DRH SENSATA | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 9
Technical content
Features
- Ratings up to 18 & 20 Amps at 600 VAC
- Fits standard 35 mm DIN Rail
- Integrated over-temperature protection
- Alarm output in case of over-temperature
- Multicolor LED with input status and alarm indicator
- AC or DC control
- Zero Voltage (resistive loads) or instantaneous (inductive loads) turn-on output
- C-UL-US Listed, IEC Rated, CE & RoHS Compliant, Horsepower Rated
- Built-in Overvoltage Protection
- Fan controlled through thermistor and microprocessor to optimize fan operation Control Voltage 18 A 20 A 90-280 VAC/VDC DRH3P60A18 DRH3P60A20 4-32 VDC DRH3P60D18 DRH3P60D20 PRODUCT SELECTION
www.sensata.comCopyright © 2019 Sensata Technologies, Inc. Input (1) Description DRH3P60Dx DRH3P60Ax Control Voltage Range 4-32 VDC 90-280 VAC/VDC Minimum Turn-On Voltage 4 VDC 90 VAC/VDC Must Turn-Off Voltage 1 VDC 10 VAC Minimum Input Current (for on-state) 2 mA 1 mA Maximum Input Current 17 mA 3 mA Nominal Input Resistance [Ohms] 2k 100k Maximum Turn-On Time [msec] 1 Cycle (4) 30 Maximum Turn-Off Time [msec] 1 Cycle 40 Power Supply (1) Description DRH3P60Dx DRH3P60Ax Voltage Range 8-32 VDC 90-265 VAC/VDC Minimum Turn-On Voltage 8 VDC 90 VAC/VDC Must Turn-Off Voltage 3 VDC 5 VAC/VDC Maximum Source Current [mA] 125 40 Maximum Start Up Time [msec] 20 50 Maximum Shut Off Time [msec] 40 500 Output (1) Description 18 A 20 A Operating Voltage (47-63Hz) [Vrms ] 48-600 48-600 Transient Overvoltage [Vpk] (2) 1200 1200 Maximum Off-State Leakage Current @ Rated Voltage [mArms] 3 3 Minimum Off-State dV/dt @ Maximum Rated Voltage [V/µsec] 500 500 Load Current, General Use UL508/IEC62314 @ 40°C [Arms] (3) 18 20 Load Current, Motor Starting UL508 FLA/IEC62314 @ 40°C [Arms] (3) 7.6 7.6 Minimum Load Current [Arms] 0.15 0.15 Maximum Surge Current [Apk] 1Cycle 60Hz 750 750 Maximum Surge Current [Apk] 1Cycle 50Hz 716 716 Maximum I²t for Fusing (8.33 msec) [A²sec] 2330 2330 Maximum I²t for Fusing (10 msec) [A²sec] 2560 2560 Maximum On-State Voltage Drop @ Rated Current [Vpk] 1.35 per channel 1.35 per channel Minimum Power Factor (with Maximum Load) 0.5 0.5 Motor Rating UL 508/ IEC60947-4-2 [HP/kW] :240 VAC 2/1.5 2/1.5 Motor Rating UL 508/ IEC60947-4-2 [HP/kW] :380 VAC 3/2.2 3/2.2 Motor Rating UL 508/ IEC60947-4-2 [HP/kW] :480 VAC 5/3.7 5/3.7 SPECIFICATIONS
www.sensata.comCopyright © 2019 Sensata Technologies, Inc. General (1) Description Parameters Dielectric Strength, Input/Output/Base (50/60Hz) (6) 3750 Vrms Minimum Insulation Resistance (@ 500 VDC) 109 Ohm Maximum Capacitance, Input/Output 20 pF Ambient Operating Temperature Range (7) -10 to 70 °C Ambient Storage Temperature Range -40 to 70 °C Weight (typical) 2 Controlled Legs (7.4 oz [210 g]) / 3 Controlled Legs (8.5 oz [242 g]) Housing Material UL94 V-0 Housing Color Black and Light Gray LED Status Indicator (color) See Status Chart Short Circuit Current Rating (8) 100kA Pollution Degree 2 Protection Degree (9) IP20 Humidity 85% non-condensing Control and Auxiliary Contact Terminal Screw Torque Range (lb-in/Nm) 12 / 1.36 Load Terminal Screw Torque Range (lb-in/Nm) 15 / 1.7 Input Terminal Wire Capacity 18-12 AWG (IEC 1-4 mm2) (stranded /solid) Output Terminal Wire Capacity 18-10 AWG (IEC 1-6 mm2) (stranded /solid) Alarm Output (1) Description DRH3P60xxx Maximum Contact Switching Voltage [Volts] 200 VDC, 120 VAC Rated Current Resistive [A] (5) 0.5 Minimum Recommended Contact Load [mA] 10 Static Contact Resistance (max. init.)[Ohms] 0.2 Turn-On / Off Condition See Status Chart
