240W All-In-One Intelligent Security Power DRS-240 seri es https://www.meanwell.com/webapp/product/search.aspx?prod=SBP-001 File Name:DRS-240-SPEC 2022-04-14 UL62368-1 IEC62368-1TPTC004BS EN/EN62368-1 AS/NZS 62368.1 https://www.meanwell.com/serviceGTIN.aspx (Pending) User’s Manual
92% 41 ±1V.8 DRS-240-48 0 ~ 5A 105 ~ 135% rated output power SPECIFICATION MODEL OUTPUT VOLTAGE Note.2 OUTPUT LINE REGULATION LOAD REGULATION SETUP, RISE TIME Note.7 HOLD UP TIME (Typ.) VOLTAGE RANGE FREQUENCY RANGE POWER FACTOR (Typ.) EFFICIENCY (Typ.)INPUT INRUSH CURRENT (Typ.) BATTERY CUT OFF WORKING TEMP. WORKING HUMIDITY STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION OPERATING ALTITUDE Note.8 OVER VOLTAGE CATEGORY DIMENSIONOTHERS NOTE OVERLOAD OVER VOLTAGE AC CURRENT (Typ.) 2400ms, 1000ms/230VAC 2400ms, 1000ms/115VAC at full load 90 ~ 127 ~ 431VDC 305VAC COLD START 30A/115VAC 60A/230VAC -30 ~ +70℃(Refer to “Derating Curve") 20 ~ 90% RH non-condensing -40 ~ +85℃, 10 ~ 95% RH non-condensing ±0.03%/℃ (0 ~ 50℃) on Load output 10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes 2000 meters / OVC Ⅲ Ⅲ; According to Dekra BS EN/EN62368-1; altitude up to 2000 meters 564.7K hrs min. Telcordia SR-332 (Bellcore); 73.3K hrs min. MIL-HDBK-217F (25℃) PF>0.95/230VAC PF>0.98/115VAC at full load 16ms/230VAC 10ms/115VAC at full load VOLTAGE TOLERANCE Note.6 ENVIRONMENT PROTECTION Protection type : Shut down o/p voltage, re-power on to recover 2.8A/115VAC 1.4A/230VAC CURRENT RANGE TOTAL OUTPUT POWER Note.4 RIPPLE & NOISE (max.) Note.5 47 ~ 63Hz Protection type: Constant current limiting, shutdown output voltage after 5 sec. FUNCTION AC FAIL BATTERY LOW/ ABNORMAL/ DISCONNECTED Relay contact output, ON : Battery OK ; OFF : Battery Low ; max. rating : 30Vdc/1A Battery low voltage:< 11±0.2V Battery low voltage:< 33±0.4V Battery low voltage:< 44±0.5V SAFETY STANDARDS SAFETY & EMC (Note.9) WITHSTAND VOLTAGE ISOLATION RESISTANCE I/P-O/P: 4KVAC I/P-FG: 2KVAC O/P-FG: 1.5KVAC I/P-O/P, I/P-FG, O/P-FG: 100M Ohms/500VDC/25℃/ 70%RH UL62368-1, Dekra BS EN/EN62368-1, RCM AS/NZS 62368.1 approved; pendingEAC TP TC 004 ±0.5% ±0.5% ±0.5% ±0.5% ±0.5% ±0.5% ±1.0% ±1.0% ±1.0% Load main output : 16.2 ~ 18.6V FIRE DETECTION AND FIRE ALARM SYSTEM PACKING 150mVp-p 360mVp-p 90% 92% DRS-240-12 DRS-240-36 12V 36V 0 ~ 20A 0 ~ 6.6A EMC IMMUNITY EMC EMISSION Parameter Parameter ESD Radiated EFT / Burst Surge Conducted Magnetic Field Conducted Radiated Harmonic Current Voltage Flicker BS EN/EN55035 , BS EN/EN61204-3, BS EN/EN61000-6-2(BS EN/EN50082-2) Standard Standard BS EN/EN55032 (CISPR32) BS EN/EN55032 (CISPR32) BS EN/EN61000-4-2 BS EN/EN61000-4-3 BS EN/EN61000-4-4 BS EN/EN61000-4-5 BS EN/EN61000-4-6 BS EN/EN61000-4-8 Test Level / Note Test Level / Note Level 3, 8KV air ; Level 2, 4KV contact; criteria A Level 3, 10V/m ; criteria A Level 3, 2KV ; criteria A Level 3, 