Technical content
Features
Pre-wired Models with Oil-resistant Reinforced PUR Cables Added to the Lineup and Easy Differentiation with Orange Head Lineup includes models with Smartclick pre-wired connectors for fast connection. 2-Wire Models Oil ResistanceOil Resistance Cable FlexibilityCable FlexibilityCable Flexibility Cable Flexibility at Cable Flexibility at Low Temperatures Low Temperatures Oil Resistance (Insulation service life): twice or three times that of oil-resistant vinyl chloride Cable Flexibility: approximately twice that of cinyl chloride cables More Flexibility at −40°C Oil Resistance Cable Flexibility at Low Temperatures Differentiation from standard models: Orange Head XS5 Smartclick connectors used to enable checking connector mating Jacket: Polyester elastomer Insulation: Oil-resistant grade PUR (polyurethane) 1/8 turn Insert all the way. Click
Lineup includes models with self-diagnostic output to provide notification of failures and unstable detection conditions, such as coil burnout.
- Contributes to preventive maintenance to keep the line from stopping. Reduced wiring, fewer resources, and low power consumption contribute to environmentalism.
- Wiring work and amount of copper wire used reduced to two thirds of that required for 3-wire models.
- Current consumption drastically reduced to less than 10% (when a DC 2-wire model is compared with a DC 3-wire model). Lineup includes models with small diameter (3 dia., 4 dia., 5.4 dia., M5)
- All small-diameter models use sealed construction. Operation is stable even when the Sensor is mounted in a small space or embedded in metal.
- Bright indicators enable easily checking the installation condition. Wide range of ambient operating temperatures: −40°C to 85°C (M8 to M30 models)
- Wide range of ambient operating temperatures also for small-diameter models: −25°C to 70°C
- Suitable for low-temperature and high-temperature applications, which are troublesome for photoelectric sensors. Lineup includes models with flexible cable (4-dia. to M30 models)
- Reduced risk of disconnection in applications with moving parts. 3-Wire Models
- : Standard Models, ▲: Different frequency, @: Self-diagnosis, ■: Different frequency and self-diagnosis, ---: Not listed 2-Wire Models Power supply Shielding Size and sensing distance Polarity Operation mode Oil-resistant reinforced PUR cable Standard cable and flexible cable (cable material: oil-resistant PVC)/Connector models Page M12 pre-wired smartclick connector models Pre-wired model with 2-m cable M12 pre-wired smartclick connector models Pre-wired model with standard 2-m cable Pre-wired model with flexible 2-m cable Pre-wired model with standard 5-m cable M12 connector (IEC pin arrangement) M12 standard pre-wired connector models M8 connector M12 connector (old pin arrangement) Ordering Information Dimensions refer- ence chart DC Shield- ed Refer to page 7. Refer to Models with Self- diagnostic Output on page 8. Refer to Models with con- ventional connector pin assign- ments on page 9. Refer to page 29. M12 3 mm M18 7 mm M30 10 mm Un- shield- ed 4 mm Yes page 8. Refer to Models with Self- diagnostic Output or Models with con- ventional connector pin assign- ments on page 9. M12 8 mm M18 14 mm M30 20 mm AC Shield- ed 1.5 mm --- Refer to page 10. M12 2 mm M18 5 mm M30 10 mm Un- shield- ed 2 mm M12 5 mm M18 10 mm M30 18 mm AC/DC Shield- ed M12 2 mm --- M18 5 mm M30 10 mm
- : Standard Models, ▲: Different frequency, ---: Not listed 3-Wire Models Power supply Shielding Size and sensing distance Polarity Operation mode Oil-resistant reinforced PUR cable Standard cable and flexible cable (cable material: oil-resistant PVC)/Connector models Page M12 pre-wired smartclick connector models Pre-wired model with 2-m cable M12 pre-wired smartclick connector models Pre-wired model with standard 2-m cable Pre-wired model with flexible 2-m cable Pre-wired model with standard 5-m cable M12 connector (IEC pin arrangement) M12 standard pre- wired connector models M8 connector Ordering Information Dimensions refer- ence chart DC NPN Shield- ed 3 dia. 0.6 mm Yes Refer to page 11. Refer to page 29. 4 dia. 0.8 mm 1 mm 5.4 dia. 1 mm 1.5mm M12 2 mm M18 5 mm M30 10 mm Un- shield- ed 2 mm Refer to page 12. M12 5 mm M18 10 mm M30 18 mm DC PNP Shield- ed 3 dia. 0.6 mm Yes Refer to page 11. 4 dia. 0.8 mm 1 mm 5.4 dia. 1 mm 1.5mm M12 2 mm M18 5 mm M30 10 mm Un- shield- ed 2 mm Refer to page 12. M12 5 mm M18 10 mm M30 18 mm
E2E Guide to Selection by Purpose Environment Maintenance Reducing troubles Higher oil resistance Easy replacement Reducing stocked models Wide operating temperature range Resists the influence of surrounding metal Mutual interference prevention Miswiring measures Early discovery of problems AC/DC 2-Wire Models E2E-X@T1 Connector Models E2E-X@D@-M1(G) E2E-X@E@-M1 E2E-X@Y@-M1 Pre-wired Connector Models E2E-X@D1-M1(G)J-(T) Smartclick Pre-wired Connector Models E2E-X@D@-M1TGJ-(U) Models with Oil-resistor reinforced PUR cable E2E-X@D@-U Models with a Different Frequency (NO Models only) E2E-X@@15 DC 2-Wire Models E2E-X@D@ DC 3-Wire Models E2E-X@E@ DC 2-Wire No-polarity Models E2E-X@D1-M1J-T Diagnostic Models E2E-X@D1S −40 to 85°C AC 2-wire: M12 to M30, DC 3-wire: M8 to M30 −25 to 70° C Models not listed above. Shielded Models DC 2-Wire Models E2E-X@D@NPN/PNP output AC/DC Load short-circuit protection No polarity Mounting to moving parts Robotics Cable Models E2E-X@D1-R E2E-X@E1-RRobotics cable Note: Refer to Models Not Listed in this Catalog for Long Body Models, Transmission Couplers, and Power Couplers. Reinforced Standard Models with Oil-resistant PVC cable
Note: The purpose of this model number legend is to provide unders tanding of the meaning of specifications from the model number. Models are not available for all combinations of code numbers. Ask your OMRON representative if you require a customized model. E2E- A BCDEFG H I - J - K - L- M No. Classification Code Meaning Remarks A Appearance C Cylindrical (not threaded) X Cylindrical (threaded) B Sensing distance Number Sensing distance (Unit: mm) Example: R6: 0.6 mm 1R5: 1.5 mmR Indication of decimal point C Shielding Blank Shielded Models M Unshielded Models D Power supply and output specifications B DC 3-wire PNP open-collector output Whether D models have polarity is defined by num- ber J. C DC 3-wire NPN open-collector output D DC 2-wire polarity/no polarity E DC 3-wire NPN collector load built-in output F DC 3-wire PNP collector load built-in output T AC/DC 2-wire Y AC 2-wire E Form of output switching el- ement
1 Normally open (NO)
2 Normally closed (NC)
F Oscillation frequency type Blank Standard frequency Used to prevent mutual in- terference.5 Different frequency G Self-diagnosis Blank No 5Y e s H Connection method Blank Pre-wired M1 M12-size metal connector M3 M8-size metal connector I Connector specifications Blank Connector Models DC 3-wire and AC 2-wire, DC 2-wire with self-diagnosis output, DC 2-wire with old pin arrangement (polarity) G Connector Models DC 2-wire with IEC pin arrangement (polarity) J Pre-wired Connector Models DC 3-wire and AC 2-wire, DC 2-wire with IEC pin arrangement (polarity), DC 3-wire and AC 2-wire, DC 2-wire with self-diagno- sis output, DC 2-wire with old pin arrangement (polarity) GJ Pre-wired Connector Models DC 2-wire with IEC pin arrangement (polarity) TJ Pre-wired Smartclick Connector Models DC 2-wire with IEC pin arrangement (no polarity) TGJ Pre-wired Smartclick Connector Models DC 2-wire with IEC pin arrangement (polarity) J DC 2-wire polarity Blank Polarity T No polarity K Cable specifications Blank Standard PVC cable (oil resistant) R Flexible PVC cable (oil resistant) U Polyurethane cable (oil resistant and reinforced) L New model N New model (Applies only to DC 2-wire pre-wired and shielded models.) This is blank if the cable specification in number K is R or U. M Cable length Letter M Cable length (Unit: m) (Applicable to Pre-wired Models and Pre- wired Connector Models.) Example: 0.3M
Ordering Information
Shielded DC 2-wire Models with No Self-diagnostic Output [Refer to Dimensions on page 29.] *1. Models with different frequencies are also available. The model number is E2E-X @D15 (example: E2E-X3D15-N 2M). *2. Models with a flexible cable are also available. Add "-R" rather than "-N" to the end of the model number (example: E2E-X2D1 -R 2M). *3. The standard stock includes models with a cable length of 5 m. Specify the cable length at the end of the model number. (Exa mple: E2E-X3D1-N 5M) *4. Refer to page 24 for details. *6. The standard cable length is 300 mm. Cables with a length of 500 mm and 1 m can also be manufactured. 2-Wire Models Appear- ance Sensing distance Connection method Cable specifications Polar- ity Opera- tion mode Pin arrangement Applicable connector code *4 Model M12 Pre-wired Smart- click Connector Mod- els (0.3m) PUR (increased oil-resistant) Yes NO 1: +V, 4: 0 V H E2E-X2D1-M1TGJ-U 0.3M NC 1: +V, 2: 0 V E2E-X2D2-M1TGJ-U 0.3M PVC (oil-resistant) NO 1: +V, 4: 0 V G E2E-X2D1-M1TGJ 0.3M Pre-wired Models (2 m) PUR (increased oil-resistant) NO --- --- E2E-X2D1-U 2M NC E2E-X2D2-U 2M PVC (oil-resistant) NO E2E-X2D1-N 2M *2*3 NC E2E-X2D2-N 2M *3 M12 Connector Mod- els --- NO 1: +V, 4: 0 V A E2E-X2D1-M1G NC 1: +V, 2: 0 V D E2E-X2D2-M1G M8 Connector Models --- NO 1: +V, 4: 0 V I E2E-X2D1-M3G NC 1: +V, 2: 0 V E2E-X2D2-M3G M12 M12 Pre-wired Smart- click Connector Mod- els (0.3m) PUR (increased oil-resistant) Yes NO 1: +V, 4: 0 V H E2E-X3D1-M1TGJ-U 0.3M NC 1: +V, 2: 0 V E2E-X3D2-M1TGJ-U 0.3M PVC (oil-resistant) NO 1: +V, 4: 0 V G E2E-X3D1-M1TGJ 0.3M Pre-wired Models (2 m) PUR (increased oil-resistant) NO --- --- E2E-X3D1-U 2M NC E2E-X3D2-U 2M PVC (oil-resistant) NO E2E-X3D1-N 2M *1*2*3 NC E2E-X3D2-N 2M *3 M12 Connector Mod- els --- NO 1: +V, 4: 0 V A E2E-X3D1-M1G *1 NC 1: +V, 2: 0 V D E2E-X3D2-M1G M12 Standard Pre- wired Connector Mod- els (0.3 m) *6 PVC (oil-resistant) Yes NO 1: +V, 4: 0 V A E2E-X3D1-M1GJ 0.3M NC 1: +V, 2: 0 V D E2E-X3D2-M1GJ 0.3M No *5 NO (3, 4): (+V, 0 V) C E2E-X3D1-M1J-T 0.3M M18 M12 Pre-wired Smart- click Connector Mod- els (0.3m) PUR (increased oil-resistant) Yes NO 1: +V, 4: 0 V H E2E-X7D1-M1TGJ-U 0.3M NC 1: +V, 2: 0 V E2E-X7D2-M1TGJ-U 0.3M PVC (oil-resistant) NO 1: +V, 4: 0 V G E2E-X7D1-M1TGJ 0.3M Pre-wired Models (2 m) PUR (increased oil-resistant) NO --- --- E2E-X7D1-U 2M NC E2E-X7D2-U 2M PVC (oil-resistant) NO E2E-X7D1-N 2M *1*2*3 NC E2E-X7D2-N 2M *3 M12 Connector Mod- els --- NO 1: +V, 4: 0 V A E2E-X7D1-M1G *1 NC 1: +V, 2: 0 V D E2E-X7D2-M1G M12 Standard Pre- wired Connector Mod- els (0.3 m) *6 PVC (oil-resistant) Yes NO 1: +V, 4: 0 V A E2E-X7D1-M1GJ 0.3M NC 1: +V, 2: 0 V D E2E-X7D2-M1GJ 0.3M No *5 NO (3, 4): (+V, 0 V) C E2E-X7D1-M1J-T 0.3M NC (1, 2): (+V, 0 V) D E2E-X7D2-M1J-T 0.3M M30 M12 Pre-wired Smart- click Connector Mod- els (0.3m) PUR (increased oil-resistant) Yes NO 1: +V, 4: 0 V H E2E-X10D1-M1TGJ-U 0.3M NC 1: +V, 2: 0 V E2E-X10D2-M1TGJ-U 0.3M PVC (oil-resistant) NO 1: +V, 4: 0 V G E2E-X10D1-M1TGJ 0.3M Pre-wired Models (2 m) PUR (increased oil-resistant) NO --- --- E2E-X10D1-U 2M NC E2E-X10D2-U 2M PVC (oil-resistant) NO E2E-X10D1-N 2M *1*2*3 NC E2E-X10D2-N 2M M12 Connector Mod- els --- NO 1: +V, 4: 0 V A E2E-X10D1-M1G *1 NC 1: +V, 2: 0 V D E2E-X10D2-M1G M12 Standard Pre- wired Connector Mod- els (0.3 m) *6 PVC (oil-resistant) Yes NO 1: +V, 4: 0 V A E2E-X10D1-M1GJ 0.3M NC 1: +V, 2: 0 V D E2E-X10D2-M1GJ 0.3M No *5 NO (3, 4): (+V, 0 V) C E2E-X10D1-M1J-T 0.3M NC (1, 2): (+V, 0 V) D E2E-X10D2-M1J-T 0.3M 2 mm 3 mm 7 mm 10 mm
