operating
Error Displays (Troubleshooting) When an error occurs, the No. 1 display or No. 2 display shows the error code. Take necessary measure according to the error code, referring the following table. Display Name Meaning Action Operation s.err Input error The input value exceeded the control range.* The input type is not set correctly. The sensor is disconnected or short- circuited. The sensor is not wired correctly. The sensor is not wired. * Control Range Temperature resistance thermometer or thermocouple input: SP Lower Limit - 20°C to SP Upper Limit + 20°C (SP Lower Limit - 40°F to SP Upper Limit + 40°F) ESIB input: Same as specified input range. Analog input: Scaling range -5% to 105% Check the wiring for input to be sure it is wired correctly, not broken, and not shorted. Also check the input type. If there are no problems in the wiring or input type settings, cycle the power supply. If the display remains the same, replace the Digital Temperature Controller. If the display is restored to normal, then the probable cause is external noise affecting the control system. Check for external noise. Note: For a temperature resistance thermometer, the input is considered disconnected if the A, B, or B’line is broken. After the error occurs and it is displayed, the alarm output will operate as if the upper limit was exceeded. It will also operate as if transfer output exceeded the upper limit. If an input error is assigned to a control output or auxiliary output, theoutput will turn ON when the input error occurs. The error message will appear in the display for the PV. Note: 1. The heating and cooling control outputs will turn OFF. 2. When the manual MV, MV at stop, or MV at error is set, the control output is determined by the set value. [[[[ Display range exceeded Below -1,999 This is not an error. It is displayed when the control range is wider than the display range and the PV exceeds the display range. The PV is displayed for the range that is given on the left (the number without the decimal point). Control continues and operation is normal. The value will appear in the display for the PV. Refer to the E5CC/E5EC Digital Controllers User’s Manual (Cat. No. H174) for information on the controllable range. ]]]] Above 9,999 e333 A/D converter error There is an error in the internal circuits. First, cycle the power supply. If the display remains the same, the controller must be repaired. If the display is restored to normal, then a probable cause can be external noise affecting the control system. Check for external noise. The control outputs, auxiliary outputs, and transfer outputs turn OFF. (A current output will be approx. 0 mA and a linear voltage output will be approx. 0V.) e111 Memory error There is an error in the internal memory operation. First, cycle the power supply. If the display remains the same, the controller must be repaired. If the display is restored to normal, then a probable cause can be external noise affecting the control system. Check for external noise. The control outputs, auxiliary outputs, and transfer outputs turn OFF. (A current output will be approx. 0 mA and a linear voltage output will be approx. 0V.) ffff Overcurrent This error is displayed when the peak current exceeds 55.0 A. - Control continues and operation is normal. The error message will appear for the following displays. Heater Current Value 1 Monitor Leakage Current Value 1 Monitor ct1 lcr1 HB or HS alarm If there is a HB or HS alarm, the No. 1 display will flash in the relevant setting level. The No. 1 display for the following parameter flashes in Operation Level or Adjustment Level. Heater Current Value 1 Monitor Leakage Current Value 1 Monitor However, control continues and operation is normal.
