CSV2000BP ADVANCEDENERGY | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 7

Technical content

©2021 Advanced Energy Industries, Inc. ARTESYN CSV2000BP

2000 Watts Distributed Power System

Total Output Power: 2000 W Input Voltage: 180 to 265 Vac DATA SHEETAdvanced Energy's Artesyn CSV series bulk front end power AC-DC supply is designed for systems where scalability and density are requirements. With multiple power levels to choose from, this family provides designers with the ability to change the power supply to optimize according to system power consumption. SPECIAL FEATURES  2000 W output power  1U power supply  Active Power Factor Correction  EN61000-3-2 Harmonic compliance  Inrush current control  80PLUS® Platinum efficiency  N+N Redundant  Hot-pluggable  Active current sharing  PMBus® compliant  Two-year warranty COMPLIANCE  Conducted/Radiated EMI Class A Limits  RoHS  IEC 60950 SAFETY  UL/cUL  CB Test Certificate  CE Mark  KC  CQC  BSMI  BIS  TÜV

2 advancedenergy.com CSV2000BP ELECTRICAL SPECIFICATIONS Input Input range 180 - 264 Vac : 2000 W 198 - 264 Vac: 2000 W Frequency 47 Hz to 63 Hz Efficiency 94.0% peak, platinum rating Max input current 11.0 A or 10 A Inrush current 30 Apk Conducted EMI Class A Radiated EMI Class A Power factor >0.9 beginning at 10% load Hold-up time 12 ms at full load Leakage current 0.575 mA Output Main DC Output Standby DC Output MIN NOM MAX MIN NOM MAX Total output regulation range 11.59 V 12.81 V 11.4 V 12.6 V Dynamic load regulation range 11.59 V 12.81 V 11.34 V 13.05 V Output ripple 120 mVp-p 120 mVp-p Output current 1.0 A 163.9 A 0.5 A 3.0 A Current sharing Within ±10% of full load rating, starting at 30% of rated load N/A Capacitive loading 100 µF 20,000 µF 50 µF 500 µF Start-up from AC to output 3,000 ms 2,500 ms Output rise time 5 ms 50 ms 1 ms 25 ms

1 For UL covered area that allows 11 A input current rating

2 Minimum current for transient load response testing only. Unit is designed to operate and be within output regulation range at zero load. Protections Main Output MIN NOM MAX Overcurrent protection

169 A 205 A

13.4 V Undervoltage protection 10.0 V Overtemperature protection Yes Fan fault protection Yes Standby Output Overcurrent protection 3.85 A 3.95 A Overvoltage protection 13.8 V Undervoltage protection 10.0 V

1 Latch mode

2 THROTTLE warning of at least 1 second before latching off

3 Standby protection is auto-recovery

advancedenergy.com 3 CSV2000BP LED Indicators Input Good (Green) Output Good (Green) Fault (Yellow) Output ON and OK On On Off Standby mode (input present, main output off) or zero output mode On Blinking 1 Hz Off No input/Input out of range Off Off Off OCP , or over-subscription fault, or OVP , or fan failure, or OTP On Off On ELECTRICAL SPECIFICATIONS (CONTINUED) ENVIRONMENTAL SPECIFICATIONS

ORDERING INFORMATION

Operating temperature 5 to 50 °C Operating altitude up to 10,000 feet Operating relative humidity +8% to 93%, non-condensing Non-operating temperature -40 to +70 °C Shipping and storage relative humidity +5% to 100%, including condensing Non-operating altitude up to 50,000 feet Vibration and shock Standard operating/non-operating random shock and vibration RoHS compliance Yes MTBF 500 k hours at 40 °C, 70% load, nominal input Operating life Minimum of 5 years at typical conditions

1 PSU ambient temperature derated at 1 °C per 600 ft above 3000 ft

Model Name Ordering Part Number Nominal Main Output Standby Output Airflow Direction CSV2000BP-3 700-014265-1000 12.2 V @ 163.9 A 12 V @ 3.0 A Standard (forward)

