www.gminternational.com D6016SIL3 2-Wire Active HART® Tx Current Repeater Isolators > Analog Input

ORDERING INFORMATION

x: S → 1 channel; D → 2 channels y: S → source current output; K → sink current output Accessories Bus Connector JDFT049, Bus Mounting Kit OPT5096. TECHNICAL DATA SIL 3 / SC 3 2 fully independent channels 4-20 mA Source-Sink Output HART® compatible High Accuracy Three port isolation, Input/Output/Supply High Density, two channels per unit The Current Repeater D6016 module is a high integrity analog input interface suitable for applications requiring SIL 3 level in safety related systems for high risk industries. It repeats a 2-wire active 4- 20 mA current signal input in floating circuit to drive a Safe Area load. The module allows bi-directional communication signals, for HART® devices.

FEATURES

24 Vdc nom (18 to 30 Vdc), reverse polarity protected. Current consumption: 33 mA (D6016SS), 20 mA (D6016SK), 57 mA (D6016DS), 31 mA (D6016DK) @ 24 Vdc with 20 mA output, typical. Power dissipation: 0.90 W (D6016SS), 1.00 W (D6016SK), 1.50 W (D6016DS), 1.80 W (D6016DK) @ 24 Vdc with 20 mA output on 250 Ω load and 24 Vdc output supply for sink models, typical. Input 4 to 20 mA (separately powered input, voltage drop ≤ 7 V), reading range 0 to 22 mA. HART Impedance: 225 Ω, typical. Output 4 to 20 mA. Sink out voltage range: 2 to 30 V. Load range: 0 to 500 Ω, with conventional Tx input 250 Ω nom (160 to 500 Ω), with smart Tx input. Current limitation: 24 mA (up to 450 Ω load) ≤ max current ≤ 26 mA. Response time: 20 ms (10 to 90 % step change). Performance Ref. Conditions: 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature. Calibration accuracy: ≤ ± 20 μA. Linearity accuracy: ≤ ± 20 μA. Temp. influence: ≤ ± 2 μA/°C. Isolation In/Out 2.5 kV; In/Supply 2.5 kV; In/In 500 V; Out/Supply 500 V; Out/Out 500 V. Environmental conditions Operating temperature: temperature limits –40 to +70 °C. Storage temperature: temperature limits –45 to +80 °C. Mounting DIN-Rail 35 mm, with or without Power Bus or on custom Term. Board. Weight: about 135 g (D6016DS and D6016DK), 115 g (D6016SS and D6016SK). Connection: by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG). Dimensions: Width 12.5 mm, Depth 123 mm, Height 120 mm. OVERALL DIMENSIONS Functional Safety Management Certification: GM International is certified to conform to IEC61508:2010 part 1 clauses 5-6 for safety related systems up to and included SIL3. In addition, GM International products have been granted I.S. certificates from the most credited Notified Bodies in the world. Data specified in this document are merely descriptive of the products and should be integrated with relevant technical specifications. Our products are in constant development and the information presented herein refers to the time of document issue. No statements concerning a certain condition or suitability for a certain application can be derived from our information. The information given does not release the user from the obligation of own judgment and verification. Terms & Conditions can be found at our website. For more information refer to istruction manual.

Additional installation diagrams may be found in Instruction Manual. Field Safe Area Functional Safety Management Certification: GM International is certified to conform to IEC61508:2010 part 1 clauses 5-6 for safety related systems up to and included SIL3. In addition, GM International products have been granted I.S. certificates from the most credited Notified Bodies in the world. Data specified in this document are merely descriptive of the products and should be integrated with relevant technical specifications. Our products are in constant development and the information presented herein refers to the time of document issue. No statements concerning a certain condition or suitability for a certain application can be derived from our information. The information given does not release the user from the obligation of own judgment and verification. Terms & Conditions can be found at our website. For more information refer to istruction manual.