Do not forget to visit us at: www.crydom.com Copyright © 2017 Crydom Inc. Specifications subject to change without notice. Start / Stop Reversing DRC Series with EMR Auxiliary Contacts
- 7.6 Amp AC Semiconductor Motor Controller
- Load voltage range up to 600 VAC
- Fits standard 35mm DIN Rail
- LED input status indicator
- AC or DC control
- Zero Voltage (resistive loads) or instantaneous (inductive loads) turn-on output
- C-UL-US Listed, IEC Rated, CE & RoHS Compliant, Horsepower Rated
- Built-in Overvoltage Protection
- Ultra-efficient thermal management design (Patented) See DRC Series models with Solid State Auxiliary Contacts Solicon DRC Series with EMR Auxiliary Contacts are Solid State Contactors intended for frequently switching on and off three phase loads up to 5 HP , 600 VAC 7.6 Amps. They are available in both contactor versions DRC3P and reversing contactor versions DRC3R. The Solicon Contactor DRC3P is available in either instantaneous turn-on (for Motor Control) or zero voltage turn-on (for Resistive Loads). It is available in either 2 or 3 controlled leg versions. The 2 legs control version is particularly suitable for motor control circuits where the neutral conductor is not utilized. The Solicon Reversing Contactor DRC3R includes an interlock control that allows only off, forward and reverse operation in a safe mode while providing high space saving; it switches instantaneously upon application of the control voltage unless an instantaneous change of direction is commanded, then it will delay the direction change by 100msec in order to prevent simultaneous forward and reverse operations. All the models of Solicon DRC Series with EMR Auxiliary Contacts combine the benefits and advantages of a solid state contactor with the functionality and simplicity of use of an electromechanical contactor thanks to the proprietary thermal management technology (Patented) and complete electrical insulation (no grounding required); the embedded EMR auxiliary contacts, normally open and/or normally closed, are intended to be used at 110VDC/140VAC. All models include overvoltage protection. PRODUCT SELECTION Control Voltage 1 NO + 1NC Auxiliary Contact 2 NO Auxiliary Contact
24 VAC/DC DRC3P48D433, DRC3P60D433
24 VDC
DRC3P48D440, DRC3P60D440 DRC3R40E440, DRC3R48E440 AVAILABLE OPTIONS Required for valid part number For options only and not required for valid part number DRC Series Operating Voltage 40: 400 VAC (3R function only) 48: 480 VAC 60: 600 VAC (3P function only) Control Voltage D: 18-30 VAC/DC (3P function only) E: 18-30 VDC (3R function only) Function 3P: Contactor 3R: Reversing Contactor
48 D3P
4: 7.6 Amp FLA (x2 Controlled Legs & 3R function);
4.8 Amp FLA
(x3 Controlled Legs only) Auxiliary Contacts, N.O. - N.C. 33: 1 Normally Open EMR ;
1 Normally Closed EMR
(3P function only) 40: 2 Normally Open EMR Switching Mode (3P function only) Blank: Zero Voltage Turn-On R: Instantaneous Turn-On Controlled Legs (3P function only) Blank: 3 Controlled Legs 2: 2 Controlled Legs R 2 FDE-07-01 REV. A
