CT10.241 C-Series 24V, 10A, THREE PHASE INPUT POWER SUPPLY ƒ 3AC 380-480V Wide-range Input ƒ 2 or 3-Phase Operation Possible ƒ Width only 62mm ƒ Efficiency up to 92.9% Due to Synchronous Rectifier ƒ Excellent Partial Load Efficiency ƒ 20% Output Power Reserves ƒ Easy fuse tripping Due to High Overload Current ƒ Input -Transient Blanking Circuit Included ƒ Minimal Inrush Current Surge ƒ Three Input Fuses Included ƒ Current Sharing Feature for Parallel Use ƒ Full Power Between -25°C and +60°C ƒ 3 Year Warranty GENERAL DESCRIPTION The Dimension C-Series are cost optimized power supplies without compromisi ng quality, reliability and performance. The C-Series is part of the DIMENSION power supply family. The most outstanding features of CT10.241 are the high effi ciency, electronic inrush current limitation, active inpu t transient filter and wide operational temperature range. The small size is achieved by a synchronous rectification and further technological design details. The C-Series includes all th e essential basic functions. The devices have a power reserve of 20% included, which may even be used cont inuously at temperatures up to +45°C. Additionally, the CT10.241 can deliver 3 times the nominal output current for 10ms which helps to trip fuses on faulty output branches. SHORT-FORM DATA Output voltage DC 24V Adjustment range 24-28V Output current 10 – 8.6A ambient <60°C 12 – 10.3A ambient <45°C Output power 240W ambient <60°C 288W ambient <45°C Output ripple < 50mVpp 20Hz to 20MHz Input voltage AC 380-480V -15%/+20% Mains frequency 50-60Hz ±6% AC Input current 0.7 / 0.6A at 3x400 / 480Vac Power factor 0.53 / 0.52 at 3x400 / 480Vac AC Inrush current typ. 4A peak Efficiency 92.8 / 92.9% at 3x400 / 480Vac Losses 18.6 / 18.3W at 3x400 / 480Vac Temperature range -25°C to +70°C operational Derating 6W/°C +60 to +70°C Hold-up time typ. 34 / 54ms at 3x400 / 480Vac Dimensions 62x124x117mm WxHxD ORDER NUMBERS Power Supply CT10.241 24-28V Standard unit Accessory ZM1.WALL Wall mount bracket ZM13.SIDE Side mount bracket YRM2.DIODE Decoupling module UF20.241 Buffer unit MARKINGS IND. CONT. EQ. UL 508 UL 60950-1 Marine, pending EMC, LVD Jan. 2010 / Rev. 1.3 DS-CT10.241-EN All parameters are specified at 24V, 10A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT10.241 C-Series 24V, 10A, THREE PHASE INPUT INDEX Page Page The information presented in this document is believed to be accurate and reliable and may change without notice. TERMINOLOGY AND ABREVIATIONS PE and symbol PE is the abbreviation for Protective Earth and has the same meaning as the symbol . Earth, Ground This document uses the term “earth” which is the same as the U.S. term “ground”. T.b.d. To be defined, value or description will follow later. AC 400V A figure displayed with the AC or DC before the value represents a nominal voltage with standard tolerances (usually ±15%) included. E.g.: DC 12V describes a 12V battery disregarding whether it is full (13.7V) or flat (10V) 400Vac A figure with the unit (Vac) at the end is a momentary figure without any additional tolerances included. 50Hz vs. 60Hz As long as not otherwise stated, AC 380V and AC 400V parameters are valid at 50Hz and AC 480V parameters are valid at 60Hz mains frequency. Jan. 2010 / Rev. 1.3 DS-CT10.241-EN All parameters are specified at 24V, 10A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT10.241 C-Series 24V, 10A, THREE PHASE INPUT 1. INTENDED USE This device is designed for installation in an enclosure and is intended for the general use such as in industrial control, office, communication, and instrumentation equipment. Do not use this power supply in aircrafts, trains and nuclear equipment where malfunction may cause severe personal injury or threaten human life. This device is designed for use in non-hazardous, ordinary or unclassified locations. Do not use in hazardous location areas. 2. INSTALLATION REQUIREMENTS This device may only be installed and put into operation by qualified personnel. This device does not contain serviceable parts. The tripping of an internal fuse (if included) is caused by an internal defect. If damage or malfunction should occur during installation or operation, immediately turn power off and send unit to the factory for inspection. Mount the unit on a DIN-rail so that the output terminals are located on top and input terminal on the bottom. For other mounting orientations see de-rating requirements in this document. This device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do not cover ventilation grid (e.g. cable conduits) by more than 30%! Keep the following installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right sides are recommended when the device is loaded permanently with more than 50% of the rated power. Increase this clearance to 15mm in case the adjacent device is a heat source (e.g. another power supply). WARNING Risk of electrical shock, fire, personal injury or death. - Do not use the power supply without proper grounding (Protective Earth). Use the terminal on the input block for earth