CS10.481 PULS | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 26

Technical content

CS10.481 C-Line 48V, 5A, SINGLE PHASE INPUT POWER SUPPLY ƒ AC 100-120 / 200-240V Auto-select Input ƒ Width only 60mm ƒ Efficiency up to 91.6% ƒ Easy Fuse Breaking due to High Overload Peak Current ƒ 20% Output Power Reserves ƒ Full Power Between -25°C and +60°C ƒ Minimal Inrush Current Surge ƒ 3 Year Warranty GENERAL DESCRIPTION The DIMENSION C-Line uni ts are cost optimized power supplies without compromisi ng quality, reliability and performance. The C-Line is part of the DIMENSION power supply family, existing alongside the high featured Q-Line. The CS10.481 includes all the essential basic functions and the devices have a power reserve of 20%. This extra current may even be used continuously at temperatures up to +45°C. The most important features are the small size, high efficiency and the wide temperature range. The Auto-select input makes worldwide installation and usage very simple. Defects or system failures caused by wrongly set switches cannot occur. High immunity to transients and power surges as well as low electromagnetic emission and a large international approval package for a variety of applications makes this unit suitable for nearly every situation. SHORT-FORM DATA Output voltage DC 48V Adjustment range 48 - 52V Output current 5.0A at 48V, amb <60°C 6.0A at 48V, amb <45°C 4.6A at 52V, amb <60°C 5.6A at 52V, amb <45°C Output power 240W ambient <60°C 288W ambient <45°C Output ripple < 100mVpp 20Hz to 20MHz AC Input voltage AC 100-120V / 200-240V ±10% Auto-select input Mains frequency 50-60Hz ±6% AC Input current 3.73 / 2.23A at 120 / 230Vac DC Input voltage - not allowed Power factor 0.59 / 0.51 at 120 / 230Vac AC Inrush current 3 / 3A peak at 120 / 230Vac Efficiency 91.0 / 91.6% at 120 / 230Vac Losses 23.7 / 22.0W at 120 / 230Vac Temperature range -25°C to +70°C operational Derating *) 6W/°C +60 to +70°C Hold-up time 46 / 47ms at 120 / 230Vac Dimensions 60x124x117mm WxHxD Weight 700g / 1.54lb ORDER NUMBERS Power Supply CS10.481 48-52V Standard unit Accessory ZM1.WALL Wall mount bracket ZM13.SIDE Side mount bracket YRM2.DIODE Redundancy module YR40.482 Redundancy module MARKINGS IND. CONT. EQ. UL 508 UL 60950-1 Class I Div 2 Marine EMC, LVD Jul. 2015 / Rev. 2.0 DS-CS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CS10.481 C-Line 48V, 5A, SINGLE PHASE INPUT INDEX Page Page 19. RoHS, REACH and Other Fulfilled Standards ...18 The information presented in this document is believed to be accurate and reliable and may change without notice. No part of this document may be reproduced or utilized in any form without permission in writing from the publisher. TERMINOLOGY, ABREVIATIONS AND DEFINITIONS PE and symbol PE is the abbreviation for Protective Earth and has the same meaning as the symbol . Earth, Ground This document uses the term “earth” which is the same as the U.S. term “ground”. T.b.d. To be defined, value or description will follow later. AC 230V A figure displayed with the AC or DC before the value represents a nominal voltage with standard tolerances (usually ±15%) included. E.g.: DC 12V describes a 12V battery disregarding whether it is full (13.7V) or flat (10V) 230Vac A figure with the unit (Vac) at the end is a momentary figure without any additional tolerances included. 50Hz vs. 60Hz As long as not otherwise stated, AC 100V a nd AC 230V parameters are valid at 50Hz mains frequency. AC 120V parameters are valid for 60Hz mains frequency. may A key word indicating flexibility of choice with no implied preference. shall A key word indicating a mandatory requirement. should A key word indicating flexibility of choice with a strongly preferred implementation. Jul. 2015 / Rev. 2.0 DS-CS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CS10.481 C-Line 48V, 5A, SINGLE PHASE INPUT 1. INTENDED USE This device is designed for installation in an enclosure and is intended for the general professional use such as in industrial control, office, communication, and instrumentation equipment. Do not use this power supply in equipment, where malfunction may cause severe personal injury or threaten human life. This device is designed for use in hazardous, non-hazardous, ordinary or unclassified locations. The power supply does not fulfil the harmonic current standard EN61000-3-2. Do not use this power supply when the following criteria apply: a) the end-device is used within the European Union and b) the end-device is connected to a public mains supply with a nominal voltage greater or equal 220Vac and c) the power supply is: - fitted in an end-device with an average input power greater than 75W or - fitted in an end-device with a continuous input power greater than 75W or - part of a lighting system. Exception: End-devices for professional applications with an input power > 1000W do not need to