M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M C l.adj ins 0.0 c-p 8.0 c-i 233 c-d M M M p 8.0 i 233 d c-db 0.0 of-r 50.0 hys 1.0 chys 1.0 pmov oapt icpt wtpt off pfpt off M chgp off M M sprt off ol-h 100.0 ol-l 0.0 at off cmwt off ct1 0.0 M hb1 0.0 lcr1 hs1 50.0 sp-0 sp-1 sp-2 sp-3 sp-4 sp-5 sp-6 sp-7 M sp-3 r-s run al-1 al1h al1l al-2 al2h al2l M o 0.0 c-o 0.0 a-m m-sp ct-1 0.0 lcr1 0.0 PID Control only Press the S Key for at least 1 s. *1 Press the O Key or the S Key for at least 1 s. *1 Operation Level Power ON Starting in manual mode. Adjustment Level Press the O Key less than 1 s. Press the O Key less than 1 s. PV/MV Starting in automatic mode. Adjustment Level Display Displayed only once when entering adjustment level. Manual Control Level Press the S Key *2 Press the S Key *2 Press the O Key for at least 3 s. Press the O and M Keys for at least 3 s. Proportional Band (Cooling) Protect Level Note: The time ta ken to move to the protect level can be adjusted by changing the "Move to protect level time" setting. *1. When the PF Setting parameter is set to A-M. *2. When the PF Setting parameter is set to PFDP. *3. These parameters are displayed regardless of the setting of the Protocol Setting parameter. Move to Protect Level: Operation/Adjustment Protect: Initial Setting/Communications Protect: Setting Change Protect: Displayed only when a password is set. Restricts moving to protect level. Restricts displaying and modifying menus in operation, adjustment, and manual control levels. This protect level restricts movement to the initial setting, communicationssetting, and advanced function setting levels. Protects changes to setups by operating the front panel keys. PF Key Protect AT Execute/Cancel Communications Writing Heater Current 1 Value Monitor Leakage Current
1 Monitor
(Cooling) Derivative Time (Cooling) Dead Band Manual Reset Value Clear the offset during stabilization of P or PD control. Hysteresis (Heating) Hysteresis (Cooling) MV Upper Limit MV Lower Limit Hysteresis settings Process Value Input Shift Process Value/Set Point (1) Process Value/Set Point (2) Auto/Manual Switch PID 1 control only. Added for Auto/Manual Switch Display Addition. Heater Current 1 Value Monitor Leakage Current 1 Monitor Multi-SP Set Point Setting Alarm Value 1 Alarm Value Upper Limit 1 Alarm Value Lower Limit 1Alarm Value 2 Alarm Value Upper Limit 2 Alarm Value Lower Limit 2 MV Monitor (Heating) MV Monitor (Cooling) Press the O and M Keys for at least 1 s. Proportional Band Integral Time Derivative Time PID settings SP Ramp Set Value RUN/STOP Display Changed Parameters Set either of these parameters. Set either of these parameters. Press the O Key less than 1 s. Communications Setting Level Note: Displayed only for models with communications. Changes are effective after cycling power or after a software reset. M M M len sbit prty even Communications Data Length*3 Communications Stop Bits Communications Parity Initial Setting Level Press the O Key for at least 3 s. Press the O Key for at least 1 s. Other than the Auto/Manual Switch display M M M M M Protocol Setting*3 Communications Unit No.*3 Communications Baud Rate Send Data Wait Time Maximum Communications Unit No. Area M M M M First Address Upper Word First Address Lower Word Receive Data Wait Time Upload Setting 1 M M M M Upload Setting 13 Download Setting 1 Download Setting 13 Copy M psel fins u-no bps 57.6 sdwt maxu adrh adrl rwat 1000 area up13 dn 1 dn13 1000 copy off up 1 M Communications Node Number unit Parameters The related setting items in each level are described below. If you press the Mode Key at the last setting item, the display will return to the first setting item in the same level.
M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M SS S S alt2 init off a1lt off a2lt off hsu on hsl off hsh 0.1 pvrp hctm off mspu off spru m rest a ret off alh2 0.2 ev-1 msp0 ev-2 stop ev-3 none ev-4 none o1st 4-20 o2st 4-20 amov sb1n n-o sb2n n-o hbu on hbl off hbh 0.1 st-b 15.0 alfa 0.65 tidu inf 0.0 mav off o-dp off prlt a1on a2on a1of a2of amad off mant hold mani 0.0 cjc on lba lbal 8.0 lbab 3.0 out1 o out2 none sub1 alm1 sub2 alm2 alma t-u m alsp sp-m pf shft spd1 spd2 odsl o pvdp on pvst off svst off d.ref 0.25 ompw 1.0 Press the O Key for at least 1 s. Advanced Function Setting Level Alarm 1 Latch Alarm 2 Latch Move to Protect Level Time HS Alarm Latch HS Alarm Hysteresis LBA Detection Time LBA Level LBA Band Control Output 1 Assignment Control Output 2 Assignment HS Alarm Use Parameter Initialization Heater Burnout Latch Number of Multi-SP Points SP Ramp Time Unit Standby Sequence Reset Auxiliary Output 1 Open in Alarm Auxiliary Output 2 Open in Alarm Heater Burnout Hysteresis HB ON/OFF PF Setting "PV/SP (1)" Display Screen Selection MV Display Selection PV Decimal Point Display PV Status Display Function SV Status Display Function "PV/SP (2)" Display Screen Selection Input Digital Filter ST Stable Range α Integral/Derivative Time Unit Alarm 1 ON Delay Alarm 2 ON Delay Alarm 1 OFF Delay Alarm 