03/18/2016 134932 - HPL-ED2016 V20.0 EN 1 / 5 Soft￿starter,￿3p,￿32A,￿200-480VAC,￿us=110/230VAC Part￿no. DS7-342SX032N0-N Article￿no. 134932 Catalog￿No. DS7-342SX032N0-N Delivery￿programme Description With internal bypass contacts Function Soft starters for three-phase loads Mains supply voltage (50/60 Hz) ULN V AC 200 - 480 Supply voltage Us 110 - 230 V AC Control voltage UC 110 - 230 V AC Assigned￿motor￿rating￿(Standard￿connection,￿In-Line) at 400 V, 50 Hz P kW 15 at 460 V, 60 Hz P HP 25 Rated￿operational￿current AC-53 Ie A 32 Startup class CLASS 10 (star-delta replacement) CLASS 20 (heavy starting duty 3 x Ie for 45 s) Rated operational voltage Ue 200 V 230 V 400 V 480 V Connection to SmartWire-DT no Technical￿data General Standards IEC/EN 60947-4-2 UL 508 CSA22.2-14 Approvals CE Approvals UL CSA C-Tick UkrSEPRO Climatic proofing Damp heat, constant, to IEC 60068-2-3 Damp heat, cyclic, to IEC 60068-2-10 Ambient temperature Operation ϑ °C -5 - +40 up to 60 at 2% derating per Kelvin temperature rise Storage ϑ °C -25 - +60 Altitude m 0 - 1000 m, above that 1 % derating per 100 m , up to 2000 m Mounting position Vertical Degree of protection Degree of Protection IP20 Protection against direct contact Finger- and back-of-hand proof Overvoltage category/pollution degree II/2 Shock resistance 8 g/11 ms Vibration resistance to EN 60721-3-2 2M2 Radio interference level (IEC/EN 55011) A Static heat dissipation, non-current-dependent Pvs W 1.5 Weight kg 0.45 Main￿conducting￿paths Rated operating voltage Ue V AC 200 - 480 Supply frequency fLN Hz 50/60

03/18/2016 134932 - HPL-ED2016 V20.0 EN 2 / 5 Rated operational current Ie A AC-53 Ie A 32 Assigned motor rating (Standard connection, In-Line) at 230 V, 50 Hz P kW 7.5 at 400 V, 50 Hz P kW 15 at 200 V, 60 Hz P HP 10 at 230 V, 60 Hz P HP 10 at 460 V, 60 Hz P HP 25 Overload cycle to IEC/EN 60947-4-2 AC-53a 32 A: AC-53a: 3 - 5: 75 - 10 Internal bypass contacts Short-circuit rating Type “1” coordination PKM0-32 (+ CL-PKZ0) Type „2“ coordination (additional with the fuses for coordination type „1“) 3 x 170M1366 Fuse base (number x part no.) 3 x 170H1007 Terminal￿capacities Cable lengths Solid mm2 1 x (0.75 - 16) 2 x (0.75 - 10) Flexible with ferrule mm2 1 x (0.75 - 16) 2 x (0.75 - 10) Stranded mm2 1 x 16 Solid or stranded AWG 18 - 6 Tightening torque Nm 3.2 Screwdriver (PZ: Pozidriv) mm PZ2; 1 x 6 mm Control cables Solid mm2 1 x (0.5 - 2.5) 2 x (0.5 - 1.0) Flexible with ferrule mm2 1 x (0.5 - 1.5) 2 x (0.5 - 0.75) Stranded mm2 1 x (0.5 - 1.5) 2 x (0.5 - 1.0) Solid or stranded AWG 1 x (21 - 14) 2 x (21 - 18) Tightening torque Nm 1.2 Screwdriver mm 0,8 x 5,5 1 x 6 Control￿circuit Digital inputs Control voltage AC operated V AC 110 V AC - 15 % - 230 V AC +10 % Current consumption 24 V mA External 24 V mA 1.6 Current consumption 230 V mA 4 Pick-up voltage x Us AC operated V AC 108 - 253 Drop-out voltage x Us AC operated V AC 0 - 15 Pick-up time AC operated ms 250 Drop-out time AC operated ms 350 Regulator supply Voltage Us V 110 V AC -15 % - 230 V AC +10 % Current consumption Ie mA 50 Notes External supply voltage