4 advancedenergy.com CSV2000BP TIMING DIAGRAM PSON Vout_main PWOK EPOW Vout_stby AC Input Tsb_On TAC_On_Delay TPSON_On_Delay TVout_Hold-up TPWOK_Off TACOK_off_dwell TPWOK_On -5% -5% TPSON_PWOK Tsb_Hold-up TACOK_PWOK_Delay Timing Specifications Description Min Max Unit Tsb_On Delay from AC being applied to standby output being within regulation 2500 ms TVout_rise Rise time of output voltage going from 10% to 90% of the nominal regulation 1 50 ms TAC_On_Delay Delay from AC being applied to main output being within regulation 3000 ms TPWOK_On Delay from output voltages within regulation limits to PWOK assertion 180 220 ms TACOK_PWOK_Delay Delay from ACOK going low to deassertion of PWOK 6 ms TVout_Hold-up Delay from loss of AC to main output being within regulation 12 ms Tsb_Hold-up Delay from loss of AC to standby output being within regulation 50 1000 ms TPWOK_Off Delay from deassertion of PWOK to output falling out of regulation 2 ms TPSON_PWOK Delay from deassertion of PSON to deassertion of PWOK 1 ms TPSON_On_Delay Delay from PSON assertion to output being within regulation 5 100 ms

advancedenergy.com 5 CSV2000BP MECHANICAL OUTLINE 40.0±0.3 38.5±0.3 DIMENSION AND TOLERANCE NEED TO BE HELD AT THE EDGE OF THE STANDOFF LOCATIONS ONLY 202.0±0.4 80.0±0.3 7.05±0.5 11.0±0.5 4.0±0.25 195.0

6 advancedenergy.com CSV2000BP Output connector part number Card-edge Mating connector part number FCI Amphenol HPCE 10122238-320424FLF Output Connector Pin Assignment Pin Pos. Name Pin Pos. Name S1 Reserved S13 SMBus_RESET# S2 Reserved S14 Reserved S3 +MAIN_VRS / +Vsense S15 ADDRESS S4 Reserved (Gnd at system side) S16 PSON_L S5 RESERVED S17 PSON_L S6 DC_GOOD / PWOK S18 EPOW# / ACOK S7 PRESENT# S19 Reserved S8 SMBALERT# S20 Throttle# S9 ISHARE S21 Reserved S10 GND / RETURN S22 -MAIN_VRS / -Vsense S11 SDA S23 Reserved S12 SCL S24 Reserved P1-P8 12Vout P29-P36 12Vout P9-P18 RETURN P21-P28 RETURN P19-P20 12Vaux Power Supply Addressing (pin S15) Resistance (pull-down at system side, 1% tol or better) Voltage (nom) Hex Address OPEN 12.00 V D0 280 k 10.49 V D2 212 k 9.01 V D4 68.1 k 7.55 V D6 40.2 k 6.00 V D8 23.7 k 4.45 V DA 13.3 k 2.98 V DC 5.76 k 1.50 V DE CONNECTOR DEFINITIONS P21-28P29-P36 P19/20 ... S24 S13 Power Supply Output Card Edge (Top Side) P1-P8/uni00A0 P9-P18 .. S1 S12 Power Supply Output Card Edge ( Bottom Side) *Not actual image

ENG-CSV2000BP-235-01 1.27 For international contact information, visit advancedenergy .com. powersales@aei.com (Sales Support) productsupport.ep@aei.com (Technical Support) +1 888 412 7832 ABOUT ADVANCED ENERGY Advanced Energy (AE) has devoted more than three decades to perfecting power for its global customers. AE designs and manufactures highly engineered, precision power conversion, measurement and control solutions for mission-critical applications and processes. Our products enable customer innovation in complex applications for a wide range of industries including semiconductor equipment, industrial, manufacturing, telecommunications, data center computing, and medical. With deep applications know-how and responsive service and support across the globe, we build collaborative partnerships to meet rapid technological developments, propel growth for our customers, and innovate the future of power. Specifications are subject to change without notice. Not responsible for errors or omissions. ©2021 Advanced Energy Industries, Inc. All rights reserved. Advanced Energy®, AE® and Artesyn™ are U.S. trademarks of Advanced Energy Industries, Inc.