CT5.121 C-Series 12V, 8A, TWO-PHASE INPUT POWER SUPPLY ƒ AC 380-480V Wide-range Input ƒ Input Fuses Already Included ƒ Requires only Two Legs of a 3-Phase System ƒ Width only 40mm ƒ Efficiency up to 85.8% ƒ Input -Transient Blanking Circuit Included ƒ Minimal Inrush Current Surge ƒ Full Power Between -25°C and +60°C ƒ 3 Year Warranty GENERAL DESCRIPTION The Dimension C-Series are cost optimized power supplies without compromisi ng quality, reliability and performance. The C-Series is part of the DIMENSION power supply family. The most outstanding features of CT5.121 are the high efficiency, electronic inrush current limitation, active input tr ansient filter and wide operational temperature range, the small size and other technological design concepts. The C-Series includes all th e essential basic functions. The CT5.121 utilizes only 2 legs of a 3-phase system which saves wiring and installation costs. Furthermore, this allows a smaller unit without compromising the size of the terminals. Due to the low power consumption, an unbalancing of the individual phases is not expected. SHORT-FORM DATA Output voltage DC 12V Adjustment range 12-15V Output current 8 – 6.4A Output power 96W Output ripple < 100mVpp 20Hz to 20MHz Input voltage AC 380-480V -15%/+20% Mains frequency 50-60Hz ±6% AC Input current 0.64 / 0.56A at 400 / 480Vac Power factor 0.44 / 0.42 at 400 / 480Vac AC Inrush current typ. 4A peak Efficiency 85.4 / 85.8% at 400 / 480Vac Losses 16.4 / 15.9W at 400 / 480Vac Temperature range -25°C to +70°C operational Derating 2.5W/°C +60 to +70°C Hold-up time typ. 33 / 58ms at 400 / 480Vac Dimensions 40x124x117mm WxHxD ORDER NUMBERS Power Supply CT5.121 12-15V Standard unit Accessory ZM1.WALL Wall mount bracket ZM12.SIDE Side mount bracket YR2.DIODE Decoupling module MARKINGS IND. CONT. EQ. UL 508 UL 60950-1 Marine,pending EMC, LVD Jan. 2010 / Rev. 1.0 DS-CT5.121-EN All parameters are specified at 12V, 8A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT5.121 C-Series 12V, 8A, TWO-PHASE INPUT INDEX Page Page The information presented in this document is believed to be accurate and reliable and may change without notice. TERMINOLOGY AND ABREVIATIONS PE and symbol PE is the abbreviation for Protective Earth and has the same meaning as the symbol . Earth, Ground This document uses the term “earth” which is the same as the U.S. term “ground”. T.b.d. To be defined, value or description will follow later. AC 400V A figure displayed with the AC or DC before the value represents a nominal voltage with standard tolerances (usually ±15%) included. E.g.: DC 12V describes a 12V battery disregarding whether it is full (13.7V) or flat (10V) 400Vac A figure with the unit (Vac) at the end is a momentary figure without any additional tolerances included. 50Hz vs. 60Hz As long as not otherwise stated, AC 380V and AC 400V parameters are valid at 50Hz and AC 480V parameters are valid at 60Hz mains frequency. Jan. 2010 / Rev. 1.0 DS-CT5.121-EN All parameters are specified at 12V, 8A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT5.121 C-Series 12V, 8A, TWO-PHASE INPUT 1. INTENDED USE This device is designed for installation in an enclosure and is intended for the general use such as in industrial control, office, communication, and instrumentation equipment. Do not use this power supply in aircrafts, trains and nuclear equipment where malfunction may cause severe personal injury or threaten human life. This device is designed for use in non-hazardous, ordinary or unclassified locations. Do not use in hazardous location areas. 2. INSTALLATION REQUIREMENTS This device may only be installed and put into operation by qualified personnel. This device does not contain serviceable parts. The tripping of an internal fuse (if included) is caused by an internal defect. If damage or malfunction should occur during installation or operation, immediately turn power off and send unit to the factory for inspection. Mount the unit on a DIN-rail so that the output terminals are located on top and input terminal on the bottom. For other mounting orientations see de-rating requirements in this document. This device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do not cover ventilation grid (e.g. cable conduits) by more than 