DS495SPE ADVANCEDENERGY | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 9

Technical content

©2022 Advanced Energy Industries, Inc. ARTESYN DS495SPE

495 Watts Distributed Power System

495 W continuous

AT A GLANCEAdvanced Energy's Artesyn DS495SPE is housed in 1U high rack-mounting enclosures measuring just 3.4 x 7.7 inches (86.3 x 196.5 mm). This form factor is significantly shorter than that of similarly rated earlier-generation power supplies — freeing up valuable system space — and is achieved by use of the latest power switching technology and high density component packaging techniques. SPECIAL FEATURES  495 W output power  1U power supply  Active power factor correction  EN61000-3-2 harmonic compliance  Inrush current control  80plus Platinum efficiency  N+N redundant  Hot-pluggable  Active current sharing  Full digital control  PMBus compliant  Standard airflow  Two-year warranty COMPLIANCE  Conducted/Radiated EMI Class A Limits + 6 dB margin  EN61000-4-11 SAFETY  IEC62368  UL/cUL  Demko +CB Report  CE Mark  UKCA Mark  CCC  BSMI

2 advancedenergy.com DS495SPE ELECTRICAL SPECIFICATIONS ELECTRICAL SPECIFICATIONS Input Input range 90 to 264 VAC Frequency 47 to 63 Hz Efficiency 94.0% peak Max input current 6.6 Arms @ 90 VAC Inrush current 25 Apk Conducted EMI Class A with 6 dB margin Radiated EMI Class A with 6 dB margin Power factor >0.9 beginning at 20% load ITHD 10% Leakage current 1 mA Hold-up time 10 ms at full load Output Main DC Output Standby DC Output MIN NOM MAX MIN NOM MAX Nominal setting -0.2% 12 V 0.2% -2.5% 12 V +2.5% Total output regulation range 11.4 V - 12.6 V 11.4 V - 12.6 V Dynamic load regulation range 11.4 V - 12.6 V 11.4 V - 12.6 V Output ripple (peak to peak) - - 120 mV - - 120 mV Output current 2.0 A - 41.25 A 0.0 A - 3.0 A Current sharing Within ±5% of full load rating N/A Capacitive loading - - 38,000 μF 47 μF - 4,700 μF 1 Minimum current for transient load response testing only. Unit is designed to operate and be within output regulation range at zero load. Protections Main output MIN NOM MAX Overcurrent protection 110% - 150% Overvoltage protection 13.5 V - 15.0 V Undervoltage protection 10.0 V - 11.0 V Overtemperature protection Yes Fan fault protection Yes Standby output MIN NOM MAX Overcurrent protection 3.6 A - 4.5 A Overvoltage protection 13.5 V - 15.0 V Undervoltage protection 10.0 V - 11.0 V

1 Latch mode

2 Standby protection is auto-recovery

advancedenergy.com 3 DS495SPE

ORDERING INFORMATION

CONTROL AND STATUS SIGNALS Model Number Nominal Main Output Standby Output Airflow Direction DS495SPE-3 12 V @ 41.25 A 12 V @ 3 A Standard (forward) DS495SPE-3-001 12 V @ 41.25 A 12 V @ 3 A Reverse Output Signals ACOK Signal used to indicate the presence of AC input to the power supply. A logic level HIGH will indicate that the AC input to the power supply is within the operating range while a logic level LOW will indicate that AC has been lost. This is an open collector/drain output. MIN MAX VoL Output logic level LOW - 0.6 V VoH Output logic level HIGH 2.0 V 3.0 V ISOURCE Current that may be sourced by this pin - 4.0 mA PWR_GOOD/PWOK Signal used to indicate that main output voltage is within regulation range. The PWR_GOOD signal will be driven HIGH when the output voltage is valid and will be driven LOW when the output falls below the under-voltage threshold. This signal also gives an advance warning when there is an impending power loss due to loss of AC input or system shutdown request. More details in the Timing Section. This is an open collector/drain output. It is recommended that this pin be connected to a 100 pF decoupling capacitor and pulled down by a 10k ohm resistor. MIN MAX VoL Output logic level LOW - 0.4 V VoH Output logic level HIGH 2.0 V 3.0 V ISINK Current that may be sunk by this pin - 10.0 mA Input Signals PSON_L Active LOW signal which enables/disables the main output. Pulling this signal LOW will turn-on the main output. It is recommended that this pin is connected to a 100 pF decoupling capacitor and pulled down by a 3.0K ohm resistor. MIN MAX VIL Input logic level LOW - 0.4 V VIH Input logic level HIGH 2.06 V 3.0 V ISOURCE Current that may be sourced by this pin at low state - 1 mA PSKILL_L First break/last mate active high signal which enables/disables the main output. When driven high, the main output shall be turned-off. MIN MAX VIL Input logic level LOW - 0.4 V VIH Input logic level HIGH 2.4 V 3.0 V ISOURCE Current that may be sourced by this pin at low state - 1.0 mA

