TD00502001E For more information visit: www.cutler-hammer.eaton.com Meter Breakers Technical Data Residential Meter Breakers Type CH Residential Type BR Residential Supersedes Technical Data TD.31F.01.T.E Pages 1-28, dated August 2001 Contents Page Residential Meter Breakers Residential Meter Breakers Product Selection Box Styles Typical Wiring Diagrams Type CH Residential 300 Ampere and 400 Ampere “House Panels” Product Selection Type BR Residential 300 Ampere and 400 Ampere “House Panels” Product Selection

For more information visit: www.cutler-hammer.eaton.com TD00502001E Technical Data Page Effective: April 2002 Meter Breakers Residential Meter Breakers Residential Meter Breakers Product Description A meter breaker is service entrance equipment that consists of a single meter socket and loadcenter (circuit breaker distribution section) or meter socket and main breaker combined in one enclosure. Sometimes called Combos, All-In-Ones, Meter Centers or Meter Mains these units are increasing in popularity as the socket and load- center or main breaker are located in one location, thus providing the contractor with a labor and material savings when installing. Application Description In addition to residential installations, meter breakers are equally applicable for rural service entrance, mobile homes, and construction site tempo- rary power. Meter breakers are most often sold in the western, southwest- ern and southeastern United States. The popularity of meter breakers is continuing to increase as more utilities deregulate and pass the responsibility of supplying watt-hour meter sockets on to the electrical contractor. Application Considerations We have the meter breaker to meet your application. Cutler-Hammer offers: n Non-EUSERC. n EUSERC/West Coast (Electrical Utility Service Equipment Requirements Committee). n House Panels. n Commercial Safety Sockets. Non-EUSERC The Cutler-Hammer line of Non-EUSERC meter breakers is designed for cus- tomers served by utilities that are not members of EUSERC. EUSERC/West Coast The Cutler-Hammer line of EUSERC approved devices adheres to the agreed upon standards. EUSERC utilities are predominately located in the western United States, but some eastern and midwestern utilities are also members. These units can also be used in many Non-EUSERC areas. House Panels Meter breaker device rated at 300 – 400A. Applied in EUSERC and Non-EUSERC areas. Commercial Safety Sockets Applied in EUSERC and Non-EUSERC service areas and used in commercial applications. Standards and Certifications n UL Specification 414 (socket). n UL File Number E52977. n AEIC-EEI-NEMA Standards (MSJ-7). n Meet EUSERC Utility requirements where noted. n Documented Seismic Qualified — UBC and CBC Title 24. n UL Specification 67 (panel). Product Specifications n Ratings single-phase, 3-wire, 120/240V AC. n 100 – 225 ampere main breaker and main lug types. n 10,000 amperes rms symmetrical short circuit rating. Features, Benefits and Functions n Both BR and CH type branch circuit breaker styles available. n Meets latest NEC wire bending space requirements. n Slotted sealing screws at hub with sealing provision provided. n Surface units are supplied with mounting tabs. n Semi-flush units are supplied with stucco flange. n Meter socket ring landing will accept locking security rings. n Overhead or underground service. n Fifth jaw can be installed in the 3 o’clock or 9 o’clock position. n Semi-flush with nail flange or surface mounting. n Meter mounting and underground pull sections are utility sealable. n Units are rated a minimum of 10 kAIC; some units are 22 kAIC. n Numerous units supplied with center keyhole for ease of mounting.

Table 1. Combination Service Entrance Devices (Non-EUSERC) Per installed main breaker rating. Provision for main is provided. WMB style devices accept Main Breaker style BR, 2-Pole. All panels are dual labeled to accept Types BW or CSR Main Breakers. lug kit is needed for load side cable connection for Meter Mains. Please order separately. When a provision for main is provided, order one of the main breakers listed in this table. All panels are dual labeled to accept Types BW, BWH and CSR Main Breakers. service territory that has the same design requirements. One-piece cover on utility side, Florida approved. Will accept maximum four 1-pole, two 2-pole, or two quad breakers. Units come with feed-through lugs. Table 2. Main Breaker Selection Chart Types BW, BWH and CSR Main Breakers.