connection and not one of the screws on the housing. - Turn power off before working on the devi ce. Protect against inadvertent re-powering. - Make sure that the wiring is correct by following all local and national codes. - Do not modify or repair the unit. - Do not open the unit as high voltages are present inside. - Use caution to prevent any foreign ob jects from entering into the housing. - Do not use in wet locations or in areas wh ere moisture or condensation can be expected. - Do not touch during power-on, and immediatel y after power-off. Hot surface may cause burns. Jan. 2010 / Rev. 1.3 DS-CT10.241-EN All parameters are specified at 24V, 10A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT10.241 C-Series 24V, 10A, THREE PHASE INPUT 3. AC-INPUT AC input nom. 3AC 380-480V TN, TT, IT-mains networks, grounding of one phase is allowed except for UL508

applications

AC input range 3x 323-576Vac continuous operation 3x 576-700Vac for max. 1 second, occasional (not periodical) 3x 200-323Vac full power for 200ms, no damage between 0 and 200Vac Allowed Voltage Phase to Earth 500Vac IEC 62103 Input frequency nom. 50–60Hz ±6% Turn-on voltage typ. 3x 260Vac steady-state value, see Fig. 3-1 Shut-down voltage typ. 3x 185Vac steady-state value, see Fig. 3-1 3AC 400V 3AC 480V Input current typ. 0.7A 0.6A at 24V, 10A, symmetrical phase voltage, see Fig. 3-3 Power factor *) typ. 0.53 0.52 at 24V, 10A, see Fig. 3-4 Start-up delay typ. 90ms 90ms see Fig. 3-2 Rise time typ. 40ms 40ms 0mF, 24V, 10A, see Fig. 3-2 typ. 85ms 85ms 10mF, 24V, 10A, see Fig. 3-2 Turn-on overshoot max. 200mV 200mV see Fig. 3-2 *) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit. Fig. 3-1 Input voltage range Fig. 3-2 Turn-on behavior, definitions Turn-on 323V Rated input range VIN POUT 185V 576V Shut-down 260V 3x700Vac < 1s Start-up delay Rise Time Overshoot - 5%Output Voltage Input Voltage Fig. 3-3 Input current vs. output load at 24V Fig. 3-4 Power factor vs. output load 12A02468 1 0 0.1 0.2 0.3 0.4 0.8A Input Current, typ. 0.5 Output Current 3x 400Vac 3x 480Vac 0.6 0.7 Power Factor, typ. 02468 1 0 1 2 A 0.35 0.4 0.45 0.5 0.55 0.6 400Vac 480Vac Output Current Jan. 2010 / Rev. 1.3 DS-CT10.241-EN All parameters are specified at 24V, 10A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT10.241 C-Series 24V, 10A, THREE PHASE INPUT 4. DC-INPUT DC input nom. DC 600V DC input range min. 450-780Vdc continuous operation Allowed Voltage Line to Earth max. 820Vdc IEC 62103 DC input current typ. 0.58A / 0.34A 450Vdc / 780Vdc, at 24V, 10A Turn-on voltage typ. 370Vdc steady state value Shut-down voltage typ. 260Vdc steady state value Fig. 4-1 Wiring for DC Input Instructions for DC use: Load PE Power Supply AC DC Battery FUSE FUSE a) Use a battery or similar DC source. For other sources contact PULS b) Connect +pole to L1 and –pole to L2. c) Terminal L3 remains unused, terminal screw of L3 must be securely tightened. d) Use appropriate external fuses in the + and – lines which are suitable for the DC-voltage. e) Connect the PE terminal to a earth wire or to the machine ground. f) DC-operation is not included in the UL approval. Additional testing might be necessary. 5. INPUT INRUSH CURRENT An active inrush limitation circuit limits the input inrush current after turn-on of the input voltage and after short input voltage interruptions. The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on. 3AC 400V 3AC 480V Inrush current max. 10Apeak 10A peak -25°C to +70°C typ. 4Apeak 4A peak -25°C to +70°C Inrush energy max. 0.5A2s 0.5A 2s -25°C to +70°C Fig. 5-1 Input inrush current, typical behavior Output Voltage Input Voltage Input Current 20ms / DIV Input: 3x 400Vac Output: 24V, 10A Ambient: 25°C Upper curve: Input current 1A / DIV Middle curve: Input voltage 500V / DIV Lower curve: Output voltage 10V / DIV Time basis: 20ms / DIV Jan. 2010 / Rev. 1.3 DS-CT10.241-EN All parameters are specified at 24V, 10A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT10.241 C-Series 24V, 10A, THREE PHASE INPUT 6. OUTPUT Output voltage nom. 24V Adjustment range min. 24-28V guaranteed max. 30V at clockwise end position of potentiometer Factory setting typ. 24.1V ±0.2%, at full load, cold unit, in “single use” mode typ. 24.1V ±0.2%, at full load, cold unit, in “parallel use” mode typ. 25.1V at no load, cold unit, in “parallel use” mode Line regulation max. 10mV 3x 323-576Vac Load regulation max. 100mV in “single use” mode: static value, 0A Æ 10A typ. 1000mV in “parallel use” mode: static value, 0A Æ 10A, see Fig. 6-2 Ripple and noise voltage max. 50mVpp 20Hz to 20MHz, 50Ohm Output capacitance typ. 6 500μF Output current nom. 12A at 24V, ambient < 45°C, see Fig. 6-1 nom. 10A at 24V, ambient < 60°C, see Fig. 6-1 nom. 10.3A at 28V, ambient < 45°C, see Fig. 6-1 nom. 8.6A at 28V, ambient < 60°C, see Fig. 6-1 Output power nom. 288W ambient < 45°C nom. 240W ambient < 60°C Short-circuit current min. 19A continuous, load impedance 100mOhm, see Fig. 6-1 max. 23A continuous, load impedance 100mOhm, see Fig. 6-1 min. 28A <20ms, load impedance 