www.gminternational.com FSM SIL 3 Data specified in this document are merely descriptive of the products and should be integrated with relevant technical specifications. Our products are in constant development and the information presented herein refers to the time of document issue. No statements concerning a certain condition or suitability for a certain application can be derived from our information. The information given does not release the user from the obligation of own judgment and verification. Terms & Conditions can be found at our website. For more information refer to istruction manual. Functional Safety Management Certification: GM International is certified to conform to IEC61508:2010 part 1 clauses 5-6 for safety related systems up to and included SIL3. In addition, GM International products have been granted I.S. certificates from the most credited Notified Bodies in the world. I.S. SIL3 2-Wire HART® Transmitter Power Supply D5011 The Repeater Power Supply D5011 module is a high integrity analog input interface suitable for applications requiring SIL 3 level in safety related systems for high risk industries. It provides a fully floating dc supply for energizing conventional 2 wires 4-20 mA transmitters located in Hazardous Area, and repeats the current in floating circuit to drive a Safe Area load. The circuit allows bi-directional communication signals, for HART® devices. Intrinsically Safe Isolators > Analog Input
FEATURES
- SIL 3 / SC 3
- Input from Zone 0/Div. 1
- Installation in Zone 2/Div. 2
- 4-20 mA Passive Input, Source Output
- HART® compatible
- Input and Output short circuit proof
- High Accuracy
- Three port isolation, Input/Output/Supply
- High Density, two channels per unit FUNCTION DIAGRAM = = 5 + 6 -
2 RLmA
Out (SIL 3) MODEL D5011S +- Termination board connectorPower Bus Supply 24 Vdc HHT2 Wire Tx I In 8 = = 5 + 6 - Out 1 (SIL 3)
4 RLmA
Out 2 (SIL 3) HHT MODEL D5011D +- Termination board connectorPow er Bus = = Supply 24 Vdc HHT2 Wire Tx I In 1
2 Wire Tx
I ? 9 Hazardous Area TECHNICAL DATA Supply 24 Vdc nom (18 to 30 Vdc), reverse polarity protected. Current consumption: 90 mA (D5011D), 45 mA (D5011S), @ 24 Vdc with 20 mA output, typical. Power dissipation: 1.35 W (D5011D), 0.675 W (D5011S), @ 24 Vdc with 20 mA output, typical. Input 4 to 20 mA (2 wires Tx current limited ≈ 25 mA), reading range 0 to 24 mA. Transmitter line voltage: 15.0 V typical, 14.5 V minimum, @ 20 mA. Output 4 to 20 mA, on max. 550 Ω load in source mode (typical 12 V compliance). Response time: 5 ms (0 to 100 % step change). Performance Ref. Conditions: 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature. Calibration accuracy: ≤ ± 0.1 % FSR. Linearity accuracy: ≤ ± 0.05 % FSR. Temp. influence: ≤ ± 0.01 % FSR on zero/span for a 1 °C change. Isolation 500 V; Out/Out 500 V. Environmental conditions Operating temperature: temperature limits –40 to +70 °C. Storage temperature: temperature limits –45 to +80 °C. Safety description Associated apparatus and non-sparking electrical equipment. Uo = 25.9 V, Io = 92 mA, Po = 594 mW at terminals 7-8, 9-10. Um = 250 Vrms or Vdc, -40 °C ≤ Ta ≤ 70 °C. Mounting DIN-Rail 35 mm, with or without Power Bus or on custom Term. Board. Weight: about 140 g (D5011D), 125 g (D5011S). Connection: by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG). Dimensions: Width 12.5 mm, Depth 123 mm, Height 120 mm.
ORDERING INFORMATION
D5011S: 1 channel D5011D: 2 channels Accessories Bus Connector JDFT049, Bus Mounting Kit OPT5096. Additional installation diagrams may be found in Instruction Manual. Safe Area/Zone 2/Div. 2