fulfill EN 61000-3-2. Comments: - The average input power must be determined in accordance with EN 61000-3-2. - Industrial mains supplies with their own transformer are considered to be “non-public”. - Where individual self-contained items of equipment are installed in a rack or case (e.g. devices connected in parallel), they are regarded as being individually connected to the mains supply. The rack or case need not be tested as a whole. Alternatively it is also permitted to assess the whole rack or case. This is recommended for devices used in professional applications with an input power greater than 1000W. If PFC according to the Harmonics Standard EN 61000-3-2 is required, please use the QS10.481 or CP10.481. Jul. 2015 / Rev. 2.0 DS-CS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CS10.481 C-Line 48V, 5A, SINGLE PHASE INPUT 2. INSTALLATION REQUIREMENTS This device may only be installed and put into operation by qualified personnel. This device does not contain serviceable parts. The tripping of an internal fuse is caused by an internal defect. If damage or malfunction should occur during installation or operation, immediately turn power off and send unit to the factory for inspection. Mount the unit on a DIN-rail so that the input terminals are located on the bottom of the unit. For other mounting orientations see de-rating requirements in this document. See chapter 24.13. This device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do not cover ventilation grid (e.g. cable conduits) by more than 15%! Keep the following installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right sides are recommended when the device is loaded permanently with more than 50% of the rated power. Increase this clearance to 15mm in case the adjacent device is a heat source (e.g. another power supply). A disconnecting means shall be provided for the output of the power supplies when used in applications according to CSA C22.2 No 107.1-01. WARNING Risk of electrical shock, fire, personal injury or death. - Do not use the power supply without proper grounding (Protective Earth). Use the terminal on the input block for earth connection and not one of the screws on the housing. - Turn power off before working on the devi ce. Protect against inadvertent re-powering. - Make sure that the wiring is correct by following all local and national codes. - Do not modify or repair the unit. - Do not open the unit as high voltages are present inside. - Use caution to prevent any foreign objects from entering the housing. - Do not use in wet locations or in areas wh ere moisture or condensation can be expected. - Do not touch during power-on, and immediatel y after power-off. Hot surfaces may cause burns. Notes for use in hazardous location areas: The power supply is suitable for use in Class I Division 2 Groups A, B, C, D locations. WARNING EXPLOSION HAZARDS! Substitution of components may impair suitability for this environment. Do not disconnect the unit or operate the voltage adjustment unless power has been switched off or the area is known to be non-hazardous. Jul. 2015 / Rev. 2.0 DS-CS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CS10.481 C-Line 48V, 5A, SINGLE PHASE INPUT 3. AC-INPUT AC input nom. AC 100-120V / 200-240V ±10% Auto-select input Mains network systems TN, TT or IT 90-132Vac / 180-264Vac 85-90Vac 264-300Vac continuous operation, lower input voltage range continuous operation, upper input voltage range short-tem or with reduced output current, see Fig. 3-5 max. 500ms AC input range min. no harm to the power supply with input voltages between 132 and 180Vac Allowed voltage L or N to earth max. 300Vac continuous, IEC 62103 Input frequency nom. 50–60Hz ±6% Turn-on voltage typ. 80Vac steady-state value, see Fig. 3-1 Shut-down voltage typ. 75Vac steady-state value, see Fig. 3-1 External input protection See recommendations in chapter 22.3. AC 100V AC 120V AC 230V Crest factor**) typ. 2.6 2.8 3.3 at 48V, 5A Start-up delay typ. 700ms 800ms 850ms see Fig. 3-2 Rise time typ. 51ms 51ms 51ms at 48V, 5A const. current load, 0mF load capacitance, see Fig. 3-2 typ. 96ms 96ms 96ms at 48V, 5A const. current load, 5mF load capacitance,, see Fig. 3-2 Turn-on overshoot max. 100mV 100mV 100mV see Fig. 3-2 *) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit. **) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform. Fig. 3-1 Input voltage ranges Fig. 3-2 Turn-on behavior, definitions Turn-on (85) 90 Rated input ranges VIN POUT 300Vac max. 500ms 264180 Shut-down 132 Upper range Lower range Start-up delay Rise Time Overshoot - 5%Output Voltage Input Voltage Jul. 2015 / Rev. 2.0 DS-CS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CS10.481 C-Line 48V, 5A, SINGLE PHASE INPUT Fig. 3-3 Input current vs. output load at 48V Fig. 3-4 Power factor vs. output load 6A1 23 4 Input Current, typ. Output Current a) 100Vac b) 120Vac c) 230Vac (a) (b) (c) 6A1 23 4 0.35 0.40 Output Current 0.45 0.50 0.55 0.60 0.65 Power Factor, typ. a) 100Vac b) 120Vac c) 230Vac (a) (b) (c) Fig. 3-5 Input voltage derating 30 40 50 70°C 12A Ambient Temperature A A... at 85Vac, continuous B... short term B Allowable Output Current at 85Vac Jul. 2015 / Rev. 2.0 DS-CS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CS10.481 C-Line 48V, 5A, SINGLE PHASE INPUT 4. DC-INPUT Do not operate this power supply with DC-input voltage. Use the CP10.241 or CP10.242 units instead. 