03/26/2014 HPL-ED2014 V2.13 EN 1 / 5 Auxiliary￿contact￿module,￿1N/O+1N/C Part￿no. DILM32-XHI11 Article￿no. 277376 Catalog￿No. XTCEXFDC11 Delivery￿programme Product range Accessories Accessories Auxiliary contact modules Description with interlocked opposing contacts Function for standard applications Pole 2 pole Connection technique Screw terminals Rated operational current AC-3 Conventional free air thermal current, 3 pole, 50 - 60 Hz Open at 60 °C Ith =Ie A 16 AC-15

220 V 230 V 240 V Ie A 4

380 V 400 V 415 V Ie A 4

N/O = Normally open 1 N/O N/C = Normally closed 1 NC Mounting type Front fixing Contact sequence For use with DILM(C)7-10… DILM(C)9-10… DILM(C)12-10… DILM(C)15-10… DILM(C)17-10… DILM(C)25-10… DILM(C)32-10… DILM38-10… DILMP20… DILMP32-10… DILMP45-10… DILL… Instructions Interlocked opposing contacts according to IEC/EN 60947-5-1 appendix L, inside the auxiliary contact modules, also for the integrated auxiliary contacts of the DILM 7 - DILM32 Auxiliary contacts used as mirror contacts according to IEC/EN 60947-4-1 Appendix F (not N/C late open) Approvals Product Standards IEC/EN 60947-4-1; UL 508; CSA-C22.2 No. 14-05; CE marking UL File No. E29184 UL Category Control No. NKCR CSA File No. 012528 CSA Class No. 3211-03 North America Certification UL listed, CSA certified Specially designed for North America No Electrical￿specifications￿for￿standard￿auxiliary￿contacts Interlocked opposing contacts within an auxiliary contact module (to IEC 60947-5-1 Annex L) Yes N/C contact (not late-break contact) suitable as a mirror contact (to IEC/ EN 60947-4-1 Annex F) DILM7 - DILM38 Rated impulse withstand voltage Uimp V AC 6000 Overvoltage category/pollution degree III/3 Rated insulation voltage Ui V AC 690 Rated operational voltage Ue V AC 500 Safe isolation to EN 61140 between coil and auxiliary contacts V AC 400 between the auxiliary contacts V AC 400

03/26/2014 HPL-ED2014 V2.13 EN 2 / 5 Rated operational current A Conventional free air thermal current, 3 pole, 50 - 60 Hz Open at 60 °C Ith =Ie A 16 AC-15 500 V Ie A 1.5 DC current DC L/R 15 ms

24 V Ie A 10

60 V Ie A 6

110 V Ie A 3

220 V Ie A 1

DC-13 (6xP) Contacts in series: A 3 24 V A 2.5 3 60 V A 1 3 110 V A 0.5 3 220 V A 0.25 Control circuit reliability Failure rate λ <10-8, < one failure at 100 million operations (at Ue = 24 V DC, Umin = 17 V, Imin = 5.4 mA) Component lifespan at Ue = 230 V, AC-15, 3 A Operations x 106 1.3 Short-circuit rating without welding max. fuse A gG/ gL Technical￿data￿ETIM￿5.0 Low-voltage industrial components (EG000017) / Auxiliary contact block (EC000041) Electric engineering, automation, process control engineering / Low-voltage switch technology / Component for low-voltage switching technology / Auxiliary switch block Number of contacts as change-over contact Number of contacts as normally open contact Number of contacts as normally closed contact Rated operation current Ie at AC-15, 230 V A 6 Type of electric connection Screw connection Mounting method Front fastening Dimensions

03/26/2014 HPL-ED2014 V2.13 EN 3 / 5 Contactor with auxiliary contact module

03/26/2014 HPL-ED2014 V2.13 EN 4 / 5 Additional￿product￿information￿(links) IL03407013Z￿(AWA2100-2126)￿Contactors IL03407013Z (AWA2100-2126) Contactors ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/IL03407013Z2012_03.pdf http://de.ecat.moeller.net/flip-cat/?edition=HPLTE&startpage=5.84 Switchgear of Power Factor Correction Systems http://www.moeller.net/binary/ver_techpapers/ver934en.pdf X-Start - Modern Switching Installations Efficiently Fitted and Wired Securely http://www.moeller.net/binary/ver_techpapers/ver938en.pdf Mirror Contacts for Highly-Reliable Information Relating to Safety-Related Control Functions http://www.moeller.net/binary/ver_techpapers/ver944en.pdf Effect of the Cabel Capacitance of Long Control Cables on the Actuation of Contactors http://www.moeller.net/binary/ver_techpapers/ver949en.pdf

03/26/2014 Eaton Industries GmbH http://www.eaton.eu © 02/2014 by Eaton Industries GmbH HPL-ED2014 V2.13 EN Motor starters and "Special Purpose Ratings" for the North American market http://www.moeller.net/binary/ver_techpapers/ver953en.pdf Switchgear for Luminaires http://www.moeller.net/binary/ver_techpapers/ver955en.pdf Standard Compliant and Functionally Safe Engineering Design with Mechanical Auxiliary Contacts http://www.moeller.net/binary/ver_techpapers/ver956en.pdf The Interaction of Contactors with PLCs http://www.moeller.net/binary/ver_techpapers/ver957en.pdf Busbar Component Adapters for modern Industrial control panels http://www.moeller.net/binary/ver_techpapers/ver960en.pdf