CPC20PN-T2-001 E-T-A | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 9

Technical content

INTELLIGENT POWER DISTRIBUTION SYSTEM ControlPlex® Controller CPC20 CPC20PN-T2-001 The intelligent ControlPlex® system CPC20 is the perfect solution for the machine building and process industry. The system com- bines the well-proven quality of a DC 24 V overcurrent protection with a PROFINET communication function. It features permanent measuring data recording, analysing and processing. This provi- des the required transparency to detect changes in the production process at an early stage and initiate corrective actions in time. The integral web server of the CPC20 bus controller allows direct access to the data of the DC 24 V power distribution. All measu- ring data and status information can be accessed even without using the /f_ield bus interface. INTELLIGENT POWER DISTRIBUTION SYSTEM ControlPlex® Controller CPC20 TYPICAL FEATURES YOUR BENEFITS

  • Control, diagnosis and monitoring via PROFINET
  • Devices including supply module, overcurrent protection, power distribution module and bus controller
  • Fully-fledged EtherNet communication interface (web server)
  • Service and maintenance interface via USB terminal
  • Adjustable configuration of up to 32 channels with 16 devices wi- thout expansion or up to 64 channels with 32 devices incl. expan- sion
  • Integrated memory for overload and short circuit diagnosis in the load circuits
  • Increased system availability through com prehensive diagnostic functions
  • Im proves protection against voltage dips through selective protec- tion of loads
  • Reduces dow ntim es through quick trouble-shooting
  • Increased flexibility of system planning through a m odular term inal block system TYP. APPLICATIONS APPROVALS / CERTIFICATIONS Automation; car production; mechanical engineering; chemical in- dustry; steel industry; machine building industry; pharmaceuticals and foodstuffs WEB LINKS COMPLIANCE Further information, Operating instructions, International approvals, Technical basics, REACH, RoHS, Contact global.e-t-a.com 5025

INTELLIGENT POWER DISTRIBUTION SYSTEM ControlPlex® Controller CPC20 GENERAL INFORMATION SAFETY AND INSTALLATION INSTRUCTIONS Installation must be done by a qualified electrician.

  • The CPC20 bus controller is only intended for use with safety extra-low voltage (=24 V DC).
  • Connection to higher or not selectively protected voltages can cause harmful conditions or damage.
  • The 18plus-ControlPlex® power distribution system is exclusively to be used.
  • The device must only be supplied with power after proper installation.
  • When a circuit protector has tripped and before the reset, the cause of the failure (short circuit or overload) must be reme- died.
  • The national standards (e.g. in Germany DIN VDE 0100) for installation and selection of the feed and return cables must be observed. For convenient adjustment and configuration by means of projecting software a generic station description markup langua- ge /f_ile (G SDM L /f_ile) is m ade available for dow nloading on the E -T-A hom epage.
  • Please observe separate CPC20 instruction manual.
  • 0 V potential for load and control voltage is compulsory and connected.
  • The CPC2 0 has a direct and perm anent connection betw een the enclosure screen of the RJ45 sockets (XF1, XF2 and X1) and the 0 V of the XD1. Electrostatically sensitive sub-assemblies can be destroyed by voltages far below the human perception threshold. These voltages already occur if you touch a component or electrical terminals of a component without being electrostatically di- scharged. The damage of a sub-assembly caused by an overvoltage is often not immediately recognised, but will be noti- ced only after a longer operating time. Note: When wiring and connecting to the PROFINET bus system the installation and wiring regulations of the PROFIBUS User Or- ganisation (PNO) must be observed. FURTHER INFORMATION CPC20 CONTROLPLEX® SYSTEM https://global.e-t-a.com/c17673/ TECHNICAL DATA (T u = +25 °C, U b = DC 24 V) ELECTRICAL DATA Rated voltage Un DC 24 V Operating voltage Ub 18...30 V Dielectric strength DC 32 V (load circuit) Quiescent current I0 Typ. 160 m A Insulation co-ordination (EN IEC 60664)0.5 kV Overvoltage category: II Pollution degree: 2 Reinforced insulation in the actuating area OVERVIEW OF COMMANDS IN THE COM MODE Writing/reading the device configuration (parameters)
  • Current limit value 50 ... 100 %
  • Rated current 1...10 A
  • Overload disconnection 105...135 %
  • Trip tim e in the event of overload 0.05… 10 s
  • Short circuit current 180 %
  • Hysteresis limit value 5...20 %
  • Sw itch-on behaviour (latest state, O FF, O N )
  • Switch-on delay 0.05… 2.5 s Reading static device information • CPC20 device type & circuit protectors
  • CPC20 serial number & circuit protectors
  • CPC20 hardware version & circuit protectors
  • CPC20 software version & circuit protectors Reading dynamic device information / measuring values
  • CPC20 enclosure status
  • Device temperature of the circuit protectors
  • Error memory global.e-t-a.com 5025