5. INPUT INRUSH CURRENT After turn-on of the input voltage, an active inrush limitation circuit limits the input inrush current. Virtually no input inrush current is generated. The charging current into the EMI suppression capacitors is disregarded in the first microseconds after switch-on. AC 100V AC 120V AC 230V Inrush current max. 10Apeak 10A peak 10A peak temperature independent typ. 3Apeak 3A peak 3A peak temperature independent Inrush energy max. 1A2s 1A 2s 1A 2s temperature independent Fig. 5-1 Typical input inrush current behavior Input: 230Vac Output: 48V, 5A Ambient: 25°C Upper curve: Input current (10A / DIV) Medium curve: Input voltage (500V / DIV) Lower curve: Output voltage (40V / DIV) Time scale: 100ms / DIV Input Current Input Voltage Output Voltage Jul. 2015 / Rev. 2.0 DS-CS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CS10.481 C-Line 48V, 5A, SINGLE PHASE INPUT 6. OUTPUT Output voltage nom. 48V Adjustment range min. 48-52V guaranteed max. 56V***) at clockwise end position of potentiometer Factory settings typ. 48.0V ±0.2%, at full load, cold unit, Line regulation max. 70mV 90-132 / 180-300Vac Load regulation max. 100mV static value, 0A Æ 5A; see Fig. 6-1 Ripple and noise voltage max. 100mVpp 20Hz to 20MHz, 50Ohm Output current nom. 5A at 48V, ambient temperature <60°C, see Fig. 6-1 nom. 6A*) at 48V, ambient temperature <45°C nom. 3.75A at 48V and 70°C ambient temperature nom. 4.6A at 52V, ambient temperature <60°C, see Fig. 6-1 nom. 5.5A*) at 52V, ambient temperature <45°C, see Fig. 6-1 nom. 3.45A at 52V and 70°C ambient temperature Reduce output current linearly between +45°C and +70°C Output power nom. 240W continuously available nom. 288W*) Power Boost® *) Overload behavior continuous current see Fig. 6-1 Short-circuit current min. 7A) load impedance <100mOhm, see Fig. 6-1 max. 9A) load impedance <100mOhm, see Fig. 6-1 Output capacitance typ. 3 100μF included inside the power supply *) Power Boost This power/ current is continuously allowed up to an ambient temperature of 45°C. Above 45°C, do not use this power/ current longer than a duty cycle of 10% and/ or not longer than 1 minute every 10 minutes. ) Discharge current of output capacitors is not included. *) This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. I t is not a guaranteed value which can be achieved. The typical value is about 54.2V. Fig. 6-1 Output voltage vs. output current, typ. Output Voltage 0 2 468 60V 10A5 317 9 Adjustment Range Output Current +60°C +25°C -25°C 48V 52V Jul. 2015 / Rev. 2.0 DS-CS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CS10.481 C-Line 48V, 5A, SINGLE PHASE INPUT 7. HOLD-UP TIME AC 100V AC 120V AC 230V Hold-up Time typ. 62ms 107ms 103ms at 48V, 2.5A, see Fig. 7-1 min. 50ms 86ms 83ms at 48V, 2.5A, see Fig. 7-1 typ. 23ms 46ms 47ms at 48V, 5A, see Fig. 7-1 min. 19ms 37ms 38ms at 48V, 5A, see Fig. 7-1 typ. 17ms 35ms 37ms at 48V, 6A, see Fig. 7-1 min. 14ms 28ms 30ms at 48V, 6A, see Fig. 7-1 Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down behavior, definitions 120ms 85 120100 180 230Vac Hold-up Time 100 Input Voltage a) 48V 2.5A typ. b) 48V 2.5A min. c) 48V 5A typ. d) 48V 5A min. e) 48V 6A min. a a b c c dd e e b - 5% Hold-up Time Zero Transition Output Voltage Input Voltage Note: At no load, the hold-up time can be up to severa l seconds. The green DC-OK lamp is on during this time. Jul. 2015 / Rev. 2.0 DS-CS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CS10.481 C-Line 48V, 5A, SINGLE PHASE INPUT 8. EFFICIENCY AND POWER LOSSES AC 100V AC 120V AC 230V Efficiency typ. 90.7% 91.0% 91.6% at 48V, 5A typ. 90.0% 90.7% 91.2% at 48V, 6A (Power Boost) 25% at 3.75A. 25% at 5A Power losses typ. 5.8W 8.4W 7.5W at 48V, 0A typ. 24.6W 23.7W 22.0W at 48V, 5A typ. 32.0W 29.5W 27.8W at 48V, 6A (Power Boost) *) The average efficiency is an assumption for a typical application where the power supply is loaded with 25% of the nominal load for 25% of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with 100% of the nominal load for the rest of the time. Fig. 8-1 Efficiency vs. output current at 48V, typ Fig. 8-2 Losses vs. output current at 48V, typ. Efficiency 92% 6A24 5 Output Current (a) (b) (c) (a) 100Vac (b) 120Vac (c) 230Vac Power Losses 012 456 A 32W Output Current (a) (b) (c) (a) 100Vac (b) 120Vac (c) 230Vac (a) (b)(c) Fig. 8-3 Efficiency