CPS250-M ADVANCEDENERGY | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 9

Technical content

©2022 Advanced Energy Industries, Inc. ARTESYN CPS250-M SERIES

250 W AC-DC Power Supplies

Total Power: 250 W Input Voltage: 90 to 264 VAC # of Outputs: Single AT A GLANCEAdvanced Energy's Artesyn CPS250-M series of single output open-frame AC-DC power supplies are offered in 12 V, 24 V, or 48 V outputs with +10% trim range. Each power supply comes with a 12 V fan output. All models feature ITE and medical safety approvals and accept a universal input of 90 to 264 VAC. Depending on operating conditions, its 2'' x 4'' x 1.29'' compact and high density design delivers up to

155 W of output power with free air convection cooling and

up to 250 W with 300 LFM of forced air. These power supplies are ideal for light industrial systems as well as for medical applications. SPECIAL FEATURES  Designed for forced air and natural convection cooling  Medical and ITE safety approvals, 2x MOPP  Dual fused  Type BF ready  Active Power Factor Correction, 61000-3-2 compliant  Built-in Class B EMI filter  Less than 1U high  LPX100 enclosure kit available  < 500 mW no-load power consumption  Compact size: 2" x 4" x 1.3"  For use in Class I or Class II

applications

 Three-year warranty (consult factory for extended terms) SAFETY  EN 62368-1/60601-1  UL/CSA 62368-1/60601-1  CSA  CE LVD Mark  CCC  UKCA Mark ** CPS250-M tested according to the medical standard IEC 60601-1-2 4th Edition.

2 advancedenergy.com CPS250-M SERIES ELECTRICAL SPECIFICATIONS ENVIRONMENTAL SPECIFICATIONS Input Input voltage ra nge 90 to 264 VAC Frequency 47 to 63 Hz (360 to 440 Hz with higher leakage) Inrush current 70 Apk, < 1 ms, cold start Efficiency 93% typical Leakage current Specified for medical approvals No load power < 500 mW Output Maximum power 250 W, forced-air cooling

155 W, free-air natural convection

Adjustment range -0%/+10% Holdup time 10 ms @ 225 W Fan output 12 V @ 500 mA Standby output 5 V @ 100 mA (For CPS253-M1 only) Control and Protection Remote On/Off For CPS253-M1 only DC OK For CPS253-M1 only Overvoltage protection Latching/AC Recycle required to restart PSU Overcurrent protection Auto-recovery Short circuit protection Auto-recovery (impedance <50 mOhm) Overtemperature protection Auto-recovery with hysteresis Operating temperature -20 °C to +70 °C (derate at 50 °C), startup at -40 °C Storage temperature -40 °C to +85 °C Operating humidity 5% to 90% (non-condensing) Non-operating humidity 5% to 95% (non-condensing) Maximum altitude 5000 m (3000 m for medical), derating may apply

advancedenergy.com 3 CPS250-M SERIES Isolation 4000 VAC (input to output)

1500 VAC (input to PE, output to PE)

Line harmonics 61000-3-2, Class A Conducted EMI* Level B, CISPR 22 and FCC Part 15 Radiated EMI* Level B, CISPR 22 and FCC Part 15 Surge immunity Level 3, 61000-4-5, Criterion A Medical EMC 60601-1-2, Edition 4 (cover may be required for some tests) MTBF (Telcordia, Issue 3, Method 1 Case 3) > 2.2 MHrs, 25 °C, 155 W Natural Convection, 115 VAC > 5.1 MHrs, 25 °C, 250 W Forced Air, 115 VAC *Applies to Class I input with ground tabs tied to a common ground plane and connected to system ground. Consult Technical Reference Notes for details. OTHER SPECIFICATIONS PIN ASSIGNMENTS Connector Pin Number Designation Mating Conectors J5 (AC input) 1 Mounting Holes AC Input L1/Line AC Input L2/Neutral PE Molex 09-50-8031 housing with 45570-3000 crimp or equivalent. AWG 20-18 wires. J0 (DC output) 1 Main Output Return Main Output Return Main Output Return Main Output Main Output Main Output Molex 09-50-8061 housing with 45570-3000 crimp or equivalent. AWG 20-18 wires. BusBar (DC output) Applies to 12 V variant only Main Output Main Output Return Ring terminal: Tyco 35148 or KST RV3-4 or equivalent. J2 (Fan supply) 1 Fan Return Fan Voltage Cvilux: CI0102S0000 housing; CI01T01MPP0 crimp Landwin: 2001S0200 housing; 2005T011V crimp AWG # 30-24 J403 Applies to CPS253-M1 only

5 Vdc Standby

VFB (Feedback loop pin) Molex 504193-0500 with 504185-1000 crimp or equivalent. AWG 30-26 wires.