Do not forget to visit us at: www.crydom.com Copyright © 2017 Crydom Inc. Specifications subject to change without notice. OUTPUT SPECIFICATIONS (1) DRC3P48D4x2DRC3P48D4x Description Load Current, General Use UL508 /AC51 @40°C [ARMS] (4) 5 7.6 Load Current, Motor Controller UL508 /AC-53a @480VAC [ARMS] (4) 4.8 7.6 Minimum Load Current [ARMS] 0.15 0.15 Maximum Surge Current [Apk] 1 Cycle 60Hz 750 750 Maximum Surge Current [Apk] 1 Cycle 50Hz 716 716 Maximum I2t for Fusing (8.33msec)[A2sec] 2330 2330 Maximum I2t for Fusing (10msec)[A2sec] 2560 2560 Maximum On-State Voltage Drop @ Rated Current [VRMS] 1.15 per channel 1.15 per channel Minimum Power Factor (with Maximum Load) 0.5 0.5 Ratings according to UL 508/IEC60947-4-2 [HP/kW]: 240 VAC 1/.75 2/1.5 Ratings according to UL 508/IEC60947-4-2 [HP/kW]: 400 VAC 2/1.5 3/2.2 Ratings according to UL 508/IEC60947-4-2 [HP/kW]: 480 VAC 3/2.2 5/3.7 Operating Voltage (47-63Hz) [VRMS] 48-530 48-530 Transient Overvoltage [Vpk] (2)(3) 1200 1200 Maximum Off-State Leakage Current @ Rated Voltage [mARMS] 3.0 3.0 Maximum Off-State dv/dt @ Maximum Rated Voltage [V/µsec] 500 500 DRC3P60D4x2DRC3P60D4x 5 7.6 4.8 7.6 0.15 0.15 750 750 716 716 2330 2330 2560 2560 1.15 per channel 1.15 per channel 0.7 0.7 1/.75 2/1.5 2/1.5 3/2.2 3/2.2 5/3.7 48-600 48-600 1200 1200 1.0 1.0 500 500 DRC3R48E440DRC3R40E440 7.6 7.6 7.6 7.6 0.15 0.15 750 625 716 597 2330 1621 2560 1779 1.3 per channel 1.3 per channel 0.5 0.5 2/1.5 2/1.5 3/2.2 3/2.2 - 5/3.7 Motor Ratings @ 600 VAC [HP/kW] - - 3/2.2 5/3.7 - - 48-415 48-510 1200 1600 5.5 5.5 500 500 INPUT SPECIFICATIONS (1)
Description
Minimum Turn-On Voltage (5) Must Turn-Off Voltage Minimum Input Current (for on-state) [mA] Maximum Input Current [mA] Nominal Input Impedance [Ohms] Maximum Delay to Turn-On [msec] (6) Maximum Turn-Off Time [msec] (7) Option D 18-30 VAC / VDC
18 VAC / VDC
4 VAC / VDC
12.5 Current Regulated Option E 18-30 VDC
18 VDC
4 VDC
12.5 Current Regulated 100 ± 30 AUXILIARY CONTACTS(1) Transient Overvoltage [Vpk] Maximum Load Current [Adc/Arms] (8) Maximum Contact Rating [W] (8) Normally Open Suffix 40 [3P] 110VDC/ 140VAC 250 0.5/0.35 Normally Closed / Normally Open Suffix 33 110VDC/ 250VAC 250 0.3/0.25 33/62.5 Normally Open Suffix 40 [3R] 110VDC/ 140VAC 250 0.5/0.35 Maximum Turn-Off Time [msec] 30 2030 Maximum Delay to Turn-On [msec] 20 100±3020 Minimum Load Current [mA] 10 10 10 Mechanical Life Expectancy [Ops.] 108 108108 Maximum Delay to Turn-On [msec] 20 100±3020 Electrical Life Expectancy [Ops.] 105 105105 GENERAL SPECIFICATIONS(1) Description Parameters Dielectric Strength, Input/Output/Base (50/60Hz) (9) 3750 Vrms Minimum Insulation Resistance (@ 500 VDC) 109 Ohms Maximum Capacitance, Input/Output 20 pF Ambient Operating Temperature Range (10) -20 to 60 °C Ambient Storage Temperature Range -30 to 85 °C Weight (typical) 2 Controlled Legs (6.9 oz [197 g]) / 3 Controlled Legs (8.0 oz [228 g]) Housing Material UL94 V-0 Housing Color Black and Light Gray LED Status Indicator (color) (11) Forward (Green) / Reverse (Amber) Short Circuit Current Rating (12) 100kA Control and Auxiliary Contact Terminal Screw Torque Range (lb-in/Nm) 12 / 1.36 Load Terminal Screw Torque Range (lb-in/Nm) 15 / 1.7 Input Terminal Wire Capacity 18-12 AWG (IEC 1-4 mm2) (stranded /solid) Output Terminal Wire Capacity 18-10 AWG (IEC 1-6 mm2 ) (stranded /solid) Humidity 85% non-condensing Protection Degree (13) IP20 Pollution Degree 2
