D3G133-BF03-06 EBMPAPST | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 5

Technical content

forward curved, dual inlet with housing (flange) D3G133-BF03-06 ebm-papst Mulfingen GmbH & Co. KG Bachmühle 2 · D-74673 Mulfingen Phone +49 7938 81-0 Fax +49 7938 81-110 info1@de.ebmpapst.com www.ebmpapst.com Limited partnership · Headquarters Mulfingen County court Stuttgart · HRA 590344 General partner Elektrobau Mulfingen GmbH · Headquarters Mulfingen County court Stuttgart · HRB 590142 Nominal data Type D3G133-BF03-06 Motor M3G055-CF Phase 1~ Nominal voltage VAC 230 Nominal voltage range VAC 195 .. 253 Frequency Hz 50/60 Type of data definition fa Speed min-1 1260 Power input W 86 Current draw A 0.64 Min. ambient temperature °C -25 Max. ambient temperature °C +40 ml = Max. load · me = Max. efficiency · fa = Running at free air · cs = Customer specs · cu = Customer unit Subject to alterations Item no. 50120-5-9980 · Revision 76342 · Release 2013-03-21 · Page 1 / 5

forward curved, dual inlet with housing (flange) D3G133-BF03-06 Technical features Mass 3 kg Size 133 mm Surface of rotor Uncoated Material of impeller Sheet steel, galvanised Housing material Sheet steel, galvanised Motor suspension Motor mounted via brackets on one side Direction of rotation Clockwise, seen on rotor Type of protection IP 42 Insulation class "B" Humidity class F3-1 Max. permissible ambient motor temp. (transp./ storage) + 80 °C Min. permissible ambient motor temp. (transp./storage) - 40 °C Mounting position Shaft horizontal Condensate discharge holes None Operation mode S1 Motor bearing Ball bearing Technical features - Output 10 VDC, max. 1.1 mA - Tach output - Motor current limit - Soft start - Control input 0-10 VDC / PWM - Control interface with SELV potential safely disconnected from the mains - Over-temperature protected motor EMC interference immunity Acc. to EN 61000-6-2 (industrial environment) EMC harmonics Acc. to EN 61000-3-2/3 EMC interference emission Acc. to EN 61000-6-3 (household environment) Touch current acc. IEC 60990 (measuring network Fig. 4, TN system) <= 3.5 mA Electrical leads With plug Motor protection Thermal overload protector (TOP) wired internally Cable exit Lateral Protection class I (if protective earth is connected by customer) Product conforming to standard EN 60335-1 Item no. 50120-5-9980 · Revision 76342 · Release 2013-03-21 · Page 2 / 5

forward curved, dual inlet with housing (flange) D3G133-BF03-06 Product drawing 1 Connection line PVC 4 x 0.25 mm² with plug: AMP Mate-N-Lok 480702-0 1.1 red 1.2 yellow

1.3 Light blue

1.4 white 2 Connection line PVC 3G x 0.5 mm² with plug: AMP Mate-N-Lok-480702-0 2.1 brown 2.2 blue 2.3 green/yellow Item no. 50120-5-9980 · Revision 76342 · Release 2013-03-21 · Page 3 / 5

forward curved, dual inlet with housing (flange) D3G133-BF03-06 Connection screen Line No. Signal Colour Function / assignment

2 L brown Power supply 230 VAC, 50-60 Hz, see type plate for voltage range

3 N blue Neutral conductor

1 PE green/yellow Protective earth

7 0-10 V PWM yellow Control input 0 - 10 V or PWM, electrically isolated

5 Tach white Tach output: Open Collector, 1 pulse per revolution, electrically isolated

6 10V / max. 1.1 mAred Voltage output 10V / 1.1mA, electrically isolated, not short-circuit-proof

4 GND blue GND - Connection for control interface

Item no. 50120-5-9980 · Revision 76342 · Release 2013-03-21 · Page 4 / 5

forward curved, dual inlet with housing (flange) D3G133-BF03-06 Charts: Air flow 50 Hz Druck p f s[Pa]für Rho=1,2kg/m^3 qv[m^3/h] 950900850800750700650600550500450400350300250200150100500 qv[cfm] 550500450400350300250200150100500p f s[Pa] 3002902802702602502402302202102001901801701601501401301201101009080706050403020100 pfs_E[IN H2O] p f s[Pa]p f s[Pa]p f s[Pa]p f s[Pa]1 1516 Measurement: LU-108839 Measurement: LU-108841 Measurement: LU-108842 Measurement: LU-108844 Air performance measured as per ISO 5801 Installation category A. For detailed information on the measuring set-up, please contact ebm-papst. Suction-side noise levels: LwA measured as per ISO 13347 / LpA measured with 1m distance to fan axis. The values given are valid under the measuring conditions mentioned above and may vary according to the actual installation situation. With any deviation from the standard set-up, the specific values have to be checked and reviewed with the unit installed. Measured values U V 230 230 230 230 230 230 230 230 230 230 230 230 230 230 230 230 f Hz n min-1 1260 1550 1825 2055 1270 1460 1720 1930 1110 1270 1440 1570 855 960 1070 1110 Ped W I A 0.64 0.63 0.48 0.36 0.63 0.54 0.39 0.30 0.41 0.34 0.23 0.17 0.19 0.16 0.12 0.09 qv m3/h 890 740 460 235 865 690 435 220 745 600 365 180 575 445 260 125 pfs Pa 165 225 149 192 104 128 U = Supply voltage · f = Frequency · n = Speed · Ped = Power input · I = Current draw · qv = Air flow · pfs = Pressure increase Item no. 50120-5-9980 · Revision 76342 · Release 2013-03-21 · Page 5 / 5