30%! Keep the following installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right sides are recommended when the device is loaded permanently with more than 50% of the rated power. Increase this clearance to 15mm in case the adjacent device is a heat source (e.g. another power supply). WARNING Risk of electrical shock, fire, personal injury or death. - Do not use the power supply without proper grounding (Protective Earth). Use the terminal on the input block for earth connection and not one of the screws on the housing. - Turn power off before working on the devi ce. Protect against inadvertent re-powering. - Make sure that the wiring is correct by following all local and national codes. - Do not modify or repair the unit. - Do not open the unit as high voltages are present inside. - Use caution to prevent any foreign ob jects from entering into the housing. - Do not use in wet locations or in areas wh ere moisture or condensation can be expected. - Do not touch during power-on, and immediatel y after power-off. Hot surface may cause burns. Jan. 2010 / Rev. 1.0 DS-CT5.121-EN All parameters are specified at 12V, 8A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT5.121 C-Series 12V, 8A, TWO-PHASE INPUT 3. AC-INPUT AC input nom. AC 380-480V TN, TT, IT-mains networks, grounding of one phase is allowed except for UL508

applications

AC input range 323-576Vac continuous operation, no damage between 0 and 323Vac 576-700Vac for max. 1 second, occasional (not periodical) Allowed Voltage Phase to Earth 500Vac IEC 62103 Input frequency nom. 50–60Hz ±6% Turn-on voltage typ. 270Vac load independent, see Fig. 3-1 Shut-down voltage typ. 185Vac at 12V, 0A, see Fig. 3-1 typ. 215Vac at 12V, 4A typ. 225Vac at 12V, 8A AC 400V AC 480V Input current typ. 0.64A 0.56A at 12V, 8A, see Fig. 3-3 Power factor *) typ. 0.44 0.42 at 12V, 8A, see Fig. 3-4 Start-up delay typ. 75ms 75ms see Fig. 3-2 Rise time typ. 50ms 50ms 0mF, 12V, 8A, see Fig. 3-2 typ. 85ms 85ms 8mF, 12V, 8A, see Fig. 3-2 Turn-on overshoot max. 100mV 100mV see Fig. 3-2 *) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit. Fig. 3-1 Input voltage range Fig. 3-2 Turn-on behavior, definitions Turn-on 323V Rated input range VIN POUT 185V 576V Shut-down 260V 700Vac < 1s Start-up delay Rise Time Overshoot - 5%Output Voltage Input Voltage Fig. 3-3 Input current vs. output load at 12V Fig. 3-4 Power factor vs. output load 8A01 34 0.1 0.2 0.4 0.5 0.6 0.8A Input Current, typ. Output Current 2 5 0.3 0.7 6 7 400Vac 480Vac 8A01 34 0.30 0.35 0.40 0.45 0.50 Power Factor, typ. Output Current 2 5 480Vac 400Vac 7 6 Jan. 2010 / Rev. 1.0 DS-CT5.121-EN All parameters are specified at 12V, 8A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT5.121 C-Series 12V, 8A, TWO-PHASE INPUT 4. DC-INPUT DC input nom. DC 600V DC input range 450-780Vdc continuous operation Allowed Voltage Line to Earth max. 820Vdc IEC 62103 DC input current typ. 0.24A / 0.14A 450Vdc / 780Vdc, 12V, 8A Turn-on voltage typ. 370Vdc steady state value Shut-down voltage typ. 260Vdc steady state value Fig. 4-1 Wiring for DC Input Instructions for DC use: Load PE Power Supply AC DC Battery FUSE FUSE a) Use a battery or similar DC source. For other sources contact PULS b) Connect +pole to L1 and –pole to L2. c) Use appropriate external fuses in the + and – lines which are suitable for the DC-voltage. d) Connect the PE terminal to a earth wire or to the machine ground. e) DC-operation is not included in the UL approval. Additional testing might be necessary. 5. INPUT INRUSH CURRENT An active inrush limitation circuit limits the input inrush current after turn-on of the input voltage and after short input voltage interruptions. The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on. AC 400V AC 480V Inrush current max. 10A peak 10A peak -25°C to +70°C typ. 4Apeak 4A peak -25°C to +70°C Inrush energy max. 0.5A2s 0.5A 2s -25°C to +70°C Fig. 5-1 Input inrush current, typical behavior 1 > 22 > 3 > Output Voltage Input Voltage Input Current 20ms / DIV Input: 400Vac Output: 12V, 8A Ambient: 25°C Upper curve: Input current 2A / DIV Middle curve: Input voltage 500V / DIV Lower curve: Output voltage 5V / DIV Time basis: 20ms / DIV Jan. 2010 / Rev. 1.0 DS-CT5.121-EN All parameters are specified at 12V, 