4 advancedenergy.com DS495SPE CONTROL AND STATUS SIGNALS (CONTINUED) Output Signals PS_PRESENT Signal used to indicate to the system that a power supply is inserted in the power bay. This pin is connected to the standby return in the power supply through a 220 ohm resistor. Recommended pull-up resistor to 12 VSB is 8.2k ohm with a 3.0k ohm pull-down to ground. A 100 pF decoupling capacitor is also recommended. PS_INTERRUPT_L Active low signal used by the power supply to indicate to the system that a change in power supply status has occurred. This event can be triggered by faults such as OVP , OCP , OTP , and fan fault. This signal can be cleared by a CLEAR_FAULT command. Recommended pull-up resistor to 12 VSB is 8.2k ohm with a 3.0k ohm pull-down to ground. A 100 pF decoupling capacitor is also recommended. MIN MAX VoL Output logic level LOW - 0.8 V VoH Output logic level HIGH 2.0 V 3.0 V ISOURCE Current that may be sourced by this pin - 4 mA ISINK Current that may be sunk by this pin at low state - 4 mA BUS Signals ISHARE Bus signal used by the power supply for active current sharing. All power supplies configured in the system for n+n sharing will refer to this bus voltage inorder to load share. Voltage Range The range of this signal for active sharing will be up to 8.0 V, which corresponds to the maximum output current. MIN MAX ISHARE Voltage Voltage at 100% load, stand-alone unit 7.75 V 8.25 V Voltage at 50% load, stand-alone unit 3.85 V 4.15 V Voltage at 0% load, stand-alone unit 0 V 0.35 V SCL, SDA Clock and data signals defined as per I C requirements. VL Input logic level LOW - 0.8 V VH Input logic level HIGH 2.0 V 3.0 V Note: All signal noise levels are below 400 mVpk-pk from 0 to 100 MHz. I C Addressing Table: Not applicable. This power supply has a fixed I C address. In order to support multiple addresses, the system will have to utilize a switcher or an I C expander.

advancedenergy.com 5 DS495SPE ELECTRICAL SPECIFICATIONS LED Indicators A single bi-color LED is used to indicate the power supply status. Conditions Status LED No AC input, with external 12 V available Blinking GREEN (2 sec on, 1 sec off) Standby mode Blinking GREEN (2 sec on, 1 sec off) Main output ON Solid GREEN Power supply failure (OCP , OVP , OTP , FAN FAULT) Blinking AMBER (1 sec on, 1 sec off) Standby fault OFF Firmware Reporting And Monitoring Accuracy Range Output loading 5 to 20% 20 to 50% 50 to 100% Input voltage ±5% ±5% ±5% Input current ±0.55 A fixed error ±5% ±5% Input power 6.25 W 5% 5% Output voltage ±2% ±2% ±2% Output current ±0.7 A error ±3% ±3% EIN ±15% from 10% to 20% load ±5% ±5% Temperature ±5°C on the operating range Fan speed Actual RPM ±250 RPM Timing Specifications Description Min Max Unit Tsb_On Delay from AC being applied to standby output being within regulation - 1700 ms TVout_Rise Rise time of output voltage going from 10% to 90% of the nominal regulation 2 20 ms Tsb_Vout Delay from standby output to main output voltage being within regulation - 300 ms TAC_On_Delay Delay from AC being applied to main output being within regulation - 2000 ms TPWOK_On Delay from output voltages within regulation limits to PWOK asserted 100 500 ms TACOK_PWOK_Delay Delay from deassertion of ACOK, due loss of input, to deassertion of PWOK 4 - ms TPWOK_Hold-up Delay from loss of AC to deassertion of PWOK 10 - ms TVout_Hold-up Delay from loss of AC to main output being within regulation 11 - ms TVout_sb_dwell Delay from main output going <1 V to stnadby voltage falling out of regulation 5 - ms TACOK_off_dwell Duration time of ACOK deassertion when the PSU has sensed a loss of input 75 120 ms Tsb_Hold-up Delay from loss of AC to standby output being within regulation *Tested with standby at 1 A load 150 - ms TPWOK_Off Delay from deassertion of PWOK to output falling out of regulation 1 - ms TPSON_On_Delay Delay from PSON assertion to output being within regulation - 350 ms