Do not forget to visit us at: www.crydom.com Copyright © 2017 Crydom Inc. Specifications subject to change without notice. (15) 20 30 40 50 60 Ambient Temperature (ºC) Load Current (Amps) THERMAL DERATE INFORMATION DRC3P (3 controlled legs) Single unit Multiple units (14) (15) Ambient Temperature (ºC) Load Current (Amps) DRC3P (2 controlled legs) & DRC3R Single unit Multiple units 20 30 40 50 60 EQUIVALENT CIRCUIT BLOCK DIAGRAMS/WIRING DIAGRAM INPUT STATUS 13 21 A1 14 22 A2 L1 L2 L3 T1 T2 T3 XXXX IND. CONT. EQ. DRC3PXXX433XX INPUT STATUS 13 23 A1 14 24 A2 L1 L2 L3 T1 T2 T3 XXXX IND. CONT. EQ. DRC3PXXX440XX DRC3Pxx433 DRC3Pxx440 48-530 VAC, 50-60 Hz 48-600 VAC, 50-60 Hz CONTROL INPUT / > / > / > 1st Auxiliary Contact (110VDC / 250 VAC) Normally Open 2nd Auxiliary Contact (110VDC / 250 VAC) Normally Closed CONTROL INPUT / > / > / > 1st Auxiliary Contact (110VDC / 140 VAC) Normally Open 2nd Auxiliary Contact (110VDC / 140 VAC) Normally Open Short circuit and overload current protection (see page 5) T1 T2 T3 General Use / T1 T2 T3 T1 T2 T3 T1 T2 T3 M Motor Controller / AC-53a Application DRC3Rxx440 INPUT STATUS 13 23 A1 14 24 A2 L1 L2 L3 T1 T2 T3 XXXX IND. CONT. EQ. DRC3RXXX440XX 48-415 VAC, 50 - 60 Hz 48-510 VAC, 50 - 60 Hz CONTROL INPUT (Reverse) / > / > / > 1st Auxiliary Contact (110VDC / 140 VAC) Normally Open 2nd Auxiliary Contact (110VDC / 140 VAC) Normally Open Short circuit and overload current protection (see page 5) T1 T2 T3 T1 T2 T3 M Motor Controller / AC-53a Application Overload current protection needs to be considered CONTROL INPUT (Forward) CONTROL INPUT (Common) DRC3P CONTACTOR (16) DRC3R REVERSING CONTACTOR(17)
Do not forget to visit us at: www.crydom.com Copyright © 2017 Crydom Inc. Specifications subject to change without notice. INSTALLATION INSTRUCTIONS Install the contactor on the DIN rail (as shown in fig.1). Wire the contactor to the input side. AWG #18 (1 mm 2) minimum, AWG #12 (4 mm2) x 2 maximum. Wire the contactor to the output side. AWG #18 (1 mm2) minimum, AWG #10 (6 mm2) x 2 (stranded/solid) maximum. Maximum recommended terminal screw torque input 12 lb-in (1.36 Nm) & output 15 lb-in (1.7 Nm). If multiple units are installed be sure to follow derating curves To remove from DIN rail To install on DIN rail fig. 1 fig. 2 Terminal screw type. Top/Bottom view. WARNING! Removing product from 35 mm rail incorrectly by not using the appropriate tool could damage the latching system DRC3P (3 controlled legs model) Main Circuit DRC3Pxx440 (2 Normally Open) Auxiliary Contacts DRC3P (2 controlled legs model) Main Circuit DRC3Pxx433 (1 Normally Open - 1 Normally Closed) Auxiliary Contacts DRC3R Forward Reverse DRC3Rxx440 models only ReverseForward EQUIVALENT CIRCUIT BLOCK DIAGRAMS/WIRING DIAGRAM