1KV/Line-Line ;Level 3, 2KV/Line-Line-Chassis ;criteria A Level 3, 10V ; criteria A Level 4, 30A/m ; criteria A Class B Class B ----- ----- DC OK CHARGER FAIL Signals normal DC output and activates when output voltage > 90% rated value. Relay contact output, ON : DC OK ; OFF : DC Fail ; max. rating : 30Vdc/1A Relay contact output, ON : Charger OK ; OFF : Charger Fail ; max. rating : 30Vdc/1A REVERSE POLARITY FORM-C RELAY DC-UPS ADJUSTABLE CHARGING CURRENT UPS switch to battery power within 10ms of AC failure By internal MOSFET, , recovers automatically after fault condition is removed.no damage BATTERY START Restart system directly from battery and does not require AC power RECOMMENDED BATTERY CAPACITY(AMP HOURS)Note.3 20 ~ 200AH 6.6 ~ 66AH 5 ~ 50AH OVER TEMPERATURE Battery low voltage:< 22±0.3V ±0.5% ±0.5% ±1.0% 240mVp-p 92% 20 9±0.5V. DRS-240-24 24V 0 ~ 10A 10 ~ 100AH BATTERY TEMPERATURE COMPENSATION The system can change the battery charging voltage by detecting the temperature (Please refer to page 9~10 for more details). MTBF Compliance to BS EN/EN54-4 File Name:DRS-240-SPEC 2022-04-14 DRS-240 seri es240W All-In-One Intelligent Security Power Signals AC failure and activates when input voltage drops below : 79~89VAC of 120AC, 132~187VAC of 220VAC. Relay contact output, ON : AC OK ; OFF : AC Fail ; max. rating : 30Vdc/1A 1.19Kg; 8pcs/ 12.5Kg / 1.08CUFT BS EN/EN61000-3-2 BS EN/EN61000-3-2 20% ~ 100% charging current adjustable by VR Automatically drop load with temperature only for bat. load. Protection type : Shut down o/p voltage, recover automatically after temperature goes down. SHORT CIRCUIT Protection type: Constant current limiting, power will shutdown after 5 sec, re-power on to recover. Combined power on all Channels must not exceed 240W, load has priority. 275W peak capability within 5s.
BAT. + BAT. - I/P CONTROL PWM O.V.P. AMBIENT TEMPERATURE (℃) LOAD (%) 100 (VERTICAL)-20 0 15 300 40 50-30 60 70 RECTIFIER PFC PFC CONTROL AUX POWER CHARGING UPS FUNCTION MCU MODBUS CANBUS OPTIONAL O.T.P. DERATING CONTROL RELAY CONTROL O.T.P. DERATING CONTROL REVERSE DETECTION BAT. start Force start Derating Curve Static Characteristics Block Diagram File Name:DRS-240-SPEC 2022-04-14 DRS-240 seri es240W All-In-One Intelligent Security Power AC Fail Battery low / Abnormal / Disconnected DC OK Charger Fail PFC fosc : 80KHz PWM fosc : 65KHz INPUT VOLTAGE (V) 60Hz 90 100 125 135 145 155 165 175 180 200 230 305 100 LOAD (%) 175 LOAD (%) 277