8A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT5.121 C-Series 12V, 8A, TWO-PHASE INPUT 6. OUTPUT Output voltage nom. 12V Adjustment range min. 12-15V guaranteed max. 16.0V at clockwise end position of potentiometer Factory setting 12.0V ±0.2%, at full load, cold unit Line regulation max. 10mV 323-576Vac Load regulation max. 100mV static value, 0A Æ 8A Ripple and noise voltage max. 100mVpp 20Hz to 20MHz, 50Ohm Output capacitance typ. 5 200μF Output current nom. 8A at 12V, see Fig. 6-1 nom. 6.4A at 15V, see Fig. 6-1 Output power nom. 96W Short-circuit current min. 12A continuous current, short circuit impedance 100mOhm max. 15A continuous current, short circuit impedance 100mOhm Fig. 6-1 Output voltage vs. output current, typ. Output Voltage 048 15V 12 1062 14A Adjustment Range Output Current Peak current capability (up to several milliseconds) The power supply can deliver a peak current which is higher than the specified short term current. This helps to start current demanding loads or to safely operate subsequent circuit breakers. The extra current is supplied by the output capacitors inside the power supply. During this event, the capacitors will be discharged and causes a voltage dip on the output. Detailed curves can be found in chapter 23.1. Peak current voltage dips typ. from 12V to 7V at 16A for 50ms, resistive load typ. from 12V to 7V at 40A for 2ms, resistive load typ. from 12V to 3.7V at 40A for 5ms, resistive load Jan. 2010 / Rev. 1.0 DS-CT5.121-EN All parameters are specified at 12V, 8A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT5.121 C-Series 12V, 8A, TWO-PHASE INPUT 7. HOLD-UP TIME AC 400V AC 480V Hold-up Time typ. 33ms 58ms at 12V, 8A, see Fig. 7-1 typ. 63ms 110ms at 12V, 4A, see Fig. 7-1 Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down behavior, definitions 100ms 320 360 400 440 480Vac Input Voltage Hold-up Time at 12Vdc 4A, typ. 8A, min.8A, typ. 4A, min. - 5% Hold-up Time Zero Transition Output Voltage Input Voltage Jan. 2010 / Rev. 1.0 DS-CT5.121-EN All parameters are specified at 12V, 8A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT5.121 C-Series 12V, 8A, TWO-PHASE INPUT 8. EFFICIENCY AND POWER LOSSES AC 400V AC 480V Efficiency typ. 85.4% 85.8% at 12V, 8A Average efficiency *) typ. 84.7% 84.1% 25% at 2A, 25% at 4A, 25% at 6A. 25% at 8A Power losses typ. 1.5W 1.6W at 0A 8.4W 9.1W at 12V, 4A typ. 16.4W 15.9W at 12V, 8A *) The average efficiency is an assumption for a typical application where the power supply is loaded with 25% of the nominal load for 25% of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with 100% of the nominal load for the rest of the time. Fig. 8-1 Efficiency vs. output current at 12V, typ. Fig. 8-2 Losses vs. output current at 12V, typ. Efficiency 87% 8A24 5 Output Current 85 400Vac 480Vac Power Losses 012 45 8 A 18W Output Current 400Vac 480Vac Fig. 8-3 Efficiency vs. input voltage at 12V, 8A, typ. Fig. 8-4 Losses vs. input voltage at 12V, 8A, typ. Efficiency 320 360 400 440 480 87% 84.5 85.5 86.5 86.0 85.0 84.0 520 560 Input Voltage Vac Power Losses 320 360 400 440 480 18W o 520 560 Input Voltage Vac Jan. 2010 / Rev. 1.0 DS-CT5.121-EN All parameters are specified at 12V, 8A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT5.121 C-Series 12V, 8A, TWO-PHASE INPUT 9. FUNCTIONAL DIAGRAM Fig. 9-1 Functional diagram VOUTOutput Over- Voltage Protection PFC Inductor Inrush Limiter Transient Filter Input Fuses Input Filter Input Rectifier Output Voltage Regulator Power Converter Output Filter Output Power Manager Temper- ature Shut- down DC-ok LED 10. FRONT SIDE AND USER ELEMENTS Fig. 10-1 Front side A Output Terminals Screw terminals, dual terminals per pole + Positive output - Negative (return) output B Input Terminals Screw terminals L1, L2 Phase input PE (Protective Earth) input C Output voltage potentiometer Open the flap to set the output voltage. Factory set: 12.0V D DC-OK LED (green) On when the voltage on the output terminals is > 10.5V A C D B Jan. 2010 / Rev. 1.0 DS-CT5.121-EN All parameters are specified at 12V, 8A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT5.121 C-Series 12V, 8A, TWO-PHASE INPUT 11. TERMINALS AND WIRING Input Output Type screw terminals screw terminals Solid wire 0.5-6mm2 0.5-6mm 2 