Do not forget to visit us at: www.crydom.com Copyright © 2017 Crydom Inc. Specifications subject to change without notice. SHORT CIRCUIT AND OVERLOAD PROTECTION FOR ALL DEVICES (Conforming to the IEC60947-4-2 and UL508) IEC standard 60947-4-1 make a distinction between two different types of protection, (called “coordination”), which are designated types “1” and "2". Any short-circuit that occurs is cleared safely by either type of coordination. The only difference between the 2 categories concerns the extent of the SSR damage caused by the short-circuit. Type "1" coordination requires that in the event of a short-circuit, the Solid State Contactor does not endanger personnel or installations, but permanent damage to the SSC is permissible. In this case the SSC may need to be replaced. For this type of co-ordination, the use of fusing or circuit breakers adequate to protect the system and wiring from short circuits, (but not specifically considering SSC protection), can be used. Type "2" coordination requires that under a short-circuit condition, the circuit is interrupted, the SSC does not endanger persons or installations, and in addition the SSR will be able to operate after the fault condition is repaired. Type of coordination 1 0.40-0.63 A GV2ME04 / GV2P04 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x 0.63-1 A GV2ME05 / GV2P05 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x 1-1.6 A GV2ME06 / GV2P06 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x 1.6-2.5 A GV2ME07 / GV2P07 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x 2.5-4 A GV2ME08 / GV2P08 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x 4-6.3 A GV2ME10 / GV2P10 DRC3Pxx4x2 DRC3Pxx4x (up to 4.8A) DRC3Rxx4x 6.3-10 A GV2ME14 / GV2P14 DRC3Pxx4x2 (up to 7.6A) - DRC3Rxx4x (up to 7.6A) Nominal Motor Current Thermal Magnetic Circuit Breaker (Schneider Electric) Solid State Contactor 2 controlled legs Solid State Contactor 3 controlled legs Solid State Contactor Reversing Protection by Thermal Magnetic Circuit Breaker (18) Protection by overload relays and fuses Nominal Motor Current Overload Relay (Schneider Electric) Class gG fuses (example from Littlefuse) Solid State Contactor 2 controlled legs Solid State Contactor 3 controlled legs Solid State Contactor Reversing 0.40-0.63 A LRD04 CY14X51G16 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x 0.63-1 A LRD05 CY14X51G16 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x 1-1.6 A LRD06 CY14X51G25 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x 1.6-2.5 A LRD07 CY14X51G25 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x 2.5-4 A LRD08 CY14X51G25 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x 4-6.3 A LRD10 CY14X51G40 DRC3Pxx4x2 DRC3Pxx4x(up to 4.8A) DRC3Rxx4x 6.3-10 A LRD14 CY14X51G40 DRC3Pxx4x2 (up to 7.6A) - DRC3Rxx4x (up to 7.6A) (18) Protection by overload relays and fuses Nominal Motor Current Overload Relay (Schneider Electric) Semiconductor fuses with less than 1621A2S Littlefuse Solid State Contactor 2 controlled legs Solid State Contactor 3 controlled legs Solid State Contactor Reversing 0.40-0.63 A LRD04 LA50QS40-4 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x 0.63-1 A LRD05 LA50QS40-4 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x 1-1.6 A LRD06 LA50QS40-4 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x 1.6-2.5 A LRD07 LA50QS40-4 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x 2.5-4 A LRD08 LA50QS40-4 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x 4-6.3 A LRD10 LA50QS40-4 DRC3Pxx4x2 DRC3Pxx4x (up to 4.8A) DRC3Rxx4x 6.3-10 A LRD14 LA50QS40-4 DRC3Pxx4x2 (up to 7.6A) - DRC3Rxx4x (up to 