100mOhm, see Fig. 6-1 max. 32A <20ms, load impedance 100mOhm, see Fig. 6-1 discharge current of output capacitors not included Fig. 6-1 Output voltage vs. output current, typ. Fig. 6-2 Output voltage in “parallel use” mode, typ. Output Voltage (Single Use, typ.) 09 1 8 28V 30A21123 6 15 24 27 Adjustment Range Output Current Extra current for 20ms Continuous current Factory setting Output Voltage (Parallel Use, typ.) 22V 048 23V 24V 25V 29V 26V 27V 28V 12A1062 Adjustment Range Factory setting Output Current Peak current capability (up to several milliseconds) The power supply can deliver a peak current which is higher than the specified short term current. This helps to start current demanding loads or to safely operate subsequent circuit breakers. The extra current is supplied by the output capacitors inside the power supply. During this event, the capacitors will be discharged and causes a voltage dip on the output. Detailed curves can be found in chapter 23.1. Peak current voltage dips typ. from 24V to 6V at 20A for 50ms, resistive load typ. from 24V to 12V at 50A for 2ms, resistive load typ. from 24V to 3V at 50A for 5ms, resistive load Jan. 2010 / Rev. 1.3 DS-CT10.241-EN All parameters are specified at 24V, 10A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT10.241 C-Series 24V, 10A, THREE PHASE INPUT 7. HOLD-UP TIME 3AC 400V 3AC 480V Hold-up Time typ. 34ms 54ms at 24V, 10A, see Fig. 7-1 typ. 68ms 108ms at 24V, 5A, see Fig. 7-1 Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down behavior, definitions 100ms 320 360 400 440 3x480Vac Input Voltage Hold-up Time at 24Vdc 5A, typ. 10A, typ. 10A, min. 5A, min. - 5% Hold-up Time Output Voltage Input Voltage L1 L2 L3 Jan. 2010 / Rev. 1.3 DS-CT10.241-EN All parameters are specified at 24V, 10A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT10.241 C-Series 24V, 10A, THREE PHASE INPUT 8. EFFICIENCY AND POWER LOSSES 3AC 400V 3AC 480V Efficiency typ. 92.8% 92.9% at 24V, 10A, 3-phase operation typ. 92.4% 92.6% at 24V, 10A, when using only two legs of a 3- phase system, see also chapter 23.6. 10A, 3-phase operation Power losses typ. 2.3W 2.6W at 0A, 3-phase operation typ. 18.6W 18.3W at 24V, 10A, 3-phase operation typ. 23.5W 22.8W at 24V, 12A, 3-phase operation *) The average efficiency is an assumption for a typical application where the power supply is loaded with 25% of the nominal load for 25% of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with 100% of the nominal load for the rest of the time. Fig. 8-1 Efficiency vs. output current at 24V, typ., 3-phase operation Fig. 8-2 Losses vs. output current at 24V, typ., 3-phase operation Efficiency 93% 12A48 1 0 Output Current 3x480Vac 3x400Vac Power Losses 024 8 1 0 1 2 A 24W Output Current 15 3x480Vac 3x400Vac 3x480Vac 3x400Vac Fig. 8-3 Efficiency vs. input voltage at 24V, 10A, typ., 3-phase operation Fig. 8-4 Losses vs. input voltage at 24V, 10A, typ., 3-phase operation Efficiency 350 400 450 500 3x550 Vac 92.0 92.2 92.4 92.6 Input Voltage 92.8 93.0 93.2% Power Losses 350 400 450 500 3x550 Vac 17.0 17.5 18.0 18.5 Input Voltage 19.0 19.5 20W Jan. 2010 / Rev. 1.3 DS-CT10.241-EN All parameters are specified at 24V, 10A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT10.241 C-Series 24V, 10A, THREE PHASE INPUT 9. FUNCTIONAL DIAGRAM Fig. 9-1 Functional diagram VOUTOutput Over- Voltage Protection PFC Inductor Inrush Limiter Transient Filter Input Fuses Input Filter Input Rectifier Output Voltage Regulator Power Converter Output Filter Output Power Manager Temper- ature Shut- down DC-ok LED Single / Parallel 10. FRONT SIDE AND USER ELEMENTS Fig. 10-1 Front side A Output Terminals Screw terminals, dual terminals per pole + Positive output - Negative (return) output B Input Terminals Screw terminals L1, L2, L3 Phase input PE (Protective Earth) input C Output voltage potentiometer Open the flap to set the output voltage. Factory set: 24.1V D “Parallel Use” “Single Use” selector Set jumper to “Parallel Use” when power supplies are connected in parallel to increase the output power. In order to achieve a sharing of the load current between the individual power supplies, the “parallel use” regulates the output voltage in such a manner that the voltage at no load is approx. 5% higher than at nominal load. See also Fig. 6-2. A missing jumper is equal to a “Single Use” mode. Factory setting is “Single Use” mode. E DC-OK LED (green) On when the voltage on the output terminals is > 21V A C D E B Jan. 2010 / Rev. 1.3 DS-CT10.241-EN All parameters are specified at 24V, 10A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT10.241 C-Series 24V, 10A, THREE PHASE INPUT 11. TERMINALS AND WIRING Input Output Type screw terminals screw terminals Solid wire 0.5-6mm2 0.5-6mm 2 Stranded wire 0.5-4mm2 0.5-4mm 2 American Wire Gauge 20-10 AWG 20-10 AWG Wire stripping length 7mm / 0.275inch 7mm / 0.275inch Screwdriver 3.5mm slotted or Pozidrive No 2 3.5mm slotted or Pozidrive No 2 Recommended tightening torque 0.8Nm, 7lb.in 0.8Nm, 7lb.in Instructions: a) Use appropriate copper cables that are