Unshielded DC 2-Wire Models with No Self-diagnosis Output [Refer to Dimensions on page 29.] *1. Models with different frequencies are also available. The model number is E2E-X @D15 (example: E2E-X8MD15 2M). *2. Models with a flexible cable are also available. Add -R to the end of the model number. (example: E2E-X4MD1-R 2M). *3. The standard stock includes models with a cable length of 5 m. Specify the cable length at the end of the model number. (Exa mple: E2E-X4MD1 5M) *4. Refer to page 24 for details. Shielded DC 2-Wire Models with Self-diagnosis Output [Refer to Dimensions on page 29.] *1. Models with different frequencies are also available. The model number is E2E-X @D15S (example: E2E-X3D15S 2M). *2. Refer to page 24 for details. 2-Wire Models Appear- ance Sensing distance Connection method Cable specifications Polar- ity Opera- tion mode Pin arrangement Applicable connector code *4 Model Pre-wired Models (2 m) PVC (oil-resistant) Yes NO --- --- E2E-X4MD1 2M *2*3 NC E2E-X4MD2 2M M12 Connector Models --- NO 1: +V, 4: 0 V A E2E-X4MD1 2M NC 1: +V, 2: 0 V D E2E-X4MD2-M1G M8 Connector Models --- NO 1: +V, 4: 0 V I E2E-X4MD1-M3G NC 1: +V, 2: 0 V E2E-X4MD2-M3G M12 12M Pre-wired Smart- click Connector Models (0.3m) PVC (oil-resistant) NO 1: +V, 4: 0 V G E2E-X8MD1-M1TGJ 0.3M Pre-wired Models (2 m) PVC (oil-resistant) NO --- --- E2E-X8MD1 2M *1*2*3 NC E2E-X8MD2 2M M12 Connector Models --- NO 1: +V, 4: 0 V A E2E-X8MD1-M1G *1 NC 1: +V, 2: 0 V D E2E-X8MD2-M1G M12 Standard Pre- wired Connector Mod- els (0.3 m) PVC (oil-resistant) NO 1: +V, 4: 0 V A E2E-X8MD1-M1GJ 0.3M M18 12M Pre-wired Smart- click Connector Models (0.3m) PVC (oil-resistant) NO 1: +V, 4: 0 V G E2E-X14MD1-M1TGJ 0.3M Pre-wired Models (2 m) PVC (oil-resistant) NO --- --- E2E-X14MD1 2M *1*2*3 NC E2E-X14MD2 2M M12 Connector Models --- NO 1: +V, 4: 0 V A E2E-X14MD1-M1G *1 NC 1: +V, 2: 0 V D E2E-X14MD2-M1G M12 Standard Pre- wired Connector Mod- els (0.3 m) PVC (oil-resistant) NO 1: +V, 4: 0 V A E2E-X14MD1-M1GJ 0.3M NC 1: +V, 2: 0 V D E2E-X14MD2-M1GJ 0.3M M30 12M Pre-wired Smart- click Connector Models (0.3m) PVC (oil-resistant) NO 1: +V, 4: 0 V G E2E-X20MD1-M1TGJ 0.3M Pre-wired Models (2 m) PVC (oil-resistant) NO --- --- E2E-X20MD1 2M *1*2*3 NC E2E-X20MD2 2M M12 Connector Models --- NO 1: +V, 4: 0 V A E2E-X20MD1-M1G *1 NC 1: +V, 2: 0 V D E2E-X20MD2-M1G M12 Standard Pre- wired Connector Mod- els (0.3 m) PVC (oil-resistant) NO 1: +V, 4: 0 V A E2E-X20MD1-M1GJ 0.3M 4 mm 8 mm 14 mm 20 mm Appear- ance Sensing distance Connection method Cable specifications Polar- ity Opera- tion mode Pin arrangement Applicable connector code *2 Model M12 Pre-wired Models (2 m) PVC (oil-resistant) Yes NO --- --- E2E-X3D1S 2M *1 M12 Connector Models --- 2: +V and diagnostic output 3: 0 V 4: +V and control output D E2E-X3D1S-M1 M18 Pre-wired Models (2 m) PVC (oil-resistant) --- --- E2E-X7D1S 2M *1 M12 Connector Models --- 2: +V and diagnostic output 3: 0 V 4: +V and control output D E2E-X7D1S-M1 M30 Pre-wired Models (2 m) PVC (oil-resistant) --- --- E2E-X10D1S 2M *1 M12 Connector Models --- 2: +V and diagnostic output 3: 0 V 4: +V and control output D E2E-X10D1S-M1 3 mm 7 mm 10 mm
Unshielded DC 2-Wire Models with Self-diagnosis Output [Refer to Dimensions on page 29.] *1. Models with different frequencies are also available. The model number is E2E-X @MD15S (example: E2E-X8MD15S 2M). *2. Refer to page 24 for details. Connector Pin Assignments of DC 2-Wire Models
- The connector pin assignments of each New E2E DC 2-Wire Model conform to IEC 947-5-2 Table III. (Only DC 2-Wire Models have been changed in comparison to the previous models.)
- The following models with conventional connector pin assignments are available as well. (Only NO Models can be used.) The cable at the right should also be used if the XW3A-P@45-G11 Connector Junction Box is already being used. Models with conventional connector pin assignments are available as well. Note: Refer to page 24 for details. 2-Wire Models Appear- ance Sensing distance Connection method Cable specifications Polar- ity Opera- tion mode Pin arrangement Applicable connector code *2 Model M12 Pre-wired Mod- els (2 m) PVC (oil-resistant) Yes NO --- --- E2E-X8MD1S 2M * M12 Connector Models --- 2: +V and diagnostic output 3: 0 V 4: +V and control output D E2E-X8MD1S-M1 M18 Pre-wired Mod- els (2 m) PVC (oil-resistant) --- --- E2E-X14MD1S 2M * M12 Connector Models --- 2: +V and diagnostic output 3: 0 V 4: +V and control output D E2E-X14MD1S-M1 M30 Pre-wired Mod- els (2 m) PVC (oil-resistant) --- --- E2E-X20MD1S 2M * M12 Connector Models --- 2: +V and diagnostic output 3: 0 V 4: +V and control output D E2E-X20MD1S-M1 8 mm 14 mm 20 mm Cable length Model 500 mm XS2W-D421-BY1 Internal Wiring (Proximity Sensor end) (Wired end) Appearance Model NO Applicable connector code * NC Applicable connector code * M8 E2E-X2D1-M1 C E2E-X2D2-M1 D M12 E2E-X3D1-M1 C E2E-X3D2-M1 D M18 E2E-X7D1-M1 C E2E-X7D2-M1 D M30 E2E-X10D1-M1 C E2E-X10D2-M1 D M8 E2E-X4MD1-M1 C E2E-X4MD2-M1 D M12 E2E-X8MD1-M1 C E2E-X8MD2-M1 D M18 E2E-X14MD1-M1 C E2E-X14MD2-M1 D M30 E2E-X20MD1-M1 C E2E-X20MD2-M1 D Shielded Unshielded
AC 2-Wire Models Shielded Models [Refer to Dimensions on page 29.] *1. Models with different frequencies are also available. The model number is E2E-X @Y@5 (example: E2E-X5Y15 2M). *2. The standard stock includes models with a cable length of 5 m. Specify the cable length at the end of the model number. (Exa mple: E2E-X2Y1 5M) *3. Refer to page 24 for details. Unshielded Models *1. Models with different frequencies are also available. The model number is E2E-X @MY@5 (example: E2E-X5MY15 2M). *2. The standard stock includes models with a cable length of 5 m. Specify the cable length at the end of the model number. (Exa mple: E2E-X5MY1 5M) *3. Refer to page 24 for details. AC 2-Wire Models Shielded Models [Refer to Dimensions on page 29.] (There are no unshielded models.) Note: Not compliant with CE. * The standard stock includes models with a cable length of 5 m. Specify the cable length at the end of the model number. (Examp le: E2E-X7T1 5M) 2-Wire Models Appear- ance Sensing distance Connection method Cable specifications Operation mode Pin arrangement Applicable con- nector code *3 Model M8 Pre-wired Models (2 m) PVC (oil-resistant) NO --- --- E2E-X1R5Y1 2M NC E2E-X1R5Y2 2M M12 Pre-wired Models (2 m) PVC (oil-resistant) NO --- --- E2E-X2Y1 2M *1*2 NC E2E-X2Y2 2M M12 Connector Models --- NO (3, 4): (AC, AC) E E2E-X2Y1-M1 NC (1, 2): (AC, AC) F E2E-X2Y2-M1 M18 Pre-wired Models (2 m) PVC (oil-resistant) NO --- --- E2E-X5Y1 2M *1*2 NC E2E-X5Y2 2M M12 Connector Models --- NO (3, 4): (AC, AC) E E2E-X5Y1-M1 NC (1, 2): (AC, AC) F E2E-X5Y2-M1 M30 Pre-wired Models (2 m) PVC (oil-resistant) NO --- --- E2E-X10Y1 2M *1*2 NC E2E-X10Y2 2M M12 Connector Models --- NO (3, 4): (AC, AC) E E2E-X10Y1-M1 NC (1, 2): (AC, AC) F E2E-X10Y2-M1 1.5 mm 2 mm 5 mm 10 mm Appear- ance Sensing distance Connection method Cable specifications Operation mode Pin arrangement Applicable con- nector code *3 Model M8 Pre-wired Models (2 m) PVC (oil-resistant) NO --- --- E2E-X2MY1 2M NC E2E-X2MY2 2M M12 Pre-wired Models (2 m) PVC (oil-resistant) NO --- --- E2E-X5MY1 2M *1*2 NC E2E-X5MY2 2M M12 Connector Models --- NO (3, 4): (AC, AC) E E2E-X5MY1 2M NC (1, 2): (AC, AC) F E2E-X5MY2-M1 M18 Pre-wired Models (2 m) PVC (oil-resistant) NO --- --- E2E-X10MY1 2M *1 NC E2E-X10MY2 2M M12 Connector Models --- NO (3, 4): (AC, AC) E E2E-X10MY1-M1 NC (1, 2): (AC, AC) F E2E-X10MY2-M1 M30 Pre-wired Models (2 m) PVC (oil-resistant) NO --- --- E2E-X18MY1 2M *1 NC E2E-X18MY2 2M M12 Connector Models --- NO (3, 4): (AC, AC) E E2E-X18MY1-M1 NC (1, 2): (AC, AC) F E2E-X18MY2-M1 2 mm 5 mm 10 mm 18 mm Appear- ance Sensing distance Connection method Cable specifications Operation mode Pin arrangement Applicable con- nector code *3 Model M12 Pre-wired Models (2 m) PVC (oil-resis- tant) NO --- --- E2E-X3T1 2M M18 Pre-wired Models (2 m) PVC (oil-resis- tant) --- --- E2E-X7T1 2M * M30 Pre-wired Models (2 m) PVC (oil-resis- tant) --- --- E2E-X10T1 2M 3 mm 7 mm 10 mm
