AC-DC Three Phase Power Converter D2U5T-H3-7000-54-HU4C.B01 Page 1 of 8 www.murata-ps.com www.murata-ps.com/support For full details go to www.murata-ps.com/rohs

FEATURES

7KW (480VAC), 3.5KW (230VAC) Output Power High Effi ciency; 96% @ 50% FL 54VDC Main Output 3.3V or 5V Standby Output Dims: 5.1"(W) x 18"(L) x 3.3" (2U) 23.1 watts/cubic inch power density N+1 redundant (including hot docking) Droop sharing on Main Output Over-voltage, over-current, over-temperature protections Internal cooling fan I2C Bus Interface with status indicators RoHS compliant Two-year warranty ORDERING GUIDE Model Number Power Output at 480Vac Main Output Standby Output Airfl ow D2U5T-H3-7000-54-HU4C 7000W 54V 3.3V or 5V (selectable) Back to front PRODUCT OVERVIEW The D2U5T-H3-7000-54-HU4C is a High Effi ciency 3500/7000 watt, power factor corrected, three phase power converter for 230/480VAC lines with a 54VDC main output and a 5V or 3.3V (20W) selectable standby output. The unit is provided with droop sharing and up to three supplies may be operated in parallel. The supply is hot pluggable. It recovers from over temperature faults, and has status LEDs on the front panel in addition to logic and PMBus status signals. The 2U package and 23.1W/cubic inch power density make them ideal for delivering reliable, effi cient power to servers, workstations, storage systems, broadcast transmitters and many other applications. CB Test Certifi cate and Test Report www.murata-ps.com/en/3d/acdc.html www.murata-ps.com/en/3d/acdc.html www.murata-ps.com/en/3d/acdc.html www.murata-ps.com/en/3d/acdc.html www.murata-ps.com/en/3d/acdc.html www.murata-ps.com/en/3d/acdc.html Available now at www.murata-ps.com/en/3d/acdc.html INPUT CHARACTERISTICS Parameter Conditions Min Typ Max Units Input Frequency 47 50/60 63 Hz Input Voltage Operating Range Range 1 180 264 Vac Range 2 320 525 Vac Turn-on Voltage (Ramp-up) Range 1 176 Vac Range 2 280 Vac Turn-off Voltage (Ramp-down) Range 1 150 Vac Range 2 260 Vac Maximum Input Current 15 Arms Inrush Current Cold Start 30 Apk Power Factor, Range 1, 230Vac, 60Hz 600W 0.930 1750W (50% FL) 0.990 3500W (100% FL) 0.995 Power Factor, Range 2, 480Vac, 60Hz 600W, 480Vac 0.850 3500W (50% FL) 0.990 7000W (100% FL) 0.995 OVERALL CHARACTERISTICS Parameter Conditions Min Typ Max Units Output Power Range 1 3500 WRange 2 7000 Effi ciency, Range 1 700W (20%), 230 Vac 89.0 1750W (50%), 230 Vac 93.5 3500W (100%), 230 Vac 94.0 Effi ciency, Range 2* 1400W (20%), 480 Vac 94.2 3500W (50%), 480 Vac 96.0 7000W (100%), 480 Vac 95.5 * See graph on page 8.

AC-DC Three Phase Power Converter D2U5T-H3-7000-54-HU4C.B01 Page 2 of 8 www.murata-ps.com/support 1 Ripple and noise are measured with 2.2µF (X7R 100V) ceramic + 180μF (UCC EKY) of electrolytic de-coupling capacitors at the output connector load side. A short coaxial cable with 50Ω scope termination is used. 2 Ripple and noise are measured with 0.1µF of ceramic capacitance and 10 µF of tantalum capacitance across the power supply outputs at the output connector load side. A short coaxial cable with 50Ω scope termination is used. OUTPUT VOLTAGE CHARACTERISTICS Output Parameter Conditions Min Typ Max Units 54V Output Current Range 1 0 64.8 AdcRange 2 0 129.6 Voltage Set Point @32.4A Range 1 54 Vdc@64.8A Range 2 54 Voltage Droop Min to Max Current, Range 1 1. 5V Min to Max Current, Range 2 3.0V Line Regulation 0.1 % Ripple Voltage & Noise1 0.5 Vp-p Load Capacitance 470 5000 μF 3.3VSB Voltage Set Point 3.30 VdcLine and Load Regulation 3.14 3.46 Ripple Voltage & Noise2 20MHz Bandwidth 100 mVp-p Output Current 0 6 A Load Capacitance 20 1000 μF 5VSB Voltage Set Point 5.00 VdcLine and Load Regulation 4.76 5.24 Ripple Voltage & Noise2 20MHz Bandwidth 100 mVp-p Output Current 0 4 A Load Capacitance 20 1000 μF OUTPUT CHARACTERISTICS Parameter Conditions Min Typ Max Units Startup Time AC ramp up 3 s Transient Response3 54V, 50-100% load step, 0.1A/μs di/dt 2.4 Vp-p 5VSB, 50-100% load step, 1A/μs di/dt 250 mVp-p 3.3VSB, 50-100% load step, 1A/μs di/dt 250 mVp-p Current sharing accuracy (up to 3 in parallel) 54V @100% load +/-10 % Hot Swap Transients All outputs within regulation Holdup Time 54V @100% load 12 msVSB @100% Load 100 3 Minimum output capacitance to be 470µF (low ESR). 2.2µF X7R 100V RG587U COAX 50/uni03A9 180µF 63V UCC EKY54V Output 100NF X7R 25V RG587U COAX 50/uni03A9C4 10µF 10V TANT VSB SCOPE SCOPE