7.6A) (18) 50.058.06.40 50.058.06.40 50.058.06.40 50.058.06.40 50.058.06.40 50.058.06.40 50.058.06.40 A093909 A093909 A093909 A093909 A093909 A093909 A093909 SIBA (Cylindric) Ferraz (Cylindric) Type of coordination 2 Note: All the Schneider Electric Thermal magnetic circuit breakers GV2 family (GV2ME and GV2P) is fully mechanical compatible with the DRC contactor using the GV2AF3 connection block. All the Schneider Electric Overload relay LRD family is fully mechanical compatible with the DRC contactor without the need of any adapter. The DRC Series can accept the LAD7C1 module (pre-wiring kit allowing direct connection of the NC contact of relay LRD to the contactor)
Do not forget to visit us at: www.crydom.com Copyright © 2017 Crydom Inc. Specifications subject to change without notice. SWITCHING FREQUENCY/LOAD CHARACTERISTIC FOR ALL DEVICES IL : Load Operating Current IR : Rated Full Load Current [FLA] ID : Direct-On-Line Inrush Current tL : Load Operating Current Time tD : Direct-On-Line Inrush Current Time tC : Cycle Time tOn : On Time tOff : Off Time Without overload relay (limit given by the contactor itself) With overload relay (limit given by the overload relay itself) tD (sec) 0.1 1 10 100 0.05 5000 2700 350 35 0.1 3200 1950 350 35 0.2 950 320 35 0.4 500 280 35 0.8 290 160 35 1.6 110 30 3.2 75 25 tOn (sec) tD (sec) 0.1 1 10 100 0.05 6000 3550 350 35 0.1 4100 3000 350 35 0.2 1300 350 35 0.4 700 320 35 0.8 400 320 35 1.6 125 35 3.2 90 35 tOn (sec) tD (sec) 0.1 1 10 100 0.05 7450 3200 350 35 0.1 4050 2100 350 35 0.2 1200 350 35 0.4 650 320 35 0.8 350 280 35 1.6 180 35 3.2 90 35 tOn (sec) tD (sec) 0.1 1 10 100 0.05 9000 3550 350 35 0.1 5400 3550 350 35 0.2 1700 350 35 0.4 850 350 35 0.8 560 350 35 1.6 240 35 3.2 180 35 tOn (sec) tD (sec) 0.1 1 10 100 0.05 2200 1650 330 30 0.1 1500 1000 280 28 0.2 550 255 26 0.4 250 150 24 0.8 80 60 20 1.6 40 16 3.2 tOn (sec) tD (sec) 0.1 1 10 100 0.05 2800 1800 320 35 0.1 1700 1300 310 32 0.2 650 290 30 0.4 300 200 26 0.8 200 90 25 1.6 65 25 3.2 tOn (sec) tD (sec) 0.1 1 10 100 0.05 5150 2800 260 35 0.1 2850 1920 250 34 0.2 1100 250 33 0.4 600 200 32 0.8 320 200 30 1.6 120 25 3.2 75 20 tOn (sec) tD (sec) 0.1 1 10 100 0.05 5600 3200 350 35 0.1 3200 2700 350 35 0.2 1400 350 35 0.4 700 350 35 0.8 350 280 35 1.6 170 35 3.2 80 25 tOn (sec) Table 1
- High inrush current (ID/IR = 4 to 7.2)
- Full load (IL/IR= 1) Table 2
- High inrush current (ID/IR = 4 to 7.2)
- 60% load (IL/IR= 0.6) Table 3
- Low inrush current (ID/IR < 4 )
- Full load (IL/IR= 1) Table 4
- Low inrush current (ID/IR < 4 )
- 60% load (IL/IR= 0.6) Table 5
- High inrush current (ID/IR = 4 to 7.2)
- Full load (IL/IR= 1) Table 6
- High inrush current (ID/IR = 4 to 7.2)
- 60% load (IL/IR= 0.6) Table 7
- Low inrush current (ID/IR < 4 )
- Full load (IL/IR= 1) Table 8
- Low inrush current (ID/IR < 4 )
- 60% load (IL/IR= 0.6) ID IR IL tD tL tC tOn tOff MAXIMUM ALLOWABLE NUMBER OF STARTS PER HOUR DEPENDING ON THE STARTING TIME tD AND THE ON PERIOD tOn (as for standard IEC 60947-4-2) FOR ALL DEVICES - - - (19) Note: Please take into consideration the mechanical and electrical life expectancy of the EMR auxiliary contacts when selecting a DRC Series contactor for your application.