Shielded DC 3-Wire Models [Refer to Dimensions on page 29.] *1. The standard stock includes models with a cable length of 5 m. Specify the cable length at the end of the model number. (Exa mple: E2E-X2E1 5M) *2. Models with a flexible cable are also available. Add -R to the end of the model number. (example: E2E-X5E1-R 2M). *3. Models with different frequencies are also available. The model number is E2E-X @@@5 (example: E2E-X5E15 2M). *4. Refer to page 24 for details. 3-Wire Models Appear- ance Sensing distance Connection method Cable specifica- tions Opera- tion mode Pin arrangement Appli- cable connec- tor code Model NPN output PNP output 3 dia. Pre-wired Models (2 m) PVC (oil-re- sistant) NO --- --- E2E-CR6C1 2M E2E-CR6B1 2M NC E2E-CR6C2 2M E2E-CR6B2 2M 4 dia. Pre-wired Models (2 m) PVC (oil-re- sistant) NO --- --- E2E-CR8C1 2M *1*2 E2E-CR8B1 2M *2 NC E2E-CR8C2 2M E2E-CR8B2 2M M5 Pre-wired Models (2 m) PVC (oil-re- sistant) NO --- --- E2E-X1C1 2M *1*2 E2E-X1B1 2M *2 NC E2E-X1C2 2M E2E-X1B2 2M 5.4 dia. Pre-wired Models (2 m) PVC (oil-re- sistant) NO --- --- E2E-C1C1 2M *1*2 E2E-C1B1 2M NC E2E-C1C2 2M E2E-C1B2 2M Pre-wired Models (2 m) PVC (oil-re- sistant) NO --- --- E2E-X1R5E1 2M *1*2 E2E-X1R5F1 2M *1*2 PVC (oil-re- sistant) NC E2E-X1R5E2 2M E2E-X1R5F2 2M M12 Connector Models --- NO 1: +V, 3: 0 V, 4: Control output B E2E-X1R5E1-M1 E2E-X1R5F1-M1 NC 1: +V, 3: 0 V, 2: Control output D E2E-X1R5E2-M1 E2E-X1R5F2-M1 M8 Connector Models --- NO 1: +V, 3: 0 V, 4: Control output I E2E-X1R5E1-M3 E2E-X1R5F1-M3 NC 1: +V, 3: 0 V, 2: Control output E2E-X1R5E2-M3 E2E-X1R5F2-M3 M12 Pre-wired Models (2 m) PVC (oil-re- sistant) NO --- --- E2E-X2E1 2M *1*2*3 E2E-X2F1 2M *1*2*3 NC E2E-X2E2 2M E2E-X2F2 2M M12 Connector Models --- NO 1: +V, 3: 0 V, 4: Control output B E2E-X2E1-M1 E2E-X2F1-M1 NC 1: +V, 3: 0 V, 2: Control output D E2E-X2E2-M1 E2E-X2F2-M1 M18 Pre-wired Models (2 m) PVC (oil-re- sistant) NO --- --- E2E-X5E1 2M *1*2*3 E2E-X5F1 2M *1*2*3 NC E2E-X5E2 2M E2E-X5F2 2M M12 Connector Models --- NO 1: +V, 3: 0 V, 4: Control output B E2E-X5E1-M1 E2E-X5F1-M1 NC 1: +V, 3: 0 V, 2: Control output D E2E-X5E2-M1 E2E-X5F2-M1 M30 Pre-wired Models (2 m) PVC (oil-re- sistant) NO --- --- E2E-X10E1 2M *1*2*3 E2E-X10F1 2M *2 NC E2E-X10E2 2M E2E-X10F2 2M M12 Connector Models --- NO 1: +V, 3: 0 V, 4: Control output B E2E-X10E1-M1 E2E-X10F1-M1 NC 1: +V, 3: 0 V, 2: Control output D E2E-X10E2-M1 E2E-X10F2-M1 0.6 mm 0.8 mm 1 mm 1 mm 1.5 mm 2 mm 5 mm 10 mm
Unshielded DC 3-Wire Models [Refer to Dimensions on page 29.] *1. The standard stock includes models with a cable length of 5 m. Specify the cable length at the end of the model number. (Exa mple: E2E-X5ME1 5M) *2. Models with a flexible cable are also available. Add -R to the end of the model number. (example: E2E-X5E1-R 2M). *3. Models with different frequencies are also available. The model number is E2E-X@M@@5 (example: E2E-X5ME15 2M). *4. Refer to page 24 for details. 3-Wire Models Appear- ance Sensing distance Connection method Cable specifications Opera- tion mode Pin arrangement Appli- cable connec- tor code Model NPN output PNP output Pre-wired Models (2 m) PVC (oil-resis- tant) NO --- --- E2E-X2ME1 2M *2 E2E-X2MF1 2M *2 NC E2E-X2ME2 2M E2E-X2MF2 2M M12 Connector Models --- NO 1: +V, 3: 0 V, 4: Control output B E2E-X2ME1-M1 E2E-X2MF1-M1 NC 1: +V, 3: 0 V, 2: Control output D E2E-X2ME2-M1 E2E-X2MF2-M1 M8 Connector Models --- NO 1: +V, 3: 0 V, 4: Control output I E2E-X2ME1-M3 E2E-X2MF1-M3 NC 1: +V, 3: 0 V, 2: Control output E2E-X2ME2-M3 E2E-X2MF2-M3 M12 Pre-wired Models (2 m) PVC (oil-resis- tant) NO --- --- E2E-X5ME1 2M *1*2*3 E2E-X5MF1 2M *2 NC E2E-X5ME2 2M E2E-X5MF2 2M M12 Connector Models --- NO 1: +V, 3: 0 V, 4: Control output B E2E-X5ME1-M1 E2E-X5MF1-M1 NC 1: +V, 3: 0 V, 2: Control output D E2E-X5ME2-M1 E2E-X5MF2-M1 M18 Pre-wired Models (2 m) PVC (oil-resis- tant) NO --- --- E2E-X10ME1 2M *1*2*3 E2E-X10MF1 2M *2 NC E2E-X10ME2 2M E2E-X10MF2 2M M12 Connector Models --- NO 1: +V, 3: 0 V, 4: Control output B E2E-X10ME1-M1 E2E-X10MF1-M1 NC 1: +V, 3: 0 V, 2: Control output D E2E-X10ME2-M1 E2E-X10MF2-M1 M30 Pre-wired Models (2 m) PVC (oil-resis- tant) NO --- --- E2E-X18ME1 2M *1*2*3 E2E-X18MF1 2M *2 NC E2E-X18ME2 2M E2E-X18MF2 2M M12 Connector Models --- NO 1: +V, 3: 0 V, 4: Control output B E2E-X18ME1-M1 E2E-X18MF1-M1 NC 1: +V, 3: 0 V, 2: Control output D E2E-X18ME2-M1 E2E-X18MF2-M1 2 mm 5 mm 10 mm 18 mm
Ratings and Specifications E2E-X@D@ DC 2-Wire Models *1. Use the E2E within the range in which the setting indicator (green LED) is ON (except D2 Models). *2. The response frequency is an average value. Measurement conditions are as follows: standard sensing object, a distance of twice the standard sensing object, and a set distance of half the sensing distance. *3. The residual voltage of each M1J-T Model is 5 V. When connecting to a device, make sure that the device can withstand the residual voltage. (Refer to page 28 for details.) Size M8 M12 M18 M30 Shielded Shielded Unshielded Shielded Unshielded Shielded Unshielded Shielded Unshielded Item Model E2E-X2D@ E2E-X4MD@ E2E-X3D@ E2E-X8MD@ E2E-X7D@ E2E-X14MD@ E2E-X10D@ E2E-X20MD@ Sensing distance 2 mm ±10% 4 mm ±10% 3 mm ±10% 8 mm ±10% 7 mm ±10% 14 mm ±10% 10 mm ±10% 20 mm ±10% Differential travel 15% max. of sensing distance 10% max. of sensing distance Detectable object Ferrous metal (The sensing distance decreases with non-ferrous metal. Refer to Engineering Data on pages 18 and 19. Standard sensing object Iron, 8 × 8 × 1m m Iron, 20 × 20 × 1 mm Iron, 12 × 12 × 1 mm Iron, 30 × 30 × 1 mm Iron, 18 × 18 × 1 mm Iron, 30 × 30 × 1 mm Iron, 54 × 54 × 1 mm Response frequency Power supply voltage (operating voltage range) 12 to 24 VDC (10 to 30 VDC), ripple (p-p): 10% max. Leakage current 0.8 mA max. Control output Load current 3 to 100 mA, Diagnostic output: 50 mA for -D1(5)S Models Residual voltage 3 V max. (Load current: 100 mA, Cable length: 2 m, M1J-T Models only: 5 V max.) Indicators D1 Models: Operation indicator (red) and setting indicator (green) D2 Models: Operation indicator (red) Operation mode (with sensing object approaching) D1 Models: NO D2 Models: NC Diagnostic output delay 0.3 to 1 s Protection circuits Surge suppressor, Load short-circuit protection (for control and diagnostic output) Ambient temperature range Operating: −25 to 70°C, Storage: −40 to 85°C (with no icing or condensation) Ambient humidity range Operating/storage: 35% to 95% (with no condensation) Temperature influence ±15% max. of sensing distance at 23°C in the temperature range of −25 to 70°C ±10% max. of sensing distance at 23°C in the temperature range of −25 to 70°C Voltage influence ±1% max. of sensing distance at rated voltage in the rated voltage ±15% range Insulation resistance 50 MΩ min. (at 500 VDC) between current-carrying parts and case Dielectric strength 1000 VAC, 50/60 Hz for 1 minute between current carry parts and case Vibration resistance Destruction: 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions Shock resistance Destruction: 500 m/s2 10 times each in X, Y, and Z directions Destruction: 1,000 m/s2 10 times each in X, Y, and Z directions Degree of protection Pre-wired Models: IEC 60529 IP67, in-house standards: oil-resistant Connector Models: IEC 60529 IP67 Connection method Pre-wired Models (Standard cable length: 2 m), Connector Models, or Pre-wired Connector Models (Standard cable length: 0.3 m) Weight (pack- ed state) Pre-wired Models Approx. 60 g Approx. 70 g Approx. 130 g Approx. 175 g Pre-wired Connector Models --- Approx. 40 g Approx. 70 g Approx. 110 g Connector Models Approx. 15 g Approx. 25 g Approx. 40 g Approx. 90 gMateri- als Case Stainless steel (SUS303) Nickel-plated brass Sensing sur- face PBT Clamping nuts Nickel-plated brass Toothed washer Zinc-plated iron Accessories Instruction manual Refer to the timing charts under I/O Circuit Diagrams on page 21 for details.
E2E-X@Y@ AC 2-Wire Models *1. When supplying 24 VAC to any of the above models, make su re that the operating ambient temperature range is at least −25°C. *2. When using an M18 or M30 Connector Model at an ambient temperature between 70 and 85 °C, make sure that the Sensor has a control output (load current) of 5 to 200 mA max. Size M8 M12 M18 M30 Shielded Shielded Unshielded Shielded Unshielded Shielded Unshielded Shielded Unshielded Item Model E2E-X1R5Y@ E2E-X2MY@ E2E-X2Y@ E2E-X5MY@ E2E-X5Y@ E2E-X10MY@ E2E-X10Y@ E2E-X18MY@ Sensing distance 1.5 mm ±10% 2 mm ±10% 5 mm ±10% 10 mm ±10% 18 mm ±10% Set distance 0 to 1.2 mm 0 to 1.6 mm 0 to 4 mm 0 to 8 mm 0 to 14 mm Differential travel 10% max. of sensing distance Detectable object Ferrous metal (The sensing distance decreases with non-ferrous metal. Refer to Engineering Data on page 19.) Standard sensing object Iron, 8 × 8 × 1m m Iron, 12 × 12 × 1 mm Iron, 15 × 15 × 1 mm Iron, 18 × 18 × 1 mm Iron, 30 × 30 × 1 mm Iron, 54 × 54 × 1 mm Response frequency 25 Hz Power supply voltage (operating voltage range)*1 24 to 240 VAC (20 to 264 VAC), 50/60 Hz Leakage current 1.7 mA max. Control output Load current *2 5 to 100 mA 5 to 200 mA 5 to 300 mA Residual voltage Refer to Engineering Data on page 20. Indicators Operation indicator (red) Operation mode (with sensing object approaching) Y1 Models: NO Y2 Models: NC Protection circuits Surge suppressor Ambient temperature range *1*2 Operating/Storage: −25 to 70°C (with no icing or condensation) Operating/Storage: −40 to 85°C (with no icing or condensation) Ambient humidity range Operating/storage: 35% to 95% (with no condensation) Temperature influence ±10% max. of sensing distance at 23°C in the temperature range of −25 to 70°C ±15% max. of sensing distance at 23°C in the temperature range of −40 to 85°C, ±10% max. of sensing distance at 23°C in the temperature range of −25 to 70°C Voltage influence ±1% max. of sensing distance at rated voltage in the rated voltage ±15% range Insulation resistance 50 MΩ min. (at 500 VDC) between current-carrying parts and case Dielectric strength 4,000 VAC (M8 Models: 2,000 VAC), 50/60 Hz for 1 min between current-carrying parts and case Vibration resistance Destruction: 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions Shock resistance Destruction: 500 m/s2 10 times each in X, Y, and Z directions Destruction: 1,000 m/s2 10 times each in X, Y, and Z directions Degree of protection Pre-wired Models: IEC 60529 IP67, in-house standards: oil-resistant Connector Models: IEC 60529 IP67 Connection method Pre-wired Models (Standard cable length: 2 m) and Connector Models Weight Pre- wired Models Model Approx. 60 g Approx. 70 g Approx. 130 g Approx. 175 g Connec- tor Models Approx. 15 g Approx. 25 g Approx. 40 g Approx. 90 g Materials Case Stainless steel (SUS303) Nickel-plated brass Sensing surface PBT Clamp- ing nuts Nickel-plated brass Toothed washer Zinc-plated iron Accessories Instruction manual Refer to the timing charts under I/O Circuit Diagrams on page 23 for details.