Stranded wire 0.5-4mm2 0.5-4mm 2 American Wire Gauge 20-10 AWG 20-10 AWG Wire stripping length 7mm / 0.275inch 7mm / 0.275inch Screwdriver 3.5mm slotted or Pozidrive No 2 3.5mm slotted or Pozidrive No 2 Recommended tightening torque 0.8Nm, 7lb.in 0.8Nm, 7lb.in Instructions: a) Use appropriate copper cables that are designed for an operating temperature of: 60°C for ambient up to 45°C and 75°C for ambient up to 60°C minimum. b) Follow national installation codes and installation regulations! c) Ensure that all strands of a strande d wire enter the terminal connection! d) Up to two stranded wires with the same cross secti on are permitted in one connection point (except PE wire). e) Do not use the unit without PE connection. f) Screws of unused terminal compa rtments should be securely tightened. g) Ferrules are allowed, but not required 12. RELIABILITY AC 400V AC 480V Lifetime expectancy *) 51 000h 55 000h at 12V, 8A and 40°C 152 000h 147 000h at 12V, 4A and 40°C 144 000h 156 000h at 12V, 8A and 25°C MTBF ) SN 29500, IEC 61709 983 000h 967 000h at 12V, 8A and 40°C 1 799 000h 1 769 000h at 12V, 8A and 25°C MTBF ) MIL HDBK 217F 484 000h 455 000h at 12V, 8A and 40°C; Ground Benign GB40 636 000h 600 000h at 12V, 8A and 25°C; Ground Benign GB25 *) The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the capacitor’s manufacturer specification. The prediction model allows only a calculation of up to 15 years from date of shipment. **) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product. Jan. 2010 / Rev. 1.0 DS-CT5.121-EN All parameters are specified at 12V, 8A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT5.121 C-Series 12V, 8A, TWO-PHASE INPUT 13. EMC The power supply is suitable for applications in industrial environment as well as in residential, commercial and light industry environment without any restrictions. The CE mark indicates conformance with EMC guideline 89/336/EC, 93/68/EC and 2004/108/EC and the low-voltage directive (LVD) 73/23/EC and 2006/95/EC. A detailed EMC report is available on request. EMC Immunity Generic standards: EN 61000-6-1 and EN 61000-6-2 Electrostatic discharge EN 61000-4-2 Contact discharge Air discharge 8kV 15kV Criterion A Criterion A Electromagnetic RF field EN 61000-4-3 80MHz-2.7GHz 10V/m Criterion A Fast transients (Burst) EN 61000-4-4 Input lines Output lines 4kV 2kV Criterion A Criterion A Surge voltage on input EN 61000-4-5 L1 Æ L2 2kV Criterion A Surge voltage on input EN 61000-4-5 L1 Æ PE, L2 Æ PE 4kV Criterion A Surge voltage on output EN 61000-4-5 + Æ - + / - Æ PE 500V 500V Criterion A Criterion A Conducted disturbance EN 61000-4-6 0.15-80MHz 10V Criterion A Mains voltage dips EN 61000-4-11 0% of 380Vac 0% of 480Vac 0Vac, 20ms 0Vac, 20ms Criterion A Criterion A Mains voltage dips EN 61000-4-11 40% of 380Vac 40% of 480Vac 70% of 380Vac 70% of 480Vac 200ms 200ms 500ms 500ms Criterion C Criterion C Criterion A Criterion A Voltage interruptions EN 61000-4-11 0Vac, 5000ms Criterion C Voltage sags SEMI F47 0706 80% of 380Vac, load: 12V, 4A 70% of 380Vac, load: 12V, 4A 50% of 380Vac, load: 12V, 4A 1000ms 500ms 200ms Criterion A Criterion A Criterion A Voltage sags SEMI F47 0706 80% of 480Vac, load: 12V, 8A 70% of 480Vac, load: 12V, 8A 50% of 480Vac, load: 12V, 8A 1000ms 500ms 200ms Criterion A Criterion A Criterion A Powerful transients VDE 0160 over entire load range 1550V, 1.3ms Criterion A Criterions: A: Power supply shows normal operation behavior within the defined limits. C: Temporary loss of function is possible. Power supply may shut-down and restarts by itself. No damage or hazards for the powe r supply will occur. EMC Emission Generic standards: EN 61000-6-3 and EN 61000-6-4 Conducted emission EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22 Class B, input lines Radiated emission EN 55011, EN 55022 Class B Harmonic input current EN 61000-3-2 fulfilled Voltage fluctuations, flicker EN 61000-3-3 fulfilled This device complies with FCC Part 15 rules. Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Switching frequency Variable between 45kHz and 170kHz depending on load and input voltage Jan. 2010 / Rev. 1.0 DS-CT5.121-EN All parameters are specified at 12V, 8A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT5.121 C-Series 12V, 8A, TWO-PHASE INPUT 14. ENVIRONMENT Operational temperature *) -25°C to +70°C (-13°F to 158°F) reduce output power according Fig. 14-1 Storage temperature -40 to +85°C (-40°F to 185°F) for storage and transportation Output de-rating 2.5W/°C 60-70°C (140°F to 158°F) Humidity **) 5 to 95% r.H. IEC 60068-2-30 Vibration sinusoidal 2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g 2 hours / axis IEC 60068-2-6 Shock 30g 6ms, 20g 11ms 3 bumps / direction, 18 bumps in total IEC 60068-2-27 Altitude 0 to 6000m (0 to 20 000ft) reduce output power or ambient temperature above 2000m sea level. Altitude de-rating 6W/1000m or 5°C/1000m above 2000m (6500ft), see Fig. 14-2 Over-voltage category III IEC 62103, EN 50178, altitudes up to 2000m II altitudes from 2000m to 6000m Degree of pollution 2 IEC 62103, EN 50178, not conductive *) Operational temperature is the same as the ambient temperature and is defined as the air temperature 2cm below the unit. **) Do not energize while condensation is present -25 0 20 40 70°C Ambient Temperature continuous Allowable Output Current at 12V 0 2000 4000 6000m Altitude A... Tamb < 60°C B... Tamb < 50°C C... Tamb < 40°C C B A Allowable Output Current at 12V Jan. 2010 / Rev. 1.0 DS-CT5.121-EN All parameters are specified at 12V, 8A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT5.121 C-Series 12V, 8A, TWO-PHASE INPUT 15. PROTECTION FEATURES Output protection Electronically protected against overload, no-load and short-circuits *) Output over-voltage protection typ. 18Vdc max. 20Vdc In case of an internal power supply defect, a redundant circuit limits the maximum output voltage. The output shuts down and automatically attempts to restart. Degree of protection IP 20 EN/IEC 60529 Penetration protection > 3.5mm e.g. screws, small parts Over-temperature protection yes output shut-down with automatic restart Input transient protection MOV (Metal Oxide Varistor) and active transient filter Internal input fuse 2x T3.15A H.B.C. not user replaceable *) In case of a protection event, audible noise may occur. 16. SAFETY FEATURES Input / output separation *) SELV IEC/EN 60950-1 PELV IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41 Class of protection I PE (Protective Earth) connection required Isolation resistance > 5MOhm input to output, 500Vdc PE resistance < 0.1Ohm Touch current (leakage current) typ. 0.14mA 400Vac, 50Hz, TN mains typ. 0.19mA 480Vac, 60Hz, TN mains < 0.18mA 440Vac, 50Hz, TN mains < 0.25mA 528Vac, 60Hz, TN mains *) Double or reinforced insulation 17. DIELECTRIC STRENGTH The output voltage is floating and has no ohmic connection to the ground. Type and factory tests are conducted by the manufacturer. Field tests may be conducted in the field using the appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down). Connect all phase-terminals together as well as all output poles before conducting the test. When testing, set the cut-off current settings to the value in the table below. Fig. 17-1 Dielectric strength A B C Type test 60s 2500Vac 3000Vac 500Vac Factory test 5s 2500Vac 2500Vac 500Vac Field test 5s 2000Vac 2000Vac 500Vac Cut-off current setting > 5mA > 5mA > 15mA A C B Input Earth Output To fulfill the PELV requirements according to EN60204-1 § 6.4.1, we recommend that either the + pole, the – pole or any other part of the output circuit shall be connected to the protective earth system. This helps to avoid situations in which a load starts unexpectedly or can not be switched off when unnoticed earth faults occur. Jan. 2010 / Rev. 1.0 DS-CT5.121-EN All parameters are specified at 12V, 8A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT5.121 C-Series 12V, 8A, TWO-PHASE INPUT 18. APPROVALS IEC 60950-1 CB Scheme, Information Technology Equipment UL 508 IND. CONT. EQ. Listed for use as Industrial Control Equipment; E-File: E198865 Mains supply circuit: 3-wire + PE, star UL 60950-1 Recognized for use as Information Technology Equipment; E-File: E137006, Level 3 Marine, pending GL (Germanischer Lloyd) classified and ABS (American Bureau for Shipping) PDA Environmental category: C, EMC2 Marine and offshore applications 19. FULFILLED STANDARDS EN 61558-2-17 Safety of Power Transformers EN/IEC 60204-1 Safety of Electrical Equipment of Machines EN/IEC 