INTELLIGENT POWER DISTRIBUTION SYSTEM ControlPlex® Controller CPC20

  • Trip counter
  • Reason of last tripping
  • Device status / event of the circuit breakers
  • Load voltage ACTUAL / MIN / MAX / MEDIUM VALUE
  • Load current: ACTUAL / MIN / MAX / MEDIUM VALUE
  • Supply voltage
  • Total current
  • Histogramm: Load current and load voltage curve in the 4 s before the circuit protector trips Control commands • Sw itch on/off or reset load output
  • Reset trip counter
  • Set parameters to factory settings
  • Delete histogramm memory MECHANICAL DATA Mounting dimensions (WxHxD) 24 x 130 x 113 mm (tolerances according to DIN ISO 286 part 1 IT13) Mass Approx. 150 g Flammability class acc. to UL 94 V-0 Mounting data DIN rail according to EN 60715-35x7.5 XD1 terminal Cable cross section [mm²] Cable cross section [AWG] Stripping length [mm] flexible w ith w ire end ferrule w ith plastic sleeve flexible w ith w ire end ferrule w ithout plas- tic sleeve X2 COM-2 terminal Bar, spring 3-pole FK-MCP 1.5/3- ST-3.5BK Cable cross section [mm²] Cable cross section [AWG] Stripping length [mm] flexible w ith w ire end ferrule w ith plastic sleeve flexible w ith w ire end ferrule w ithout plas- tic sleeve Interfaces PROFINET interface (XF1, XF2) RJ45; connection to the PROFINET bus system with integral switch ETHERNET interface (X1) RJ45; communication interface to the web server Service and maintenance interface (X3) USB 2.0 Type C Cable length max. 2.5 m ELBus ® interface (COM-1) Direct connection to the 18plus terminal module (no wiring required) ELBus ® interface (X2 COM-2) Terminal for a 2. 18plus power distribution module for expansion by a maximum of 16 additional circuit breakers Cable length max. 3 m Terminal 16/ ADR: Addressing Terminal 15/ ELB: Data line ELBus® AMBIENT CONDITIONS Ambient temperature -0...+60 °C (without condensation) Storage temperature -40...+70 °C Mounting temperature +10...+30 °C Damp heat Test according to IEC 60068-2-78, test cab. climate class 3K3 to EN60721 96 h at 95 % rel. hum idity/40 °C Vibration Test according to IEC 60068-2-6, test Fc 3 g IP code (standard) IP20 according to EN60529 EMC requirements - emitted interfe- rence (EMC directive) EN 61000-6-3 global.e-t-a.com 5025

INTELLIGENT POWER DISTRIBUTION SYSTEM ControlPlex® Controller CPC20 EMC requirements - resistance to dis- turbances (EMC directive) EN 61000-6-2 FURTHER INFORMATION CPC20PN - VISUAL INDICATION OF THE RJ45 INTERFACES X1, XF1 AND XF2 RJ45 interface X1 Operating mode LED LNK Link available G reen No link available OFF Operating mode LED ACT Activity available blinking orange No activity available OFF RJ45 interfaces XF1 and XF2 Operating mode LED LNK Link available G reen No link available OFF PROFINET device localisation green blinking Operating mode LED ACT Activity available blinking orange No activity available OFF CPC20PN - VISUAL INDICATION OF THE OPERATING CONDITIONS Operating mode LED US1 LED BF LED SF Start-up mode Orange Orange Orange Fieldbus error G reen Red OFF System error G reen OFF Red Firmware Update Red flashing Red flashing Red flashing PROFINET connection active G reen OFF OFF LED US1 Applied supply voltage indica- tion LED BF Bus error indication LED SF System error indication ORDERING NUMBER CODE C P C P N T

1 TYPE NUMBER

CPC20 Bus terminal controller for 18plus ControlPlex® with ESX60D

2 VERSION: BUS SYSTEM

PN PROFINET (terminal: 2x RJ45 socket) EN EtherNet/IP (connection: 2x RJ45 socket)