File Name:DRS-240-SPEC 2022-04-14 DRS-240 seri es240W All-In-One Intelligent Security Power 1.Alarm signals (1) Alarm Signal is sent out through " AC fail " & " Battery low " & " "pins via relay contact.Charger fail (2) An external voltage source is required for this function. The maximum applied voltage is 30Vdc and the maximum sink current is 1A. Please refer to Fig 1.2. (3) Table1.1 explains the alarm function built in the power supply Table 1.1 Explanation of alarm signal 2-3 AC fail 1-3 5-6 4-6 8-9 7-9 11-12 10-12 DC OK AC only open open closed ----- ----- ----- ----- ----- ----- ----- ----- ----- ----- Charger fail AC + BAT. BAT. only Low BAT. (<30% capacity) closed open closed open Charger Fail closed closed open openclosed open closed open closed closed open closed open open closed INPUT Battery low/Abnormal /Disconnected ----- ----- ----- ----- ----- ----- ----- ----- External voltage source (V) and resistor (R) (The max. Sink is 1A and 30Vdc) AC fail (Battery low) R V Fig 1.2 Internal circuit of AC fail (Battery low), via relay contact 2 1 Fig 1.1 alarm signal Terminals +V -V -V+V 1 2 3 4 5 6 7 8 9 10 11 12 AC Fail DC OK Battery Low Charger Fail DC OK AC Fail Status Use copper wire only“ ” Maximum surrounding air temperature: 50“ ℃” “Install in a pollution degree 2 environment” MEAN WELL ENTERPRISES CO.,LTD. No. 28,Wuquan 3rd Rd., Wugu Dist., New Taipei City 24891, Taiwan Manual:www.meanwell.com/manual.html Battery Start Charging Current Adj. MADE IN CHINAMW02 N L BAT- “Terminal torque 5 Lb-in” “Terminal torque 4.43 Lb-in” BAT+ Force Button RTH+RTH- 3.3VGND A0A1 DRS-240-12 INPUT: 100-277VAC 2.8A 50/60Hz OUTPUT:12V Max.20A BAT. Total Power: Max.240W Max.15.4A12V “Terminal torque 1.77 Lb-in”Terminal torque 5 Lb-in“ ” 35-1222255 Communication Port(RJ45)
File Name:DRS-240-SPEC 2022-04-14 DRS-240 seri es240W All-In-One Intelligent Security Power 2.DC-UPS function When AC mains drops below:79~89VAC of 120VAC,132~187VAC of 220VAC, UPS function will activate and power source switch battery backup. AC mains MODBus Communication (CANBus optional) Charging Load Output Signals/Form C ▪ AC fail ▪ DC OK Battery low/Abnormal/Disconnected▪ Charger fail▪ BatteryButton Battery start ◎ 2 stage charging curve ◎ Default 3 stage charging curve Charge Current Charge CurrentConstant Current Constant Current stage 1 stage 1stage 2 stage 2Battery Full Cut off for stop charging stage 3 Constant Voltage Constant Voltage Float Start Start Charge Voltage Charge Voltage 100% CC 100% CC 10% CC 10% CC boost boost float V V V Orange OrangeGreen GreenColor of LED Loading Indicator Color of LED Loading Indicator State Constant Current 28.8V 43.2V DRS-240-24 DRS-240-36 Vboost 7.7A 5.1A ◎ Suitable for lead-acid batteries (flooded, Gel and AGM) and ◎ Suitable for lead-acid batteries (flooded, Gel and AGM) and Li-ion batteries (lithium iron and lithium manganese). Li-ion batteries (lithium iron and lithium manganese). State Vboost Vfloat 28.8V 27.6V 43.2V 41.4V Constant Current DRS-240-24 DRS-240-36 7.7A 5.1A 57.6V DRS-240-48 3.85A 57.6V 55.2V DRS-240-48 3.85A ※ The default curve is programmable, whereas other pre-defined curves can be activated by the means of the DIP S.W; please refer to the table below and the Mechanical Specification.