www.sensata.comCopyright © 2019 Sensata Technologies, Inc. THERMAL DERATE INFORMATION MECHANICAL SPECIFICATIONS Tolerance: ±0.02 in / 0.5 mm All dimensions are in: inches [millimeters] Top/Bottom view (Fig. 1 ) Fig. 1 TERMINAL SCREW TYPE INPUT STATUS XXXX IND. CONT. EQ. DRH3 1.23 [31.3] 2.29 [58.3] 2.58 [65.5] 1.68 [42.7] 3.41 [86.7] 1.78 [45.3] 3.76 [95.6] 3.51 [89] 2.91 [73.9] 0.23 [5.8] +A1 -A2 13+A3 14-A4
www.sensata.comCopyright © 2019 Sensata Technologies, Inc. WIRING AND BLOCK DIAGRAM
www.sensata.comCopyright © 2019 Sensata Technologies, Inc. SHORT CIRCUIT AND OVERLOAD PROTECTION FOR ALL DEVICES IEC standard 60947-4-1 make a distinction between two different types of protection, (called “coordination”), which are designated types “1” and “2”. Any short-circuit that occurs is cleared safely by either type of coordination. The only difference between the 2 categories concerns the extent of the SSR damage caused by the short-circuit. Type “1” coordination requires that in the event of a short-circuit, the Solid State Contactor does not endanger personnel or installations, but permanent damage to the SSC is permissible. In this case the SSC may need to be replaced. For this type of co-ordination, the use of fusing or circuit breakers adequate to protect the system and wiring from short circuits, (but not specifically considering SSC protection), can be used. Type “2” coordination requires that under a short-circuit condition, the circuit is interrupted, the SSC does not endanger persons or installations, and in addition the SSR will be able to operate after the fault condition is repaired. Type of coordination 1 Type of coordination 2
www.sensata.comCopyright © 2019 Sensata Technologies, Inc. STATUS CHART
www.sensata.comCopyright © 2019 Sensata Technologies, Inc. ORDERING OPTIONS Example : DRH3P60A18R Family DRH Function 3P : Contactor Operating Voltage 60 : 48-600 VAC Control Voltage A : 90-280 VAC/VDC D : 4-32 VDC Rated Load Current 18 : 18 Amps (3 Controlled legs) 20 : 20 Amps (2 Controlled legs) Switching Type Blank : Zero Voltage Turn-On R : Instantaneous Turn-On DRH - 3P - 60 - A - 18 - R GENERAL NOTES (1) All parameters at 25°C unless otherwise specified. (2) Relay will self trigger between 950-1200V, Not suitable for capacitive loads. (3) Mounted in the Vertical position. (4) Turn-on time for Instantaneous turn-on version is 4 msec. (5) Decrease Maximun Current 15mA/°C above 40°C ambient temperature. (6) For input to alarm output the dielectric strength is 1.5kV. (7) UL approval up to 40°C surrounding temperature. (8) 100kA, 480 VAC, when protected with CC class fuses rated 600VAC, 20 A or equivalent. (9) IP20 rating is not associated with the UL approval. (10) Minimum spacing to obtain max. current is 22mm between adjacent units. (11) Combination of these Protective Devices and Solid State Contactor have not been evaluated by UL. ACCESSORIES Required for valid part number For options only and not required for valid part number