3 VARYING NUMBER OF POWER DISTRIBUTORS TO BE CONNECTED

T2 Connection option for two 18plus ControlPlex® power distribution modules

4 PRODUCT VERSIONS

001 Marking version

global.e-t-a.com 5025

INTELLIGENT POWER DISTRIBUTION SYSTEM ControlPlex® Controller CPC20 APPROVALS APPROVALS Approval authority Test standard File Certificate No. Rated voltage [V] UL UL 2367 E306740 DC 24 UL UL 508 listed CSA C22.2 No. E492388 DC 24 Find further information about approvals here: https://www.e-t-a.de/approvals_en DIMENSIONS DIMENSIONAL DRAWING CPC20 BUS CONTROLLER global.e-t-a.com 5025

INTELLIGENT POWER DISTRIBUTION SYSTEM ControlPlex® Controller CPC20 INSTALLATION INSTRUCTIONS MOUNTING POSITION SCHEMATIC DIAGRAMS global.e-t-a.com 5025

INTELLIGENT POWER DISTRIBUTION SYSTEM ControlPlex® Controller CPC20 APPLICATION EXAMPLES WIRING DIAGRAM WIRING DIAGRAM global.e-t-a.com 5025

INTELLIGENT POWER DISTRIBUTION SYSTEM ControlPlex® Controller CPC20 ACCESSORIES REQUIRED ACCESSORIES X22261102 B usbar for LIN E , 0 V, FE , grey insulation, 500 m m 18PLUS010 I 18PLUS-AM03-00-PT01-01 18plus connection moduleControlPlex® for circuit breaker type ESX60D /uni00A0/uni00A0/uni00A0↳ X22261102 B usbar for LIN E , 0 V, FE , grey insulation, 500 m m /uni00A0/uni00A0/uni00A0↳ X22357102 Supply busbar L=284 mm 18PLUS /uni00A0/uni00A0/uni00A0↳ X22357101 FTG busbar for LIN E , 0 V, FE , grey insulation, 500 m m /uni00A0/uni00A0/uni00A0↳ Y31197801 Retaining clips 18PLUS011 I 18PLUS-EM03-00-PT01-01 18PLUS supply module, ELBus® Version ControlPlex® /uni00A0/uni00A0/uni00A0↳ X22261102 B usbar for LIN E , 0 V, FE , grey insulation, 500 m m /uni00A0/uni00A0/uni00A0↳ X22357102 Supply busbar L=284 mm 18PLUS /uni00A0/uni00A0/uni00A0↳ X22357101 FTG busbar for LIN E , 0 V, FE , grey insulation, 500 m m /uni00A0/uni00A0/uni00A0↳ Y31197801 Retaining clips REQUIRED ACCESSORIES FROM ESX60D-S You get an intelligent pow er distribution system by com bining the electronic ESX60D is a double channel, communication-capable circuit protector with the CPC20 bus controller and the 18plus ControlPlex® module. OPTIONAL ACCESSORIES X22357102 Supply busbar L=284 mm 18PLUS X22357101 FTG busbar for LIN E , 0 V, FE , grey insulation, 500 m m 18PLUS012 I 18PLUS-TM03-00-PT01-01 18PLUS transfer module ControlPlex® extension for CPC20 controller global.e-t-a.com 5025

INTELLIGENT POWER DISTRIBUTION SYSTEM ControlPlex® Controller CPC20 /uni00A0/uni00A0/uni00A0↳ X22261102 B usbar for LIN E , 0 V, FE , grey insulation, 500 m m /uni00A0/uni00A0/uni00A0↳ X22357102 Supply busbar L=284 mm 18PLUS /uni00A0/uni00A0/uni00A0↳ X22357101 FTG busbar for LIN E , 0 V, FE , grey insulation, 500 m m /uni00A0/uni00A0/uni00A0↳ Y31197801 Retaining clips Y31154801 Terminal strip 3-pole FK-M CP 1.5/3-ST-3 (X2 CO M 2 ) FURTHER INFORMATION ABOUT ACCESSORIES (DRAWINGS) ACCESSORIES All information and data given on our products are accurate and reliable to the best of our knowledge, but E-T-A does not accept any responsibility for the use in applications which are not in accordance with the present specification. E-T-A reserves the right to change specifications at any time in the interest of technical improvement. Dimensions are subject to change without notice. Please enquire for the latest dimensional drawing with tolerances if required. All dimensions, data, pictures and descriptions are for information only and are not binding. Amendments, errors and omissions excepted. Ordering part numbers may differ from the device marking. global.e-t-a.com 5025