Table 3. Combination Service Entrance Devices (EUSERC) 2 Interrupting rating is dependent on the main breaker that is installed. 4 When a provision for main is provided, order one of the main breakers listed in Table 2. All panels are dual labeled to accept Types BW or CSR Main Breakers. 5 Semi-flush flange, not full stucco flange. 6 Units come with feed-through lugs. 7 Includes factory mounted 2-1/2 inch hub on bottom endwall. UG feed only. 8 Use WMB70SMK if second main kit is needed. Table 4. Main Breaker Selection Chart

9 When a provision for main is provided,

Types BW, BWH and CSR Main Breakers.

Figure 1. Five Different Styles (Shapes) of Product Table 5. Box Dimensions Table 6. Meter Breaker Parts Table 7. Wire Size Chart Table 8. Wire Size is Determined by the Circuit Breaker Installed in Table 9. Hub Selection Chart

Figure 42. Knockouts for Stucco and Surface Units Table 19. Top Endwall (Surface)

1 Use when DS H1 Type 1, 1-1/4 and 1-1/2-inch

Table 20. Top Endwall (Stucco) Table 21. Bottom Endwall

300 Ampere and 400 Ampere

rated at 300 amperes or 400 amperes. Table 24. 300 – 400 Ampere “House Panels” 1 Confirm security type for individual EUSERC utility requirements. 2 Semi-Flush Flange kit — HPPR. 3 If manual bypass is needed, order bypass kit HPBPK. 4 Feed-through lugs included.

Figure 45. Type CH Wiring Diagram 1 — Figure 46. Type CH Wiring Diagram 2 — Figure 47. Type CH Wiring Diagram 3 — Figure 48. Type CH Wiring Diagram 4 — Figure 49. Type CH Wiring Diagram 5 — Figure 50. Type CH Wiring Diagram 6 — Figure 51. Type CH Wiring Diagram 7 — Figure 52. Type CH Wiring Diagram 8 — Figure 53. Type CH Wiring Diagram Key

400 AMPS

Figure 54. House Panel Dimensions and Knockouts

4 Knockouts

1.469 TYP

2 Knockouts per 50-1827-31

3 Knockouts per A50-25989

rated at 300 amperes or 400 amperes. Table 25. 300 – 400 Ampere “House Panels” 1 Confirm security type for individual EUSERC utility requirements. 2 Included in all of the following devices. 3 If unit needs to be semi-flush, order accessory item catalog number HPPR to convert all surface mounting devices to semi-flush mounting. 4 Includes manual bypass and additional ground lug to meet Nevada Power requirements. 5 Secondary sub-main installed in panel. 6 Feed-through lugs included.

Figure 55. Type BR Wiring Diagram 1 — Figure 56. Type BR Wiring Diagram 2 — Figure 57. Type BR Wiring Diagram 3 — Figure 58. Type BR Wiring Diagram 4 — Figure 59. Type BR Wiring Diagram 5 — Figure 60. Type BR Wiring Diagram 6 — Figure 61. Type BR Wiring Diagram 7 — Figure 62. Type BR Wiring Diagram Key

Figure 63. Type BR Wiring Diagram 8 — Figure 64. Type BR Wiring Diagram 9 — Figure 65. Type BR Wiring Diagram 10 — Figure 66. Type BR Wiring Diagram 11 — Figure 67. Type BR Wiring Diagram 12 — Figure 68. Type BR Wiring Diagram Key

Figure 69. Type BR Meter Breaker Dimension Drawing 1

For more information visit: www.cutler-hammer.eaton.com TD00502001E Technical Data Page 26 Effective: April 2002 Meter Breakers This page intentionally left blank.

TD00502001E For more information visit: www.cutler-hammer.eaton.com Technical Data Effective: April 2002 Page 27 Meter Breakers This page intentionally left blank.

Page 28 Effective: April 2002 Meter Breakers © 2002 Eaton Corporation All Rights Reserved Printed in USA Publication No. TD00502001E April 2002 Eaton Corporation Cutler-Hammer business unit