www.gminternational.com D5244 I.S. SIL2/3 Loop-Powered Digital Relay Output Intrinsically Safe Isolators > Digital Relay Output
ORDERING INFORMATION
D5244S: 1 channel D5244D: 2 channels Accessories DIN-Rail stopper MCHP196. TECHNICAL DATA SIL 2 / SC 3 Output to Zone 0 Installation in Zone 2 2 fully independent channels Voltage level input Two SPDT Relay Output Signals Two port isolation, Input/Output/Supply High Reliability, SMD components High Density, two channels per unit The Loop-Powered Digital Relay Output D5244 is a loop powered digital output module enabling a Safe Area loop voltage signal, to control a device in Hazardous Area, providing 2 port isolation (input/output). Outputs are galvanically isolated. Typical applications include switching of Hazardous Area circuits, changing of polarities and sounder tones, calibrating of strain gauge bridges, resetting of field devices, testing of fire detectors. Each output channel provides a SPDT relay, with two contacts defined NO (Normally Open) and NC (Normally Close) when the output relay is de-energized. Considering each channel NE (Normally Energized), the output relay is energized,so that NO contact is closed (useful for NE loads or Hazardous Area circuits) and NC contact is open (useful for ND loads or Hazardous Area circuits). The safe state is reached when the channel and the output relay are de-energized, so that NO contact is open (de-energizing loads or Hazardous Area circuits) and NC contact is closed (energizing loads or Hazardous Area circuits).
FEATURES
24 Vdc nom (18 to 30 Vdc), reverse polarity protected. Current consumption: 20 mA/channel @ 24 Vdc with relay energized, typical. Power dissipation: 0.4 W/channel @ 24 Vdc with loop voltage and relays energized, typical. Voltage range: 0 V ≤ OFF ≤ 5 V, 18 V ≤ ON ≤ 30 V. Output Voltage free SPDT relay contact. Contact material: AgNi90/10. Contact rating: 40 Vdc, 2 A for use in Intrinsic Safety applications, 2 A 250 Vac 500 VA, 2 A 250 Vdc 80 W (resistive load) for non Intrinsic Safety applications. DC and AC load breaking capacity: refer to Instruction Manual. Mechanical / electrical life: 15 * 10⁶ / 10 * 10⁴ operations, typical. Operate / release time: 50 ms, typical. Isolation Environmental conditions Operating temperature: temperature limits –40 to +70 °C. Storage temperature: temperature limits –45 to +80 °C. Safety description Associated apparatus and non-sparking electrical equipment. Uo = 0 V, Io = 0 mA, Po = 0 mW at terminals 13-14-15/16, 17-18-19/20 (Uo, Io, Po equal to the connected Intrinsic Safety circuit). Ui = 40 V, Ii = 2 A, Ci = 0 nF, Li = 0 nH at term. 13-14-15/16, 17-18-19/20. Um = 250 Vrms or Vdc, -40 °C ≤ Ta ≤ 70 °C. Mounting DIN-Rail 35 mm, or on custom Term. Board. Weight: about 175 g (D5244D), 165 g (D5244S). Connection: by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm² (13 AWG). Dimensions: Width 22.5 mm, Depth 123 mm, Height 120 mm. OVERALL DIMENSIONS Functional Safety Management Certification: GM International is certified to conform to IEC61508:2010 part 1 clauses 5-6 for safety related systems up to and included SIL3. In addition, GM International products have been granted I.S. certificates from the most credited Notified Bodies in the world. Data specified in this document are merely descriptive of the products and should be integrated with relevant technical specifications. Our products are in constant development and the information presented herein refers to the time of document issue. No statements concerning a certain condition or suitability for a certain application can be derived from our information. The information given does not release the user from the obligation of own judgment and verification. Terms & Conditions can be found at our website. For more information refer to istruction manual.
Additional installation diagrams may be found in Instruction Manual. Hazardous Area Safe Area/Zone 2 Functional Safety Management Certification: GM International is certified to conform to IEC61508:2010 part 1 clauses 5-6 for safety related systems up to and included SIL3. In addition, GM International products have been granted I.S. certificates from the most credited Notified Bodies in the world. Data specified in this document are merely descriptive of the products and should be integrated with relevant technical specifications. Our products are in constant development and the information presented herein refers to the time of document issue. No statements concerning a certain condition or suitability for a certain application can be derived from our information. The information given does not release the user from the obligation of own judgment and verification. Terms & Conditions can be found at our website. For more information refer to istruction manual.