Technical content

/g32 /g32 B Magnelab.com RoHS2 ISO 9001:2008 /g32 /g32/g32 /g32/g32 /g32 /g32/g32/g32 /g32 /g32 /g32 /g32 /g32 /g32 Split-Core DC Voltage Output Transducer DCT-0010-XXX, 5 VDC Output Description: Magnelab’s DCT-0010-XXX split-core current transducer “senses” AC current up to 50 Amps passing through the center conductor. Split-core transformers are ideal for installation on existing electrical wiring by snapping around the conductor. The DCT-0010-XXX has a self-locking mechanism. Features:  Rated input up to 50 Amp AC  Output of 5 Vdc at rated current (7.5 Vdc limit built in)  Accuracy ± 2% full scale  Operating temperature -20°C to 50°C  Line Response Time 300 ms  Output Ripple within 5% of Output Voltage  Frequency range 50/60 Hz  2 X M3-Screw terminals  System Voltage: CAT III 600VAC  UL recognized IEC 61010-1, CE, and RoHS Compliant DCT-0010-005 5 Amp PART NUMBER AND RATING DCT-0010-010 10 Amp DCT-0010-025 DCT-0010-050

25 Amp

50 Amp

8.5 kOhms 6.8 kOhms 6.2 kOhms A B 51.00 33.00 C 23.60 D 26.70 E 14.70 2.00 INCH MM 1.30 0.93 1.05 0.58 DIMENSION MAGNELAB 10mm Opening With Ratings Up to 50 Amps