2 OFF Delay Auxiliary Output 1 Assignment Auxiliary Output 2 Assignment Soak Time Unit Alarm SP Selection Integrated Alarm Assignment Moving Average Count Auto/Manual Select Addition Manual Output Method Manual MV Initial Value Monitor/Setting Item Display 1 Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to 5 parameters (advanced function setting level). Monitor/Setting Item Display 2 Monitor/Setting Item Display 3 Monitor/Setting Item Display 4 Monitor/Setting Item Display 5 Monitor/Setting Item Level Alarm 2 Type Move to Advanced Function Setting Level: Displayed when initial setting/ communications protect is set to 0. Move by setting password (−169). Event Input Assignment 1 Event Input Assignment 2 Alarm 2 Hysteresis Event Input Assignment 3 Event Input Assignment 4 Display Refresh Period PV Rate of Change Calculation Period Heating/Cooling Tuning Method Minimum Output ON/OFF Band Automatic Display Return Time MV Display Control Output 1 Signal Type Control Output 2 Signal Type (E5EC only) (E5EC only) Cold Junction Compensation Method M M M M M M M M M M M M M M M in-t in-h 100 in-l dp d-u c sl-h 1300 sl-l -200 cntl onof s-hc stnd st on cp c-cp orev or-r alt1 alh1 0.2 Press the O Key less than 1 s. ST Input Type Control Period (Heating) Scaling Upper Limit Scaling Lower Limit Decimal Point Temperature Unit SP Upper Limit SP Lower Limit PID ON/OFF Standard or Heating/Cooling Control Period (Cooling) Direct/Reverse Operation For input type of analog Limit the set point For input type of temperature, standard control, or PID Set the ON/OFF output cycle. Temperature for °C or °F input type. Alarm 1 Hysteresis Alarm 1 Type
- Be sure to read the precautions for all E5CC/E5EC-800 models in the website at: http://www.ia.omron.com/. Do not touch the terminals while power is being supplied. Doing so may occasionally result in minor injury due to electric shock. Electric shock may occur. Do not touch any cables or connectors with wet hands. Electric shock, fire, or malfunction may occasionally occur. Do not allow metal objects, conductors, cuttings from installation work, or moisture to enter the Digital Temperature Controller or the Setup Tool port or ports. Attach the cover to the front-panel Setup Tool port whenever you are not using it to prevent foreign objects from entering the port. Do not use the Digital Temperature Controller where subject to flammable or explosive gas. Otherwise, minor injury from explosion may occasionally occur. Not doing so may occasionally result in fire. Do not allow dirt or other foreign objects to enter the Setup Tool port or ports, or between the pins on the connectors on the Setup Tool cable. Minor electric shock or fire may occasionally occur. Do not use any cables that are damaged. Never disassemble, modify, or repair the product or touch any of the internal parts. Minor electric shock, fire, or malfunction may occasionally occur. CAUTION - Risk of Fire and Electric Shock a. This product is UL recognised as Open Type Process Control Equipment. It must be mounted in an enclosure that does not allow fire to escape externally. b. More than one disconnect switch may be required to de- energize the equipment before servicing the product. c. Signal inputs are SELV, limited energy. *1 d. Caution: To reduce the risk of fire or electric shock, do not interconnect the outputs of different Class 2 circuits. *2 If the output relays are used past their life expectancy, contact fusing or burning may occasionally occur. Always consider the application conditions and use the output relays within their rated load and electrical life expectancy. The life expectancy of output relays varies considerably with the output load and switching conditions. Tighten the terminal screws to the rated torque of between 0.43 and 0.58 Nm. Loose screws may occasionally result in fire. Set the parameters of the product so that they are suitable for the system being controlled. If they are not suitable, unexpected operation may occasionally result in property damage or accidents. A malfunction in the product may occasionally make control operations impossible or prevent alarm outputs, resulting in property damage. To maintain safety in the event of malfunction of the product, take appropriate safety measures, such as installing a monitoring device on a separate line. *1. An SELV circuit is one separated from the power supply withdouble insulation or reinforced insulation, that does not exceed 30 V r.m.s. and 42.4 V peak or 60 VDC. *2. A class 2 power supply is one tested and certified by UL as having the current and voltage of the secondary output restricted to specific levels. CAUTION
Be sure to observe the following precautions to prevent malfunction or adverse affects on the performance or functionality of the product. Not doing so may occasionally result in faulty operation. 1. This product is specifically designed for indoor use only. Do not use this product in the following places:
- Places directly subject to heat radiated from heating equipment.