1 OFF: 3 stage(Default), ON: 2 stage
3 Charging curve adjustable:see below
14.4V DRS-240-12 15.4A 14.4V 13.8V DRS-240-12 15.4A AC Fail Battery Low DC OK Charger Fail Charging Current Adj. AC Fail DC OK Status Battery Start CN1 ON 2 13 3.Charger setting ※ This series provides 2 or 3 stage charging curve. 3.1.1 2 or 3-stage selectable by DIP S.W Communication Port(RJ45) 3.1.2 Charging curve can be adjustable by DIP S.W +V +V -V -V N L BAT- BAT+
File Name:DRS-240-SPEC 2022-04-14 DRS-240 seri es240W All-In-One Intelligent Security Power ◎ 2 stage charging curve (programable) ◎ 3 stage charging curve (programable) OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF DIP SW position DIP SW position DIP SW position DIP SW position DIP SW position DIP SW position Vboost Vboost Vboost Vboost Vboost Vboost CC(default) CC(default) CC(default) CC(default) CC(default) CC(default) 28.8 28.8 43.2 43.2 57.6 57.6 Vfloat Vfloat Vfloat 27.6 41.4 55.2 Description Description Description Description Description Description 24V model 36V model 36V model 48V model 48V model 24V model Default, programmable Default, programmable Default, programmable Default, programmable Default, programmable Default, programmable 7.7A 5.1A 3.85A 2 3 2 3 2 3 2 3 2 3
3.2 SBP-001 can adjust the charging curves (Only CANBus Model)
※ SBP-001 is a programmer, particularly for MEAN WELL's various programmable battery charger models to program the parameters of charging curves, such as the Constant current (CC), tapper current(TC), Constant voltage (CV), float voltage (FV) and so on, to accommodate the diversified battery specification in industry. With the design accounting for simplicity and convenience, users can easily configure MEAN WELL's programmable battery chargers with SBP-001 programmer and the computer; all of the setups are able to be finished easily by the means of the specific software. Note:(1) Tapper current(TC) default is 10%, can be fine tuned from 2% to 30% by SBP-001 with computer or CANBus Interface. (2) Please contact MEAN WELL for more details. OFF OFF OFF OFF DIP SW position DIP SW position Vboost VboostCC(default) CC(default) 14.4 14.4 Vfloat 13.8 Description Description 12V model 12V model Default, programmable Default, programmable15.4A 2 3 ◎ Embedded 2 stage charging curve ◎ Embedded 3 stage charging curve OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON DIP SW position DIP SW position DIP SW position DIP SW position DIP SW position DIP SW position Vboost Vboost Vboost CC(default) CC(default) CC(default) 7.7A 5.1A 3.85A 43.2 57.6 56.0 42.6 56.8 43.8 58.4
Description
Default, programmable Default, programmable Default, programmable Pre-defined, gel batter Pre-defined, gel battery Pre-defined, gel battery Pre-defined, flooded battery Pre-defined, flooded battery Pre-defined, flooded battery Pre-defined, AGM battery,LiFe04 Pre-defined, AGM battery,LiFe04 Pre-defined, AGM battery,LiFe04 2 3 2 3 28.8 28.0 28.4 29.2 OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON Vboost Vboost Vboost CC(default) CC(default) CC(default) 57.6 56.0 56.8 58.4 Vfloat Vfloat Vfloat 27.6 41.4 55.2 27.2 40.8 54.4 26.8 40.2 53.6 28.0 42.0 56.0 Default, programmable Default, programmable Default, programmable Pre-defined, gel batter Pre-defined, gel battery Pre-defined, gel battery Pre-defined, flooded battery Pre-defined, flooded battery Pre-defined, flooded battery Pre-defined, AGM battery,LiFe04 Pre-defined, AGM battery,LiFe04 Pre-defined, AGM battery,LiFe04 43.2 42.6 43.8 28.8 28.0 28.4 29.2 OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON DIP SW position DIP SW position VboostCC(default) 15.4A Default, programmable Pre-defined, gel batter Pre-defined, flooded battery Pre-defined, AGM battery,LiFe04 14.4 14.0 14.2 14.6 OFF OFF ON ON VboostCC(default) Vfloat 13.8 13.6 13.4 14.0 Default, programmable Pre-defined, gel batter Pre-defined, flooded battery Pre-defined, AGM battery,LiFe04 14.4 14.0 14.2 14.6 7.7A 5.1A 3.85A 15.4A 7.7A 5.1A 3.85A 15.4A