designed for an operating temperature of: 60°C for ambient up to 45°C and 75°C for ambient up to 60°C minimum. b) Follow national installation codes and installation regulations! c) Ensure that all strands of a strande d wire enter the terminal connection! d) Up to two stranded wires with the same cross secti on are permitted in one connection point (except PE wire). e) Do not use the unit without PE connection. f) Screws of unused terminal compa rtments should be securely tightened. g) Ferrules are allowed, but not required 12. RELIABILITY 3-Phase operation 3AC 400V 3AC 480V Lifetime expectancy *) 54 000h 62 000h at 24V, 10A and 40°C 133 000h 134 000h at 24V, 5A and 40°C 151 000h 176 000h at 24V, 10A and 25°C MTBF ) SN 29500, IEC 61709 975 000h 985 000h at 24V, 10A and 40°C 1 706 000h 1 723 000h at 24V, 10A and 25°C MTBF ) MIL HDBK 217F 445 000h 429 000h at 24V, 10A and 40°C; Ground Benign GB40 584 000h 427 000h at 24V, 10A and 25°C; Ground Benign GB25 Operation only on 2 legs of a three phase system 2AC 400V 2AC 480V Lifetime expectancy *) 48 000h 58 000h at 24V, 10A and 40°C 134 000h 145 000h at 24V, 5A and 40°C 135 000h 164 000h at 24V, 10A and 25°C MTBF ) SN 29500, IEC 61709 925 000h 939 000h at 24V, 10A and 40°C 1 633 000h 1 656 000h at 24V, 10A and 25°C MTBF ) MIL HDBK 217F 437 000h 423 000h at 24V, 10A and 40°C; Ground Benign GB40 573 000h 556 000h at 24V, 10A and 25°C; Ground Benign GB25 *) The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the capacitor’s manufacturer specification. The prediction model allows only a calculation of up to 15 years from date of shipment. **) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product. Jan. 2010 / Rev. 1.3 DS-CT10.241-EN All parameters are specified at 24V, 10A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT10.241 C-Series 24V, 10A, THREE PHASE INPUT 13. EMC The power supply is suitable for applications in industrial environment as well as in residential, commercial and light industry environment without any restrictions. The CE mark indicates conformance with EMC guideline 89/336/EC, 93/68/EC and 2004/108/EC and the low-voltage directive (LVD) 73/23/EC and 2006/95/EC. A detailed EMC report is available on request. EMC Immunity Generic standards: EN 61000-6-1 and EN 61000-6-2 Electrostatic discharge EN 61000-4-2 Contact discharge Air discharge 8kV 15kV Criterion A Criterion A Electromagnetic RF field EN 61000-4-3 80MHz-2.7GHz 10V/m Criterion A Fast transients (Burst) EN 61000-4-4 Input lines Output lines 4kV 2kV Criterion A Criterion A Surge voltage on input EN 61000-4-5 L1 Æ L2, L2 Æ L3, L1 Æ L3 2kV Criterion A Surge voltage on input EN 61000-4-5 L1 / L2 / L3 Æ PE 4kV Criterion A Surge voltage on output EN 61000-4-5 + Æ - + / - Æ PE 500V 500V Criterion A Criterion A Conducted disturbance EN 61000-4-6 0.15-80MHz 10V Criterion A Mains voltage dips (Dips on three phases) EN 61000-4-11 0% of 380Vac 0% of 480Vac 0Vac, 20ms 0Vac, 20ms Criterion A Criterion A Mains voltage dips (Dips on two phases) EN 61000-4-11 40% of 380Vac 40% of 480Vac 70% of 380Vac 70% of 480Vac 200ms 200ms 500ms 500ms Criterion A Criterion A Criterion A Criterion A Voltage interruptions EN 61000-4-11 0Vac, 5000ms Criterion C Voltage sags SEMI F47 0706 Dips on two phases according to section 7.2. of the SEMI F47 standard 80% of 380Vac 70% of 380Vac 50% of 380Vac 1000ms 500ms 200ms Criterion A Criterion A Criterion A Powerful transients VDE 0160 over entire load range 1550V, 1.3ms Criterion A Criterions: A: Power supply shows normal operation behavior within the defined limits. C: Temporary loss of function is possible. Power supply may shut-down and restarts by itself. No damage or hazards for the powe r supply will occur. EMC Emission Generic standards: EN 61000-6-3 and EN 61000-6-4 Conducted emission EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22 Class B, input lines Radiated emission EN 55011, EN 55022 Class B Harmonic input current EN 61000-3-2 fulfilled Voltage fluctuations, flicker EN 61000-3-3 fulfilled This device complies with FCC Part 15 rules. Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Switching frequency Variable between 60kHz and 140kHz depending on load and input voltage Jan. 2010 / Rev. 1.3 DS-CT10.241-EN All parameters are specified at 24V, 10A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT10.241 C-Series 24V, 10A, THREE PHASE INPUT 14. ENVIRONMENT Operational temperature *) -25°C to +70°C (-13°F to 158°F) reduce output power according Fig. 14-1 Storage temperature -40 to +85°C (-40°F to 185°F) for storage and transportation Output de-rating 3.2W/°C 45-60°C (113°F to 140°F) Humidity **) 5 to 95% r.H. IEC 60068-2-30 Vibration sinusoidal 2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g 2 hours / axis IEC 60068-2-6 Shock 30g 6ms, 20g 11ms 3 bumps / direction, 18 bumps in total IEC 60068-2-27 Altitude 0 to 6000m (0 to 20 000ft) reduce output power or ambient temperature above 2000m sea level. Altitude de-rating 15W/1000m or 5°C/1000m above 2000m (6500ft), see Fig. 14-2 Over-voltage category III IEC 