E2E-X@T1 AC/DC 2-Wire Models *1. The response frequency is an average value. Measurement conditions are as follows: standard sensing object, a distance of twice the standard sensing object, and a set distance of half the sensing distance. *2. Power Supply Voltage Waveform: Use a sine wave for the power supply. Using a rectangular AC power supply may result in faulty reset. Size M12 M18 M30 Shielded Shielded Item Model E2E-X3T1 E2E-X7T1 E2E-X10T1 Sensing distance 3 mm ±10% 7 mm ±10% 10 mm ±10% Set distance 0 to 2.4 mm 0 to 5.6 mm 0 to 8 mm Differential travel 10% max. of sensing distance Detectable object Ferrous metal (The sensing distance decreases with non-ferrous metal. Refer to Engineering Data on page 18.) Standard sensing object Iron, 12 × 12 × 1 mm Iron, 18 × 18 × 1 mm Iron, 30 × 30 × 1 mm Response frequency *1 DC 1 kHz 0.5 kHz 0.4 kHz AC 25 Hz Power supply voltage (operating voltage range) *2 24 to 240 VDC (20 to 264 VDC) 48 to 240 VAC (40 to 264 VAC) Leakage current DC: 1 mA max. AC: 2 mA max. Control output Load current 5 to 100 mA Residual voltage DC: 6 V max. (Load current: 100 mA, Cable length: 2 m) AC: 10 V max. (Load current: 5 mA, Cable length: 2 m) Indicators Operation indicator (red), Setting indicator (green) Operation mode (with sensing object approaching) NO (Refer to the timing charts under I/O Circuit Diagrams on page 21 for details.) Protection circuits Load short-circuit protection (20 to 40 VDC only), Surge suppressor Ambient temperature range Operating: −25 to 70°C, Storage: −40 to 85°C (with no icing or condensation) Ambient humidity range Operating/Storage: 35% to 95% (with no condensation) Temperature influence ±10% max. of sensing distance at 23°C in the temperature range of −25 to 70°C Voltage influence ±1% max. of sensing distance at rated voltage in the rated voltage ±15% range Insulation resistance 50 MΩ min. (at 500 VDC) between current-carrying parts and case Dielectric strength 4,000 VAC, 50/60 Hz for 1 minute between current-carrying parts and case Vibration resistance Destruction: 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions Shock resistance Destruction: 1,000 m/s2 10 times each in X, Y, and Z directions Degree of protection IEC 60529 IP67, in-house standards: oil-resistant Connection method Pre-wired Models (Standard cable length: 2 m) Weight (packed state) Approx. 80 g Approx. 140 g Approx. 190 g Materials Case Nickel-plated brass Sensing surface PBT Clamping nuts Nickel-plated brass Toothed washer Zinc-plated iron Accessories Instruction manual
E2E-X@E@/F@ DC 3-Wire Models *1. The response frequency is an average value. Measurement conditions are as follows: standard sensing object, a distance of twice the standard sensing object, and a set distance of half the sensing distance. *2. When using an M8 Model at an ambient temperature between 70 and 85°C, supply 10 to 30 VDC to the Sensor and make sure that the Sensor has a control output of 100 mA maximum. Size M8 M12 M18 M30 Shielded Shielded Unshielded Shielded Unshielded Shielded Unshielded Shielded Unshielded Item Model E2E -X1R5E@/F@ E2E -X2ME@/F@ E2E -X2E@/F@ E2E -X5ME@/F@ E2E -X5E@/F@ E2E -X10ME@/F@ E2E-X10E@/ E2E -X18ME@/F@ Sensing distance 1.5 mm ±10% 2 mm ±10% 5 mm ±10% 10 mm ±10% 18 mm ±10% Set distance 0 to 1.2 mm 0 to 1.6 mm 0 to 4 mm 0 to 8 mm 0 to 14 mm Differential travel 10% max. of sensing distance Detectable object Ferrous metal (The sensing distance decreases with non-ferrous metal. Refer to Engineering Data on pages 18 and 19.) Standard sensing object Iron, 8 × 8 × 1m m Iron, 12 × 12 × 1 mm Iron, 15 ×15 × 1m m Iron, 18 × 18 × 1 mm Iron, 30 × 30 × 1 mm Iron, 54 × 54 × 1 mm Response frequency Power supply voltage (operating voltage range) 12 to 24 VDC (10 to 40 VDC), ripple (p-p): 10% max. Current consumption 13 mA max. Control output Load current *2 200 mA max. Residual voltage 2 V max. (Load current: 200 mA, Cable length: 2 m) Indicators Operation indicator (red) Operation mode (with sensing object approaching) E1/F1 Models: NO E2/F2 Models: NC Refer to the timing charts under I/O Circuit Diagrams on page 21 for details. Protection circuits Load short-circuit protection, Surge suppressor, Reverse polarity protection Ambient temperature range *2 Operating/Storage: −40 to 85°C (with no icing or condensation) Ambient humidity range Operating/Storage: 35% to 95% (with no condensation) Temperature influence ±15% max. of sensing distance at 23°C in the temperature range of −40 to 85°C ±10% max. of sensing distance at 23°C in the temperature range of −25 to 70°C Voltage influence ±1% max. of sensing distance at rated voltage in the rated voltage ±15% range Insulation resistance 50 MΩ min. (at 500 VDC) between current-carrying parts and case Dielectric strength 1,000 VAC, 50/60 Hz for 1 minute between current carry parts and case Vibration resistance Destruction: 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions Shock resistance Destruction: 500 m/s2 10 times each in X, Y, and Z directions Destruction: 1,000 m/s 2 10 times each in X, Y, and Z directions Degree of protection Pre-wired Models : IEC 60529 IP67, in-house standards: oil-resistant Connector Models : IEC 60529 IP67 Connection method Pre-wired Models (Standard cable length: 2 m) and Connector Models Weight Pre- wired Models Approx. 65 g Approx. 75 g Approx. 150 g Approx. 195 g Connec- tor Models Approx. 15 g Approx. 25 g Approx. 40 g Approx. 90 g Materials Case Stainless steel (SUS303) Nickel-plated brass Sensing surface PBT Clamp- ing nuts Nickel-plated brass Toothed washer Zinc-plated iron Accessories Instruction manual
E2E-C@C/B@ and E2E-X1C/B@ DC 3-Wire Models * The response frequency is an average value. Measurement conditions are as follows: standard sensing object, a distance of twice the standard sensing object, and a set distance of half the sensing distance. Size 3 dia. 4 dia. M5 5.4 dia. Shielded Shielded Item Model E2E-CR6C/B@ E2E-CR8C/B@ E2E-X1C/B@ E2E-C1C/B@ Sensing distance 0.6 mm ±15% 0.8 mm ±15% 1 mm ±15% Set distance 0 to 0.4 mm 0 to 0.5 mm 0 to 0.7 mm Differential travel 15% max. of sensing distance Detectable object Ferrous metal (The sensing distance decreases with non-ferrous metal. Refer to Engineering Data on pages 18 and 19.) Standard sensing ob- ject Iron, 3 × 3 × 1 mm Iron, 5 × 5 × 1 mm Response frequency * 2 kHz 3 kHz Power supply voltage (operating voltage range) 12 to 24 VDC (10 to 30 VDC), ripple (p-p): 10% max. Current consumption 10 mA max. 17 mA max. Control output Load current Open-collector output, 80 mA max. (30 VDC max.) Open-collector output, 100 mA max. (30 VDC max.) Residual voltage 1 V max. (Load current: 80 mA, Cable length: 2 m) 2 V max. (Load current: 100 mA, Cable length: 2 m) Indicators Operation indicator (red) Operation mode (with sensing object approaching) C1/B1 Models: NO C2 Models: NC Protection circuits Reverse polarity protection, Surge suppressor Ambient temperature range Operating/Storage: −25 to 70°C (with no icing or condensation) Ambient humidity range Operating/Storage: 35% to 95% (with no condensation) Temperature influ- ence ±15% max. of sensing distance at 23°C in the temperature range of −25 to 70°C Voltage influence ±5% max. of sensing distance at rated voltage in the rated voltage ±10% range ±2.5% max. of sensing distance at rated voltage in the rated voltage ±15% range Insulation resistance 50 MΩ min. (at 500 VDC) between current-carrying parts and case Dielectric strength 500 VAC, 50/60 Hz for 1 min between current-carrying parts and case Vibration resistance Destruction: 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions Shock resistance Destruction: 500 m/s2 10 times each in X, Y, and Z directions Degree of protection IEC 60529 IP66 IEC 60529 IP67, in-house standards: oil-resistant Connection method Pre-wired Models (Standard cable length: 2 m) Weight (packed state) Approx. 60 g Materials Case Stainless steel (SUS303) Nickel-plated brass Sensing surface Heat-resistant ABS Clamping nuts Nickel-plated brass (E2E-X1C/B@ only) Toothed washer Zinc-plated iron (E2E-X1C/B@ only) Accessories Instruction manual Refer to the timing charts under I/O Circuit Diagrams on page 22 for details.
