05/06/2015 174334 - HPL-ED2015 V12.0 EN 1 / 5 Speed￿starters,￿three-phase￿power￿supply￿connection,￿three-phase￿motor Part￿no. DE1-342D1FN-N20N Article￿no. 174334 Catalog￿No. DE1-342D1FN-N20N Delivery￿programme Product range PowerXL™ DE1 Speed Starters Rated operational voltage Ue 400 V AC, 3-phase Output voltage with V<sub>e</sub> U2 400 V AC, 3-phase Mains voltage (50/60Hz) ULN V 380 (-10%) - 480 (+10%) Rated￿operational￿current At 150% overload Ie A 2.1 Note Rated operational current at an operating frequency of 16 kHz and an ambient air temperature of +50 °C Note Overload cycle for 60 s every 600 s Assigned￿motor￿rating Note for normal internally and externally ventilated 4 pole, three-phase asynchronous motors with 1500 rpm-1 at 50 Hz or 1800 min-1 at 60 Hz Note Overload cycle for 60 s every 600 s Note at 400 V, 50 Hz 150 % Overload P kW 0.75 150 % Overload Ie A 1.9 Note at 440 - 480 V, 60 Hz 150 % Overload P HP 1 150 % Overload Ie A 2.1 Degree of Protection IP20/NEMA 0 Interface/field bus (built-in) OP-Bus (RS485)/Modbus RTU Fitted with Radio interference suppression filter Frame size FS1 Connection to SmartWire-DT with SmartWire-DT module DX-NET-SWD3 Technical￿data General Standards Specification for general requirements: IEC/EN 61800-2 EMC requirements: IEC/EN 61800-3 Safety requirements: IEC/EN 61800-5-1 Certifications CE, UL, cUL, c-Tick Production quality RoHS, ISO 9001 Climatic proofing ρw % < 95%, average relative humidity (RH), non-condensing, non-corrosive (EN 50178) Ambient temperature °C operation (150 % overload) ϑ °C -10 - +50 (max. +60 bis fPWM = 16 kHz without derating) Storage ϑ °C -40 - +70 Radio interference level Radio interference class (EMC) C2, C3, depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary. Environment (EMC) 1st and 2nd environments maximum motor cable length I m C2 ≤ 10 m C3 ≤ 25 m Mechanical shock resistance g 15 (11 m/s, EN 60068-2-27) Vibration EN 61800-5-1

05/06/2015 174334 - HPL-ED2015 V12.0 EN 2 / 5 Altitude m 0 - 1000 m above sea level above 1000 m with 1 % performance reduction per 100 m max. 2000 m Degree of Protection IP20/NEMA 0 Protection against direct contact BGV A3 (VBG4, finger- and back-of-hand proof) Main￿circuit Supply Rated operational voltage Ue 400 V AC, 3-phase Mains voltage (50/60Hz) ULN V 380 (-10%) - 480 (+10%) Input current (150% overload) ILN A 3.1 Supply frequency fLN Hz 50/60 Frequency range fLN Hz 45 - 66 Mains switch-on frequency Maximum of one time every 30 seconds Power section Overload current (150% overload) IL A 3.15 max. starting current (High Overload) IH % 200 Note about max. starting current for 1.875 seconds every 600 seconds Output voltage with Ve U2 400 V AC, 3-phase Output Frequency f2 Hz 0 - 50/60 (max. 300) Switching frequency fPWM kHz 16 adjustable 4 - 32 (audible) Operation Mode U/f control Speed control with slip compensation Frequency resolution (setpoint value) Δf Hz 0.025 Rated operational current At 150% overload Ie A 2.1 Note Rated operational current at an operating frequency of 16 kHz and an ambient air temperature of +50 °C Maximum leakage current to ground (PE) without motor IPE mA < 3,5 AC, < 10 DC Fitted with Radio interference suppression filter Frame size FS1 Motor feeder Note for normal internally and externally ventilated 4 pole, three-phase asynchronous motors with 1500 rpm-1 at 50 Hz or 1800 min-1 at 60 Hz Note Overload cycle for 60 s every 600 s Note at 400 V, 50 Hz 150 % Overload P kW 0.75 Note at 440 - 480 V, 60 Hz 150 % Overload P HP 1 Apparent power Apparent power at rated operation 400 V S kVA 1.45 Apparent power at rated operation 480 V S kVA 1.75 Braking function Standard braking torque max. 30 % MN DC braking torque 100 %, adjustable Control￿section Reference voltage Us V 10 V DC (max. 0.2 mA) Analog inputs 1, parameterizable, 0 - 10 V DC, 0/4 - 20 mA Digital inputs 4, parameterizable, 10 - 30 V DC Relay outputs 1, parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1) Interface/field bus (built-in) OP-Bus (RS485)/Modbus RTU Assigned￿switching￿and￿protective￿elements Power Wiring Safety device (fuse or miniature circuit-breaker) IEC (Typ B, gG) FAZ-B6/3 UL (Class CC or J) A 6 Mains contactor

05/06/2015 174334 - HPL-ED2015 V12.0 EN 3 / 5 150 % overload (CT/IH, at 50 °C) DILEM-… 110 % overload (VT/IL, at 40 °C) DILM7-… Main choke 150 % overload (CT/IH, at 50 °C) DX-LN3-004 Radio interference suppression filter (external) DX-EMC34-008-FS1… Note regarding radio interference suppression filter Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments Motor feeder motor choke 150 % overload (CT/IH, at 50 °C) DX-LM3-005 Sine filter 150 % overload (CT/IH, at 50 °C) DX-SIN3-004 Design￿verification￿as￿per￿IEC/EN￿61439 Technical data for design verification Rated operational current for specified heat dissipation In A 2.1 Equipment heat dissipation, current-dependent Pvid W 28 Operating ambient temperature min. °C -10 Operating ambient temperature max. °C 50 IEC/EN 61439 design verification

10.2 Strength of materials and parts

10.2.2 Corrosion resistance Meets the product standard's requirements. 10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements. 10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.