- Places subject to splashing liquid or oil atmosphere.
- Places subject to direct sunlight.
- Places subject to dust or corrosive gas (in particular, sulfide gas and ammonia gas).
- Places subject to intense temperature change.
- Places subject to icing and condensation.
- Places subject to vibration and large shocks. 2. Use and store the product within the rated ambient temperatureand humidity. Gang-mounting two or more Digital Temperature Controllers, or mounting Digital Temperature Controllers above each other may cause heat to build up inside the Digital Temperature Controllers, which will shorten their service life. In such a case, use forced cooling by fans or other means of air ventilation to cool down the Digital Temperature Controllers. 3. To allow heat to escape, do not block the area around the Digital Temperature Controller. Do not block the ventilation holes on the Digital Temperature Controller. 4. Be sure to wire properly with correct polarity of terminals. 5. Use the specified size of crimp terminals for wiring (M3, width of 5.8 mm or less). For open-wired connections, use stranded or solid copper wires with a gauge of AWG24 to AWG18 (equal to a crosssectional area of 0.205 to 0.823 mm 2). (The stripping length is 6 to 8 mm.) Up to two wires of the same size and type or two crimp terminals can be connected to one terminal. Do not connect more than two wires or more than two crimp terminals to the same terminal. 6. Do not wire the terminals that are not used. 7. Use a commercial power supply for the power supply voltage input to a Digital Temperature Controller with AC input specifications. Do not use the output from an inverter as the power supply. Depending on the output characteristics of the inverter, temperature increases in the Digital Temperature Controller may cause smoke or fire damage even if the inverter has a specified output frequency of 50/60 Hz. 8. To avoid inductive noise, keep the wiring for the product’s terminal block away from power cables carry high voltages or large currents. Also, do not wire power lines together with or parallel to product wiring. Using shielded cables and using separate conduits or ducts is recommended. Attach a surge suppressor or noise filter to peripheral devices that generate noise (in particular, motors, transformers, solenoids, magnetic coils, or other equipment that have an inductance component). When a noise filter is used at the power supply, first check the voltage or current, and attach the noise filter as close as possible to the product. Allow as much space as possible between the product and devices that generate powerful high frequencies (high-frequency welders, high-frequency sewing machines, etc.) or surge. 9. Use this product within the rated load and power supply. 10.Make sure that the rated voltage is attained within two seconds of turning ON the power using a switch or relay contact. If the voltage is applied gradually, the power may not be reset or output malfunctions may occur. 11.Make sure that the Digital Temperature Controller has 30 minutes or more to warm up after turning ON the power before starting actual control operations to ensure the correct temperature display. 12.When executing self-tuning, turn ON power to the load (e.g., heater) at the same time as or before supplying power to the product. If power is turned ON to the product before turning ON power to the load, self-tuning will not be performed properly and optimum control will not be achieved. 13.A switch or circuit breaker must be provided close to the product. The switch or circuit breaker must be within easy reach of the operator, and must be marked as a disconnecting means for this unit. 14.Use a soft and dry cloth to clean the product carefully. Do not use organic solvent, such as paint thinner, benzine or alcohol to clean the product. 15.Design the system (e.g., control panel) considering the 2 seconds of delay that the product's output to be set after power ON. 16.The output may turn OFF when you move to the initial setting level. Take this into consideration when performing control operations. 17.The number of non-volatile memory write operations is limited. Therefore, use RAM write mode when frequently overwriting data during communications or other operations. 18.Use suitable tools when taking the Digital Temperature Temperature Controller apart for disposal. Sharp parts inside the Digital Temperature Controller may cause injury. 19.Do not touch the external power supply terminals or other metal parts on the Digital Temperature Controller. 20.Do not exceed the communications distance that is given in the specifications. Use the specified communications cable. Refer to the E5CC/E5EC Digital Controllers User’s Manual (Cat. No. H174) for information on the communications distances and cables. 