vs. input voltage at 48V, 5A, typ. Fig. 8-4 Losses vs. input voltage at 48V, 5A, typ. Efficiency 85 120 155 190 225 260Vac Input Voltage 92% Power Losses 27W 85 120 155 190 225 260Vac Input Voltage Jul. 2015 / Rev. 2.0 DS-CS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CS10.481 C-Line 48V, 5A, SINGLE PHASE INPUT 9. LIFETIME EXPECTANCY AND MTBF AC 100V AC 120V AC 230V Lifetime expectancy*) 97 000h 106 000h 122 000h at 48V, 2.5A and 40°C 275 000h*) 299 000h *) 346 000h *) at 48V, 2.5A and 25°C 45 000h 60 000h 96 000h at 48V, 5A and 40°C 128 000h 171 000h*) 272 000h *) at 48V, 5A and 25°C 33 000h 42 000h 63 000h at 48V, 6A and 40°C 93 000h 119 000h 179 000h*) at 48V, 6A and 25°C MTBF) SN 29500, IEC 61709 627 000h 653 000h 830 000h at 48V, 5A and 40°C 536 000h 558 000h 709 000h at 48V, 6A and 40°C 1 060 000h 1 104 000h 1 403 000h at 48V, 5A and 25°C MTBF) MIL HDBK 217F 459 000h 450 000h 475 000h at 48V, 5A and 40°C; Ground Benign GB40 413 000h 406 000h 426 000h at 48V, 6A and 40°C; Ground Benign GB40 655 000h 642 000h 659 000h at 48V, 5A and 25°C; Ground Bening GB25 *) The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years (131 400h). Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices. **) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product. The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means that statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it can not be determined if the failed unit has been running for 50 000h or only for 100h. 10. FUNCTIONAL DIAGRAM Fig. 10-1 Functional diagram VOUT Input Fuse Input Filter Output Voltage Regulator Power Converter Output Filter DC ok L N Output Over- Voltage Input Rectifier Inrush Limiter Protection 115/230V Auto Select Jul. 2015 / Rev. 2.0 DS-CS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CS10.481 C-Line 48V, 5A, SINGLE PHASE INPUT 11. TERMINALS AND WIRING The terminals are IP20 Finger safe constructed and suitable for field- and factory wiring. Type Screw terminals Solid wire 0.5-6mm2 Stranded wire 0.5-4mm2 American Wire Gauge AWG20-10 Max. wire diameter 2.8mm (including ferrules) Wire stripping length 7mm / 0.28inch Screwdriver 3.5mm slotted or cross-head No 2 Recommended tightening torque 1Nm, 9lb.in Pull-out force according to UL 486E Instructions: a) Use appropriate copper cables that are designed for minimum operating temperatures of: 60°C for ambient up to 45°C and 75°C for ambient up to 60°C minimum 90°C for ambient up to 70°C minimum. b) Follow national installation c odes and installation regulations! c) Ensure that all strands of a strande d wire enter the terminal connection! d) Do not use the unit without PE connection. e) Unused terminal compartments should be securely tightened. f) Ferrules are allowed. Jul. 2015 / Rev. 2.0 DS-CS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CS10.481 C-Line 48V, 5A, SINGLE PHASE INPUT 12. FRONT SIDE AND USER ELEMENTS Fig. 12-1 Front side A Input Terminals (screw terminals) N, L Line input PE (Protective Earth) input B Output Terminals (screw terminals, two pins per pole) + Positive output – Negative (return) output C Output voltage potentiometer Open the flap to adjust the output voltage. Factory set: 24.1V D DC-OK LED (green) On, when the voltage on the output terminals is >21V Jul. 2015 / Rev. 2.0 DS-CS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CS10.481 C-Line 48V, 5A, SINGLE PHASE INPUT 13. EMC The power supply is suitable for applications in industrial environment as well as in residential, commercial and light industry environment. Restrictions apply on public mains (PFC), see chapter 1 for more information. A detailed EMC report is available on request. EMC Immunity According generic standards: EN 61000-6-1 and EN 61000-6-2 Electrostatic discharge EN 61000-4-2 contact discharge air discharge 8kV 15kV Criterion A Criterion A Electromagnetic RF field EN 61000-4-3 80MHz-2.7GHz 10V/m Criterion A Fast transients (Burst) EN 61000-4-4 input lines output lines 4kV 2kV Criterion A Criterion A Surge voltage on input EN 61000-4-5 L Æ N L Æ PE, N Æ PE 2kV 4kV Criterion A Criterion A Surge voltage on output EN 61000-4-5 + Æ - + / - Æ PE 500V 1kV Criterion A Criterion A Conducted disturbance EN 61000-4-6 0.15-80MHz 10V Criterion A Mains voltage dips EN 61000-4-11 0% of 100Vac 40% of 100Vac 70% of 100Vac 0% of 200Vac 40% of 200Vac 70% of 200Vac 0Vac, 20ms 40Vac, 200ms 70Vac, 500ms 0Vac, 20ms 80Vac, 200ms 140Vac, 500ms Criterion A Criterion C Criterion C Criterion A Criterion C Criterion C Voltage interruptions EN 61000-4-11 5000ms Criterion C Powerful transients VDE 0160 over entire load range 750V, 1.3ms Criterion A Criterions: A: Power supply shows normal operation behavior within the defined limits. B: Temporary voltage dips possible. No change in operation mode. C: Temporary loss of function is possible. Power supply may shut-down and restarts by itself. No damage or hazards for the power supply will occur. EMC Emission According generic standards: EN 61000-6-4 Conducted emission input lines EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22 Class B Conducted emission output lines **) IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 limits for DC power port according EN 61000-6-3 not fulfilled Radiated emission EN 55011, EN 55022 Class B Harmonic input current EN 61000-3-2 not fulfilled Voltage fluctuations, flicker EN 61000-3-3 fulfilled*) This device complies with FCC Part 15 rules. Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. *) tested with constant current loads, non pulsing **) for information only, not mandatory for EN 61000-6-3 Switching frequency 85kHz to 110kHz Main converter, input voltage dependent Jul. 2015 / Rev. 2.0 DS-CS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CS10.481 C-Line 48V, 5A, SINGLE PHASE INPUT 14. ENVIRONMENT Operational temperature*) -25°C to +70°C (-13°F to 158°F) reduce output power according Fig. 14-1 Storage temperature -40°C to +85°C (-40°F to 185°F) for storage and transportation Output de-rating 3.2W/°C 6W/°C 45°C to 60°C (113°F to 140°F) 60°C to 70°C (140°F to 158°F) Humidity) 5 to 95% r.h. IEC 60068-2-30 Vibration sinusoidal 2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g*) 2 hours / axis*) IEC 60068-2-6 Shock 30g 6ms, 20g 11ms*) 3 bumps / direction, 18 bumps in total IEC 60068-2-27 Altitude 0 to 2000m (0 to 6 560ft) without any restrictions 2000 to 6000m (6 560 to 20 000ft) reduce output power or ambient temperature, see Fig. 14-2 IEC 62103, EN 50178, overvoltage category II Altitude de-rating 15W/1000m or 5°C/1000m > 2000m (6500ft), see Fig. 14-2 Over-voltage category III IEC 62103, EN 50178, altitudes up to 2000m II altitudes from 2000m to 6000m Degree of pollution 2 IEC 62103, EN 50178, not conductive LABS compatibility The unit does not release any silicone or other LABS-critical substances and is suitable for use in paint shops. *) Operational temperature is the same as the ambient or surrounding temperature and is defined as the air temperature 2cm bel ow the unit. ) Do not energize while condensation is present *) Tested in combination with DIN-Rails according to EN 60715 with a height of 15mm and a thickness of 1.3mm and standard orientation. Allowable Output Current at 48V -25 0 20 40 70°C Ambient Temperature continuous short term 0 2000 4000 6000m Altitude A... Tamb < 60°C B... Tamb < 50°C C... Tamb < 40°C CB A short termAllowable Output Current at 48V Jul. 2015 / Rev. 2.0 DS-CS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CS10.481 C-Line 48V, 5A, SINGLE PHASE INPUT 15. PROTECTION FEATURES Output protection Electronically protected against overload, no-load and short-circuits*) Output over-voltage protection typ. 56Vdc max. 60Vdc In case of an internal power supply defect, a redundant circuit limits the maximum output voltage. The output shuts down and automatically attempts to restart. Degree of protection IP 20 EN/IEC 60529 Caution: For use in a controlled environment according to CSA 22.2 No 107.1-01. Penetration protection > 3.5mm e.g. screws, small parts Over-temperature protection yes Output shut-down with automatic restart Input transient protection MOV (Metal Oxide Varistor) Internal input fuse included not user replaceable *) In case of a protection event, audible noise may occur. 16. SAFETY FEATURES Input / output separation*) SELV IEC/EN 60950-1 PELV IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41 double or reinforced insulation Class of protection I PE (Protective Earth) connection required Isolation resistance > 5MOhm input to output, 500Vdc PE resistance < 0.1Ohm between housing and PE terminal Touch current (leakage current) typ. 0.36mA / 0.91mA 100Vac, 50Hz, TN-,TT-mains / IT-mains typ. 0.50mA / 1.25mA 120Vac, 60Hz, TN-,TT-mains / IT-mains typ. 0.64mA / 1.59mA 230Vac, 50Hz, TN-,TT-mains / IT-mains max. 0.45mA / 1.13mA 110Vac, 50Hz, TN-,TT-mains / IT-mains max. 0.62mA / 1.55mA 132Vac, 60Hz, TN-,TT-mains / IT-mains max. 0.85mA / 2.11mA 264Vac, 50Hz, TN-,TT-mains / IT-mains Jul. 2015 / Rev. 2.0 DS-CS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CS10.481 C-Line 48V, 5A, SINGLE PHASE INPUT 17. DIELECTRIC STRENGTH The output voltage is floating and has no ohmic connection to the ground. Type and factory tests are conducted by the manufacturer. Field tests may be conducted in the field using the appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down). Connect all input-terminals together as well as all output poles before conducting the test. When testing, set the cut-off current settings to the value in the table below. Fig. 17-1 Dielectric strength A B C Type test 60s 2500Vac 3000Vac 500Vac Factory test 5s 2500Vac 2500Vac 500Vac Field test 5s 2000Vac 2000Vac 500Vac Cut-off current setting > 15mA > 15mA > 20mA A C L