D5048 GMI | Alldatasheet

Document overview

  • PDF pages: 2

Technical content

www.gminternational.com D5048 I.S. SIL3 Loop-Powered Digital Output Driver Intrinsically Safe Isolators > Digital Output

ORDERING INFORMATION

D5048S: 1 channel Accessories Bus Connector JDFT049, Bus Mounting Kit OPT5096. TECHNICAL DATA SIL 3 / SC 3 Output to Zone 0/Div. 1 Installation in Zone 2/Div. 2 Loop powered for NE loads Line & Load short/open circuit detection Output short circuit proof In-field programmability by DIP Switch Three port isolation, Input/Output/Fault The Loop-Powered Digital Output Driver D5048 is a module suitable for applications requiring SIL 3 level in safety related systems for high risk industries. It can drive solenoid valves, visual or audible alarms to alert a plant operator, or other process control devices in Hazardous Area from control signals located in Safe Area. They can also be used as switchable supplies to power measuring or process control equipments. Line and load open/short circuit detection is provided, when the load is on: the fault in the field is directly mirrored to the PLC DO and it is also reported by opening the fault output. If required, the override input can switch off the output regardless of the input status. For each channel three basic output circuits are selectable, with different safety parameters, to interface the majority of devices on the market.

FEATURES

Loop powered control signal. Voltage range: 24 Vdc nom (20 to 30 Vdc), reverse polarity protected. Current consumption: 65 mA @ 24 Vdc with 45 mA output, typical, ≤ 10 mA when fault circuit enabled and fault condition detected. Power dissipation: 1.1 W @ 24 Vdc with 45 mA output, typical. Override input Override control signal de-energizes output when enabled by dip-switch. Voltage range: 0 V ≤ OFF ≤ 5 V, 20 V ≤ ON ≤ 30 V, reverse polarity protected. Current consumption: 15 mA @ 24 Vdc, typical. Output 45 mA @ 13.0 V (21.0 V no load, 174 Ω series resistance) at terminals 7- 10 Out A. 45 mA @ 10.2 V (21.0 V no load, 236 Ω series resistance) at terminals 8-10 Out B. 45 mA @ 8.5 V (21.0 V no load, 275 Ω series resistance) at terminals 9-10 Out C. Short circuit current: ≥ 50 mA, 55 mA typical. Output diagram : refer to Instruction Manual. Response time: ≤ 75 ms. Fault Field device and wiring open circuit or short circuit detection dip-switch selectable. When fault is detected, output is de-energized until normal condition is restored. Short output: load resistance ≤ 50 Ω (≈ 2 mA forcing to detect fault). Open output: load resistance > 10 kΩ. Fault signalling: voltage free NE SPST optocoupled open-collector transistor (output de-energized in fault condition). Open-collector/drain rating: 100 mA @ 35 Vdc (≤ 1.5 V voltage drop). Leakage current: ≤ 50 µA @ 35 Vdc. Response time: ≤ 75 ms. Isolation V; In/Override 500 V; Fault/Override 500 V. Environmental conditions Operating temperature: temperature limits –40 to +70 °C. Storage temperature: temperature limits –45 to +80 °C. Safety description Associated apparatus and non-sparking electrical equipment. Uo = 24.8 V, Io = 147 mA, Po = 907 mW at terminals 7-10 Out A. Uo = 24.8 V, Io = 108 mA, Po = 667 mW at terminals 8-10 Out B. Uo = 24.8 V, Io = 93 mA, Po = 571 mW at terminals 9-10 Out C. Um = 250 Vrms or Vdc, -40 °C ≤ Ta ≤ 70 °C. Mounting DIN-Rail 35 mm, with or without Power Bus or on custom Term. Board. Weight: about 130 g. Connection: by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm² (13 AWG). Dimensions: Width 12.5 mm, Depth 123 mm, Height 120 mm. OVERALL DIMENSIONS Functional Safety Management Certification: GM International is certified to conform to IEC61508:2010 part 1 clauses 5-6 for safety related systems up to and included SIL3. In addition, GM International products have been granted I.S. certificates from the most credited Notified Bodies in the world. Data specified in this document are merely descriptive of the products and should be integrated with relevant technical specifications. Our products are in constant development and the information presented herein refers to the time of document issue. No statements concerning a certain condition or suitability for a certain application can be derived from our information. The information given does not release the user from the obligation of own judgment and verification. Terms & Conditions can be found at our website. For more information refer to istruction manual.

Additional installation diagrams may be found in Instruction Manual. Hazardous Area Safe Area/Zone 2/Div. 2 Functional Safety Management Certification: GM International is certified to conform to IEC61508:2010 part 1 clauses 5-6 for safety related systems up to and included SIL3. In addition, GM International products have been granted I.S. certificates from the most credited Notified Bodies in the world. Data specified in this document are merely descriptive of the products and should be integrated with relevant technical specifications. Our products are in constant development and the information presented herein refers to the time of document issue. No statements concerning a certain condition or suitability for a certain application can be derived from our information. The information given does not release the user from the obligation of own judgment and verification. Terms & Conditions can be found at our website. For more information refer to istruction manual.