File Name:DRC-180-SPEC 2022-03-02 180W Single Output with Battery Charger(UPS Function) DRC-180 seri es

(as available on http://www.meanwell.com) 0.71Kg; 12pcs/10.5Kg/1.02CUFT File Name:DRC-180-SPEC 2022-03-02 180W Single Output with Battery Charger(UPS Function) DRC-180 seri es OUTPUT SAFETY STANDARDS UL62368-1, Dekra BS EN/EN62368-1, , AS/NZS 62368.1 approved EAC TP TC 004 WITHSTAND VOLTAGE ISOLATION RESISTANCE I/P-O/P:3KVAC I/P-FG:2.0KVAC O/P-FG:0.5KVAC I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH SAFETY & EMC (Note 7) SPECIFICATION WORKING TEMP. WORKING HUMIDITY STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION -20 ~ +70℃ (Refer to "Derating Curve") 20 ~ 90% RH non-condensing -20 ~ +85℃, 10 ~ 95% RH non-condensing ±0.03%/℃ (0~40℃) on CH1 output 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes ENVIRONMENT RATED CURRENT CURRENT RANGE RATED POWER VOLTAGE RANGE FREQUENCY RANGE EFFICIENCY (Typ.)INPUT ALARM INRUSH CURRENT (Typ.) LEAKAGE CURRENT AC OK Note.5 BATTERY LOW AC CURRENT (Typ.) 90 ~ 264VAC 127 ~ 370VDC 47 ~ 63Hz 88% 2.5A/115VAC 1.5A/230VAC COLD START 35A/115VAC 70A/230VAC <2mA / 240VAC FUNCTION Battery low voltage : < 11V Battery low voltage : < 22V Relay contact output, Closed : AC OK ; Open : AC Fail ; Max. rating : 30V / 1A Relay contact output, Open : Battery OK ; Closed : Battery Low ; Max. rating : 30V / 1A 4.5A 0 ~ 6.5A 179.4W 4A(Battery charger) 0 ~ 13A 179.4W POWER FACTOR (Typ.) PF≧0.95/230VAC PF≧0.98/115VAC at full load 90% MODEL DRC-180BDRC-180A DC VOLTAGE 27.6V CH1 13.8V CH2 13.8V CH1OUTPUT NUMBER VOLTAGE ADJ. RANGE LINE REGULATION LOAD REGULATION SETUP, RISE TIME Note.4 HOLD UP TIME (Typ.) 2000ms, 30ms/230VAC 2000ms, 30ms/115VAC at full load 20ms/230VAC 20ms/115VAC at full load 240mVp-p CH1: 24 ~ 29V ±1.0% ±0.5% ±0.5% 150mVp-p CH1: 12 ~ 15V ±1.0% ±0.5% ±0.5% RIPPLE & NOISE (max.) Note.2 VOLTAGE TOLERANCE Note.3 OVERLOAD OVER VOLTAGE BATTERY CUT OFF CH1:30.5 ~ 37.7V 20±1V 105 ~ 150% rated output power CH1:15.8 ~ 19.5V Protection type : Hiccup mode, recovers automatically after fault condition is removed Protection type : Shut down o/p voltage, re-power on to recover 10±0.5V PROTECTION 2A(Battery charger) 27.6V CH2 ESD Radiated EFT / Burst Surge Conducted Magnetic Field Voltage Dips and Interruptions BS EN/EN61000-4-2 BS EN/EN61000-4-3 BS EN/EN61000-4-4 BS EN/EN61000-4-5 BS EN/EN61000-4-6 BS EN/EN61000-4-8 BS EN/EN61000-4-11 Level 3, 8KV air ; Level 2, 4KV contact ; criteria A Level 2, 3V/m ; criteria A Level 2, 1KV ; criteria A Level 3, 1KV/Line-Line 2KV/Line-Earth ; criteria A Level 2, 3V ; criteria A Level 1, 1A/m ; criteria A >95% dip 0.5 periods, 30% dip 25 periods, >95% interruptions 250 periods Conducted Parameter Parameter Radiated Standard Standard Test Level / Note Test Level / Note Class BBS EN/EN55032(CISPR32) BS EN/EN55032(CISPR32) Class B BS EN/EN55024 OPERATING ALTITUDE Note.6 OVER VOLTAGE CATEGORY 5000 meters / OVCⅡ Ⅱ; According to Dekra BS EN/EN62368-1; altitude up to 5000 meters OVER TEMPERATURE Shut down o/p voltage, re-power on to recover 1536.3K hrs min. Telcordia SR-332 (Bellcore); 245.6K hrs min. MIL-HDBK-217F (25℃)

O.L.P. EMI FILTER RECTIFIER POWER SWITCHING FILTER RECTIFIERS +V Bat. + Battery Charger Back up Control AC OK Bat. - Bat. Low CONTROL PWM O.V.P. O.T.P. 180W Single Output with Battery Charger(UPS Function) DRC-180 seri es PFC CIRCUITI/P FG File Name:DRC-180-SPEC 2022-03-02 Output Derating VS Input Voltage INPUT VOLTAGE (VAC) 60Hz 90 10095 120115 160140 200180 240220 264 LOAD (%) 100 Output Derating AMBIENT TEMPERATURE (℃) LOAD (%) -20 0 2010 30 40 100 6050 70 (Vertical)

TB3 Pin2(Pin4) External voltage source (V) and resistor (R) (The max. Sink is 1A and 30V) 1.Backup connection for AC interruption 2.Alarm signal for AC OK and Battery Low (1) Please refer to the Fig1.1 for suggested connection. (1) Alarm signal is sent out through " AC OK " & " Battery Low " pins.(relay contact type) (2) An external voltage source is required for this function. The maximum applied voltage is 30V and the maximum sink current is 1A. (3) Table2.1 explains the alarm function built in the power supply AC OK (Battery Low) TB3 Pin1(Pin3) Function Output of Alarm Closed Open

Description

when the power supply turns ON when the voltage of battery is under A:11V, B:22V when the voltage of battery is above A:11V, B:22V when the power supply turns OFFAC OK Battery Low The power supply charges the battery and provides energy to the load at the same time when the AC main is OK. The battery starts to supply power to the load when the AC mains fails. Fig 1.1 Suggested system connection Table 2.1 Explanation of Alarm Signal R V Closed Open 180W Single Output with Battery Charger(UPS Function) DRC-180 seri es (4) RL1 (AC OK)signal will go into hiccup mode when the overload protection is activating. Fig 2.2 Internal circuit of AC OK (Battery Low) File Name:DRC-180-SPEC 2022-03-02

Mechanical SpecificationMechanical Specification AC OK Bat+ Bat- 180W Single Output with Battery Charger(UPS Function) DRC-180 seri es File Name:DRC-180-SPEC 2022-03-02 Case No. 979G Unit:mm Terminal Pin No. Assignment (TB1) Terminal Pin No. Assignment (TB3) Pin No. Pin No. Assignment Assignment FG AC/L AC/N 1 2 3 4 1 2 1 2 3 125.2 115 TB1 TB3 DC OK +V ADJ. 3 4 1,2 3,4 Installation Manual Please refer to : http://www.meanwell.com/manual.html Installation Instruction ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15 (For reference only. Not included with unit.) This series fits DIN rail TS35/7.5 or TS35/15. For installation details, please refer to the Instruction manual. TB2 Terminal Pin No. Assignment (TB2) Pin No. Assignment