Do not forget to visit us at: www.crydom.com Copyright © 2017 Crydom Inc. Specifications subject to change without notice. FWD REV Open Close Open Close Input A1 Input A3 Open Open Close Close Off On Off Off Off Off On Off TIMING DIAGRAM 1, 4, 10 3, 9 STEP DESCRIPTION A1 is activated, FWD Output waits for 100msec FWD direction is activated A1 changes to off. FWD Output is disabled at the same time A3 is activated. REV Outputs waits for 100msec
6 REV direction is On
8 A3 is open, A1 is closed, activation delayed 100msec
7 Interlock fuction is activated. REV is disabled due to A1 & A3 both being active Initial Condition. A1 & A3 open Input/Output 1 2 3 4 5 6 7 8 9 10 Input A1 Input A3 FWD Direction 100 msec 100 msec REV Direction 100 msec TIMING DIAGRAM FOR DRC3R interlock MECHANICAL SPECIFICATIONS Tolerances: ±0.02 in / 0.5 mm All dimensions are in: inches [millimeters] INPUT STATUS XXXX IND. CONT. EQ. DRC3 1.23 [31.3] 2.29 [58.3] 2.58 [65.5] 1.68 [42.7]3.41 [86.7] 1.78 [45.3] 3.76 [95.6] 3.51 [89] 2.91 [73.9] 0.23 [5.8] A3 2313 2414
Do not forget to visit us at: www.crydom.com Copyright © 2017 Crydom Inc. Specifications subject to change without notice. ACCESSORIES FOR ALL DEVICES Recommended Accessories Motor Nominal Current Thermal Magnetic Circuit Breaker (Push Button) Thermal Magnetic Circuit Breaker (Selector) 0.40 - 0.63 A 0.63 - 1 A 1 - 1.6 A 1.6 - 2.5 A 2.5 - 4 A 4 - 6.3 A 6.3 - 10 A Fully compatible with Schneider Electric thermal overload relays & thermal magnetic circuit breakers LRD04 LRD05 LRD06 LRD07 LRD08 LRD10 LRD14 GV2ME04 GV2ME05 GV2ME06 GV2ME07 GV2ME08 GV2ME10 GV2ME14 GV2P04 GV2P05 GV2P06 GV2P07 GV2P08 GV2P10 GV2P14 LR97 D015xx LR97 D015xx LR97 D07xx LR97 D07xx LR97 D07xx LR97 D25xx LR97 D25xx Bimetal Overload Relay Electronic Overload Relay ID Marker Strips CNLB, CNLN, CNL2 Packages of 10 plastic strips comprising 10 individual markers which can be placed for easy identification during the use of multiple units. Blank Strips Part no.: CNLB Numbered 1 to 10 Strips Part no.: CNLN Numbered 11 to 20 Strips Part no.: CNL2 Note: All the Schneider Electric Thermal magnetic circuit breakers GV2 family (GV2ME and GV2P) is fully mechanical compatible with the DRC contactor using the GV2AF3 connection block. All the Schneider Electric Overload relay LRD family is fully mechanical compatible with the DRC contactor without the need of any adapter. The DRC Series can accept the LAD7C1 module (pre-wiring kit allowing direct connection of the NC contact of relay LRD to the contactor) When the LAD7C1 module is used, the common terminal for the control input is not anymore the ”A2” terminal of DRC but it is the “96” terminal of the overload relay.