61131-2 Programmable Controllers EN 50178, IEC 62103 Electronic Equipment in Power Installations 20. USED SUBSTANCES The unit does not release any silicone and is suitable for the use in paint shops. The unit conforms to the RoHS directive 2002/96/EC Electrolytic capacitors included in this unit do not use electrolytes such as Quaternary Ammonium Salt Systems. Plastic housings and other molded plastic materials are free of halogens, wires and cables are not PVC insulated. The production material within our production does not include following toxic chemicals: Polychlorized Biphenyl (PCB), Polychlorized Terphenyl (PCT), Pentachlorophenol (PCP), Polychlorinated naphthalene (PCN), Polybrom Biphenyll (PBB), Polybrom Bipheny-oxyd (PBO), Polybrominated Diphenylether (PBDE), Polychlorinated Diphenylether (PCDE), Polydibromphenyl Oxyd (PBDO), Cadmium, Asbestos, Mercury, Silicia Jan. 2010 / Rev. 1.0 DS-CT5.121-EN All parameters are specified at 12V, 8A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT5.121 C-Series 12V, 8A, TWO-PHASE INPUT 21. PHYSICAL DIMENSIONS AND WEIGHT Weight 500g / 1.1lb DIN-Rail Use 35mm DIN-rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm. The DIN-rail height must be added to the unit depth (117mm) to calculate the total required installation depth. Installation Clearances See chapter 2 Fig. 21-1 Front view Fig. 21-2 Side view Jan. 2010 / Rev. 1.0 DS-CT5.121-EN All parameters are specified at 12V, 8A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT5.121 C-Series 12V, 8A, TWO-PHASE INPUT 22. ACCESSORIES ZM1.WALL Wall mounting bracket This bracket is used to mount specific Dimension units onto a flat surface without utilizing a DIN-Rail. The two aluminum brackets and the black plastic slider of the unit have to be removed, so that the two steel brackets can be mounted. Fig. 22-1 ZM1.WALL Wall mounting bracket Fig. 22-2 Assembled wall mounting bracket *) *) Picture of the power supply is for representation only ZM12.SIDE Side mounting bracket This bracket is used to mount Dimension units sideways with or without utilizing a DIN-Rail. The two aluminum brackets and the black plastic slider of the unit have to be detached, so that the steel brackets can be mounted. For sideway DIN-rail mounting, the removed aluminum brackets and the black plastic slider need to be mounted on the steel bracket. Fig. 22-3 ZM12.SIDE Side mounting bracket *) Fig. 22-4 Side mounting with DIN-rail brackets *) *) Picture of the power supply is for representation only Jan. 2010 / Rev. 1.0 DS-CT5.121-EN All parameters are specified at 12V, 8A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT5.121 C-Series 12V, 8A, TWO-PHASE INPUT 23. APPLICATION NOTES 23.1. PEAK CURRENT CAPABILITY Solenoids, contactors and pneumatic modules often have a steady state coil and a pick-up coil. The inrush current demand of the pick-up coil is several times higher than the steady-state current and usually exceeds the nominal output current (including the PowerBoost) The same situation applies, when starting a capacitive load. Branch circuits are often protected with circuit breakers or fuses. In case of a short or an overload in the branch circuit, the fuse needs a certain amount of over-current to trip or to blow. The peak current capability ensures the safe operation of subsequent circuit breakers. Assuming the input voltage is turned on before such an event, the built-in large sized output capacitors inside the power supply can deliver extra current. Discharging this capacitor causes a voltage dip on the output. The following two examples show typical voltage dips: Fig. 23-1 Peak load 16A for 50ms, typ. Fig. 23-2 Peak load 40A for 5ms, typ. 10ms/DIV Output Voltage Output Current 12V 16A 1ms/DIV Output Voltage Output Current 12V 40A 3.7V Peak load 16A (resistive load) for 50ms Output voltage dips from 12V to 7V. Peak load 40A (resistive load) for 5ms Output voltage dips from 12V to 3.7V. 23.2. BACK-FEEDING LOADS Loads such as decelerating motors and inductors can feed voltage back to the power supply. This feature is also called return voltage immunity or resistance against Back- E.M.F. (Electro Magnetic Force). This power supply is resistant and does not show malfunctioning when a load feeds back voltage to