File Name:DRS-240-SPEC 2022-04-14 DRS-240 seri es240W All-In-One Intelligent Security Power Charging curve adjustable 2 or 3-stage selectable Model selection Charging timeout setting ※ User Interface: DRS-240 USB SBP-001 UART_RX PMBUS_D CANH 3.3V UART_TX PMBUS_C CANL GND GND LED 5V(Orange) 3.3V(Green) To the personal computer USB port (Type A) To the programmer (Mini USB) Smart programmer (Sold separately) 10 9 10 pins (HRS DF11-10DS) (DRS-240)
File Name:DRS-240-SPEC 2022-04-14 DRS-240 seri es240W All-In-One Intelligent Security Power 4.Power Boost Mode The maximum current on the load output is the 2 times the rated current for 4 minutes max. and 3 times the rated current for 4 seconds max. For example (48V model): Output load 10A 15A power power power BAT. BAT. BAT. max.4min. max.4sec. ※ Communication cable for DRS series or equivalent HRS DF11-10DS CANbus PMbus or equivalent UL1061 28AWG RJ45 CAT.5e 24AWG PVC UTP SBP#2 180 150 (DRS series) (SBP-001) Charging parameters can be modified by MODBus (Built-in) or CANBus(optional) communication commands.
3.3 Communication interface
(Connector part No.:HRS DF11-10DS) DRS-240 RJ45 Communication port Wire color ----- ----- ----- ----- Green White/Brown ----- ----- ----- Brown Connector Pin Assigment 2 3 4 5 (CANH) (CANL) (GND)7 8 9 DRS series pin assigment : For details, please refer to: http://www.meanwell.com/manual.html
5.Battery temperature compensation File Name:DRS-240-SPEC 2022-04-14 DRS-240 seri es240W All-In-One Intelligent Security Power Bat- Bat + Battery AC Input 8 pins (JS-2008R-2*4-T) RTH+RTH- (NTC) Extend cable by customer ◎ To exploit the temperature compensation function, please attach the temperature sensor(NTC) which is enclosed with DRS-240, to the battery or the battery's vicinity. DRS-240 is able to work normally without the temperature sensor(NTC).◎ 5.1 The compensation parameters included Disable, -3, -4 and -5mV/ ℃ /Cell .It can be modified by communication command of CANBus, MODBus. The factory default value is -3mV/ ℃ /Cell. 5.2 It will be regarded as normal temperature and will not be compensated when temperature compensation resistance is not connected; And temperature compensation will only compensate lead-acid battery, not lithium iron battery. 5.3The range of temperature compensation is 0-40℃ , normal temperature 25℃ is the central value, no compensation; When the temperature is < 0 ℃ or > 40 ℃, the current temperature compensation value will be limited to 0 ℃ or 40℃. 24V model as an example Assuming that V =28.8V, temperature compensation set to -5mV/℃/Cellby communication, TEMP_bat is NTCtemperature detection.boost The compensating voltage can be calculated by the following equation: V =28.8V-5mV*(TEMP_bat -25℃)*12Cellboost_comp Max. compensation voltage: V =28.8V-5mV*(0℃-25℃)*12Cell=30.3Vboost_H Min. compensation voltage: V =28.8V-5mV*(40℃-25℃)*12Cell=27.9Vboost_L
File Name:DRS-240-SPEC 2022-04-14 DRS-240 seri es240W All-In-One Intelligent Security Power Part No.: NGS05C250J5 1 UL2468 24x2C UL1007 28AWG NTC(RTH+) NTC(RTH-) 50 7 JS-2007-2*4-T
5.4 Accessory List