AC-DC Three Phase Power Converter D2U5T-H3-7000-54-HU4C.B01 Page 3 of 8 www.murata-ps.com/support GENERAL CHARACTERISTICS Parameter Conditions Min Typ Max Units Storage Temperature Range -40 70 °C Operating Temperature Range 0 50 °C Operating Humidity Non-condensing 10 90 % Storage Humidity Non-condensing 5 90 % Altitude (without de-rating at 40°C) 3000 mAltitude (without de-rating at 50°C) 1800 Shock 30G non-operating Sinusoidal Vibration 0.5G, 5 – 500 Hz MTBF Calculated per Telcordia SR-332 @40°C 250K hrs Weight 7 kg Safety Approvals c-CSA-us (CSA 60950-1-07/UL 60950-1, Second Edition) TÜV EN 60950-1:2006+A11+A1+A12 IEC 60950-1:2005 (2nd Ed) + A1:2009, and EN 60950-1:2006/A11:2009/A1:2010/A12:2011 Input Fuses One internal 16A/500V fast blow fuse on each of the three AC line inputs Material Flammability UL 94V0 Airflow Direction From Back (connector side) to Front. Optional Front to Back. PROTECTION CHARACTERISTICS Output Parameter Conditions Min Typ Max Units Over-temperature (intake) Auto-restart 52 55 63 °C 54V Over Voltage Latching, toggling ON/OFF switch unlatches 58 60 62 V Over Current Ranges 1 &2 Hiccup mode. Restart every 500msec. Recovers once load drops below OCP level 105 130 % 3.3VSB Over Voltage Latching, AC OFF/ON cycling required to unlatch 3.9 4.3 V Over Current Constant Current Limit (Latches if Output drops below 2V). Hiccup is optional 6.3 9 A 5VSB Over Voltage Latching, AC OFF/ON cycling required to unlatch 5.6 6.0 V Over Current Constant Current Limit (Latches if Output drops below 3V). Hiccup is optional 4.2 6 A EMISSIONS AND IMMUNITY Characteristic Standard Compliance Input Current Harmonics IEC/EN 61000-3-2 Complies Conducted Emissions FCC 47 CFR Parts 15 CISPR 22 EN55022 Class A, 6dB margin Radiated Emissions (in the application) Class A, 6dB margin ESD Immunity IEC/EN 61000-4-2 Level 3 criteria A Radiated Field Immunity IEC/EN 61000-4-3 Level 3 criteria B Electrical Fast Transients/Burst Immunity IEC/EN 61000-4-4 Level 3 criteria A Surge Immunity IEC/EN 61000-4-5 Level 3 criteria A RF Conducted Immunity IEC/EN 61000-4-6 Level 3 criteria A Magnetic Field Immunity IEC/EN 61000-4-8 3 A/m criteria B Voltage Dips & Interruptions IEC/EN 61000-4-11 400Vrms Input Voltage 54V & VSB Outputs, Performance a) 100% load, Phase 0°, Dip 100% Duration 10ms 50% load, Phase 0°, Dip 100% Duration 20ms 54V & VSB Outputs, Performance b) 100% load, Phase 0°, Dip 100% Duration >10ms Any Load, Phase 0°, Dip 100% Duration >100ms Voltage imbalance (Circuit will stop when input voltage imbalance exceeds 8% for more than 100ms. Unit will restart when imbalance returns below 8%) Any valid Input Voltage, any load 54V & VSB Outputs, Performance a) Dip 30% on single Phase or Line, Duration 100ms 54V & VSB Outputs, Performance b) Dip 30% on single Phase or Line, Duration >100ms

