DR06D03 SENSATA | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 6
Technical content
Features
Applications
- Ratings from 3 up to 24 Amps
- Load voltage ratings of 1-60 VDC and 1-100 VDC
- Fits standard 35mm DIN Rail
- LED input status indicator
- DC control
- UL and cUL Listed, CE & RoHS Compliant
- UL 508 Endurance Rating for Enhanced Reliability
- UL Class I and II, Division 2, for Hazardous Locations
- Battery Management Systems
- Backup Power Supplies
- Valve Control
- Lighting control
- Automation Equipment Sensata | Crydom SeriesOne DR family of DIN Rail mount Solid State Relays incorporate proprietary thermal management technology to achieve exceptional output ratings of 3 up to 24 Amps at 1 to 100 VDC in compact 11mm and 18mm wide housings. These compact SSRs are ideal for use in demanding applications where space may be limited, providing greater power density than other DIN Rail Solid State Relays. Control Voltage 60V, 3 A 60V, 6 A 60V, 12 A 100V, 3 A 100V, 6 A 100V, 10A 100V, 12A 100V, 24 A 4-32 VDC DR06D03 DR06D06 DR06D12 DR10D03 DR10D06 DR10D10 DR10D12 DR10D24 PRODUCT SELECTION 3, 6 & 10 Amps 12 & 24 Amps
www.sensata.comCopyright © 2022 Sensata Technologies, Inc. Input (1) Description Parameters Control Voltage Range (3) 4-32 VDC Minimum Turn-On Voltage 4.0 VDC Must Turn-Off Voltage 1.0 VDC Minimum Input Current for [mA] (4) 9 Maximum Input Current for [mA] (4) 11 Maximum Turn-on Time [msec] (5) 0.6 Maximum Turn-off Time [msec] 0.3 Min/Max stranded/solid wire 22/16 AWG SPECIFICATIONS Output (1) Description DR06D03 DR10D03 DR06D06 DR10D06 DR10D10 DR06D12 DR10D12 DR10D24 Operating Voltage [VDC] 1-60 1-100 1-60 1-60 1-100 1-60 1-60 1-100 Maximum Load Current [Adc] (2) 3 3 6 6 10 12 12 24 Maximum Off-State Leakage Current Maximum On-State Voltage Drop @ Maximum Surge Current (10ms) [Apk] 60 60 60 60 80 100 100 160 On-State resistance at rated current Min/Max stranded wire 22/14 AWG 22/14 AWG 22/14 AWG 22/14 AWG 22/14 AWG 22/14 AWG 22/14 AWG 22/14 AWG Min/Max solid wire 22/14 AWG 22/14 AWG 22/14 AWG 22/14 AWG 22/14 AWG 22/14 AWG 22/14 AWG 22/14 AWG Weight (Typical) 1.76 oz (50 g) 1.76 oz (50 g) 1.94 oz (55 g) 1.76 oz (50 g) 1.76 oz (50 g) 3.17 oz (90 g) 3.17 oz (90 g) 3.17 oz (90 g) General (2) Description Parameters Dielectric Strength, Input/Output/Base (50/60Hz)
2500 Vrms
Minimum Insulation Resistance (@ 500 V DC)
109 Ohms
Maximum Capacitance, Input/Output 10 pF Ambient Operating Temperature Range -30 to 80 °C Ambient Storage Temperature Range -30 to 100 °C Recommended Terminal Screw Torque Range
www.sensata.comCopyright © 2022 Sensata Technologies, Inc. EQUIVALENT CIRCUIT BLOCK DIAGRAMS/WIRING DIAGRAMS MECHANICAL SPECIFICATIONS (1)
3 A , 6 A & 10 A 12 A & 24 A
THERMAL DERATE INFORMATION
www.sensata.comCopyright © 2022 Sensata Technologies, Inc. STANDARDS OF COMPLIANCE Shock and Vibration (Applies to all part numbers) Vibration Resistance according to IEC 60068-2-6: 0.35mm and 0.75mm Amplitude over 10-55 Hz Shock Resistance according to IEC 60068-2-27: 15g/11ms EMC (Applies to all part numbers) IEC 61000-4-2: Electrostatic Discharge- Level 3 IEC 61000-4-4: Electrically Fast Transients- Level 3 IEC 61000-4-5: Electrical Surges- Level 3 ANSI / ISA 12.12.01-2013 Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Division 1 and 2 Hazardous (classified) locations This equipment is open-type device and is meant to be installed in an enclosure suitable for the enviroment such that the equipment is only accesible with the use of a tool suitable for use in Class 1, Division 2, Group A,B,C and Hazardous locations, or Nonhazardous locations only WARNING-Explosion Hazard- Do not disconnect equipment while the circuit is live or unless the area is known to be free of ignitable concentrations WARNING-Explosion Hazard- Substitution of any component may impair suitability for Class I, Division 2 DR10D10 DR10D24 Single and multiple units (for DRxxx03) Single unit, distance to adjacent components ≥ 11 mm for DRxxx06, DR10D10 and ≥ 18 mm for DRxxx12, DR10D24 Multiple units, no minimum spacing between components