62103, EN 50178, altitudes up to 2000m II altitudes from 2000m to 6000m Degree of pollution 2 IEC 62103, EN 50178, not conductive *) Operational temperature is the same as the ambient temperature and is defined as the air temperature 2cm below the unit. **) Do not energize while condensation is present -25 0 20 40 70°C 12A Ambient Temperature continuous short term Allowable Output Current at 24V 0 2000 4000 6000m 12A Altitude A... Tamb < 60°C B... Tamb < 50°C C... Tamb < 40°C CB A short termAllowable Output Current at 24V Jan. 2010 / Rev. 1.3 DS-CT10.241-EN All parameters are specified at 24V, 10A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT10.241 C-Series 24V, 10A, THREE PHASE INPUT 15. PROTECTION FEATURES Output protection Electronically protected against overload, no-load and short-circuits *) Output over-voltage protection typ. 30.5Vdc max. 32Vdc In case of an internal power supply defect, a redundant circuit limits the maximum output voltage. The output shuts down and automatically attempts to restart. Degree of protection IP 20 EN/IEC 60529 Penetration protection > 3.5mm e.g. screws, small parts Over-temperature protection yes output shut-down with automatic restart Input transient protection MOV (Metal Oxide Varistor) and active transient filter Internal input fuse 3x T3.15A H.B.C. not user replaceable *) In case of a protection event, audible noise may occur. 16. SAFETY FEATURES Input / output separation *) SELV IEC/EN 60950-1 PELV IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41 Class of protection I PE (Protective Earth) connection required Isolation resistance > 5MOhm input to output, 500Vdc PE resistance < 0.1Ohm Touch current (leakage current) typ. 0.17mA 3x 400Vac, 50Hz, TN mains typ. 0.24mA 3x 480Vac, 60Hz, TN mains < 0.22mA 3x 440Vac, 50Hz, TN mains < 0.31mA 3x 528Vac, 60Hz, TN mains *) Double or reinforced insulation 17. DIELECTRIC STRENGTH The output voltage is floating and has no ohmic connection to the ground. Type and factory tests are conducted by the manufacturer. Field tests may be conducted in the field using the appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down). Connect all phase-terminals together as well as all output poles before conducting the test. When testing, set the cut-off current settings to the value in the table below. Fig. 17-1 Dielectric strength A B C Type test 60s 2500Vac 3000Vac 500Vac Factory test 5s 2500Vac 2500Vac 500Vac Field test 5s 2000Vac 2000Vac 500Vac Cut-off current setting > 10mA > 10mA > 30mA A C B Input Earth Output To fulfill the PELV requirements according to EN60204-1 § 6.4.1, we recommend that either the + pole, the – pole or any other part of the output circuit shall be connected to the protective earth system. This helps to avoid situations in which a load starts unexpectedly or can not be switched off when unnoticed earth faults occur. Jan. 2010 / Rev. 1.3 DS-CT10.241-EN All parameters are specified at 24V, 10A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT10.241 C-Series 24V, 10A, THREE PHASE INPUT 18. APPROVALS IEC 60950-1 CB Scheme, Information Technology Equipment UL 508 IND. CONT. EQ. Listed for use as Industrial Control Equipment; E-File: E198865 Mains supply circuit: 3-wire + PE, star UL 60950-1 Recognized for use as Information Technology Equipment; E-File: E137006, Level 5 Marine, pending GL (Germanischer Lloyd) classified and ABS (American Bureau for Shipping) PDA Environmental category: C, EMC2 Marine and offshore applications SEMI F47 SEMI F47-0706 Ride-through compliance for the semiconductor industry. Full SEMI range compliance (Dips on two phases: 304Vac for 1000ms, 266Vac for 500ms and 190Vac for 200ms) 19. FULFILLED STANDARDS EN 61558-2-17 Safety of Power Transformers EN/IEC 60204-1 Safety of Electrical Equipment of Machines EN/IEC 61131-2 Programmable Controllers EN 50178, IEC 62103 Electronic Equipment in Power Installations 20. USED SUBSTANCES The unit does not release any silicone and is suitable for the use in paint shops. The unit conforms to the RoHS directive 2002/96/EC Electrolytic capacitors included in this unit do not use electrolytes such as Quaternary Ammonium Salt Systems. Plastic housings and other molded plastic materials are free of halogens, wires and cables are not PVC insulated. The production material within our production does not include following toxic chemicals: Polychlorized Biphenyl (PCB), Polychlorized Terphenyl (PCT), Pentachlorophenol (PCP), Polychlorinated naphthalene (PCN), Polybrom Biphenyll (PBB), Polybrom Bipheny-oxyd (PBO), Polybrominated Diphenylether (PBDE), Polychlorinated Diphenylether (PCDE), Polydibromphenyl Oxyd (PBDO), Cadmium, Asbestos, Mercury, Silicia Jan. 2010 / Rev. 1.3 DS-CT10.241-EN All parameters are specified at 24V, 10A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT10.241 C-Series 24V, 10A, THREE PHASE INPUT 21. PHYSICAL DIMENSIONS AND WEIGHT Weight 750g / 1.65lb DIN-Rail Use 35mm DIN-rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm. The DIN-rail height must be added to the unit depth (117mm) to