Engineering Data (Typical) Sensing Area Shielded Models E2E-C @C@/-X@C@ Unshielded Models Influence of Sensing Object Size and Material E2E-X2D@ E2E-X3D@/-X3T1 E2E-X7D @/-X7T1 E2E-X10D@/-X10T1 E2E-X4MD @ E2E-X8MD@ X Y E2E-X10 E2E-X7 E2E-X3 E2E-X2 −20 −15 −10 −5 0 5 10 15 Distance Y (mm) Distance X (mm) E2E-X10 E2E -X1R5 E2E-X5 E2E-X2 X Y −15 −10 −5 0 5 10 Distance Y (mm) Distance X (mm) E2E-X1/E2E-C1 E2E-CR8 E2E-CR6 X Y 1.6 1.4 1.2 1.0 0.8 0.6 0.4 0.2 Distance Y (mm) Distance X (mm) X Y E2E -X20M E2E -X14M E2E -X8M E2E -X4M −30 −20 −10 0 10 20 Distance Y (mm) Distance X (mm) E2E-X18M E2E-X10M E2E-X5M E2E-X2M X Y −30 −20 −10 0 10 20 Distance Y (mm) Distance X (mm) 0 5 10 15 20 25 3.0 2.5 2.0 1.5 1.0 0.5 X d × d t = 1 mm Side length of sensing object: d (mm) Iron Stainless steel (SUS304) Brass Aluminum Copper Distance X (mm) 0 5 10 15 20 25 30 35 40 4.0 3.5 3.0 2.5 2.0 1.5 1.0 0.5 X d × d t = 1 mm Side length of sensing object: d (mm) Iron Stainless steel (SUS304) Brass Aluminum Copper Distance X (mm) 0 10 20 30 40 50 X d × d t = 1 mm Side length of sensing object: d (mm) Iron Stainless steel (SUS304) Brass Aluminum Copper Distance X (mm) 0 10 20 30 40 50 60 70 X d × d t = 1 mm Side length of sensing object: d (mm) Iron Stainless steel (SUS304) Brass Aluminum Copper Distance X (mm) 0 10 20 30 40 50 60 70 X d × d t = 1 mm Brass Copper Side length of sensing object: d (mm) Iron Stainless steel (SUS304) Aluminum Distance X (mm) 0 10 15 20 30 40 50 60 70 X d × d t = 1 mm Side length of sensing object: d (mm) Iron Stainless steel (SUS304) Brass Aluminum Copper Distance X (mm)
E2E-X14MD@ E2E-X20MD@ E2E-X1R5E@/-X1R5Y@/-X1R5F@ E2E-X2E@/-X2Y@/-X2F@ E2E-X5E@/-X5Y@/-X5F@ E2E-X10E@/-X10Y@/-X10F@ E2E-X2ME@/-X2MY@/-X2MF@ E2E-X5ME@/-X5MY@/-X5MF@ E2E-X10ME@/-X10MY@/-X10MF@ E2E-X18ME@/-X18MY@/-X18MF@ E2E-CR6@ E2E-CR8@ 0 10 20 30 40 50 60 70 X d × d t = 1 mm Side length of sensing object: d (mm) Iron Stainless steel (SUS304) Brass Aluminum Copper Distance X (mm) 0 10 20 30 40 50 60 70 80 90 100 X d × d t = 1 mm Side length of sensing object: d (mm) Iron Stainless steel (SUS304) Brass Aluminum Copper Distance X (mm) 0 5 10 15 20 25 2.5 2.0 1.5 1.0 0.5 X d × d t = 1 mm Side length of sensing object: d (mm) Iron Stainless steel (SUS304) Brass Aluminum Distance X (mm) 0 5 10 15 20 25 2.5 2.0 1.5 1.0 0.5 X d × d t = 1 mm Side length of sensing object: d (mm) Iron Stainless steel (SUS304) Brass Aluminum Distance X (mm) 0 10 20 30 40 50 X d × d t = 1 mm Side length of sensing object: d (mm) Stainless steel (SUS304) Iron Brass Aluminum Distance X (mm) 0 10 20 30 40 50 60 X d × d t = 1 mm Side length of sensing object: d (mm) Stainless steel (SUS304) Iron Brass Aluminum Distance X (mm) 0 5 10 15 20 25 30 2.5 2.0 1.5 1.0 0.5 X d × d t = 1 mm Side length of sensing object: d (mm) Iron Stainless steel (SUS304) Brass Aluminum Copper Distance X (mm) 0 10 20 30 40 50 X d × d t = 1 mm Side length of sensing object: d (mm) Stainless steel (SUS304) Iron Brass Aluminum Distance X (mm) 0 10 20 30 40 50 60 X Side length of sensing object: d (mm) Stainless steel (SUS304) Iron Brass Aluminum d × d t = 1 mm Distance X (mm) 0 20 40 60 80 100 X d × d t = 1 mm Side length of sensing object: d (mm) Stainless steel (SUS304) Iron Brass Aluminum Distance X (mm) 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 5 10 15 20 X d × d t = 1 mm Side length of sensing object: d (mm) Stainless steel (SUS304) Iron Brass Aluminum Distance X (mm) 0 5 10 15 20 25 30 1.2 1.0 0.8 0.6 0.4 0.2 X d × d t = 1 mm Side length of sensing object: d (mm) Stainless steel (SUS304) Iron Brass Aluminum Copper Distance X (mm)
E2E-X1@/-C1@ Leakage Current E2E-X@D@ E2E-X@Y@ E2E-X@T1 Residual Output Voltage E2E-X@D@ E2E-X@T1 E2E-X@Y@ at 24 VAC E2E-X @Y@ at 100 VAC E2E-X @Y@ at 200 VAC 0 5 10 15 20 25 1.2 1.0 0.8 0.6 0.4 0.2 X d × d t = 1 mm Side length of sensing object: d (mm) Stainless steel (SUS304) Iron Brass Aluminum Distance X (mm) 0 5 10 15 20 25 30 1.0 0.8 0.6 0.4 0.2 E2E-X2D1-N E2E-X7D1-N E2E-X3D1-N E2E-X10D1-N Power supply voltage (V) Leakage current (mA) V 0 50 100 150 200 250 300 1.4 1.2 1.0 0.8 0.6 0.4 0.2 ~mA Power supply voltage (V) AC power Protective resistance Proximity Sensor (OFF) Leakage current (mA) 0 50 100 150 200 250 300 1.4 1.2 1.0 0.8 0.6 0.4 0.2 Power supply voltage (V) AC power DC power Leakage current (mA) 1 3 5 10 30 50 100 E2E-X@D@ E2E-X@D1-M1J-T Load current (mA) Residual output voltage (V) 1 3 5 10 30 50 100
24 VDC
100 VAC
200 VAC
Load current (mA) Residual output voltage (V) V 01 3 5 10 30 50 100 300 500 V L
24 VAC
Load voltage VL (V) Load current (mA) Residual load voltage Residual output voltage V 120 100 01 3 5 10 30 50 100 300 500 V L OFF ON Load current (mA) Residual output voltage Residual load voltage Load voltage VL (V) V 1 3 5 10 30 50 100 300 500 OFF Load current (mA) Residual output voltage Residual load voltage Load voltage VL (V)
E2E-X@D@ DC 2-Wire Models Operation mode Model Timing Chart Output circuit Without self- diagnostic output: NO E2E-X@D1-N E2E-X@D1-M1G(J) E2E-X@D1-(M1TGJ)-U E2E-X@D1-M3G E2E-X@D1-M1J-T Without self- diagnostic output: NC E2E-X@D2-N E2E-X@D2-M1G E2E-X@D2-(M1TGJ)-U E2E-X@D2-M3G With self- diagnostic output: NO E2E-X@D1S E2E-X@D1S-M1 (%) 80 0100 Sensing object Rated sensing distance Stable sensing area Non-sensing area Unstable sensing area Set position Proximity Sensor ON OFF ON OFF ON OFF Setting indicator (green) Operation indicator (red) Control output 0 V Load Brown Blue Polarity: Yes Note: The load can be connected to either the +V or 0 V side. Prox- imity Sensor main circuit 0 V (+V) (0 V) Load Prox- imity Sensor main circuit Polarity: None Note 1. The load can be connected to either the +V or 0 V side. 2. The E2E-X @D1-M1J-T has no polarity. Therefore, terminals 3 and 4 have no polarity. 0(%) 100 Sensing object Rated sensing distance Sensing area Non-sensing area Proximity Sensor ON OFF ON OFF Operation indicator (red) Control output 0 V Load Brown Blue Note: The load can be connected to either the +V or 0 V side. Prox- imity Sensor main circuit (%) 800100 Sensing object Rated sensing distance Stable sensing area Non-sensing area Unstable sensing area Set position Proximity Sensor ON OFF ON OFF ON OFF ON OFF Setting indicator (green) Operation indicator (red) Control output Diagnostic output* * The diagnostic output is ON when there is a coil burnout or the sensing object is located in the unstable sensing area for 0.3 s or longer. Load Load Brown (4) Orange (2) (diagnostic output) Blue (3)Note: Connect both the loads to the +V side of the control output and diagnostic output. Prox- imity Sensor main circuit
Model Timing Chart Output circuit NO NPN output E2E-X@E@ E2E-X@E@-M1 E2E-X@E@-M3 NC NO PNP output E2E-X@F@ E2E-X@F@-M1 E2E-X@F@-M3 NC NO NPN open- collector output E2E-C/X@C@ NC NO PNP open- collector output E2E-C/X@B@ NC Present Not present ON OFF ON OFF High Low Operation indicator (red) Sensing object Control output (between brown and black leads) Output voltage (between black and blue leads) Tr 0 V 100 Ω Load Brown Black *Constant current output is 1.5 to 3 mA. Blue Constant current* Proximity Sensor main circuit Note: For Connector Models, the connection between pins 1, 4 and 3 uses an NO contact, and the connection between pins 1, 2 and 3 uses an NC contact. Present Not present ON OFF ON OFF High Low Operation indicator (red) Sensing object Control output (between brown and black leads) Output voltage (between black and blue leads) Present Not present ON OFF ON OFF High Low Operation indicator (red) Sensing object Control output (Between blue and black leads) Output voltage (between brown and black leads) 100 Ω Tr Load Brown Black *When a transistor is connected Blue Proximity Sensor main circuit Note: For Connector Models, the connection between pins 1, 4 and 3 uses an NO contact, and the connection between pins 1, 2 and 3 uses an NC contact. 0 V Present Not present ON OFF ON OFF High Low Operation indicator (red) Sensing object Control output (Between blue and black leads) Output voltage (between brown and black leads) Present Not present ON OFF ON OFF Operation indicator (red) Sensing object Control output 100 Ω * 0 V Load Brown Black Blue Proximity Sensor main circuit *The E2E-CR6@ does not have 100-Ω resistance. Present Not present ON OFF ON OFF Operation indicator (red) Sensing object Control output Present Not present ON OFF ON OFF Operation indicator (red) Sensing object Control output 0 V 100 Ω * Load Brown Black Blue Proximity Sensor main circuit *The E2E-CR6@ does not have 100-Ω resistance. Present Not present ON OFF ON OFF Operation indicator (red) Sensing object Control output
mode Model Timing Chart Output circuit NO E2E-X@Y@ E2E-X@Y@-M1 NC Operation mode Model Timing Chart Output circuit NO E2E-X@T1 Present Not present ON OFF Operate Reset Operation indicator (red) Sensing object Control output Load Brown 3 (or 1) Blue 4 (or 2) Proximity Sensor main circuit Note: For Connector Models, the connection between pins 3 and 4 uses an NO contact, and the connection between pins 1 and 2 uses an NC contact. Present Not present ON OFF Operate Reset Operation indicator (red) Sensing object Control output 80100 0(%) Sensing object Rated sensing distance Stable sensing area Non-sensing area Unstable sensing area Set position Proximity Sensor ON OFF ON OFF ON OFF Setting indicator (green) Operation indicator (red) Control output 24 to 240 VDC 48 to 240 VAC Load Brown Blue Proximity Sensor main circuit Power supply Note: The load can be connected to either the +V or 0 V side. There is no need to be concerned about the polarity (brown/blue) of the Proximity Sensor.