the power supply. It does not matter, whether the power supply is on or off. The maximum allowed feed-back-voltage is 25Vdc. The absorbing energy can be calculated according to the built-in large sized output capacitance which is specified in chapter 6. Jan. 2010 / Rev. 1.0 DS-CT5.121-EN All parameters are specified at 12V, 8A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT5.121 C-Series 12V, 8A, TWO-PHASE INPUT 23.3. CHARGING OF BATTERIES The power supply can be used to charge 12V lead-acid or maintenance free batteries. Instructions for charging batteries: a) Ensure that the ambient temperature of the power supply is below 45°C b) Set output voltage (measured at no load and at the battery end of the cable) very precisely to the end-of-charge voltage. End-of-charge voltage 13.9V 13.75V 13.6V 13.4V Battery temperature 10°C 20°C 30°C 40°C c) Use a 10A circuit breaker (or blocking diode) between the power supply and the battery. d) Ensure that the output current of the power supply is below the allowed charging current of the battery. e) The return current to the power supply (battery discharge current) is typ. 5.5mA when the power supply is switched off (except in case a blocking diode is utilized). 23.4. EXTERNAL INPUT PROTECTION The unit is tested and approved for branch circuits up to 30A (U.S.A.) and 32A (IEC). An external protection is only required, if the supplying branch has an ampacity greater than this. Check also local codes and local requirements. In some countries local regulations might apply. If an external fuse is necessary or utilized, minimum requirements need to be considered to avoid nuisance tripping of the circuit breaker. A minimum value of 6A B- or 3A C-Characteristic breaker should be used 23.5. INDUCTIVE AND CAPACITIVE LOADS The unit is designed to supply any kind of loads, including unlimited capacitive and inductive loads. Jan. 2010 / Rev. 1.0 DS-CT5.121-EN All parameters are specified at 12V, 8A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT5.121 C-Series 12V, 8A, TWO-PHASE INPUT 23.6. PARALLEL USE TO INCREASE OUTPUT POWER CT5.121 power supplies can be paralleled to increase the output power. This power supply has no feature included which balances the load current between the power supplies. Usually the power supply with the higher adjusted output voltage draws current until it goes into current limitation. Therefore, the power supply can only be used in parallel as long as the ambient temperature stays below 45°C. The output voltages of all power supplies shall be adjusted to the same value (±100mV). A fuse or diode on the output of each unit is only required if more than three units are connected in parallel. If a fuse (or circuit breaker) is used, choose one with approximately 150% of the rated output current of one power supply. Keep an installation clearance of 15mm (left / right) between two power supplies and avoid installing the power supplies on top of each other. Do not use power supplies in parallel in mounting orientations other than the standard mounting orientation (input terminals on the bottom and output terminals on top of the unit) or in any other condition where a derating of the output current is required (e.g. altitude, above 60°C, …). Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple power supplies. Unit A AC DC Unit B AC DC Load 23.7. PARALLEL USE FOR REDUNDANCY Power supplies can be paralleled for redundancy to gain higher system availability. Redundant systems require a certain amount of extra power to support the load in case one power supply unit fails. The simplest way is to put two power supplies in parallel. This is called a 1+1 redundancy. In case one power supply unit fails, the other one is automatically able to support the load current without any interruption. Redundant systems for a higher power demand are usually built in a N+1 method. E.g. six power supplies, each rated for 8A are paralleled to build a 40A redundant system. For N+1 redundancy the same restrictions apply as for increasing the output power, see also section 23.6. Please note: This simple way to build a redundant system does not cover failures such as an internal short circuit in the secondary side of the power supply. In such a case, the defect unit