calculate the total required installation depth. Installation Clearances See chapter 2 Fig. 21-1 Front view Fig. 21-2 Side view Jan. 2010 / Rev. 1.3 DS-CT10.241-EN All parameters are specified at 24V, 10A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT10.241 C-Series 24V, 10A, THREE PHASE INPUT 22. ACCESSORIES ZM1.WALL Wall mounting bracket This bracket is used to mount specific Dimension units onto a flat surface without utilizing a DIN-Rail. The two aluminum brackets and the black plastic slider of the unit have to be removed, so that the two steel brackets can be mounted. Fig. 22-1 ZM1.WALL Wall mounting bracket Fig. 22-2 Assembled wall mounting bracket *) *) Picture of the power supply is for representation only ZM13.SIDE Side mounting bracket This bracket is used to mount Dimension units sideways with or without utilizing a DIN-Rail. The two aluminum brackets and the black plastic slider of the unit have to be detached, so that the steel brackets can be mounted. For sideway DIN-rail mounting, the removed aluminum brackets and the black plastic slider need to be mounted on the steel bracket. Fig. 22-3 ZM13.SIDE Side mounting bracket *) Fig. 22-4 Side mounting with DIN-rail brackets *) *) Picture of the power supply is for representation only Jan. 2010 / Rev. 1.3 DS-CT10.241-EN All parameters are specified at 24V, 10A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT10.241 C-Series 24V, 10A, THREE PHASE INPUT 23. APPLICATION NOTES 23.1. PEAK CURRENT CAPABILITY Solenoids, contactors and pneumatic modules often have a steady state coil and a pick-up coil. The inrush current demand of the pick-up coil is several times higher than the steady-state current and usually exceeds the nominal output current (including the PowerBoost) The same situation applies, when starting a capacitive load. Branch circuits are often protected with circuit breakers or fuses. In case of a short or an overload in the branch circuit, the fuse needs a certain amount of over-current to trip or to blow. The peak current capability ensures the safe operation of subsequent circuit breakers. Assuming the input voltage is turned on before such an event, the built-in large sized output capacitors inside the power supply can deliver extra current. Discharging this capacitor causes a voltage dip on the output. The following two examples show typical voltage dips: Fig. 23-1 Peak load 20A for 50ms, typ. Fig. 23-2 Peak load 50A for 5ms, typ. 10ms/DIV Output Voltage Output Current 24V 20A 1ms/DIV Output Voltage Output Current 24V 50A Peak load 20A (resistive) for 50ms Output voltage dips from 24V to 6V. Peak load 50A (resistive) for 5ms Output voltage dips from 24V to 3V. 23.2. BACK-FEEDING LOADS Loads such as decelerating motors and inductors can feed voltage back to the power supply. This feature is also called return voltage immunity or resistance against Back- E.M.F. (Electro Magnetic Force). This power supply is resistant and does not show malfunctioning when a load feeds back voltage to the power supply. It does not matter, whether the power supply is on or off. The maximum allowed feed-back-voltage is 35Vdc. The absorbing energy can be calculated according to the built-in large sized output capacitor which is specified in chapter 6. Jan. 2010 / Rev. 1.3 DS-CT10.241-EN All parameters are specified at 24V, 10A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT10.241 C-Series 24V, 10A, THREE PHASE INPUT 23.3. CHARGING OF BATTERIES The power supply can be used to charge lead-acid or maintenance free batteries. (Two 12V batteries in series) Instructions for charging batteries: a) Set jumper on the front of the unit into “Parallel Use” b) Set output voltage (measured at no load and at the battery end of the cable) very precisely to the end-of-charge voltage. End-of-charge voltage 27.8V 27.5V 27.15V 26.8V Battery temperature 10°C 20°C 30°C 40°C c) Use a 16A circuit breaker (or blocking diode) between the power supply and the battery. d) Ensure that the output current of the power supply is below the allowed charging current of the battery. e) Use only matched batteries when putting 12V types in series. f) The return current to the power supply (battery discharge current) is typ. 8mA when the power supply is switched off (except in case a blocking diode is utilized). 