Input Earth, PE Output N B To fulfil the PELV requirements according to EN60204-1 § 6.4.1, we recommend that either the + pole, the – pole or any other part of the output circuit shall be connected to the protective earth system. This helps to avoid situations in which a load starts unexpectedly or can not be switched off when unnoticed earth faults occur. Jul. 2015 / Rev. 2.0 DS-CS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CS10.481 C-Line 48V, 5A, SINGLE PHASE INPUT 18. APPROVALS EC Declaration of Conformity The CE mark indicates conformance with the - EMC directive 2004/108/EC and the - Low-voltage directive (LVD) 2006/95/EC IEC 60950-1 nd Edition CB Scheme, Information Technology Equipment UL 508 IND. CONT. EQ. Listed for use as Industrial Control Equipment; E-File: E198865 UL 60950-1 nd Edition Recognized for use as Information Technology Equipment, E-File: E137006 Applicable for altitudes up to 2000m. ANSI / ISA 12.12.01-2007 Class I Div 2 Recognized for use in Hazardous Location Class I Div 2 T3 Canada (C22.2 No. 213-M1987) GL (Germanischer Lloyd) classified Environmental category: C, EMC2 Marine and offshore applications Marine ABS (American Bureau for Shipping) PDA EAC TR Registration Registration for the Eurasian Customs Union market (Russia, Kazakhstan, Belarus) 19. ROHS, REACH AND OTHER FULFILLED STANDARDS RoHS Directive Directive 2011/65/EU of the European Parliament and the Council of June 8th, 2011 on the restriction of the use of certain hazardous substances in electrical and electronic equipment. REACH Directive Directive 1907/2006/EU of the European Parliament and the Council of June 1st, 2007 regarding the Registration, Evaluation, Authorisation and Restriction of Chemicals (REACH) Jul. 2015 / Rev. 2.0 DS-CS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CS10.481 C-Line 48V, 5A, SINGLE PHASE INPUT 20. PHYSICAL DIMENSIONS AND WEIGHT Width 60mm 2.36’’ Height 124mm 4.88’’ Depth 117mm 4.61’’ The DIN-rail height must be added to the unit depth to calculate the total required installation depth. Weight 700g / 1.54lb DIN-Rail Use 35mm DIN-rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm. Housing material Body: Aluminium alloy Cover: zinc-plated steel Installation clearances See chapter 2 Fig. 20-1 Front view Fig. 20-2 Side view Jul. 2015 / Rev. 2.0 DS-CS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CS10.481 C-Line 48V, 5A, SINGLE PHASE INPUT 21. ACCESSORIES 21.1. ZM1.WALL - WALL MOUNTING BRACKET This bracket is used to mount the power supply onto a flat surface without utilizing a DIN-Rail. 21.2. ZM13.SIDE - SIDE MOUNTING BRACKET This bracket is used to mount Dimension units sideways with or without utilizing a DIN-Rail. The two aluminum brackets and the black plastic slider of the unit must be detached so that the steel brackets can be installed. For sideway DIN-rail mounting, the removed aluminum brackets and the black plastic slider need to be mounted on the steel bracket. Side mounting with DIN-rail brackets Side mounting without DIN-rail brackets Jul. 2015 / Rev. 2.0 DS-CS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CS10.481 C-Line 48V, 5A, SINGLE PHASE INPUT 21.3. REDUNDANCY MODULES YRM2.DIODE – (2x 10A Inputs, 1x 20A output) The YRM2.DIODE is a dual redundancy module, which can be used to build 1+1 and N+1 redundant systems. It is equipped with two input channels, which are individually decoupled by utilizing diodes. The YRM2.DIODE does not require an additional auxiliary voltage and is self-powered even in case of a short circuit across the output. The YRM2.DIODE has a monitoring circuit included and is the perfect solution when the power supply has no DC-OK function. Two LEDs and two relay contacts signal when one of the two DC-input voltages is not in range due to a non-functioning or disconnected power supply. Due to the compact design, the unit is very slender and only requires 32mm width on the DIN-rail. YR40.482 – (2x 20A input, 1x 40A output) The YR40.482 is a dual redundancy module, which can be used to build redundant systems. It is equipped with two input channels, which are individually decoupled by utilizing MOSFET technology. Using MOSFET instead of diodes reduces the heat generation and the voltage drop between input and output. The YR40.482 does not require an additional auxiliary voltage and is self-powered even in case of a short circuit across the output. Due to the low power losses, the unit is very slender and only requires 46mm width on the DIN-rail. Fig. 21-1 Typical 1+1 Redundant configuration for 48V, 5A load current Failure Monitor optional I I Load YRM2.DIODE + -OUT + - IN 1 + - IN 2 IN 1 IN 2 L N PE CS10 Power Supply + + - - 48V, 5A L N PE CS10 Power Supply + + - - 48V, 5A L N PE Jul. 2015 / Rev. 2.0 DS-CS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CS10.481 C-Line 48V, 5A, SINGLE PHASE INPUT 22. APPLICATION NOTES 