AC-DC Three Phase Power Converter D2U5T-H3-7000-54-HU4C.B01 Page 4 of 8 www.murata-ps.com/support ISOLATION CHARACTERISTICS Parameter Conditions Min Typ Max Units Insulation Safety Rating/Test Voltage Input to Output – Reinforced 3000 Vrms Input to Chassis – Basic 1500 Vrms Output to Chassis – Functional 500 Vdc STATUS INDICATORS (LEDs) Status Indicators Input OK (Green) Output OK (Green) Fault5 (Yellow) AC present and within the regulation range; Standby - ON; Main Output – OFF Solid Green Blinking Off AC present, but its level is not within the required regulation range Blinking Green at 1Hz rate (0.5s on, 0.5s off) Off Off When hot-unplugging the power supply from a power shelf

4 Blinking Green at 1Hz rate

(0.5s on, 0.5s off) Off Off AC input voltage is not present Off Off Off AC present and within the regulation range; Standby – ON, Main Output – ON and both within the regulation range Solid Green Solid Green Off AC present and within the regulation range; Standby - ON; Main Output - ON; power supply is in a power limit or in an overcurrent condition. Solid Green Solid Green On Any warning Levels (Input UV/OV, OC, Inlet Temp, Output and STBY OV/UV, OC, OTP , FAN) No Change No Change Blinking 1Hz Any Fault Levels (Input UV/OV, OC, Inlet Temp, Output and STBY OV/UV, OC, OTP , FAN) Depends on PS Status Depends on PS Status On 4 The Input OK LED blinks to indicate that there is still energy inside the power supply until the input bulk capacitors are completely discharged or the housekeeping circuit is shut down. 5 The Fault LED and PS Fault signal shall be turned on to indicate that there is one or more of the following internal faults currently detected inside the power supply:

  • VSB out of range
  • Output stage OT
  • Fan fault
  • ORING fault (Output voltage less than bus voltage)
  • OC shutdown
  • OT shutdown
  • OV shutdown
  • Input stage OT
  • Fault induced shutdown occurred
  • Thermal sensor fault
  • Vout out of range
  • PFC Boost Vbulk fault As soon as all of the above faults are removed and the power supply operates normally, the Fault LED and PS Fault signal shall be turned off. LED Definition: Three LEDs shall be located on the front faceplate, and these are: LED Status Fault = ON Input OK = ON Output OK = ON

AC-DC Three Phase Power Converter D2U5T-H3-7000-54-HU4C.B01 Page 5 of 8 www.murata-ps.com/support Control Signals Signal (I/O) Description PS_ON_H (Input) Internal 10K pull-up resistor to internal VDD6

  • Leaving signal pin open = Main Output ON
  • Tying signal pin to GND = Main Output OFF PS_KILL (Input) Short pin; internal 10K pull-up resistor to internal VDD6
  • Leaving signal pin open = All Outputs off
  • Tying signal pin to GND = All Outputs enabled PS_FAULT_L (Output) Internal 10K pull-up resistor to internal VDD6
  • PSU Fault Status PWR_GOOD_H (Output) Internal 10K pull-up resistor to internal VDD6
  • Main Output Status OK I_SHARE (Input/output -bus) Analog representation of main output current; can be left open if not used STBY_SEL_IN (Input) Internal 10K pull-up resistor to internal VDD6
  • Leaving signal pin open = +5V STBY
  • Tying signal pin to GND = 3V3STBY AC_OK_H (Output) Internal 10K pull-up resistor to internal VDD6
  • AC OK Status SMB_ALERT_L (Output) Internal 10K pull-up resistor to internal VDD6
  • SMB Alert signal output 6 VDD depends on Standby Voltage selection of either 3.3V or 5V. 1.795 [45.59] 0.401 [10.18] 1 2 3 4 5 2X Ø0.100 [Ø2.54] THRU 0.802 [20.36] 1.295 [32.89] AC POWER CONNECTOR Header Positronic PLS5W5F1000 Contacts Position Part Number Function

1 Positronic: FS612N2 Safety Ground

2 Positronic: FS612N2 AC Line Voltage Ph 1

4 Positronic: FS612N2 AC Line Voltage Ph 2

5 Positronic: FS612N2 AC Line Voltage Ph 3

AC-DC Three Phase Power Converter D2U5T-H3-7000-54-HU4C.B01 Page 6 of 8 www.murata-ps.com/support 1.795±0.020 [45.59±0.51] 0.401 [10.18] 123 2X Ø0.100 [Ø2.54] THRU 0.802 [20.36] 1.295 [32.89] CUSTOMER AC POWER CONNECTOR Header Positronic PLS5W5M1000 Contacts Position Part Number Function