Model for Connectors and Pre-wired Connectors: A Connector is not provided with the Sensor. Be sure to order a Connector separately. [Refer to Dimensions for the XS2, XS3, and XS5.] Note: Refer to Introduction to Sensor I/O Connectors for details and for information on Cable length and Robotics Cables. *1. Images of straight and L-shaped connectors. *2. Refer to Connection Diagrams on page 25 for information on Proximity Sensor and I/O Connector connections. Applicable connector code Connector Applicable Proximity Sensor model number Connection diagram No. *2Screw Appearance *1 Cable length 2m Cable length 5m CablConnector model number CablConnector model number A M12 Straight XS2F-D421-DA0-A XS2F-D421-GA0-A E2E-X@D1-M1G(J) 1L-shape XS2F-D422-DA0-A XS2F-D422-GA0-A B Straight XS2F-D421-DC0-A XS2F-D421-GC0-A E2E-X@E1-M1 E2E-X@F1-M1 10L-shape XS2F-D422-DC0-A XS2F-D422-GC0-A C Straight XS2F-D421-DD0 XS2F-D421-GD0 E2E-X@D1-M1J-T 3 E2E-X@D1-M1 2 L-shape XS2F-D422-DD0 XS2F-D422-GD0 E2E-X@D1-M1J-T 3 E2E-X@D1-M1 2 D Straight XS2F-D421-D80-A XS2F-D421-G80-A E2E-X@D2-M1G(J) 6 E2E-X@D2-M1J-T 8 E2E-X@D2-M1 7 E2E-X@D1S-M1 5 E2E-X@E2-M1 E2E-X@F2-M1 11 L-shape XS2F-D422-D80-A XS2F-D422-G80-A E2E-X@D2-M1G(J) 6 E2E-X@D2-M1J-T 8 E2E-X@D2-M1 7 E2E-X@D1S-M1 5 E2E-X@E2-M1 E2E-X@F2-M1 11 E Straight XS2F-A421-DB0-A XS2F-A421-GB0-A E2E-X@Y1-M1 14L-shape XS2F-A422-DB0-A XS2F-A422-GB0-A F Straight XS2F-A421-D90-A XS2F-A421-G90-A E2E-X@Y2-M1 15 G Smartclick Connector, Straight XS5F-D421-D80-A XS5F-D421-G80-A E2E-X@D1-M1TGJ 16 H Smartclick Connector, Straight Oil-resistant Reinforced Cables XS5F-D421-D80-P XS5F-D421-G80-P E2E-X@D1-M1TGJ-U 17 E2E-X@D2-M1TGJ-U 18 IM 8 Straight XS3F-M421-402-A XS3F-M421-405-A E2E-X@D1-M3G 4 E2E-X@D2-M3G 9 E2E-X@E1-M3 E2E-X@F1-M3 12 E2E-X@E2-M3 E2E-X@F2-M3 13 L-shape XS3F-M422-402-A XS3F-M422-405-A E2E-X@D1-M3G 4 E2E-X@D2-M3G 9 E2E-X@E1-M3 E2E-X@F1-M3 12 E2E-X@E2-M3 E2E-X@F2-M3 13 M12 Straight M12 L-shape M8 Straight M8 L-shape
Connections for Sensor I/O Connectors * Different from Proximity Sensor wire colors. Connection diagram No. Proximity Sensor Sensor I/O Connector model number ConnectionsType Operation mode Model
1 DC 2-wire
(IEC pin wiring) NO E2E-X@D1-M1G(J) DC 2-wire (previous pin wiring) E2E-X@D1-M1
3 DC 2-wire
(no polarity) E2E-X@D1-M1J-T
4 DC 2-wire
(M8 connector) E2E-X@D1-M3G DC 2-wire (diagnostic type) E2E-X@D1S-M1
6 DC 2-wire
(IEC pin wiring) NC E2E-X@D2-M1G(J) DC 2-wire (previous pin wiring) E2E-X@D2-M1
8 DC 2-wire
(no polarity) E2E-X@D2-M1J-T
9 DC 2-wire
(M8 connector) E2E-X@D2-M3G XS2F-D42@-@A0-A 1: Straight 2: L-shape D: 2-m cable G: 5-m cable XS2FE2E Main circuit Brown (+) Blue (−) XS2F-D42@-@D0 1: Straight 2: L-shape D: 2-m cable G: 5-m cable XS2FE2E Blue (−) Brown (+) Main circuit XS2F-D42@-@D0 1: Straight 2: L-shape D: 2-m cable G: 5-m cable E2E Main circuit XS2F Blue (+) (−) Brown (−) (+) XS3F-M42@-40@-A 1: Straight 2: L-shape 2: 2-m cable 5: 5-m cable *XS3F E2E Brown (+) White (not connected) Blue (not connected) Black (−) Main circuit XS2F-D42@-@80-A 1: Straight 2: L-shape D: 2-m cable G: 5-m cable *XS2F E2E Brown (not connected) White (diagnostic output) (+) Blue (0 V) Black (control output) (+) Main circuit XS2F-D42@-@80-A 1: Straight 2: L-shape D: 2-m cable G: 5-m cable *XS2F E2E White (−) Blue (not connected) Brown (+) Black (not connected) Main circuit XS2F-D42@-@80-A 1: Straight 2: L-shape D: 2-m cable G: 5-m cable *XS2F E2E White (+) Blue (−) Brown (not connected) Black (not connected) Main circuit XS2F-D42@-@80-A 1: Straight 2: L-shape D: 2-m cable G: 5-m cable *XS2F E2E Main circuit White (−)(+) Blue (not connected) Brown (+)(−) Black (not connected) XS3F-M42@-40@-A 1: Straight 2: L-shape 2: 2-m cable 5: 5-m cable *XS3F E2E White (−) Blue (not connected) Brown (+) Black (not connected) Main circuit
- Different from Proximity Sensor wire colors. Connection diagram No. Proximity Sensor Sensor I/O Connector model number ConnectionsType Operation mode Model DC 3-wire NO E2E-X @E/F1-M1
11 NC E2E-X @E2/F2-M1
(M8 connector) NO E2E-X@E1/F1-M3
13 NC E2E-X@E2/F2-M3
NO E2E-X @Y1-M1
15 NC E2E-X @Y2-M1
(Smartclick connector) NO E2E-X@D1-M1TGJ
17 E2E-X@D1-
18 NC E2E-X@D2-
Refer to Introduction to Sensor I/O Connectors for details. XS2F-D42@-@C0-A 1: Straight 2: L-shape D: 2-m cable G: 5-m cable XS2F E2E Brown (+V) Blue (0 V) Black (output) Main circuit XS2F-D42@-@80-A 1: Straight 2: L-shape D: 2-m cable G: 5-m cable XS3F E2E Brown (+V) White (not connected) Blue (0 V) Black (output) Main XS3F-M42@-40@-A 1: Straight 2: L-shape 2: 2-m cable 5: 5-m cable XS3F E2E Brown (+V) White (not connected) Blue (0 V) Black (output) Main circuit XS3F-M42@-40@-A 1: Straight 2: L-shape 2: 2-m cable 5: 5-m cable XS3F E2E Brown (+V) White (output) Blue (0 V) Black (not connected) Main circuit XS2F-A42@-@B0-A 1: Straight 2: L-shape D: 2-m cable G: 5-m cable XS2F E2E Brown Blue Main circuit XS2F-A421-@90-A D: 2-m cable G: 5-m cable *XS2F E2E Blue (not connected) Black (not connected) Brown White Main circuit XS5F-D421-@80-A D: 2-m cable G: 5-m cable XS5F E2E Blue (not connected) Black (−) Brown (+) White (not connected) Main circuit XS5F-D421-@80-P D: 2-m cable G: 5-m cable XS5F E2E Blue (not connected) Black (−) Brown (+) White (not connected) Main circuit XS5F-D421-@80-P D: 2-m cable G: 5-m cable XS5F E2E Blue (not connected) Black (not connected) Brown (+) White (−) Main circuit
Refer to Warranty and Limitations of Liability. This product is not designed or rated for ensuring safety of persons either directly or indirectly. Do not use it for such purposes. Do not use this product under ambient conditions that exceed the ratings.
- Design Influence of Surrounding Metal When mounting the Sensor within a metal panel, ensure that the clearances given in the following table are maintained. Failure to maintain these distances may cause deterioration in the performance of the Sensor. WARNING CAUTION
- Do not short the load. Explosion or burning may result.
- Do not supply power to the Sensor with no load, otherwise Sensor may be damaged. Applicable Models E2E-CR6@ E2E-CR8@ E2E-X1@ E2E-C1@ Precautions for Correct Use l m n m D d dia. l Influence of Surrounding Metal (Unit: mm) Model Item M8 M12 M18 M30 DC 2-Wire Models E2E-X@D@ AC/DC 2-Wire Models E2E-X@T1 Shielded d 8 12 18 30 m 4 . 5 82 04 0 n 1 21 82 74 5 Unshielded l 1 21 52 23 0 d 2 44 07 09 0 D 1 21 52 23 0 m 8 20 40 70 n 2 44 07 09 0 DC 3-Wire Models E2E-X@E@ E2E-X@F@ AC 2-Wire Models E2E-X@Y@ Shielded d 8 12 18 30 m 4 . 5 82 04 0 n 1 21 82 74 5 Unshielded l 6 15 22 30 d 2 44 05 59 0 D 6 15 22 30 m 8 20 40 70 n 2 43 65 49 0 Model Item 3 dia. 4 dia. M5 5.4 dia. DC 3-Wire Models E2E-X@C/B@ E2E-C@C/B@ Shielded d 345 5 . 4 m2 2 . 4 3 n6 8 Relationship between Sizes and Models Model Model 3 dia. Shielded E2E-CR6C/B 4 dia. E2E-CR8C@ E2E-CR8B@ M5 E2E-X1C@ E2E-X1B@ 5.4 dia. E2E-C1C@ E2E-C1B@ Shielded E2E-X2D@ E2E-X1R5E@ E2E-X1R5F@ E2E-X1R5Y@ Unshielded E2E-X4MD@ E2E-X2ME@ E2E-X2MF@ E2E-X2MY@ M12 Shielded E2E-X3D@ E2E-X2E@ E2E-X2F@ E2E-X2Y@ E2E-X3T1 Unshielded E2E-X8MD@ E2E-X5ME@ E2E-X5MF@ E2E-X5MY@ M18 Shielded E2E-X7D@ E2E-X5E@ E2E-X5F@ E2E-X5Y@ E2E-X7T1 Unshielded E2E-X14MD@ E2E-X10ME@ E2E-X10MF@ E2E-X10MY@ M30 Shielded E2E-X10D@ E2E-X10E@ E2E-X10F@ E2E-X10Y@ E2E-X10T1 Unshielded E2E-X20MD@ E2E-X18ME@ E2E-X18MF@ E2E-X18MY@
Loads with Large Surge Currents (E2E-X@T@) If a load with a large surge current is connected, such as a relay, lamp, or motor, the surge current may cause the load short-circuit protection circuit to operate, resulting in operating errors.
- Mounting Tightening Force Do not tighten the nut with excessive force. A washer must be used with the nut. Note: 1. The allowable tightening strength depends on the distance from the edge of the head, as shown in the following table. (A is the distance from the edge of the head. B includes the nut on the head side. If the edge of the nut is in part A, the tightening torque for part A applies instead.) 2. The following strengths assume washers are being used. Refer to the following to mount the E2E-CR6, E2E-CR8 and E2E-C1 Unthreaded Cylindrical Models. When using a set screw, tighten it to a torque of 0.2 N·m max. (E2E-C1: 0.4 N·m max.) Connecting a DC 2-Wire Proximity Sensor to a PLC (Programmable Controller) Required Conditions Connection to a PLC is possible if the specifications of the PLC and the Proximity Sensor satisfy the following conditions. (The meanings of the symbols are given at the right.) 1. The ON voltage of the PLC and the residual voltage of the Proximity Sensor must satisfy the following. VON ≤ VCC− VR 2. The OFF current of the PLC and the leakage current of the Proximity Sensor must satisfy the following. IOFF ≥ Ileak (If the OFF current is not listed in the PLC’s input specifications, take it to be 1.3 mA.) 3. The ON current of the PLC and the control output of the Proximity Sensor must satisfy the following. IOUT (min.) ≤ ION ≤ IOUT (max.) The ON current of the PLC will vary, however, with the power supply voltage and the input impedance, as shown in the following equation. ION = (VCC − VR − VPC)/RIN Example In this example, the above conditions are checked when the PLC Unit is the C200H-ID212, the Proximity Sensor is the E2E-X7D1-N, and the power supply voltage is 24 V. 1. VON (14.4 V) ≤ VCc (20.4 V) − VR (3 V) = 17.4 V:OK 2. IOFF (1.3 mA) ≥ Ileak (0.8 mA): OK 3. ION = [VCC (20.4 V) − VR (3 V) − VPLC (4 V)]/RIN (3 kΩ) = Approx. 4.5 mA Therefore, IOUT (min.) (3 mA) ≤ ION (4.5 mA): OK Connection is thus possible. Mutual Interference (Unit: mm) Note: Values in parentheses apply to Sensors operating at different frequencies. Model Item M8 M12 M18 M30 DC 2-Wire Models E2E-X@D@ AC/DC 2-Wire Models E2E-X@T1 Shielded A 20 30 (20) 50 (30) 100 (50) B 15 20 (12) 35 (18) 70 (35) Unshielded A 80 120 (60) 200 (100) 300 (100) B 60 100 (50) 110 (60) 200 (100) DC 3-Wire Models E2E-X@E@/X@F@ AC 2-Wire Models E2E-X@Y@ Shielded A 20 30 (20) 50 (30) 100 (50) B 15 20 (12) 35 (18) 70 (35) Unshielded A 80 120 (60) 200 (100) 300 (100) B 60 100 (50) 110 (60) 200 (100) Model Item 3 dia. 4 dia. M5 5.4 dia. DC 3-Wire Models E2E-X@C/B@ E2E-C@C/B@ Shielded A2 0 B1 5 Mutual Interference When installing Sensors face-to-face or side-by-side, ensure that the minimum distances given in the following table are maintained. A B Model Part A Part B Dimension Torque Torque M5 1 N·m Shielded 9
9 N·m 12 N·m
M12 30 N·m M18 70 N·m M30 180 N·m Part B Part A Part B Part A Shielded Models Unshielded Models 8 to 21 mm 9 to 21 mm E2E-CR8, E2E-C1 E2E-CR6 Dimpled end of set screw (M3) (No screws are provided with the E2E-CR8 or E2E-C1.) VON:ON voltage of PLC (14.4 V) ION: ON current of PLC (typically 7 mA) IOFF: OFF current of PLC (1.3 mA) RIN: Input impedance of PLC (3 k Ω) VPC: Internal residual voltage of PLC (4 V) VR: Output residual voltage of Proximity Sensor (3 V) Ileak: Leakage current of Proximity Sensor (0.8 mA) IOUT Control output of Proximity Sensor (3 to 100 mA) VCC: Power supply voltage (PLC: 20.4 to 26.4 V) Values in parentheses apply to the following PLC model and Proximity Sensor model. PLC: C200H-ID212 Sensor: E2E-X7D1-N
