Creation Date : September 22, 2020 (GMT) DRF960-24-1 Sales Region Worldwide (except Japan) Series DRF Model Status Production Feature DIN DIN rail installation compatible Peak Load Peak power capability Options Option Lineup Please refer to here. Recommended EMC Filter Accessories Please refer to the catalog
Electrical Characteristics
Input Voltage Range[AC] 180 to 264Vac Input Voltage Range[DC] Efficiency 95% Typ. Rated Output Voltage[DC] 24Vdc Output Voltage Range[DC] 24 to 28Vdc Maximum Output Current 40A Maximum Average Current Maximum Peak Current 60A Maximum Output Power 960W Maximum Average Power Maximum Peak Power 1440W Package Type & Size Package / Mounting DIN rail Width(W) 110mm Nom. (4.33in Nom.) Height(H) 123.4mm Nom. (4.86in Nom.) Depth(D) 139mm Nom. (5.47in Nom.) Weight 1735g Typ. (3.8lbs Typ.) Other Operating Temp. Range -25 to 70°C Cooling Convection Safety Standard(Certified) IEC60950-1 EN60950-1 UL60950-1 UL508
Safety Standard(Conformed) Remarks This page only shows representative characteristics. Please refer to the technical data for detailed specifications and conditions. ! Images are for reference only and show exemplary products. ! This PDF document was created based on the data listed on the TDK Corporation website. ! All specifications are subject to change without notice. Copyright(c) TDK Corporation. All rights reserved.