10.2.3.3 Verification of resistance of insulating materials to abnormal heat

and fire due to internal electric effects Meets the product standard's requirements. 10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements. 10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated. 10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated. 10.2.7 Inscriptions Meets the product standard's requirements. 10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated. 10.4 Clearances and creepage distances Meets the product standard's requirements. 10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated. 10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated. 10.7 Internal electrical circuits and connections Is the panel builder's responsibility. 10.8 Connections for external conductors Is the panel builder's responsibility.

10.9 Insulation properties

10.9.2 Power-frequency electric strength Is the panel builder's responsibility. 10.9.3 Impulse withstand voltage Is the panel builder's responsibility. 10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility. 10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. 10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be observed. 10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.13 Mechanical function The device meets the requirements, provided the information in the instruction

leaflet (IL) is observed. Technical￿data￿ETIM￿5.0 Low-voltage industrial components (EG000017) / Frequency controller =< 1 kV (EC001857) Electric engineering, automation, process control engineering / Electrical drive / Static frequency converter / Static frequency converter = < 1 kv (ecl@ss8-27-02-31-01 [AKE177010]) Mains voltage V 380 - 480 Mains frequency 50/60 Hz Number of phases input 3 Number of phases output 3 Max. output frequency Hz 300

05/06/2015 174334 - HPL-ED2015 V12.0 EN 4 / 5 Rated output voltage V 400 Measuring output current A 2.1 Output power at rated output voltage kW 0.5 Max. output at quadratic load at rated output voltage kW 0.5 Max. output at linear load at rated output voltage kW 0.5 With control unit No Application in industrial area permitted Yes Application in domestic- and commercial area permitted Yes Supporting protocol for TCP/IP No Supporting protocol for PROFIBUS No Supporting protocol for CAN No Supporting protocol for INTERBUS No Supporting protocol for ASI No Supporting protocol for KNX No Supporting protocol for MODBUS Yes Supporting protocol for Data-Highway No Supporting protocol for DeviceNet No Supporting protocol for SUCONET No Supporting protocol for LON No Supporting protocol for PROFINET IO No Supporting protocol for PROFINET CBA No Supporting protocol for SERCOS No Supporting protocol for Foundation Fieldbus No Supporting protocol for EtherNet/IP No Supporting protocol for AS-Interface Safety at Work No Supporting protocol for DeviceNet Safety No Supporting protocol for INTERBUS-Safety No Supporting protocol for PROFIsafe No Supporting protocol for SafetyBUS p No Supporting protocol for other bus systems Yes Number of HW-interfaces industrial Ethernet 0 Number of HW-interfaces PROFINET 0 Number of HW-interfaces RS-232 0 Number of HW-interfaces RS-422 0 Number of HW-interfaces RS-485 1 Number of HW-interfaces serial TTY 0 Number of HW-interfaces USB 0 Number of HW-interfaces parallel 0 Number of HW-interfaces other 0 With optical interface No With PC connection Yes Integrated braking resistance No 4-quadrant operation possible No Type of converter U converter Degree of protection (IP) IP20 Height mm 230 Width mm 45 Depth mm 168 Relative symmetric net frequency tolerance % 5 Relative symmetric net current tolerance % 10 Approvals Product Standards UL 508C; CSA-C22.2 No. 14; IEC/EN61800-3; IEC/EN61800-5; CE marking UL File No. E172143 UL Category Control No. NMMS, NMMS7

05/06/2015 Eaton Industries GmbH http://www.eaton.eu © 04/2015 by Eaton Industries GmbH 174334 - HPL-ED2015 V12.0 EN CSA File No. UL report applies to both US and Canada North America Certification UL listed, certified by UL for use in Canada Specially designed for North America No Suitable for Branch circuits Max. Voltage Rating 3~ 480 V AC IEC: TN-S UL/CSA: "Y" (Solidly Grounded Wey) Degree of Protection IEC: IP20 Dimensions Additional￿product￿information￿(links) IL040005ZU￿Variable￿frequency￿drives￿DE1 IL040005ZU Variable frequency drives DE1 ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/IL040005ZU2014_07.pdf MN040011￿DE1￿Variable￿speed￿starter,￿Manual MN040011 Drehzahlstarter DE1, Handbuch - Deutsch ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN040011_DE.pdf MN040011 DE1 Variable speed starter, Manual - English ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN040011_EN.pdf MN040011 Démarreur à vitesse variable DE1, manuel d'utilisation - français ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN040011_FR.pdf MN040011 Avviatore a velocità variabile DE1, Manuale - italiano ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN040011_IT.pdf MN040011 DE1 Variable speed starter, Manual ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN040011_NO.pdf MN040011 Rozrusznik silnikowy z regulacją prędkości DE1, podręcznik - polski ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN040011_PL.pdf MN040011 DE1 Variable speed starter, Manual ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN040011_RO.pdf