※ NTC Sensor and mating wire along with DRS-240 (Standard accessory) Item NTC sensor wire Mating wire or equivalent Quantity Connection Diagram Connect to DRS-240 Connect to battery Connected Extend cable by customer
6.LED alarm File Name:DRS-240-SPEC 2022-04-14 DRS-240 seri es240W All-In-One Intelligent Security Power Function Output of alarm Red OFF OFF Green Battery discharge peak power timeout. Over load / short Over temperature Green Orange AC fail DC fail AC OK DC OK Float Charging: CC/CV Red : 1 Blink/Pause Red : 3 Blink/Pause Red : 4 Blink/Pause Red : 5 Blink/Pause Red : 6 Blink/Pause Red : 2 Blink/Pause Orange: 1 Blink/PauseDischarging Timeout Red : 7 Blink/Pause
File Name:DRS-240-SPEC 2022-04-14 DRS-240 seri es240W All-In-One Intelligent Security Power Suggested Application 1.Backup connection for AC interruption (1) Please refer to Fig2.1 for suggested connection. The power supply charges the battery and provides energy to the load at the same time when AC mains is OK. The battery starts to supply power to the load when AC mains fails. (2) Backup time Backup time depends on: from the load current※ from the size of the batteries.※ The following table is an example (battery capacity at C10 discharge rate). Load 1.5A 7.5A 10A 15A 10AH 20AH 50AH 100AH 200AH 350min 125min 60min 35min 23min 13min 13h 350min 180min 90min 60min 35min 33h 17h 600min 350min 240min 125min 67h 33h 20h 13h 10h 350min 133h 67h 40h 27h 20h 13h Battery Fig 2.1 Suggested system connection DRS Series Example of Application Load + - AC fail Battery low/ Abnormal/ Disconnecte Charging curve programmable by CANBus(Optional models) Charger fail Bat- Bat + Battery AC Input RJ45 SBP-001 smart programmable Personal Computer DC OK Communication Port MODBus communication(Standard models) RJ45 Communication Port RS-485 Personal Computer RJ45 USBCAN Personal Computer Communication Port CANBus communication(Optional models)
+V +V -V -V N L BAT- BAT+ DRS-240 seri es File Name:DRS-240-SPEC 2022-04-14 240W All-In-One Intelligent Security Power Mechanical Specification Case No. 984G Unit:mm 129.2 85.5 125.2 TB1 TB3 TB4 1 2 3 4 5 6 7 8 9 10 11121 2 3 4 1 2 3 Charging Current Adj. AC Fail DC OK Status Battery Start CN1 ON 2 13 TB2 1 2 3 4 Force button Connector (CN1): JS-2008R-4*2-T or equivalent Communication Port(RJ45) Terminal Pin No. Assignment (TB1) Terminal Pin No. Assignment (TB3) Pin No. Pin No. 1,2 3,4 Assignment Assignment FG AC/L AC/N Terminal Pin No. Assignment (TB2) Pin No. 1,2 3,4 Assignment BAT.- BAT. + Terminal Pin No. Assignment (TB4) Pin No. 1,2,3 4,5,6 Assignment AC fail Charger fail 7,8,9 10,11,12 DC OK Battery low/ Abnormal/ Disconnected Terminal Pin No. Assignment (RJ45) Pin No. 1,2,3,4,5 Function NC CANH Retain for future use.
8 GND-AUX
For MODBus model:Serial Date used in the MODBus interface. Auxillary voltage output GND. The signal return is isolated from the output terminals(+V & -V). Data+ For CANBus model:Date line used in the CANBus interface. CANL Data- For MODBus model:Serial Clock used in the MODBus interface. For CANBus model:Date line used in the CANBus interface. Open: Normal Short: Force start Pin No. Assignment RTH+ RTH- 3.3V GND 5 A0 6 A1 7,8
Please refer to : http://www.meanwell.com/manual.html DRS-240 seri es File Name:DRS-240-SPEC 2022-04-14 Back View This series fits DIN rail TS35/7.5 or TS35/15. For installation details, please refer to the Instruction manual. ADMISSIBLE DIN rail:TS35/7.5 OR TS35/15 (For reference only. Not included with unit.) 240W All-In-One Intelligent Security Power