becomes a load for the other power supplies and the output voltage can not be maintained any more. This can only be avoided by utilizing decoupling diodes which are included in the decoupling module YR2.DIODE. Recommendations for building redundant power systems: a) Use separate input fuses for each power supply. b) Monitor the individual power supply units. c) 1+1 Redundancy is allowed up to an ambient temperature of 60°C N+1 Redundancy is allowed up to an ambient temperature of 45°C d) It is desirable to set the output voltages of all units to the same value (± 100mV) or leave it at the factory setting. Jan. 2010 / Rev. 1.0 DS-CT5.121-EN All parameters are specified at 12V, 8A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT5.121 C-Series 12V, 8A, TWO-PHASE INPUT 23.8. DAISY CHAINING OF OUTPUTS Daisy chaining (jumping from one power supply output to the next) is allowed as long as the average output current through one terminal pin does not exceed 25A. If the current is higher, use a separate distribution terminal block. Fig. 23-3 Daisy chaining of outputs Fig. 23-4 Using distribution terminals Power Supply + + - - Input Output Load + - max 25A! Power Supply + + - - Input Output Load + - Distribution Terminals Power Supply + + - - Input Output Power Supply + + - - Input Output 23.9. SERIES OPERATION Earth Unit A AC DC Unit B AC DC Load Power supplies of the same type can be connected in series for higher output voltages. It is possible to connect as many units in series as needed, providing the sum of the output voltage does not exceed 150Vdc. Voltages with a potential above 60Vdc are not SELV any more and can be dangerous. Such voltages must be installed with a protection against touching. Earthing of the output is required when the sum of the output voltage is above 60Vdc. Avoid return voltage (e.g. from a decelerating motor or battery) which is applied to the output terminals. Keep an installation clearance of 15mm (left / right) between two power supplies and avoid installing the power supplies on top of each other. Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple power supplies. 23.10. USE IN A TIGHTLY SEALED ENCLOSURE When the power supply is installed in a tightly sealed enclosure, the temperature inside the enclosure will be higher than outside. In such situations, the inside temperature defines the ambient temperature for the power supply. The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure. The power supply is placed in the middle of the box, no other heat producing items are inside the box Enclosure: Rittal Typ IP66 Box PK 9516 100, plastic, 110x180x165mm Load: 12V, 6.4A; (=80%) load is placed outside the box Input: 2x 400Vac Temperature inside enclosure: 51.1°C (i n the middle of the right side of the power supply with a distance of 2cm) Temperature outside enclosure: 25.2°C Temperature rise: 25.9K Jan. 2010 / Rev. 1.0 DS-CT5.121-EN All parameters are specified at 12V, 8A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT5.121 C-Series 12V, 8A, TWO-PHASE INPUT Jan. 2010 / Rev. 1.0 DS-CT5.121-EN All parameters are specified at 12V, 8A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 23.11. MOUNTING ORIENTATIONS Mounting orientations other than input terminals on the bottom and output on the top require a reduction in continuous output power or a limitation in the maximal allowed ambient temperature. The amount of reduction influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous operation can be found below: Curve A1 Recommended output current. Curve A2 Max allowed output current (res ults in approximately half the lifetime expectancy of A1). Fig. 23-5 Mounting Orientation A (Standard orientation) Power Supply OUTPUT INPUT Output Current 10 20 30 40 60°C Ambient Temperature Fig. 23-6 Mounting Orientation B (Upside down) Power Supply OUTPUT INPUT Output Current 10 20 30 40 60°C Ambient Temperature Fig. 23-7 Mounting Orientation C (Table-top mounting) Output Current 10 20 30 40 60°C Ambient Temperature Fig. 23-8 Mounting Orientation D (Horizontal cw) Power Supply OUTPUT INPUT Output Current 10 20 30 40 60°C Ambient Temperature Fig. 23-9 Mounting Orientation E (Horizontal ccw) Power Supply OUTPUT INPUT Output Current 10 20 30 40 60°C Ambient Temperature