09/13/2013 HPL-ED2013 V1.0 EN 1 / 6 StepswitchFlushmounting Partno. T0-6-8271/E Articleno. 015124 CatalogNo. CT06-8271-DOKBQ Deliveryprogramme Product range Control switches Basic function Step switches Part group reference T0 Design Built-in Protection type Front IP65 with black thumb grip and front plate One contact closed per step Without overlapping Without 0 (Off) position Contact sequence Front plate no. Main conducting paths main circuits poles M 3 Max. motor rating AC-23A 400/415 V 50-60 Hz P kW 6.5 Approvals Product Standards UL 508; CSA-C22.2 No. 14-05; IEC/EN 60947-3; CE marking UL File No. E36332 UL Category Control No. NLRV CSA File No. 12528 CSA Class No. 3211-05 North America Certification UL listed, CSA certified Specially designed for North America Yes, in combination with "+NA" (105864) Suitable for Branch circuits Degree of Protection IEC: IP65; UL/CSA Type 3R, 12 General Standards IEC/EN 60947, VDE 0660, IEC/EN 60204, CSA, UL Switch-disconnectors to IEC/EN 60947-3 Load-break switches to IEC/EN 60947-3 Lifespan, mechanical Operations x 106 0.4 Maximum operating frequency Operations/ h 3000
09/13/2013 HPL-ED2013 V1.0 EN 2 / 6 Climatic proofing Damp heat, constant, to IEC 60068-2-78; Damp heat, cyclical, to IEC 60068-2-30 Ambient temperature °C Open °C - 25 - 50 Enclosed °C - 25 - 40 Mounting position As required Mechanical shock resistance to IEC 60068-2-27 Half- sinusoidal shock 20 ms g > 15 Contacts Rated operational voltage Ue V AC 690 Rated impulse withstand voltage Uimp V AC 6000 Overvoltage category/pollution degree III/3 Rated uninterrupted current Iu A Rated uninterrupted current Iu A 20 open Iu A 20 Enclosed Iu A 20 Load rating with intermittent operation, class 12 AB 25 % DF x Ie 2 AB 40 % DF x Ie 1.6 AB 60 % DF x Ie 1.3 Short-circuit rating Fuse A gG/ gL Rated short-time withstand current (1 s current) Icw Arms 320 Safe isolation to EN 61140 between the contacts V AC 440 Protection against direct contact Finger and back-of-hand proof to IEC 536 Switching angles ° 90 Contact units 11 Double-break contacts max. 22 Current heat loss per contact at Ie W 0.6 Switchingcapacity AC x Us Rated making capacity cos ϕ = 0.35 A 130 Bemessungsausschaltvermögen Motorschalter cos ϕ = 0.35 A
230 V A 100
400 V A 110
500 V A 80
690 V A 60
Rated operational current 440 V load-break switch AC-21A Ie A 20 Rating, AC-3 motor load switch P kW
220 V 230 V P kW 3
230 V Star-delta P kW 4
380 V 400 V P kW 4
400 V Star-delta P kW 5.5 500 V P kW 5.5 500 V Star-delta P kW 7.5
660 V 690 V P kW 4
690 V Star-delta P kW 5.5 Bemessungsbetriebsleistung AC-23A, 50 - 60 Hz P kW 230 V P kW 3.5
09/13/2013 HPL-ED2013 V1.0 EN 3 / 6 400 V P kW 6.5 500 V P kW 7.5 Rated operational current control switch AC-15
220 V 230 V 240 V Ie A 6
380 V 400 V 415 V Ie A 4
500 V Ie A 2
DC-1, Load-break switches L/R = 1 ms Rated operational current Ie A 10 Voltage per contact pair in series V 60 DC-21A Ie A Rated operational current 240 V Ie A 1
240 V Contacts Quantity 1
DC-23A, motor load switch L/R = 15 ms 24 V Rated operational current Ie A 10 Contacts Quantity 1 48 V Rated operational current Ie A 10 Contacts Quantity 2 60 V Rated operational current Ie A 10 Contacts Quantity 3 120 V Rated operational current Ie A 5 Contacts Quantity 3 240 V Rated operational current Ie A 5 Contacts Quantity 5 DC-13, Control switches L/R = 50 ms Rated operational current Ie A 10 Voltage per contact pair in series V 32 Control circuit reliability at 24 V DC, 10 mA Fault probability HF < 10 -5, < 1 fault in 100000 operations Terminalcapacities Solid or stranded mm2 1 x (1 - 2.5) 2 x (1 - 2.5) Flexible with ferrules to DIN 46228 mm2 1 x (0.75 - 1.5) 2 x (0.75 - 1.5) Terminal screw M3.5 Tightening torque Nm 1 Notes The following applies for solid, multiwire, and flexible terminal capacities: If 2 conductors are being used, a max. difference of 2 cross-section categories is permissible TechnicaldataETIM4.0 Switch function Level switch Number of poles 3 Max. rated operation voltage Ue AC V 690 Rated permanent current Iu A 20 Number of switch positions 4 With 0 (off) position No With retraction in 0-position No Device construction Built-in device Suitable for ground mounting No Suitable for front mounting 4-hole Yes
09/13/2013 HPL-ED2013 V1.0 EN 4 / 6 Suitable for distribution board installation No Suitable for intermediate mounting No Complete device in housing No Type of control element Toggle Front shield size 48x48 mm Degree of protection (IP), front side IP65 Characteristics For utilisation category AC-4 (extreme load: 100 % inching, reversing or plugging) The blocked rotor current of the motor should not exceed the rated current of the switch for AC-21A to ensure a reasonable device lifespan. Dimensions ② Label mount not included as standard One contact unit depth: 9.5 mm
09/13/2013 HPL-ED2013 V1.0 EN 5 / 6 Diameter of drilled hole Door
09/13/2013 Eaton Industries GmbH http://www.eaton.eu © 09/2013 by Eaton Industries GmbH HPL-ED2013 V1.0 EN Key operation lock mechanism T0.../E + S-(SOND-)T0 Additionalproductinformation(links) http://ecat.moeller.net/flip-cat/?edition=HPLEN&startpage=4.87 http://ecat.moeller.net/flip-cat/?edition=K115A&startpage=82