21.Do not bend the communications cables past their natural bending radius. Do not pull on the communication s cables. 22.Connectors may be damaged if they are inserted with excessive force. When connecting a connector, always may sure that it is oriented correctly. Do not force the connector if it does not connect smoothly. 23.Do not exceed the communications distance that is given in the specifications. Use the specified communications cable. Refer to the E5CC/E5EC Digital Controllers User’s Manual (Cat. No. H174) for information on the communications distances and cables. 24.Do not bend the communications cables past their natural bending radius. Do not pull on the communications cables. Precautions for Safe Use
The E5CC-800 and E5EC-800 comply with Lloyd's standards. When applying the standards, the following installation and wiring requirements must be met in the application. Application Conditions
- Installation Location The E5CC-800 and E5EC-800 comply with installation category ENV1 and ENV2 of Lloyd's standards. Therefore, they must be installed in a location equipped with air conditioning. They must therefore be installed in a location equipped with air conditioning. They cannot be used on the bridge or decks, or in a location subject to strong vibration.
- Service Life 1. Use the product within the following temperature and humidity ranges: Temperature: -10 to 55°C (with no icing or condensation) Humidity: 25 % to 85% If the product is installed inside a control board, the ambient temperature must be kept to under 55°C, including the temperature around the product. 2. The service life of electronic devices like Digital Temperature Controllers is determined not only by the number of times the relay is switched but also by the service life of internal electronic components. Component service life is affected by the ambient temperature: the higher the temperature, the shorter the service life and, the lower the temperature, the longer the service life. Therefore, the service life can be extended by lowering the temperature of the Digital Temperature Controller. 3. When two or more Digital Temperature Controllers are mounted horizontally close to each other or vertically next to one another, the internal temperature will increase due to heat radiated by the Digital Temperature Controllers and the service life will decrease. In such a case, use forced cooling by fans or other means of air ventilation to cool down the Digital Temperature Controllers. When providing forced cooling, however, be careful not to cool down the terminals sections alone to avoid measurement errors.
- Measurement Accuracy 1. When extending or connecting the thermocouple lead wire, be sure to use compensating wires that match the thermocouple types. 2. When extending or connecting the lead wire of the platinum resistance thermometer, be sure to use wires that have low resistance and keep the resistance of the three lead wires the same. 3. Mount the product so that it is horizontally level. 4. If the measurement accuracy is low, check to see if input shift has been set correctly.
- Waterproofing The degree of protection is as shown below. Sections without any specification on their degree of protection or those with IP@0 are not waterproof. Front panel: IP66, Rear case: IP20, Terminal section: IP00
- Operating Precautions 1. It takes approximately two seconds for the outputs to turn ON from after the power supply is turned ON. Due consideration must be given to this time when incorporating Digital Temperature Controllers in a sequence circuit. 2. Make sure that the Digital Temperature Controller has 30 minutes or more to warm up after turning ON the power before starting actual control operations to ensure the correct temperature display. 3. When using self-tuning, turn ON power for the load (e.g., heater) at the same time as or before supplying power to the Temperature Controller. If power is turned ON for the Temperature Controller before turning ON power for the load, self-tuning will not be performed properly and optimum control will not be achieved. 4. When starting operation after the Digital Temperature Controller has warmed up, turn OFF the power and then turn it ON again at the same time as turning ON power for the load. (Instead of turning the Digital Temperature Controller OFF and ON again, switching from STOP mode to RUN mode can also be used.) 5. Avoid using the Controller in places near a radio, television set, or wireless installing. These devices can cause radio disturbances which adversely affect the performance of the Controller.