22.1. PEAK CURRENT CAPABILITY The unit can deliver peak currents (up to several milliseconds) which are higher than the specified short term currents. This helps to start current demanding loads. Solenoids, contactors and pneumatic modules often have a steady state coil and a pick-up coil. The inrush current demand of the pick-up coil is several times higher than the steady-state current and usually exceeds the nominal output current (including the PowerBoost). The same situation applies when starting a capacitive load. The peak current capability also ensures the safe operation of subsequent circuit breakers of load circuits. The load branches are often individually protected with circuit breakers or fuses. In case of a short or an overload in one branch circuit, the fuse or circuit breaker need a certain amount of over-current to open in a timely manner. This avoids voltage loss in adjacent circuits. The extra current (peak current) is supplied by the power converter and the built-in large sized output capacitors of the power supply. The capacitors get discharged during such an event, which causes a voltage dip on the output. The following two examples show typical voltage dips: Fig. 22-1 Peak load with 2x the nominal current for 50ms, typ. Fig. 22-2 Peak load with 5x the nominal current for 5ms, typ. Output Voltage48V 10ms/DIV Output Current 10A 38V 48V Output Voltage Output Current0A 1ms/DIV 25A 28V 10A Peak load (resistive) for 50ms Output voltage dips from 48V to 38V. 25A Peak load (resistive) for 5ms Output voltage dips from 48V to 28V. Peak current voltage dips typ. from 48V to 38V at 10A for 50ms, resistive load typ. from 48V to 35V at 25A for 2ms, resistive load typ. from 48V to 28V at 25A for 5ms, resistive load Jul. 2015 / Rev. 2.0 DS-CS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CS10.481 C-Line 48V, 5A, SINGLE PHASE INPUT 22.2. BACK-FEEDING LOADS Loads such as decelerating motors and inductors can feed voltage back to the power supply. This feature is also called return voltage immunity or resistance against Back- E.M.F. (Electro Magnetic Force). This power supply is resistant and does not show malfunctioning when a load feeds back voltage to the power supply. It does not matter whether the power supply is on or off. The maximum allowed feed-back-voltage is 63Vdc. The absorbing energy can be calculated according to the built-in large sized output capacitor which is specified in chapter 6. 22.3. EXTERNAL INPUT PROTECTION The unit is tested and approved for branch circuits up to 20A. An external protection is only required if the supplying branch has an ampacity greater than this. Check also local codes and local requirements. In some countries local regulations might apply. If an external fuse is necessary or utilized, minimum requirements need to be considered to avoid nuisance tripping of the circuit breaker. A minimum value of 10A B- or 6A C-Characteristic breaker should be used. 22.4. OUTPUT CIRCUIT BREAKERS Standard miniature circuit breakers (MCB’s or UL 1077 circuit breakers) are commonly used for AC-supply systems and may also be used on 48V branches. MCB’s are designed to protect wires and circuits. If the ampere value and the characteristics of the MCB are adapted to the wire size that is used, the wiring is considered as thermally safe regardless of whether the MCB opens or not. To avoid voltage dips and under-voltage situations in adjacent 48V branches which are supplied by the same source, a fast (magnetic) tripping of the MCB is desired. A quick shutdown within 10ms is necessary corresponding roughly to the ride-through time of PLC's. This requires power supplies with high current reserves and large output capacitors. Furthermore, the impedance of the faulty branch must be sufficiently small in order for the current to actually flow. The best current reserve in the power supply does not help if Ohm’s law does not permit current flow. The following table has typical test results showing which B- and C-Characteristic MCBs magnetically trip depending on the wire cross section and wire length. Fig. 22-3 Test circuit Maximal wire length for a fast (magnetic) tripping: 0.75mm² 1.0mm² 1.5mm² 2.5mm² C-2A 59m 78m 108m 157m C-3A 36m 48m 64m 105m C-4A 21m 27m 38m 58m C-6A 10m 13m 19m 28m C-8A 4m 6m 10m 14m C-10A 3m 4m 7m 10m B-6A 22m 30m 42m 62m B-10A 11m 15m 25m 26m MCBPower Supply AC DC Load B-13A 7m 10m 14m 18m Wire length S1... Fault simulation switch *) Don’t forget to consider twice the distance to the load (or cable length) when calculating the total wire length (+ and – wire). Jul. 2015 / Rev. 2.0 DS-CS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CS10.481 C-Line 48V, 5A, SINGLE PHASE INPUT 22.5. PARALLEL USE TO INCREASE OUTPUT POWER The power supply shall not be used in parallel to increase the output current. 