03/18/2016 134932 - HPL-ED2016 V20.0 EN 3 / 5 Relay outputs Number 2 (TOR, Ready) Voltage range V AC 250 AC-11 current range A 1 A, AC-11 Soft￿start￿function Ramp times Acceleration s 1 - 30 Deceleration s 0 - 30 Start voltage (= turn-off voltage) % 30 100 Start pedestal % 30 - 100 Fields of application Fields of application Soft starting of three-phase asynchronous motors 1-phase motors ● 3-phase motors Functions Fast switching (semiconductor contactor) - (minimum ramp time 1s) Soft start function Reversing starter External solution required Suppression of closing transients Suppression of DC components for motors Potential isolation between power and control sections Notes Rated impulse withstand voltage:

  • 1.2 µs/50 µs (rise time/fall time of the pulse to IEC/EN 60947‐2 or ‐3)
  • Applies for control circuit/power section/enclosure Design￿verification￿as￿per￿IEC/EN￿61439 Technical data for design verification Rated operational current for specified heat dissipation In A 32 Heat dissipation per pole, current-dependent Pvid W 0 Equipment heat dissipation, current-dependent Pvid W 1.5 Static heat dissipation, non-current-dependent Pvs W 1.5 Heat dissipation capacity Pdiss W 0 Operating ambient temperature min. °C -5 Operating ambient temperature max. °C 40 IEC/EN 61439 design verification

10.2 Strength of materials and parts

10.2.2 Corrosion resistance Meets the product standard's requirements. 10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements. 10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.

10.2.3.3 Verification of resistance of insulating materials to abnormal heat

and fire due to internal electric effects Meets the product standard's requirements. 10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements. 10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated. 10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated. 10.2.7 Inscriptions Meets the product standard's requirements. 10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated. 10.4 Clearances and creepage distances Meets the product standard's requirements. 10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated. 10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated. 10.7 Internal electrical circuits and connections Is the panel builder's responsibility. 10.8 Connections for external conductors Is the panel builder's responsibility.

10.9 Insulation properties

03/18/2016 134932 - HPL-ED2016 V20.0 EN 4 / 5 10.9.2 Power-frequency electric strength Is the panel builder's responsibility. 10.9.3 Impulse withstand voltage Is the panel builder's responsibility. 10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility. 10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. 10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be observed. 10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.13 Mechanical function The device meets the requirements, provided the information in the instruction

leaflet (IL) is observed. Technical￿data￿ETIM￿6.0 Low-voltage industrial components (EG000017) / Soft starter (EC000640) Electric engineering, automation, process control engineering / Low-voltage switch technology / Load breakout, motor breakout / Semiconductor motor controller or soft starter Rated operation current Ie at 40 °C Tu A 32 Rated operating voltage Ue V 230 - 460 Rated power three-phase motor, inline, at 230 V kW 7.5 Rated power three-phase motor, inline, at 400 V kW 15 Rated power three-phase motor, inside delta, at 230 V kW 0 Rated power three-phase motor, inside delta, at 400 V kW 0 Internal bypass Yes With display No Torque control No Rated surrounding temperature without derating °C 40 Rated control supply voltage Us at AC 50HZ V 110 - 230 Rated control supply voltage Us at AC 60HZ V 110 - 230 Rated control supply voltage Us at DC V 0 - 0 Voltage type for actuating AC Integrated motor overload protection No Approvals IEC/EN 60947-4-2; GB 14048.6; UL 508; CSA-C22.2 No 0-M91; CSA-C22.2 No 14-05 CE marking E251034 2511305 321106 No Branch circuits No 480 V IP20; UL/CSA Type 1

03/18/2016 Eaton Industries GmbH http://www.eaton.eu © 03/2016 by Eaton Industries GmbH 134932 - HPL-ED2016 V20.0 EN Dimensions Additional￿product￿information￿(links) IL03902004Z￿Instructions￿for￿DS7￿Soft￿Starter IL03902004Z Instructions for DS7 Soft Starter ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/IL03902004Z2012_07.pdf MN03901001Z￿Manual￿DS7￿soft￿starters MN03901001Z Handbuch Softstarter DS7 - Deutsch ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN03901001Z_DE.pdf MN03901001Z Manual DS7 soft starters - English ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN03901001Z_EN.pdf CA04020001Z_EN-INT Product range catalog: Efficient Engineering for starting and controlling motors. http://www.eaton.eu/ecm/groups/public/@pub/@europe/@electrical/documents/content/pct_1095238.pdf