- Mounting Mounting to a Panel E5CC There are two models of Terminal Covers that you can use with the E5CC. 1. For waterproof mounting, waterproof packing must be installed on the Controller. Waterproofing is not possible when group mounting several Controllers. Waterproof packing is not necessary when there is no need for the waterproofing function. 2. Insert the E5CC into the mounting hole in the panel. 3. Push the adapter from the terminals up to the panel, and temporarily fasten the E5CC. 4. Tighten the two fastening screws on the adapter. Alternately tighten the two screws little by little to maintain a balance. Tighten the screws to a torque of 0.29 to 0.39 Nm. E5EC 1. For waterproof mounting, waterproof packing must be installed on the Controller. Waterproofing is not possible when group mounting several Controllers. Waterproof packing is not necessary when there is no need for the waterproofing function. 2. Insert the E5EC into the mounting hole in the panel. 3. Push the adapter from the terminals up to the panel, and temporarily fasten the E5EC. 4. Tighten the two fastening screws on the adapter. Alternately tighten the two screws little by little to maintain a balance. Tighten the screws to a torque of 0.29 to 0.39 Nm. Shipping Standards Precautions for Correct Use Panel Water Proof Packing Terminal Cover (E53-COV17) (Sold separately) Adapter Terminal Cover (E53-COV23) Adapter AdapterPanel Terminal Cover (E53-COV24) Terminal Cover (E53-COV24)
Mounting the Terminal Cover E5CC Slightly bend the E53-COV23 Terminal Cover to attach it to the terminal block as shown in the following diagram. The Terminal Cover cannot be attached in the opposite direction. E53-COV17 Terminal Cover can be also attached. Make sure that the "UP" mark is facing up, and then attach the E53- COV17 Terminal Cover to the holes on the top and bottom of the Digital Temperature Controller.E5EC Slightly bend the E53-COV24 Terminal Cover to attach it to the terminal block as shown in the following diagram. The Terminal Cover cannot be attached in the opposite direction.
- Precautions when Wiring
- Separate input leads and power lines in order to prevent external noise.
- Use a shielded, AWG24 to AWG18 (cross-sectional area of 0.205 to 0.8231 mm2) twisted-pair cable.
- Use crimp terminals when wiring the terminals.
- Use the suitable wiring material and crimp tools for crimp terminals.
- Tighten the terminal screws to a torque of 0.43 to 0.58 Nm.
- Use the following types of crimp terminals for M3 screws. Adapter Terminal Cover (E53-COV17) (Sold separately) E53-COV17 E53-COV23 Enlarged illustration of Terminal Section Enlarged illustration of Slightly bend the E53-COV24 Terminal Cover in the direction shown by the arrows to attach it to the terminal block. 5.8 mm max. 5.8 mm max.
- Period of Guarantee The guarantee period of the Unit is three years starting from the date the Unit is shipped from the factory. Scope of Guarantee The Unit is guaranteed under the following operating conditions. 1. Average Operating Temperature (see note): −10°C to 50°C 2. Mounting Method: Standard mounting Note: Average Operating Temperature Refer to the process temperature of the Unit mounted to a control panel and connected to peripheral devices on condition that the Unit is in stable operation, sensor input type K is selected for the Unit, the positive and negative thermocouple input terminals of the Unit are short-circuited, and the ambient temperature is stable. Should the Unit malfunction during the guarantee period, OMRON shall repair the Unit or replace any parts of the Unit at the expense of OMRON. Top Bottom
Terms and Conditions of Sale 1. Offer; Acceptance . These terms and conditions (these "Terms ") are deemed part of all quotes, agreements, purchase orders, acknowledgments, price lists, catalogs, manuals, brochures and other documents, whether electronic or in writing, relating to the sale of products or services (collectively, the "Products by Omron Electronics LLC and its subsidiary companies (“Omron ”). Omron objects to any terms or conditions proposed in Buyer’s purchase order or other documents which are inconsistent with, or in addition to, these Terms. 2. Prices; Payment Terms. All prices stated are current, subject to change with- out notice by Omron. Omron reserves the right to increase or decrease prices on any unshipped portions of outstanding orders. Payments for Products are due net 30 days unless otherwise stated in the invoice. 3. Discounts. Cash discounts, if any, will apply only on the net amount of invoices sent to Buyer after deducting transportation charges, taxes and duties, and will be allowed only if (i) the invoice is paid according to Omron’s payment terms and (ii) Buyer has no past due amounts. 4. Interest. Omron, at its option, may charge Buyer 1-1/2% interest per month or the maximum legal rate, whichever is less, on any balance not paid within the stated terms. 