Model Number-Dimensions Drawing Number Lookup Table Note 1. Two clamping nuts and one toothed was her are provided with M8 to M30 Models. 2. The model numbers of M8 to M30 Pre-wired Models are laser-mark ed on the milled section and cable section. This does not apply, however, to models that end in -U. Model DC 2-Wire Models DC 3-Wire Models AC 2-Wire Models AC/DC 2-Wire Models Model Shielded Model No. Model No. Model No. Model No. Pre-wired Models Shielded 3 dia. --- E2E-CR6@ 1 --- --- 4 dia. E2E-CR8 @ 2 M5 E2E-X1 @ 4 5.4 dia. E2E-C1 @ 3 M8 E2E-X2D @ 5 E2E-X1R5E @/F@ 5 E2E-X1R5Y @ 7 M12 E2E-X3D @ 9 E2E-X2E @/F@ 9 E2E-X2Y @ 11 E2E-X3T1 13 M18 E2E-X7D @ 14 E2E-X5E @/F@ 14 E2E-X5Y @ 14 E2E-X7T1 14 M30 E2E-X10D @ 16 E2E-X10E @/F@ 16 E2E-X10Y @ 16 E2E-X10T1 16 Unshielded M8 E2E-X4MD @ 6 E2E-X2ME @/F@ 6 E2E-X2MY @ 8 --- M12 E2E-X8MD @ 10 E2E-X5ME @/F@ 10 E2E-X5MY @ 12 M18 E2E-X14MD @ 15 E2E-X10ME @/F@ 15 E2E-X10MY @ 15 M30 E2E-X20MD @ 17 E2E-X18ME @/F@ 17 E2E-X18MY @ 17 Connector Models (M12) Shielded M8 E2E-X2D @-M1(G) 18 E2E-X1R5E/F @-M1 18 --- --- M12 E2E-X3D @-M1(G) 20 E2E-X2E/F @-M1 20 E2E-X2Y @-M1 22 M18 E2E-X7D @-M1(G) 24 E2E-X5E/F @-M1 24 E2E-X5Y @-M1 24 M30 E2E-X10D @-M1(G) 26 E2E-X10E/F @-M1 26 E2E-X10Y @-M1 26 Unshielded M8 E2E-X4MD @-M1(G) 19 E2E-X2ME/F @-M1 19 --- --- M12 E2E-X8MD @-M1(G) 21 E2E-X5ME/F @-M1 21 E2E-X5MY @-M1 23 M18 E2E-X14MD @-M1(G) 25 E2E-X10ME/F @-M1 25 E2E-X10MY @-M1 25 M30 E2E-X20MD @-M1(G) 27 E2E-X18ME/F @-M1 27 E2E-X18MY @-M1 27 Connector Models (M8) Shielded E2E-X2D@-M3G 28 E2E-X1R5E/F @-M3 28 --- --- Unshielded E2E-X4MD @-M3G 29 E2E-X2ME/F @-M3 29 Pre-wired Connector Models Shielded M8 E2E-X2D @-M1(T)GJ(-U) 30 --- --- --- M12 E2E-X3D @-M1(T)GJ(-U) 31 M18 E2E-X7D @-M1(T)GJ(-U) 33 M30 E2E-X10D @-M1(T)GJ(-U) 35 Unshielded M12 E2E-X8MD1-M1(T)GJ 32 --- --- ---M18 E2E-X14MD1-M1(T)GJ 34 M30 E2E-X20MD1-M1(T)GJ 36 Pre-wired Connector Models (no polarity) Shielded M12 E2E-X3D1-M1J-T 31 M30 E2E-X10D @-M1J-T 35 (Unit: mm) Tolerance class IT16 applies to dimensions in this data sheet unless otherwise specified. Pre-wired Models (Shielded) 3 dia. Operation indicator (red) ±0.1 *2.4-dia. vinyl-insulated round cable with 3 conductors (Conductor cross section: 0.08 mm2, Insulator diameter: 0.7 mm) Diagram 1 E2E-CR6B @/CR6C@ Diagram 3 E2E-C1B @/C1C@ 17.5 255.4 dia. Operation indicator (red) *2.9-dia. vinyl-insulated round cable with 3 conductors (Conductor cross section: 0.14 mm2, Insulator diameter: 0.9 mm), Standard length: 2 m Robotics Cable Models: 2.9-dia. vinyl-insulated round cable with 3 conductors (Conductor cross section: 0.15 mm 2, Insulator diameter: 1.05 mm), Standard length: 2 m The cable can be extended up to 100 m (separate metal conduit). Diagram 2 E2E-CR8B @/CR8C@ 17.5 254 dia. Operation indicator (red) *2.9-dia. vinyl-insulated round cable with 3 conductors (Conductor cross section: 0.14 mm2, Insulator diameter: 0.9 mm), Standard length: 2 m Robotics Cable Models: 2.9-dia. vinyl-insulated round cable with 3 conductors (Conductor cross section: 0.15 mm 2, Insulator diameter: 1.05 mm), Standard length: 2 m The cable can be extended up to 100 m (separate metal conduit). Mounting Hole Dimensions F Dimension 3 dia. 4 dia. 5.4 dia. +0.5 +0.5
(Shielded) F Mounting Hole Dimensions Dimension M5 M8 M12 +0.5 +0.5 10 dia. 17.5 158 M5 × 0.5 4 Operation indicator (red) Two clamping nuts Two toothed washers *2.9-dia. vinyl-insulated round cable with 3 conductors (Conductor cross section: 0.14 mm2, Insulator diameter: 0.9 mm), Standard length: 2 m Robotics Cable Models: 2.9-dia. vinyl-insulated round cable with 3 conductors (Conductor cross section: 0.15 mm 2, Insulator diameter: 1.05 mm), Standard length: 2 m The cable can be extended up to 100 m (separate metal conduit). Diagram 4 E2E-X1B @/X1C@ Pre-wired Models (Unshielded) 30 7 M8 × 1 15 dia. *1Indicators *2 Two clamping nuts Toothed washer *1. 4-dia. vinyl-insulated round cable with 2 conductors (Conductor cross section: 0.3 mm2, Insulator diameter: 1.3 mm), Standard length: 2 m 4-dia. vinyl-insulated round cable with 3 conductors (Conductor cross section: 0.3 mm2, Insulator diameter: 1.3 mm), Standard length: 2 m Robotics Cable Models: 4-dia. vinyl-insulated round cable with 2 conductors (Conductor cross section: 0.3 mm2, Insulator diameter: 1.27 mm), Standard length: 2 m 4-dia. vinyl-insulated round cable with 3 conductors (Conductor cross section: 0.3 mm2, Insulator diameter: 1.27 mm), Standard length: 2 m Models with Highly Oil-resistant Cables: 4-dia. polyurethane-insulated round cable with 2 conductors (Conductor cross section: 0.3 mm2, Insulator diameter: 1.3 mm), Standard length: 2 m The cable can be extended up to 200 m (separate metal conduit). *2. D1 Models: Operation indicator (red) and setting indicator (green), D2/E/F Models: Operation indicator (red) Diagram 5 E2E-X2D @ E2E-X1R5E@/F@ 30 7 13 63 15 dia. M8 × 1 6.1 dia. Indicators *2 Two clamping nuts Toothed washer *1. 4-dia. vinyl-insulated round cable with 2 conductors (Conductor cross section: 0.3 mm2, Insulator diameter: 1.3 mm), Standard length: 2 m 4-dia. vinyl-insulated round cable with 3 conductors (Conductor cross section: 0.3 mm2, Insulator diameter: 1.3 mm), Standard length: 2 m Robotics Cable Models: 4-dia. vinyl-insulated round cable with 2 conductors (Conductor cross section: 0.3 mm2, Insulator diameter: 1.27 mm), Standard length: 2 m 4-dia. vinyl-insulated round cable with 3 conductors (Conductor cross section: 0.3 mm2, Insulator diameter: 1.27 mm), Standard length: 2 m The cable can be extended up to 200 m (separate metal conduit). *2. D1 Models: Operation indicator (red) and setting indicator (green), D2/E/F Models: Operation indicator (red) Diagram 6 E2E-X4MD @ E2E-X2ME@/F@ Diagram 7 E2E-X1R5Y @ 15 dia. 313 740 M8 × 1 Toothed washer Two clamping nuts Operation indicator (red) 4-dia. vinyl-insulated round cable with 2 conductors (Conductor cross section: 0.3 mm2, Insulator diameter: 1.3 mm), Standard length: 2 m The cable can be extended up to 200 m (separate metal conduit). Diagram 8 E2E-X2MY @ 40 7 13 63 15 dia. M8 × 1 6.1 dia. Operation indicator (red) Two clamping nuts Toothed washer 4-dia. vinyl-insulated round cable with 2 conductors (Conductor cross section: 0.3 mm2, Insulator diameter: 1.3 mm), Standard length: 2 m The cable can be extended up to 200 m (separate metal conduit). 38 9 17 4 21 dia. M12 × 1 Indicators * 2 Two clamping nuts Toothed washer *1. 4-dia. vinyl-insulated round cable with 2 conductors (Conductor cross section: 0.3 mm2, Insulator diameter: 1.3 mm), Standard length: 2 m 4-dia. vinyl-insulated round cable with 3 conductors (Conductor cross section: 0.3 mm2, Insulator diameter: 1.3 mm), Standard length: 2 m Robotics Cable Models: 4-dia. vinyl-insulated round cable with 2 conductors (Conductor cross section: 0.3 mm2, Insulator diameter: 1.27 mm), Standard length: 2 m 4-dia. vinyl-insulated round cable with 3 conductors (Conductor cross section: 0.3 mm2, Insulator diameter: 1.27 mm), Standard length: 2 m Models with Highly Oil-resistant Cables: 4-dia. polyurethane-insulated round cable with 2 conductors (Conductor cross section: 0.3 mm2, Insulator diameter: 1.3 mm), Standard length: 2 m The cable can be extended (separate metal conduit) up to 200 m for the control output and up to 100 m for the diagnostic output. *2. D1 Models: Operation indicator (red) and setting indicator (green), D2/E/F Models: Operation indicator (red) Diagram 9 E2E-X3D @ E2E-X2E@/F@ Diagram 10 E2E-X8MD @ E2E-X5ME@/F@ 38 9 17 74 9 dia. 21 dia. M12 × 1 Indicators *2 Two clamping nuts Toothed washer *1. 4-dia. vinyl-insulated round cable with 2 conductors (Conductor cross section: 0.3 mm2, Insulator diameter: 1.3 mm), Standard length: 2 m 4-dia. vinyl-insulated round cable with 3 conductors (Conductor cross section: 0.3 mm2, Insulator diameter: 1.3 mm), Standard length: 2 m Robotics Cable Models: 4-dia. vinyl-insulated round cable with 2 conductors (Conductor cross section: 0.3 mm2, Insulator diameter: 1.27 mm), Standard length: 2 m 4-dia. vinyl-insulated round cable with 3 conductors (Conductor cross section: 0.3 mm2, Insulator diameter: 1.27 mm), Standard length: 2 m The cable can be extended (separate metal conduit) up to 200 m for the control output and up to 100 m for the diagnostic output. *2. D1 Models: Operation indicator (red) and setting indicator (green), D2/E/F Models: Operation indicator (red)
Diagram 11 E2E-X2Y @ 43 9 17 4 21 dia. M12 × 1 Operation indicator (red) Two clamping nuts Toothed washer 4-dia. vinyl-insulated round cable with 2 conductors (Conductor cross section: 0.3 mm2, Insulator diameter: 1.3 mm), Standard length: 2 m The cable can be extended up to 200 m (separate metal conduit). Diagram 12 E2E-X5MY @ 43 9 17 74 21 dia. M12 × 1 9 dia. Operation indicator (red) Two clamping nuts Toothed washer 4-dia. vinyl-insulated round cable with 2 conductors (Conductor cross section: 0.3 mm2, Insulator diameter: 1.3 mm), Standard length: 2 m The cable can be extended up to 200 m (separate metal conduit). Mounting Hole Dimensions Pre-wired Models (Shielded) F Dimension M8 M12 M18 M30 +0.5 +0.5 +0.5 60 9 21 dia. M12 × 1 Indicators *2 Two clamping nuts Toothed washer *1 4-dia. vinyl-insulated round cable with 2 conductors (Conductor cross section: 0.3 mm Insulator diameter: 1.3 mm), Standard length: 2 m The cable can be extended up to 200 m (separate metal conduit). *2 Operation indicator (red), Setting indicator (green) Diagram 13 E2E-X3T1 Pre-wired Models (Unshielded) 43 12 424 29 dia. M18 × 1 Indicators *2 Two clamping nuts Toothed washer *1. 6-dia. vinyl-insulated round cable with 2 conductors (Conductor cross section: 0.5 mm2, Insulator diameter: 1.9 mm), Standard length: 2 m 6-dia. vinyl-insulated round cable with 3 conductors (Conductor cross section: 0.5 mm2, Insulator diameter: 1.9 mm), Standard length: 2 m Robotics Cable Models: 6-dia. vinyl-insulated round cable with 2 conductors (Conductor cross section: 0.5 mm2, Insulator diameter: 1.74 mm), Standard length: 2 m 6-dia. vinyl-insulated round cable with 3 conductors (Conductor cross section: 0.5 mm2, Insulator diameter: 1.74 mm), Standard length: 2 m Models with Highly Oil-resistant Cables: 6-dia. polyurethane-insulated round cable with 2 conductors (Conductor cross section: 0.5 mm2, Insulator diameter: 1.9 mm), Standard length: 2 m The cable can be extended (separate metal conduit) up to 200 m for the control output and up to 100 m for the diagnostic output. *2. D1/T Models: Operation indicator (red), Setting indicator (green) D2/E/F/Y Models: Operation indicator (red) Diagram 14 E2E-X7D @/E2E-X5E@/F@ E2E-X5Y@/E2E-X7T1 43 12 424 29 dia. M18 × 1 14.8 dia. *1*1 *1. 6-dia. vinyl-insulated round cable with 2 conductors (Conductor cross section: 0.5 mm2, Insulator diameter: 1.9 mm), Standard length: 2 m 6-dia. vinyl-insulated round cable with 3 conductors (Conductor cross section: 0.5 mm2, Insulator diameter: 1.9 mm), Standard length: 2 m Robotics Cable Models: 6-dia. vinyl-insulated round cable with 2 conductors (Conductor cross section: 0.5 mm2, Insulator diameter: 1.74 mm), Standard length: 2 m 6-dia. vinyl-insulated round cable with 3 conductors (Conductor cross section: 0.5 mm2, Insulator diameter: 1.74 mm), Standard length: 2 m The cable can be extended (separate metal conduit) up to 200 m for the control output and up to 100 m for the diagnostic output. *2. D1/T Models: Operation indicator (red), Setting indicator (green) D2/E/F/Y Models: Operation indicator (red) Indicators *2 Two clamping nuts Toothed washer Diagram 15 E2E-X14MD @/E2E-X10ME@/F@ E2E-X10MY@