1 Positronic: MS612N Safety Ground

2 Positronic: MS612N-228.2 AC Line Voltage Ph 1 3 - Not fitted 4 Positronic: MS612N-228.2 AC Line Voltage Ph 2 5 Positronic: MS612N-228.2 AC Line Voltage Ph 3 NOTE: The Safety Ground MUST mate first. The Customer SHALL use the longer pin specified for position 1 and the shorter pins specified for positions 2, 4 and 5. OUTPUT CONNECTOR Connector: FCI Power Blade. Right Angle Header, 24 Signal Pins & 12 Power Blades. Part # 51939-486LF Mating connector option #1: FCI Power Blade. Right Angle Connector, 24 Signal Pins & 12 Power Blades. Part # 51915-132 Mating connector option #2: FCI Power Blade. Straight Connector, 24 Signal Pins & 12 Power Blades. Part # 51940-323 E1 P1 PA PA P2 P3 P4 P5 P6 P7 P8 P9 P10 P11 P12 U T SR T SR T SR T SR UUU G FE H G FE H E21 2 3 4 5 6 ROWS POWER SIGNAL D C B A

AC-DC Three Phase Power Converter D2U5T-H3-7000-54-HU4C.B01 Page 7 of 8 www.murata-ps.com/support OUTPUT CONNECTOR & SIGNAL PIN ASSIGNMENT Connector: FCI Power Blade Part # 51939-486LF Power Blade Number Signal Function Signal Direction P12 +VOUT 54Vdc Output P11 +VOUT 54Vdc Output P10 +VOUT 54Vdc Output P9 -VOUT 54Vdc Return Output P8 -VOUT 54Vdc Return Output P7 -VOUT 54Vdc Return Output P6 -VOUT 54Vdc Return Output P5 -VOUT 54Vdc Return Output P4 -VOUT 54Vdc Return Output P3 +VOUT 54Vdc Output P2 +VOUT 54Vdc Output P1 +VOUT 54Vdc Output Signal Pin Number Signal Function Signal Direction A1 A1 I2C Address Bit 1 Signal Input A2 PS_FAULT_L PSU Fault Status Output A3 A0 I2C Address Bit 0 Signal Input A4 VSB_RTN VSTBY_RTN Output A5 SCL I2C Clock Signal Bi-Directional A6 VOUT_SENSE+ VOUT_SENSE+ Input B1 A2 I2C Address Bit 2 Signal Input B2 PS_ON_H Enable PSU Input B3 +VSB +3.3V/5V STBY Out Output B4 VSB_RTN VSTBY_RTN Output B5 PS_KILL Enable PSU Shortest pin of the connector Input B6 N/A Reserved No User Connection Output C1 STBY_SEL_IN Selects +3V3 or +5VSTBY Input C2 AC_OK_H AC(DC) OK Status Output C3 +VSB +3.3V/5V STBY Out Output C4 VSB_RTN VSTBY_RTN Output C5 SDA I2C Data Signal Bi-Directional C6 VOUT_SENSE- VOUT_SENSE- Input D1 SMB_ALERT_L SMB Alert signal output Output D2 PWR_GOOD_H Power OK Status Output D3 +VSB +3.3V/5V STBY Out Output D4 VSB_RTN VSTBY_RTN Output D5 VSB_RTN VSTBY_RTN Output D6 VSB_RTN VSTBY_RTN Output

AC-DC Three Phase Power Converter D2U5T-H3-7000-54-HU4C.B01 Page 8 of 8 www.murata-ps.com/support Murata Power Solutions, Inc. makes no representation that the use of its products in the circuits described herein, or the use of other technical information contained herein, will not infringe upon existing or future patent rights. The descriptions contained herein do not imply the granting of licenses to make, use, or sell equipment constructed in accordance therewith. Specifications are subject to change without notice. © 2017 Murata Power Solutions, Inc. Murata Power Solutions, Inc. 11 Cabot Boulevard, Mansfield, MA 02048-1151 U.S.A. ISO 9001 and 14001 REGISTERED This product is subject to the following operating requirements and the Life and Safety Critical Application Sales Policy: Refer to: http://www.murata-ps.com/requirements/ MECHANICAL DIMENSIONS EFFICIENCY 0 10 20 30 50 60 8040 70 90 100 Efficiency (%) Full Load (%) 480VAC OPTIONAL ACCESSORIES Description Part Number 54V D2U5T Output Connector Card D2U5T-54-CONC APPLICATION NOTES Document Number Description Link ACAN-55 D2U5T PMBusTM Communication Protocol http://power.murata.com/datasheet?/data/apnotes/acan-55.pdf ACAN-56 D2U5T Output Interface Connector Card http://power.murata.com/datasheet?/data/apnotes/acan-56.pdf