6 advancedenergy.com DS495SPE TIMING DIAGRAM ENVIRONMENTAL SPECIFICATIONS Operating temperature 0°C to 55°C at 100% load; DS495SPE-3 can operate up to 65°C at 300 W without damage DS495SPE-3-001 can operate up to 60°C at 300 W without damage Operating altitude Up to 16,400 feet, with ambient temperature derated to 45°C at 10,000 feet Operating relative humidity 10% to 95% non-condensing Non-operating temperature -40°C to +70°C Non-operating relative humidity 10% to 95% non-condensing Non-operating altitude Up to 50,000 feet Vibration and shock Standard operating/non-operating random shock and vibration ROHS compliance Yes MTBF > 900 khours at 55°C, 80% load Operating life > 5 years at 55°C at 80% load

advancedenergy.com 7 DS495SPE MECHANICAL OUTLINE A B B A 8.8±0.2 196.5±0.5 9.31± 0.38 86.3± 0.5 17.8 14.8±0.3 191.4± 0.5 2.8±0.1 4±0.2 9.5 38.5± 0.5 14± 0.3 49.5 40.1 +0.3/-0.1 DS495SPE-3 (FORWARD FLOW) DS495SPE-3-001 (REVERSE FLOW) DS495SPE-3 (FORWARD) 1. RED HANDLE 2. NO FAN GRILL DS495SPE-3-001 (REVERSE) 1. BLUE HANDLE 2. WITH FAN GRILL 3D VIEW LBLD-PRODUCT EMI CLIP LATCH BUTTON (BLACK) HANDLE (SEE TABLE 1)

8 advancedenergy.com DS495SPE CONNECTOR DEFINITIONS Output Connector Part Number Card-edge Mating Connector Part Number FCI 10107844-002LF or equivalent P21-28P29-P36 P19/20 ... S24 S13 Power Supply Output Card Edge (Bottom Side) P1-P8/uni00A0 P9-P18 .. S1 S12 Power Supply Output Card Edge (Top Side) Output Connector Pin Configuration S1 PS PRESENT S13 PS_ON_L S2 Reserved S14 PS_KILL_L S3 Reserved S15 Reserved S4 Pwr_Good (PWOK) S16 RETURN S5 ACOK (AC Input Present) S17 SDA S6 RETURN S18 RETURN S7 ISHARE S19 SCL S8 RESERVE S20 RETURN S9 PS INTERRUPT_L S21 REMOTE SENSE- S10 RETURN S22 RETURN S11 Reserved S23 REMOTE SENSE+ S12 Reserved S24 RESERVE P1-P8 Vo P19-P20 VSB P9-P18 RTN P21-P28 RTN P29-P36 Vo

ENG-DS495SPE-235-01 5.05.22 For international contact information, visit advancedenergy .com. powersales@aei.com (Sales Support) productsupport.ep@aei.com (Technical Support) +1 888 412 7832 ABOUT ADVANCED ENERGY Advanced Energy (AE) has devoted more than three decades to perfecting power for its global customers. AE designs and manufactures highly engineered, precision power conversion, measurement and control solutions for mission-critical applications and processes. Our products enable customer innovation in complex applications for a wide range of industries including semiconductor equipment, industrial, manufacturing, telecommunications, data center computing, and medical. With deep applications know-how and responsive service and support across the globe, we build collaborative partnerships to meet rapid technological developments, propel growth for our customers, and innovate the future of power. Specifications are subject to change without notice. Not responsible for errors or omissions. ©2022 Advanced Energy Industries, Inc. All rights reserved. Advanced Energy®, AE® and Artesyn™ are U.S. trademarks of Advanced Energy Industries, Inc.