42 dia. M30 × 1.5 Indicators *2 Two clamping nuts Toothed washer *1. 6-dia. vinyl-insulated round cable with 2 conductors (Conductor cross section: 0.5 mm2, Insulator diameter: 1.9 mm), Standard length: 2 m 6-dia. vinyl-insulated round cable with 3 conductors (Conductor cross section: 0.5 mm2, Insulator diameter: 1.9 mm), Standard length: 2 m Ro botics Cable Models: 6-dia. vinyl-insulated round cable with 2 conductors (Conductor cross section: 0.5 mm2, Insulator diameter: 1.74 mm), Standard length: 2 m 6-dia. vinyl-insulated round cable with 3 conductors (Conductor cross section: 0.5 mm2, Insulator diameter: 1.74 mm), Standard length: 2 m Models with Highly Oil-resistant: 6-dia. poly urethane-insulated round cable with 2 conductors (Conductor cross section: 0.5 mm2, Insulator diameter: 1.9 mm), Standard length: 2 m The ca ble can be extended (separate metal conduit) up to 200 m for the control output and up to 100 m for the diagnostic output. *2. D1/T Models: Operation indicator (red), Setting indicator (green) D2/E/F/Y Models: Operation indicator (red) Diagram 16 E2E-X10D @/E2E-X10E@/F@ E2E-X10Y@/E2E-X10T1 48 12 1013 536 42 dia. M30 × 1.5 26.8 dia. Indicators *2 Two clamping nuts Toothed washer *1. 6-dia. vinyl-insulated round cable with 2 conductors (Conductor cross section: 0.5 mm2, Insulator diameter: 1.9 mm), Standard length: 2 m 6-dia. vinyl-insulated round cable with 3 conductors (Conductor cross section: 0.5 mm2, Insulator diameter: 1.9 mm), Standard length: 2 m Ro botics Cable Models: 6-dia. vinyl-insulated round cable with 2 conductors (Conductor cross section: 0.5 mm2, Insulator diameter: 1.74 mm), Standard length: 2 m 6-dia. vinyl-insulated round cable with 3 conductors (Conductor cross section: 0.5 mm2, Insulator diameter: 1.74 mm), Standard length: 2 m The ca ble can be extended (separate metal conduit) up to 200 m for the control output and up to 100 m for the diagnostic output. *2. D1/T Models: Operation indicator (red), Setting indicator (green) D2/E/F/Y Models: Operation indicator (red) Diagram 17 E2E-X20MD @/E2E-X18ME@/F@ E2E-X18MY@ M8 Connector Models (Shielded) M8 Connector Models (Unshielded) M8 × 1 13 3 15 dia. M8 × 1 Indicators* Toothed washer Two clamping nuts * D Models: Operation indicator (red), Setting indicator (green) D2/E/F Models: Operation indicator (red) Diagram 28 E2E-X2D @-M3G/E2E-X1R5E@-M3/X1RF@-M3 M8 × 1 13 6 3 15 dia. M8 × 1 6.1 dia. Indicators* Toothed washer Two clamping nuts * D Models: Operation indicator (red), Setting indicator (green) D2/E/F Models: Operation indicator (red) Diagram 29 E2E-X4MD @-M3G/E2E-X2ME@-M3/X2MF@-M3 M12 Connector Models (Shielded) M12 Connector Models (Unshielded) M12 × 1 13 3 15 dia. M8 × 1 Indicators* Toothed washer Two clamping nuts * D1 Models: Operation indicator (red), Setting indicator (green) D2/E/F Models: Operation indicator (red) Diagram 18 E2E-X2D @-M1(G) E2E-X1R5E@-M1/E2E-X1R5F@-M1 M12 × 1 13 6 3 6.1 dia. 15 dia. M8 × 1 Indicators* Two clamping nuts Toothed washer * D1 Models: Operation indicator (red), Setting indicator (green) D2/E/F Models: Operation indicator (red) Diagram 19 E2E-X4MD @-M1(G) E2E-X2ME@-M1/E2E-X2MF@-M1
M12 × 1 17 4 21 dia. M12 × 1 Indicators * Toothed washer Two clamping nuts * D1 Models: Operation indicator (red), Setting indicator (green) D2/E/F Models: Operation indicator (red) Diagram 20 E2E-X3D @-M1(G) E2E-X2E@-M1/E2E-X2F@-M1 M12 × 1 17 7 4 21 dia. M12 × 1 9 dia. Indicators* Toothed washer Two clamping nuts * D1 Models: Operation indicator (red), Setting indicator (green) D2/E/F Models: Operation indicator (red) Diagram 21 E2E-X8MD @-M1(G) E2E-X5ME@-M1/E2E-X5MF@-M1 M12 × 1 17 4 21 dia. M12 × 1 Operation indicator (red) Toothed washer Two clamping nuts Diagram 22 E2E-X2Y @-M1 M12 × 1 17 7 4 21 dia. M12 × 1 9 dia. Operation indicator (red) Toothed washer Two clamping nuts Diagram 23 E2E-X5MY @-M1 M12 × 1 24 4 29 dia. M18 × 1 Indicators* Two clamping nuts Toothed washer * D1 Models: Operation indicator (red), Setting indicator (green) D2/E/Y Models: Operation indicator (red) Diagram 24 E2E-X7D @-M1(G)/E2E-X5E@-M1/X5F@-M1 E2E-X5Y@-M1 M12 × 1 24 10 4 29 dia. M18 × 1 14.8 dia. Indicators* Toothed washer Two clamping nuts * D1 Models: Operation indicator (red), Setting indicator (green) D2/E/Y Models: Operation indicator (red) Diagram 25 E2E-X14MD @-M1(G)/E2E-X10ME@-M1 X10MF@-M1 E2E-X10MY@-M1 36 5 42 dia. M30 × 1.5 M12 × 1 Indicators* Two clamping nuts Toothed washer * D1 Models: Operation indicator (red), Setting indicator (green) D2/E/Y Models: Operation indicator (red) Diagram 26 E2E-X10D @-M1(G)/E2E-X10E@-M1/X10F@-M1 E2E-X10Y@-M1 36 13 5 42 dia. M30 × 1.5 26.8 dia. M12 × 1 Indicators* Two clamping nuts Toothed washer * D1 Models: Operation indicator (red), Setting indicator (green) D2/E/Y Models: Operation indicator (red) Diagram 27 E2E-X20MD @-M1(G)/E2E-X18ME@-M1/ X18MF@-M1 E2E-X18MY@-M1 Mounting Hole Dimensions F Dimensions M8 M12 M18 M30 +0.5 +0.5 +0.5
Pre-wired Connector Models (Unshielded) Dimension M12 M18 M30 +0.5 +0.5 Pre-wired Connector Models (Shielded) Mounting Hole Dimensions F 730 M8 × 1 M12 × 1 Indicators *2 Toothed washer Two clamping nuts *1. No U suffix: 4-dia. Vinyl-insulated round cable U s uffix: 4-dia. Polyurethane insulated round cable, Standard length: 300 mm *2. D1 Models: Operation indicator (red), Setting indicator (green) D2 Models: Operation indicator (red) *3. The connectors for M1TGJ models are XS5 Smartclick connectors. 15 dia. Diagram 30 E2E-X2D @-M1TGJ-U *3 E2E-X2D1-M1TGJ Diagram 31 E2E-X3D @-M1GJ E2E-X3D1-M1J-T E2E-X3D@-M1TGJ-U *3 E2E-X3D1-M1TGJ 938 M12 × 1 M12 × 1 21 dia. Indicators *2 Toothed washer Two clamping nuts *1. No U suffix: 4-dia. Vinyl-insulated round cable U s uffix: 4-dia. Polyurethane insulated round cable, Standard length: 300 mm *2. D1 Models: Operation indicator (red), Setting indicator (green) D2 Models: Operation indicator (red) *3. The connectors for M1TGJ models are XS5 Smartclick connectors. Diagram 33 E2E-X7D @-M1GJ E2E-X7D@-M1J-T E2E-X7D@-M1TGJ-U *3 E2E-X7D1-M1TGJ 1243 M18 × 1 M12 × 1 29 dia. Indicators *2 Toothed washer Two clamping nuts *1. No U suffix: 6-dia. Vinyl-insulated round cable U s uffix: 6-dia. Polyurethane insulated round cable, Standard length: 300 mm *2. D1 Models: Operation indicator (red), Setting indicator (green) D2 Models: Operation indicator (red) *3. The connectors for M1TGJ models are XS5 Smartclick connectors. Diagram 35 E2E-X10D @-M1GJ E2E-X10D@-M1J-T E2E-X10D@-M1TGJ-U *3 E2E-X10D1-M1TGJ 1248 36 5 42 dia. M30 × 1.5 M12 × 1 Indicators *2 Toothed washer Two clamping nuts *1. No U suffix: 6-dia. Vinyl-insulated round cable U s uffix: 6-dia. Polyurethane insulated round cable, Standard length: 300 mm *2. D1 Models: Operation indicator (red), Setting indicator (green) D2 Models: Operation indicator (red) *3. The connectors for M1TGJ models are XS5 Smartclick connectors. Diagram 32 E2E-X8MD1-M1GJ E2E-X8MD1-M1TGJ 938 17 7 4 9 dia. 21 dia. M12 × 1 M12 × 1Indicators *2 Toothed washer Two clamping nuts *1. 4-dia. vinyl-insulated round cable, Standard length: 300 mm *2. Operation indicator (red), Setting indicator (green)
Dimensions for Proximity Sensors with Sensor I/O Connectors Accessories (Order Separately) Sensor I/O Connectors Refer to Introduction to Sensor I/O Connectors for details. Diagram 34 E2E-X14MD @-M1GJ E2E-X14MD1-M1TGJ 1243 10 429 dia. M18 × 1 14.8 dia. M12 × 1Indicators*2 Toothed washer Two clamping nuts *1. 6-dia. vinyl-insulated round cable, Standard length: 300 mm *2. D1 Models: Operation indicator (red), Setting indicator (green) D2 Models: Operation indicator (red) Diagram 36 E2E-X20MD1-M1GJ E2E-X20MD1-M1TGJ 1248 36 13 5 26.8 dia. 42 dia. M30 × 1.5 M12 × 1 Indicators*2 Toothed washer Two clamping nuts *1. 6-dia. vinyl-insulated round cable, Standard length: 300 mm *2. Operation indicator (red), Setting indicator (green) Straight Connectors L-shape Connectors Straight Connectors L-shape Connectors Shielded Models Unshielded Models Dimensions with the XS2F Connected (Unit: mm) * The overall length of the Sensor is different between AC and DC Models for Sensors with diameters of M12. This will change the dimension when the I/O Connector is connected. Dimensions with the XS3F Connected (Unit: mm) Dimension Sensor diameter L1 L2 M8 Approx. 75 Approx. 62 M12* DC Approx. 80 Approx. 67 AC Approx. 85 Approx. 72 M18 Approx. 85 Approx. 72 M30 Approx. 90 Approx. 77 Dimension Sensor diameter L1 L2 M8 Approx. 65 Approx. 54 Mounting Brackets Protective Covers Sputter Protective Covers Refer to Y92@ for details.
Read and Understand This Catalog Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranty and Limitations of Liability WARRANTY OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED. LIMITATIONS OF LIABILITY OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY. In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR. Application Considerations SUITABILITY FOR USE OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the products. At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product, machine, system, or other application or use. The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products: Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog. Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations. Systems, machines, and equipment that could present a risk to life or property. Please know and observe all prohibitions of use applicable to the products. NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. PROGRAMMABLE PRODUCTS OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof. Disclaimers CHANGE IN SPECIFICATIONS Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual specifications of purchased products. DIMENSIONS AND WEIGHTS Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown. PERFORMANCE DATA Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability. ERRORS AND OMISSIONS The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical, or proofreading errors, or omissions. 2012.4 In the interest of product improvement, specifications are subject to change without notice. OMRON Corporation Industrial Automation Company http://www.ia.omron.com/ (c)Copyright OMRON Corporation 2012 All Right Reserved.