www.sensata.comCopyright © 2022 Sensata Technologies, Inc. Series DR Operating Voltage 06: 1-60 VDC 10: 1-100 VDC Control Voltage D: 4-32 VDC Rated Load Current 03: 3 Amps 06: 6 Amps 10: 10 Amps (100 VDC only) 12: 12 Amps 24: 24 Amps (100 VDC only) ATEX Approvals Blank: Not ATEX approved X: ATEX II 3G Ex nA IIC T4 Gc approved (3, 6 and 12 Amps only) ORDERING OPTIONS Example : DR06D12 Required for valid part number For options only and not required for valid part number (1) All parameters at 25°C unless otherwise specified. (2) See Derating curves (3) DC control includes reverse polarity protection. (4) Input circuitry incorporates active current limiter. (5) Turn-on/off time for 10A is 0.5/0.3 msec & for 24A is 1/0.5 msec. GENERAL NOTES AGENCY APPROVALS & CERTIFICATIONS (3, 6 and 12 Amps only) DR 06 D 12 SSR Relay, DIN Rail Mount 18mm, 60VDC/12A,4-32VDC In, FET Output
+1 (877) 502 5500 – Option 2 sales.crydom@sensata.com Europe, Middle East & Africa +44 (1202) 416170 ssr-info.eu@sensata.com Asia Pacific sales.isasia@list.sensata.com China +86 (21) 2306 1500 Japan +81 (45) 277 7117 Korea +82 (31) 601 2004 India +91 (80) 67920890 Rest of Asia +886 (2) 27602006 ext 2808 Rev:08/26/2022 ECN 21137 FDE-07-01 Rev. B www.sensata.com CONTACT USCopyright © 2022 Sensata Technologies, Inc. Sensata Technologies, Inc. (“Sensata”) data sheets are solely intended to assist designers (“Buyers”) who are developing systems that incorporate Sensata products (also referred to herein as “components”). Buyer understands and agrees that Buyer remains responsible for using its independent analysis, valuation, and judgment in designing Buyer’s systems and products. Sensata data sheets have been created using standard laboratory conditions and engineering practices. Sensata has not conducted any testing other than that specifically described in the published documentation for a particular data sheet. Sensata may make corrections, enhancements, improvements, and other changes to its data sheets or components without notice. Buyers are authorized to use Sensata data sheets with the Sensata component(s) identified in each particular data sheet. HOWEVER, NO OTHER LICENSE, EXPRESS OR IMPLIED, BY ESTOPPEL OTHERWISE TO ANY OTHER SENSATA INTELLECTUAL PROPERTY RIGHT, AND NO LICENSE TO ANY THIRD PARTY TECHNOLOGY OR INTELLECTUAL PROPERTY RIGHT, IS GRANTED HEREIN. SENSATA DATA SHEETS ARE PROVIDED “AS IS”. SENSATA MAKES NO WARRANTIES OR REPRESENTATIONS WITH REGARD TO THE DATA SHEETS OR USE OF THE DATA SHEETS, EXPRESS, IMPLIED, OR STATUTORY , INCLUDING ACCURACY OR COMPLETENESS. SENSATA DISCLAIMS ANY WARRANTY OF TITLE AND ANY IMPLIED WARRANTIES OF MERCHANTABILITY , FITNESS FOR A PARTICULAR PURPOSE, QUIET ENJOYMENT, QUIET POSSESSION, AND NON-INFRINGEMENT OF ANY THIRD PARTY INTELLECTUAL PROPERTY RIGHTS WITH REGARD TO SENSATA DATA SHEETS OR USE THEREOF. All products are sold subject to Sensata’s terms and conditions of sale supplied at www.sensata.com SENSATA ASSUMES NO LIABILITY FOR APPLICATIONS ASSISTANCE OR THE DESIGN OF BUYERS’ PRODUCTS. BUYER ACKNOWLEDGES AND AGREES THAT IT IS SOLELY RESPONSIBLE FOR COMPLIANCE WITH ALL LEGAL, REGULATORY , AND SAFETY-ELATED REQUIREMENTS CONCERNING ITS PRODUCTS, AND ANY USE OF SENSATA COMPONENTS IN ITS APPLICATIONS, NOTWITHSTANDING ANY APPLICATIONS-RELATED INFORMATION OR SUPPORT THAT MAY BE PROVIDED BY SENSATA. Mailing Address: Sensata Technologies, Inc., 529 Pleasant Street, Attleboro, MA 02703, USA ACCESSORIES WARNINGS RISK OF MATERIAL DAMAGE AND HOT ENCLOSURE
- The product’s side panels may be hot, allow the product to cool before touching
- Follow proper mounting instructions including torque values
- Do not allow liquids or foreign objects to enter this product Failure to follow these instructions can result in serious injury, or equipment damage. HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
- Disconnect all power before installing or working with this equipment
- Verify all connections and replace all covers before turning on power Failure to follow these instructions will result in death or serious injury. ID Marker Strips CNLB, CNLN, CNL2 Black Strips Part no.: CNLB Numbered 1 to 10 Strips Part no.: CNLN Numbered 11 to 20 Strips Part no.: CNL2 A package of 10 plastic strips comprising 10 individual unprinted markers which can be placed on sockets’ terminal block for easy identification during the use of multiple units. A package of 10 plastic strips comprising 10 markers printed individually from 1 to 10 which can be placed on sockets’ terminal block for easy identification during the use of multiple units. A package of 10 plastic strips comprising 10 markers printed individually from 11 to 20 which can be placed on sockets’ terminal block for easy identification during the use of multiple units.