Do not forget to visit us at: www.crydom.com Copyright © 2017 Crydom Inc. Specifications subject to change without notice. AGENCY APPROVALS, CONFORMANCES AND EMC Approvals E116949 Conformances Vibration Resistance Shock Resistance IEC 60068-2-6: Amplitude Range 10-55 Hz, Displacement 0.75 mm IEC 60068-2-27: Peak Acceleration 15g, Duration 11ms. United States Standard for Industrial Control Equipment - UL 508 and Canadian Standard Association for Industrial Control Equipment – C22.2 No. 14. Electromagnetic Compatibility Generic Standard Immunity Tests Test Specification Level IEC 61000-6-2 Immunity for Industrial Environments Electrostatic Discharge IEC 61000-4-2 Fast transients (burst) IEC 61000-4-4 Surge IEC 61000-4-5 8kV air discharge 6kV contact discharge Output 2kV, 5kHz, 100kHz Input 1kV, 5kHz, 100kHz 1kV Line to Line 2kV Line to Earth Output Performance Criterion A Criterion A Criterion B Criterion A Criterion B Criterion B GENERAL NOTES (1) All parameters at 25°C unless otherwise specified. (2) For DRC3P relay will self trigger between 900-1200V, Not suitable for capacitive loads. (3) For DRC3R over rated voltage internal self protection will be activated increasing leakage current. (4) Mounted in the Vertical position. (5) For low temperature operation consider nominal control voltage. (6) For DRC3P Instantaneous Turn-on, turn-on time is 4 msec. (7) When control signal is completely removed. For DRC3R the turn-off time is 20msec. (8) Operating voltage / current on auxiliary contacts must not exceed the power rating (Resistive load). (9) For input to auxiliary output the dielectric strength is 1060 Vrms. (10) UL approval up to 40°C surrounding temperature. (11) Reverse Amber Indicator is for DRC3R models only. (12) 100kA, 480VAC, when protected with CC class fuses rated 600VAC, 20 A or equivalent. (13) IP20 rating is not associated with the UL approval. (14) Derate information is valid when DCR contactors are used with or without accessories, installed on top and/or bottom. (15) Minimum spacing to obtain max. current is 22mm between adjacent units. (16) For DRC3P models external loads can be connected in parallel to the control input. (17) DRC3R internal safety interlock circuit prevents the product to work if any leakage current is present in the control input currently not enabled. (18) Combinations of these Protective Devices and Solid State Contactor have not been evaluated by UL. (19) Only main circuit, not apply for auxiliary contacts. Rev. 071917 ECN 20277
Do not forget to visit us at: www.crydom.com Copyright © 2017 Crydom Inc. Specifications subject to change without notice. DANGER / PELIGRO / DANGER /GEFAHR / PERICOLO / 危险危险 HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH.
- Disconnect all power before installing or working with this equipment.
- Verify all connections and replace all covers before turning on power. Failure to follow these instructions will result in death or serious injury. RIESGO DE DESCARGA ELECTRICA O EXPLOSION.
- Desconectar todos los suministros de energia a este equipo antes de trabajar con este equipo.
- Verificar todas las conexiones y colocar todas las tapas antes de energizer el equipo. El incumplimiento de estas instrucciones puede provocar la muerte o lesiones serias. RISQUE DE DESCHARGE ELECTRIQUE OU EXPLOSION
- Eteindre toutes les sources d'énergie de cet appareil avant de travailler dessus de cet appareil
- Vérifier tous connections, et remettre tous couverts en olace avant de mettre sous De non-suivi de ces instructions provoquera la mort ou des lésions sérieuses sérieuses. GEFAHR EINES ELEKTRISCHE N SCHLAGES ODER EINER EXPLOSION.
- Stellen Sie jeglichen Strom ab, der dieses Gerät versorgt, bevor Sie an dem Gerät Arbeiten durchführen
- Vor dem Drehen auf Energie alle Anschlüsse überprüfen und alle Abdeckungen ersetzen. Unterlassung dieser Anweisungen können zum Tode oder zu schweren Verletzungen führen. RISCHIO DI SCOSSA ELETTRICA O DELL’ESPLOSIONE.