4 advancedenergy.com CPS250-M SERIES MECHANICAL DRAWINGS - 12 V VARIANT

advancedenergy.com 5 CPS250-M SERIES MECHANICAL DRAWINGS - 24 V AND 48 V VARIANTS

6 advancedenergy.com CPS250-M SERIES MECHANICAL DRAWINGS - CPS253-M1 Thermal Hot Spot Reference Component Temperature Limit L2 135 °C T501 145 °C Q501 120 °C C12 95 °C INPUT T501 DETAIL A C12 ASSY-J0 J5J5 -PIN 1 PREFERRED EARTH J2-PIN 1 Vo(+) BARCODE J403 SEE DETAIL B MODEL LABEL WARNING LABEL Q501 SEE DETAIL A Q501 (2X)94.6 101.6 50.8 (2X)43.8 32.77MAX (4X) 4 DETAIL B J403 - PIN1 Notes: OCP can not be adjusted on the fly. Default setting is for 250 W Forced Air. Unit should be turned off before trimpot adjustment. OCP does not vary linearly with the trimpot adjustment. It is either Full clockwise (250 W) or Full counter clockwise (155 W). Thermal Hot Spot Reference - Do not exceed indicated temperature limits to ensure operation is within the conponent thermal derating limits. Measure the component temperatures using K type thermocouples. Recommended Mounting Screw - M3.0 (4X) Pan head screw with teeth washer, 6 mm length, 6~8 Kgf-cm Torque. Unit weight 200 g max

Figure 1. Output Power vs. Ambient Temperature at Natural Convection and Forced Air Figure 2. Output Power vs. Input Line at Natural Convection and Forced Air Cooling [300 Figure 3. Typical Efficiency for 12 V Output Figure 4. Typical Efficiency for 24 V Output Figure 5. Typical Efficiency for 48 V Output Figure 6. Estimated Product Useful Life Based on C12 (bulk capacitor) Case Temperature

115 Vac

230 Vac

8 advancedenergy.com CPS250-M SERIES

ORDERING INFORMATION

ACCESSORIES AND CONNECTOR KITS Model number Output voltage Minimum load Max. Continuous Load (Free Air) Peak Load (Free Air) Max. Continuous Load (Forced Air)

2 Regulation

Ripple (p-p) CPS253-M 12 V 0 A 12.92 A 15.5 A 20.83 A ±2% 120 mV CPS253-M1 12 V 0 A 12.92 A 15.5 A 20.83 A ± 2% 120 mV CPS255-M 24 V 0 A 6.45 A 7.74 A 10.42 A ±2% 240 mV CPS258-M 48 V 0 A 3.23 A 3.88 A 5.21 A ± 2% 480 mV 1 Peak Load current not to exceed 30 seconds with maximum 10% duty cycle. 2 Requires at least 300 LFM of airflow. 3 At 25 °C including factory setpoint, Line voltage and Load current variations. 4 Peak to peak ripple measured at the output terminals with 10 µF tantalum capacitor in parallel with 0.1 µF ceramic capacitor across the output & at 25 °C and output load ≥ 6 W. Part Number Description 70-841-032 CPS255-M (24 V) and CPS258-M (48 V): Complete mating connector kit for Input (J5); Output (J0) and 12 V fan supply (J2) 70-841-033 CPS253-M (12 V): Complete mating connector kit for Input (J5); DC busbar ring lugs and 12 V fan supply (J2) 70-841-034 CPS253-M1 (12 V + M1 option): Complete mating connector kit for Input (J5); DC busbar ring lugs; 12 V fan supply (J2) and “-M1” optional features (J403)

ENG-CPS250-M-235-01 4.20 For international contact information, visit advancedenergy .com. powersales@aei.com (Sales Support) productsupport.ep@aei.com (Technical Support) +1 888 412 7832 ABOUT ADVANCED ENERGY Advanced Energy (AE) has devoted more than three decades to perfecting power for its global customers. AE designs and manufactures highly engineered, precision power conversion, measurement and control solutions for mission-critical applications and processes. Our products enable customer innovation in complex applications for a wide range of industries including semiconductor equipment, industrial, manufacturing, telecommunications, data center computing, and medical. With deep applications know-how and responsive service and support across the globe, we build collaborative partnerships to meet rapid technological developments, propel growth for our customers, and innovate the future of power. Specifications are subject to change without notice. Not responsible for errors or omissions. ©2022 Advanced Energy Industries, Inc. All rights reserved. Advanced Energy®, AE® and Artesyn™ are U.S. trademarks of Advanced Energy Industries, Inc.