23.4. OUTPUT CIRCUIT BREAKERS Standard miniature circuit breakers (MCB’s or UL1077 circuit breakers) are without doubt, one of the most efficient and economical ways to open circuits on faulty branches. Most of these breakers may also be used on 24V branches. MCB’s are designed to protect wires and circuits. If the ampere value and the characteristics of the MCB are adapted to the wire size that is used, the wiring is considered as thermally safe regardless of whether the MCB opens or not. To avoid voltage dips and under-voltage situations in adjacent 24V branches which are supplied by the same source, a fast (magnetic) tripping of the MCB is desired. A quick shutdown within 10ms is necessary corresponding roughly to the ride-through time of PLC's. This requires power supplies with high current reserves and large output capacitors. Furthermore, the impedance of the faulty branch must be sufficiently small in order for the current to actually flow. The best current reserve in the power supply does not help if Ohm’s law does not permit current flow. The following table has typical test results showing which B- and C-Characteristic MCBs magnetically trip depending on the wire cross section and wire length. Fig. 23-3 Test circuit Maximal wire length for a magnetic (fast) tripping *): 0.75mm² 1.0mm² 1.5mm² 2.5mm² C-2A 23m 28m 43m 69m C-3A 18m 23m 34m 54m C-4A 6m 12m 18m 28m C-6A 3m 4m 6m 7m C-8A 2m 3m 4m 5m C-10A 1m 2m 3m 4m B-6A 9m 14m 19m 33m B-10A 4m 5m 6m 9m MCB Power Supply AC DC Load B-13A 3m 4m 5m 8m Wire length *) Don’t forget to consider two times the distance to the load (or cable length) when calculating the total wire length (+ and – wire). Jan. 2010 / Rev. 1.3 DS-CT10.241-EN All parameters are specified at 24V, 10A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT10.241 C-Series 24V, 10A, THREE PHASE INPUT 23.5. EXTERNAL INPUT PROTECTION The unit is tested and approved for branch circuits up to 30A (U.S.A.) and 32A (IEC). An external protection is only required, if the supplying branch has an ampacity greater than this. Check also local codes and local requirements. In some countries local regulations might apply. If an external fuse is necessary or utilized, minimum requirements need to be considered to avoid nuisance tripping of the circuit breaker. A minimum value of 6A B- or 3A C-Characteristic breaker should be used 23.6. USING ONLY 2 LEGS OF A 3-PHASE SYSTEM oss e The power supply is allowed to run permanently on two legs of a 3-phase system, when the output power is reduced according to the curves below. A long-term exceeding of these limits will result in a thermal shut-down of the unit. No external protection device is required to protect against a phase-l failure. EMC performance, hold-up time and losses differ from a three phas operation. Therefore, check suitability of your individual application. The screw of the terminal which remains unused must be securely tightened. Using only two legs of a 3-phase system is not included in the UL approval. Therefore, additional testing might be necessary. DC L3open AC PE Power Supply Fig. 23-4 Allowed output current for use on only two legs of a 3-phase system Fig. 23-5 Hold-up time for use on only two legs of a 3-phase system Allowed Output Current at 24V (2-Ph) -25 0 20 70°C 12A Ambient Temperature 40 60 A... 2x340-576Vac B... 2x320-340Vac C... short term 2x320-576Vac B A C 100ms 320 360 400 440 2x480Vac Input Voltage Hold-up Time at 24Vdc 5A, typ. 10A, typ. 10A, min. 5A, min. Fig. 23-6 Efficiency vs. output current at 24V for use on only two legs of a 3-phase system Fig. 23-7 Losses vs. output current at 24V for use on only two legs of a 3-phase system Efficiency 94% 12A48 1 0 Output Current 92 2x400Vac 2x480Vac Power Losses 024 8 1 0 1 2 A 24W 2x480Vac 2x400Vac Output Current Jan. 2010 / Rev. 1.3 DS-CT10.241-EN All parameters are specified at 24V, 10A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT10.241 C-Series 24V, 10A, THREE PHASE INPUT 23.7. INDUCTIVE AND CAPACITIVE LOADS The unit is designed to supply any kind of loads, including unlimited capacitive and inductive loads. 23.8. PARALLEL USE TO INCREASE OUTPUT POWER CT10.241 power supplies can be paralleled to increase the output power. This power supply can also be paralleled with power supplies from the DIMENSION CT, QS or QT-series. The output voltage of all power supplies shall be adjusted to the same value (±100mV) in “Single use” mode with the same load conditions on all units, or the units can be left with the factory settings. After the adjustments, the jumper on the front of the unit shall be moved from “Single use” to “Parallel use”, in order to achieve load sharing. The “Parallel use” mode regulates the output voltage in such a manner that the voltage at no load is approx. 5% higher than at nominal load. See also chapter 6. If no jumper is plugged in, the unit is in “Single use”. Factory setting is “Single use” mode. A fuse (or diode) on the output of each unit is only required if more than three units are connected in parallel. If a fuse (or circuit breaker) is used, choose one with approximately 150% of the rated output current of the power supply. Keep an installation clearance of 15mm (left / right) between two power supplies and avoid installing the power supplies on top of each other. Do not use power supplies in parallel in mounting orientations other than the standard mounting orientation (input terminals on the bottom and output terminals on top of the unit) or in any other condition where a derating of the output current is required (e.g. altitude, above 60°C, …). Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple power supplies. Unit B Load Fuse Fuse AC DC AC DC Unit A 23.9. PARALLEL USE FOR REDUNDANCY Power supplies can be paralleled for redundancy to gain higher system availability. Redundant systems require a certain amount of extra power to support the load in case one power supply unit fails. The simplest way is to put two power supplies in parallel. This is called a 1+1 redundancy. In case one power supply unit fails, the other one is automatically able to support the load current without any interruption. Redundant systems for a higher power demand are usually built in a N+1 method. E.g. five power supplies, each rated for 10A are paralleled to build a 40A redundant system. For N+1 redundancy the same restrictions apply as for increasing the output power, see also section 23.8. Please note: This simple way to build a redundant system does not cover failures such as an internal short circuit in the secondary side of the power supply. In such a case, the defect unit becomes a load for the other power supplies and the output voltage can not be maintained any more. This can only be avoided by utilizing decoupling diodes which are included in the decoupling module YRM2.DIODE. Recommendations for building redundant power systems: a) Use separate input fuses for each power supply. b) Set the power supply into “Parallel Use”. c) Monitor the individual power supply units. A DC-ok lamp and a DC-ok contact are included in the redundancy module YRM2.DIODE. This feature reports a faulty unit. d) It is desirable to set the output voltages of all units to the same value (± 100mV) or leave it at the factory setting. Jan. 2010 / Rev. 1.3 DS-CT10.241-EN All parameters are specified at 24V, 10A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT10.241 C-Series 24V, 10A, THREE PHASE INPUT 23.10. DAISY CHAINING OF OUTPUTS Daisy chaining (jumping from one power supply output to the next) is allowed as long as the average output current through one terminal pin does not exceed 25A. If the current is higher, use a separate distribution terminal block. Fig. 23-8 Daisy chaining of outputs Fig. 23-9 Using distribution terminals Power Supply + + - - Input Output Load + - max 25A! Power Supply + + - - Input Output Load + - Distribution Terminals Power Supply + + - - Input Output Power Supply + + - - Input Output 23.11. SERIES OPERATION Unit B Load AC DC AC DC Unit A Earth (see notes) Power supplies of the same type can be connected in series for higher output voltages. It is possible to connect as many units in series as needed, providing the sum of the output voltage does not exceed 150Vdc. Voltages with a potential above 60Vdc are not SELV any more and can be dangerous. Such voltages must be installed with a protection against touching. Earthing of the output is required when the sum of the output voltage is above 60Vdc. Avoid return voltage (e.g. from a decelerating motor or battery) which is applied to the output terminals. Keep an installation clearance of 15mm (left / right) between two power supplies and avoid installing the power supplies on top of each other. Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple power supplies. 23.12. USE IN A TIGHTLY SEALED ENCLOSURE When the power supply is installed in a tightly sealed enclosure, the temperature inside the enclosure will be higher than outside. In such situations, the inside temperature defines the ambient temperature for the power supply. The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure. The power supply is placed in the middle of the box, no other heat producing items are inside the box Enclosure: Rittal Typ IP66 Box PK 9519 100, plastic, 180x180x165mm Load: 24V, 8A; (=80%) load is placed outside the box Input: 3x 400Vac Temperature inside enclosure: 48.4°C (i n the middle of the right side of the power supply with a distance of 2cm) Temperature outside enclosure: 24.5°C Temperature rise: 23.9K Jan. 2010 / Rev. 1.3 DS-CT10.241-EN All parameters are specified at 24V, 10A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CT10.241 C-Series 24V, 10A, THREE PHASE INPUT Jan. 2010 / Rev. 1.3 DS-CT10.241-EN All parameters are specified at 24V, 10A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 23.13. MOUNTING ORIENTATIONS Mounting orientations other than input terminals on the bottom and output on the top require a reduction in continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous operation can be found below: Curve A1 Recommended output current. Curve A2 Max allowed output current (res ults in approximately half the lifetime expectancy of A1). Fig. 23-10 Mounting Orientation A (Standard orientation) Power Supply OUTPUT INPUT Output Current 10 20 30 40 60°C 12A Ambient Temperature Fig. 23-11 Mounting Orientation B (Upside down) Power Supply OUTPUT INPUT Output Current 10 20 30 40 60°C 12A Ambient Temperature Fig. 23-12 Mounting Orientation C (Table-top mounting) Output Current 10 20 30 40 60°C 12A Ambient Temperature Fig. 23-13 Mounting Orientation D (Horizontal cw) Power Supply OUTPUT INPUT Output Current 10 20 30 40 60°C 12A Ambient Temperature Fig. 23-14 Mounting Orientation E (Horizontal ccw) Power Supply OUTPUT INPUT Output Current 10 20 30 40 60°C 12A Ambient Temperature