5. Orders . Omron will accept no order less than $200 net billing. 6. Governmental Approvals. Buyer shall be responsible for, and shall bear all costs involved in, obtaining any government approvals required for the impor- tation or sale of the Products. 7. Taxes . All taxes, duties and other governmental charges (other than general real property and income taxes), including any interest or penalties thereon, imposed directly or indirectly on Omron or required to be collected directly or indirectly by Omron for the manufacture, production, sale, delivery, importa- tion, consumption or use of the Products sold hereunder (including customs duties and sales, excise, use, turnover and license taxes) shall be charged to and remitted by Buyer to Omron. 8. Financial. If the financial position of Buyer at any time becomes unsatisfactory to Omron, Omron reserves the right to stop shipments or require satisfactory security or payment in advance. If Buyer fails to make payment or otherwise comply with these Terms or any related agreement, Omron may (without liabil- ity and in addition to other remedies) cancel any unshipped portion of Prod- ucts sold hereunder and stop any Products in transit until Buyer pays all amounts, including amounts payable hereunder, whether or not then due, which are owing to it by Buyer. Buyer shall in any event remain liable for all unpaid accounts. 9. Cancellation; Etc. Orders are not subject to rescheduling or cancellation unless Buyer indemnifies Omron against all related costs or expenses. 10. Force Majeure . Omron shall not be liable for any delay or failure in delivery resulting from causes beyond its control, including earthquakes, fires, floods, strikes or other labor disputes, shortage of labor or materials, accidents to machinery, acts of sabotage, riots, delay in or lack of transportation or the requirements of any government authority. 11. Shipping; Delivery. Unless otherwise expressly agreed in writing by Omron: a. Shipments shall be by a carrier selected by Omron; Omron will not drop ship except in “break down” situations. b. Such carrier shall act as the agent of Buyer and delivery to such carrier shall constitute delivery to Buyer; c. All sales and shipments of Products shall be FOB shipping point (unless oth- erwise stated in writing by Omron), at which point title and risk of loss shall pass from Omron to Buyer; provided that Omron shall retain a security inter- est in the Products until the full purchase price is paid; d. Delivery and shipping dates are estimates only; and e. Omron will package Products as it deems proper for protection against nor- mal handling and extra charges apply to special conditions. 12. Claims. Any claim by Buyer against Omron for shortage or damage to the Products occurring before delivery to the carrier must be presented in writing to Omron within 30 days of receipt of shipment and include the original trans- portation bill signed by the carrier noting that the carrier received the Products from Omron in the condition claimed. 13. Warranties . (a) Exclusive Warranty . Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron disclaims all other warranties, express or implied. (b) Limitations . OMRON MAKES NO WARRANTY OR REPRESENTA TION, EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABIL- ITY OR FITNESS FOR A P ARTICULAR PURPOSE OF THE PRO DUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THA T THE PRODUCTS WILL SUITABL Y MEET THE REQUIREMENTS OF THEIR INTENDED USE. Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products or oth- erwise of any intellectual property right. (c) Buyer Remedy . Omron’s sole obli- gation hereunder shall be, at Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsi- ble for warranty, repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were prop- erly handled, stored, installed and maintained and not subject to contamina- tion, abuse, misuse or inappropriate modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Compa- nies shall not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system assemblies or any other materials or substances or environ- ments. Any advice, recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above warranty. See http://www.omron247.com or contact your Omron representative for pub- lished information. 14. Limitation on Liability; Etc . OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT , INCIDENT AL, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY , NEGLIGENCE OR STRICT LIABILITY . Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted. 15. Indemnities . Buyer shall indemnify and hold harmless Omron Companies and their employees from and against all liabilities, losses, claims, costs and expenses (including attorney's fees and expenses) related to any claim, inves- tigation, litigation or proceeding (whether or not Omron is a party) which arises or is alleged to arise from Buyer's acts or omissions under these Terms or in any way with respect to the Products. Without limiting the foregoing, Buyer (at its own expense) shall indemnify and hold harmless Omron and defend or set- tle any action brought against such Companies to the extent based on a claim that any Product made to Buyer specifications infringed intellectual property rights of another party. 16. Property; Confidentiality. Any intellectual property in the Products is the exclu- sive property of Omron Companies and Buyer shall not attempt to duplicate it in any way without the written permission of Omron. Notwithstanding any charges to Buyer for engineering or tooling, all engineering and tooling shall remain the exclusive property of Omron. All information and materials supplied by Omron to Buyer relating to the Products are confidential and proprietary, and Buyer shall limit distribution thereof to its trusted employees and strictly prevent disclosure to any third party. 17. Export Controls. Buyer shall comply with all applicable laws, regulations and licenses regarding (i) export of products or information; (iii) sale of products to “forbidden” or other proscribed persons; and (ii) disclosure to non-citizens of regulated technology or information. 18. Miscellaneous . (a) Waiver. No failure or delay by Omron in exercising any right and no course of dealing between Buyer and Omron shall operate as a waiver of rights by Omron. (b) Assignment . Buyer may not assign its rights hereunder without Omron's written consent. (c) Law. These Terms are governed by the law of the jurisdiction of the home office of the Omron company from which Buyer is purchasing the Products (without regard to conflict of law princi- ples). (d) Amendment . These Terms constitute the entire agreement between Buyer and Omron relating to the Products, and no provision may be changed or waived unless in writing signed by the parties. (e) Severability . If any provi- sion hereof is rendered ineffective or invalid, such provision shall not invalidate any other provision. (f) Setoff . Buyer shall have no right to set off any amounts against the amount owing in respect of this invoice. (g) Definitions . As used herein, “including” means “including without limitation”; and “Omron Compa- nies” (or similar words) mean Omron Corporation and any direct or indirect subsidiary or affiliate thereof. Certain Precautions on Specifications and Use 1. Suitability of Use . Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is not sufficient for a complete determination of the suitability of the Prod- uct in combination with the end product, machine, system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases but the following is a non-exhaustive list of applications for which particular attention must be given: (i) Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this document. (ii) Use in consumer products or any use in significant quantities. (iii) Energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equip- ment, and installations subject to separate industry or government regulations. (iv) Systems, machines and equipment that could present a risk to life or prop- erty. Please know and observe all prohibitions of use applicable to this Prod- uct. NEVER USE THE PRODUCT FOR AN APPLICA TION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON’S PRO DUCT IS PROP- ERL Y RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. 2. Programmable Products. Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof. 3. Performance Data . Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining suitabil- ity and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it to actual application require- ments. Actual performance is subject to the Omron’s Warranty and Limitations of Liability. 4. Change in Specifications . Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our prac- tice to change part numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifica- tions of the Product may be changed without any notice. When in doubt, spe- cial part numbers may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to confirm actual specifications of purchased Product. 5. Errors and Omissions. Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical or proofreading errors or omissions.
OMRON CANADA, INC. • HEAD OFFICE OMRON ELECTRONICS DE MEXICO • HEAD OFFICE México DF • 52. OMRON ELECTRONICS DE MEXICO • SALES OFFICE OMRON ELETRÔNICA DO BRASIL LTDA • HEAD OFFICE OMRON ARGENTINA • SALES OFFICE Cono Sur • 54.11.4783.5300 OMRON CHILE • SALES OFFICE Santiago • 56.9.9917.3920 OTHER OMRON LATIN AMERICA SALES 54.11.4783.5300 OMRON INDUSTRIAL AUTOMATION • THE AMERICAS HEADQUARTERS OMRON EUROpE B.V. • Wegalaan 67-69, NL -2132 JD, Hoofddorp, The Netherlands. • Tel: +31 (0) 23 568 13 00 Fax: +31 (0) 23 568 13 88 • www.industrial.omron.eu