+1 (877) 502 5500 sales.crydom@sensata.com Europe, Middle East & Africa +44 (1202) 416170 ssr-info.eu@sensata.com Asia Pacific sales.isasia@list.sensata.com China +86 (21) 2306 1500 Japan +81 (45) 277 7117 Korea +82 (31) 601 2004 India +91 (80) 67920890 Rest of Asia +886 (2) 27602006 ext 2808 www.sensata.com CONTACT USCopyright © 2019 Sensata Technologies, Inc. Sensata Technologies, Inc. (“Sensata”) data sheets are solely intended to assist designers (“Buyers”) who are developing systems that incorporate Sensata products (also referred to herein as “components”). Buyer understands and agrees that Buyer remains responsible for using its independent analysis, evaluation and judgment in designing Buyer’s systems and products. Sensata data sheets have been created using standard laboratory conditions and engineering practices. Sensata has not conducted any testing other than that specifically described in the published documentation for a particular data sheet. Sensata may make corrections, enhancements, improvements and other changes to its data sheets or components without notice. Buyers are authorized to use Sensata data sheets with the Sensata component(s) identified in each particular data sheet. HOWEVER, NO OTHER LICENSE, EXPRESS OR IMPLIED, BY ESTOPPEL OR OTHERWISE TO ANY OTHER SENSATA INTELLECTUAL PROPERTY RIGHT, AND NO LICENSE TO ANY THIRD PARTY TECHNOLOGY OR INTELLECTUAL PROPERTY RIGHT, IS GRANTED HEREIN. SENSATA DATA SHEETS ARE PROVIDED “AS IS”. SENSATA MAKES NO WARRANTIES OR REPRESENTATIONS WITH REGARD TO THE DATA SHEETS OR USE OF THE DATA SHEETS, EXPRESS, IMPLIED OR STATUTORY , INCLUDING ACCURACY OR COMPLETENESS. SENSATA DISCLAIMS ANY WARRANTY OF TITLE AND ANY IMPLIED WARRANTIES OF MERCHANTABILITY , FITNESS FOR A PARTICULAR PURPOSE, QUIET ENJOYMENT, QUIET POSSESSION, AND NON-INFRINGEMENT OF ANY THIRD PARTY INTELLECTUAL PROPERTY RIGHTS WITH REGARD TO SENSATA DATA SHEETS OR USE THEREOF. All products are sold subject to Sensata’s terms and conditions of sale supplied at www.sensata.com SENSATA ASSUMES NO LIABILITY FOR APPLICATIONS ASSISTANCE OR THE DESIGN OF BUYERS’ PRODUCTS. BUYER ACKNOWLEDGES AND AGREES THAT IT IS SOLELY RESPONSIBLE FOR COMPLIANCE WITH ALL LEGAL, REGULATORY AND SAFETY-RELATED REQUIREMENTS CONCERNING ITS PRODUCTS, AND ANY USE OF SENSATA COMPONENTS IN ITS APPLICATIONS, NOTWITHSTANDING ANY APPLICATIONS-RELATED INFORMATION OR SUPPORT THAT MAY BE PROVIDED BY SENSATA. Mailing Address: Sensata Technologies, Inc., 529 Pleasant Street, Attleboro, MA 02703, USA. Rev:02/11/19 ECN 20395 FDE-07-01 Rev. B WARNINGS RISK OF MATERIAL DAMAGE AND HOT ENCLOSURE
- The product’s side panels may be hot, allow the product to cool before touching
- Follow proper mounting instructions including torque values
- Do not allow liquids or foreign objects to enter this product Failure to follow these instructions can result in serious injury, or equipment damage. HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
- Disconnect all power before installing or working with this equipment
- Verify all connections and replace all covers before turning on power Failure to follow these instructions will result in death or serious injury. AGENCY APPROVALS & CERTIFICATIONS Certification in accordance with: United States Standard for Industrial Control Equipment - UL 508 and Canadian Standard Association for Industrial Control Equipment – C22.2 No. 14. DRH series conforms to the harmonized EN standard EN/IEC 60947-4-2 Electromagnetic Compatibility: IEC 61000-4-2 : Electrostatic Discharge – Level 3 IEC 61000-4-4 : Electrically Fast Transients – Level 3 IEC 61000-4-5 : Electrical Surges – Level 3 Vibration Resistance: IEC 60068-2-6: Amplitude Range 10-55 Hz, Displacement 0.75mm Shock Resistance: IEC 60068-2-27: Peak Acceleration 15g, Duration 11msec.