- Spenga tutta l'alimentazione che fornisce questa apparecchiatura prima di lavorare a questa apparecchiatura
- Verificare tutti i collegamenti e sostituire tutte le coperture prima dell’accensione L'omissione di queste istruzioni provocherà la morte o lesioni serie 存在电击、 爆炸或电弧 闪烁危险
- 在操作此设 备之前请先 关闭电源。 若不遵守这些说明, 可能会导致严重的 人身伤害甚至死亡。 WARNING / AVERTISSEMENT / WARNUNG /ADVERTENCIA / AVVERTENZA / 警告 RISK OF MATERIAL DAMAGE AND HOT ENCLOSURE
- The product's side panels may be hot, allow the product to cool before touching.
- Follow proper mounting instructions including torque values.
- Do not allow liquids or foreign objects to enter this product. Failure to follow these instructions can result in serious injury, or equipment damage. RISQUE DE DOMMAGE MATERIEL ET DE SURCHAUFFE DU BOITIER
- Les panneaux latéraux du produit peuvent être chauds. Laisser le produit refroidir avant de le toucher.
- Respecter les consignes de montage, et notamment les couples de serrage.
- Ne pas laisser pénétrer de liquide ni de corps étrangers à l'intérieur du produit. Le non-respect de cette directive peut entraîner, des lésions corporelles graves ou des dommages matériels. Die Nichtbeachtung dieser Anweisung kann Körperverletzung oder Materialschäden zur Folge haben. GEFAHR VON MATERIALSCHÄDEN UND GEHÄUSEERHITZUNG
- Die Seitenwände können heiß sein. Lassen Sie das Produkt abkühlen, bevor Sie es berühren.
- Beachten Sie die Montageanweisungen,
- Führen Sie keine Flüssigkeiten oder Fremdkörper in das Produkt ein. Si no se respetan estas precauciones pueden producirse graves lesiones, daños materiales. RIESGO DE DAÑOS MATERIALES Y DE SOBRECALENTAMIENTO DE LA UNIDAD
- Los paneles laterales del producto pueden estar calientes. Esperar que el producto se enfríe antes de tocarlo.
- Respetar las instrucciones de montaje, y en particular los pares de apretado.
- No dejar que penetren líquidos o cuerpos extraños en el producto. La mancata osservanza di questa precauzione può causare gravi rischi per l'incolumità personale o danni alle apparecchiature. RISCHIO DI DANNI MATERIALI E D'INVOLUCRO CALDO
- I pannelli laterali dell'apparecchio possono scottare; lasciar quindi raffreddare il prodotto prima di toccarlo.
- Seguire le istruzioni di montaggio corrette.
- Non far entrare liquidi o oggetti estranei in questo apparecchio. 如不能正确执行这些操作说明, 极有可能造成严重人体伤害或者设备的损坏。 材料损和高温外壳的危险性
- 产品的一侧面板可能很热,在其冷却前请 不要触碰。
- 遵照正确的安装说明,包括扭矩值。
- 请勿让液体及其他异物进入本产品。
Do not forget to visit us at: www.crydom.com Copyright © 2017 Crydom Inc. Specifications subject to change without notice. ANNEX - ENVIROMENTAL INFORMATION The environmental information disclosed in this annex including the EIP Pollution logo are in compliance with People’s Republic of China Electronic Industry Standard SJ/T11364 – 2006, Marking for Control of Pollution Caused by Electronic Information Products. Part Name Toxic or hazardous Substance and Elements Lead Mercury Cadmium Hexavalent Polybrominated Polybrominated (Pb) (Hg) (Cd) Chromium (Cr (VI)) biphenyls (PBB) diphenyl ethers (PBDE) Semiconductor die Solder 附件 - 环保信息 此附件所标示的包括电子信息产品污染图标的环保信息符合中华人民共和国电子行业标准 SJ/T11364 - 2006, 电子信息产品污染控制标识要求。 有毒有害物质或元素件部 名称 铅 汞 镉 六价铬 多溴联苯 多溴二苯醚 (Pb) (Hg) (Cd) (Cr (VI)) (PBB) (PBDE) 半导体芯片 焊接点