22.6. PARALLEL USE FOR REDUNDANCY Power supplies can be paralleled for redundancy to gain higher system availability. Redundant systems require a certain amount of extra power to support the load in case one power supply unit fails. The simplest way is to put two power supplies in parallel. This is called a 1+1 redundancy. In case one power supply unit fails, the other one is automatically able to support the load current without any interruption, see also chapter 22.5. Please note: This simple way to build a redundant system does not cover failures such as an internal short circuit in the secondary side of the power supply. In such a case, the defective unit becomes a load for the other power supplies and the output voltage can no longer be maintained. This can be avoided by utilizing redundancy modules, which have decoupling devices (diodes or MOSFETs) included. Further information and wiring configurations can be found in chapter 21.3. Recommendations for building redundant power systems: a) Use separate input fuses for each power supply. b) Monitor the individual power supply units. Therefore, use the DC-OK relay contact of the YRM2.DIODE. c) It is desirable to set the output voltages of all units to the same value (± 100mV) or leave it at the factory setting. 22.7. SERIES OPERATION Unit A AC DC Unit B AC DC Load Earth (see notes) Power supplies of the same type can be connected in series for higher output voltages. It is possible to connect as many units in series as needed, providing the sum of the output voltage does not exceed 150Vdc. Voltages with a potential above 60Vdc are no longer SELV and can be dangerous. Such voltages must be installed with a protection against touching. Earthing of the output is required when the sum of the output voltage is above 60Vdc. Avoid return voltage (e.g. from a decelerating motor or battery) which is applied to the output terminals. Keep an installation clearance of 15mm (left / right) between two power supplies and avoid installing the power supplies on top of each other. Do not use power supplies in series in mounting orientations other than the standard mounting orientation (input terminals on bottom of the unit). Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple power supplies. 22.8. INDUCTIVE AND CAPACITIVE LOADS The unit is designed to supply any kind of loads, including capacitive and inductive loads. Jul. 2015 / Rev. 2.0 DS-CS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CS10.481 C-Line 48V, 5A, SINGLE PHASE INPUT 22.9. CHARGING OF BATTERIES The power supply shall not be used to charge batteries. Choose power supplies of the QS-Series or CP-Series for charging batteries. 22.10. OPERATION ON TWO PHASES 240V +10% max. Fuse L N PE Power Supply AC DC internal fuse The power supply can also be used on two-phases of a three-phase-system. A phase-to-phase connection is allowed as long as the supplying voltage is below 240V+10%. 22.11. USE IN A TIGHTLY SEALED ENCLOSURE When the power supply is installed in a tightly sealed enclosure, the temperature inside the enclosure will be higher than outside. In such situations, the inside temperature defines the ambient temperature for the power supply. The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure. The power supply is placed in the middle of the box, no other heat producing items are inside the box Enclosure: Rittal Typ IP66 Box PK 9519 100, plastic, 180x180x165mm Load: 48V, 4A; (=80%) load is placed outside the box Input: 230Vac Temperature inside enclosure: 48.9°C (i n the middle of the right side of the power supply with a distance of 2cm) Temperature outside enclosure: 23.2°C Temperature rise: 25.7K Jul. 2015 / Rev. 2.0 DS-CS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

CS10.481 C-Line 48V, 5A, SINGLE PHASE INPUT Jul. 2015 / Rev. 2.0 DS-CS10.481-EN All parameters are specified at 48V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 22.12. MOUNTING ORIENTATIONS Mounting orientations other than the input terminals on the bottom require a reduction in continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous operation can be found below: Curve A1 Recommended output current. Curve A2 Max allowed output current (res ults in approximately half the lifetime expectancy of A1). Fig. 22-4 Mounting Orientation A (Standard orientation) Power Supply OUTPUT INPUT Output Current 10 20 30 40 60°C 1.5 4.5 Ambient Temperature Fig. 22-5 Mounting Orientation B (Upside down) Power Supply OUTPUT INPUT Output Current 10 20 30 40 60°C 1.5 4.5 Ambient Temperature Fig. 22-6 Mounting Orientation C (Table-top mounting) Output Current 10 20 30 40 60°C 1.5 4.5 Ambient Temperature Fig. 22-7 Mounting Orientation D (Horizontal cw) Power Supply OUTPUT INPUT Output Current 10 20 30 40 60°C 1.5 4.5 Ambient Temperature Fig. 22-8 Mounting Orientation E (Horizontal ccw) Power Supply OUTPUT INPUT Output Current 10 20 30 40 60°C 1.5 4.5 Ambient Temperature