60W Single Output with Battery Charger (UPS Function) DRC-60 seri es File Name:DRC-60-SPEC 2014-1122 Bauar Sicherheit egel gema t gepruft od be www. ID 2000000000 tuv.com wac g o s LPS
60W Single Output with Battery Charger (UPS Function) DRC-60 seri es MODEL DC VOLTAGE OUTPUT NUMBER RATED CURRENT CURRENT RANGE RATED POWER OUTPUT VOLTAGE ADJ. RANGE LINE REGULATION LOAD REGULATION SETUP, RISE TIME Note.4 HOLD UP TIME (Typ.) VOLTAGE RANGE FREQUENCY RANGE EFFICIENCY (Typ.)INPUT INRUSH CURRENT (Typ.) SAFETY STANDARDS WORKING TEMP. BATTERY CUT OFF WORKING HUMIDITY STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION MTBF DIMENSIONOTHERS NOTE PACKING OVERLOAD OVER VOLTAGE AC CURRENT (Typ.) 400ms, 50ms/230VAC 800ms, 50ms/115VAC at full load 50ms/230VAC 10ms/115VAC at full load 90 ~ 264VAC 127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)] 47 ~ 63Hz 86% CH1:28.98 ~ 37.26V 20±1V 88% 1.3A/115VAC 0.8A/230VAC COLD START 30A/115VAC 60A/230VAC 105 ~ 150% rated output power CH1:14.49 ~ 18.63V Protection type : Hiccup mode, recovers automatically after fault condition is removed Protection type : Shut down o/p voltage, re-power on to recover UL60950-1, TUV EN60950-1 approved Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3 Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61204-3, light industry level, criteria A -30 ~ +70℃ (Refer to "Derating Curve") 10±0.5V 20 ~ 90% RH non-condensing ±0.03%/℃ (0 ~ 50℃) on CH1 output 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes 504.1K hrs min. MIL-HDBK-217F (25℃) 40*90*100mm (W*H*D) 0.3Kg; 42pcs/13.6Kg/0.82CUFT DRC-60B 27.6V13.8V 27.6V CH1CH2 CH2 1.4A1.5A 0.75A 59.34W CH1:24 ~ 30V ±1.0% ±0.5% ±0.5% DRC-60A 13.8V CH1 2.8A 0 ~ 4.3A 59.34W 120mVp-p CH1:12 ~ 15V ±1.0% ±0.5% ±0.5% RIPPLE & NOISE (max.) Note.2 VOLTAGE TOLERANCE Note.3 ENVIRONMENT PROTECTION WITHSTAND VOLTAGE ISOLATION RESISTANCE I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH SAFETY & EMC (Note 5) EMC IMMUNITY EMC EMISSION AC OK BATTERY LOW Battery low voltage : < 22V FUNCTION Relay contact output, ON : AC OK ; OFF : AC Fail ; max. rating : 30V/1A Relay contact output, OFF : Battery OK ; ON : Battery Low ; max. rating : 30V/1A Battery low voltage : < 11V File Name:DRC-60-SPEC 2014-10-22
O.L.P. EMI FILTER RECTIFIER POWER SWITCHING FILTER RECTIFIERS +V Bat. + Battery Charger Back up Control AC OK Bat. - Bat. Low I/P CONTROL PWM O.V.P. AMBIENT TEMPERATURE (℃) LOAD (%) INPUT VOLTAGE (V) 60Hz 90 100 125 135 145 155 165 175 180 200 230 264 100 LOAD (%) 175 LOAD (%) 230VAC Input only 100 (VERTICAL)-20 0 15 300 40 50-30 60 70 60W Single Output with Battery Charger (UPS Function) DRC-60 seri es File Name:DRC-60-SPEC 2014-10-22 Derating Curve Static Characteristics Block Diagram
1.Backup connection for AC interruption (1) Please refer to Fig1.1 for suggested connection. The power supply charges the battery and provides energy to the load at the same time when AC mains is OK. The battery starts to supply power to the load when AC mains fails. 60W Single Output with Battery Charger (UPS Function) DRC-60 seri es File Name:DRC-60-SPEC 2014-10-22 2.Alarm signal for AC OK and battery low (1) Alarm Signal is sent out through " AC OK " & " Battery Low " pins via relay contact. (2) An external voltage source is required for this function. The maximum applied voltage is 30V and the maximum sink current is 1A. Please refer to Fig 2.2. (3) Table2.1 explains the alarm function built in the power supply V-V+Bat-Bat+ Load A : 12V B : 24V Battery ++ -- Fig 1.1 Suggested system connection External voltage sorece (V) and resistor (R) (The max. Sink is 1A and 30V) AC OK (Battery low) Fig 2.2 Internal circuit of AC OK (Battery Low), via relay contact Function Output of alarm Low or short Low or short High or open (External applied voltage 30V max.) High or open (External applied voltage 30V max.)
Description
The signal is "Low" when the power supply turns ON. The signal is "Low" when the voltage of battery is under A:11V, B:22V. The signal is "High" when the voltage of battery is above A:11V, B:22V. The signal turns to be "High" when the power supply turns OFF. AC OK Battery Low Table 2.1 Explanation of alarm signal (4) AC OK signal (RL1,referring to Block Diagram) will go into hiccup mode when the overload protecton is activated. R V DC OK +V ADJ
60W Single Output with Battery Charger (UPS Function) DRC-60 seri es Terminal Pin No. Assignment (TB2): Terminal Pin No. Assignment (TB1): Pin No. Pin No. Pin No. 5,6 7,8 Assignment Assignment Assignment AC/L or DC+ Bat. + AC/N or DC- FG AC OK Bat. Low Bat. - Mechanical SpecificationMechanical Specification Installation Instruction Back View Mechanical SpecificationMechanical Specification Case No.962A Unit:mm This series fits DIN rail TS35/7.5 or TS35/15. (This diagram is for reference. The rail is not included with unit.) 12345678 TB1 TB2 DC OK +V ADJ 3.81×7 7.57.5 File Name:DRC-60-SPEC 2014-10-22 100