Features
- New CP1E CPU Units now available. - Lineup including CPU Units with built-in three ports: USB, RS-232C, RS-485. - The depth of CPU Units with RS-232C connectors is reduced by 20 mm. (N30/40/60S(1)) Easy connection with computers using commercially available USB cables. With E30/40/60(S), N30/40/60(S@) or NA20 CPU Units, Add I/O, Analog I/O or Temperature Inputs by Connecting Expansion Units or Expansion I/O Units. Input interrupts Complete High-speed Counter Functionality. Versatile pulse control for Transistor Output for N14/20/30/40/60(S@) or NA20 CPU Units. PWM Outputs for Transistor Output for N14/20/30/40/60(S@) or NA20 CPU Units. Mounting Serial Option Boards, Ethernet Option Board and Analog Option Board to N30/40/60 or NA20 CPU Units. Built-in analog I/O, two inputs and one output, for NA-type CPU Units.Windows is a registered trademark of Microsoft Corporation in the United States and other countries. Other company names and product names in this document are the trademarks or registered trademarks of their respective companies. The product photographs and figures that are used in this catalog may vary somewhat from the actual products. CP1E-E20SDR-A CP1E-N40S1DR-A Includes products no longer available to order. See Ordering Information for details.
■Basic Model Basic System Configuration Using an E@@S-type CPU Unit Basic System Configuration Using an E@@-type CPU Unit Expansion I/O Units Expansion Units 20 or 40 I/O Points 8 inputs 8 outputs 16 outputs 32 outputs Up to 3 Units can be connected CP1W-CN811 CP1E CPU Unit Expansion Units and Expansion I/O Units I/O Connecting Cable /circle6When a two level layout is created by expansion and distance is required DIN Track Analog I/O Analog inputs Analog outputs Temperature sensors CompoBus/S I/O Link Unit Personal computer Support Software CX-Programmer IBM PC/AT or equivalent CP1E-E14SDR-/box2 CP1E-E20SDR-/box2 CP1E-E30SDR-/box2 CP1E-E40SDR-/box2 CP1E-E60SDR-/box2 Personal computer CP1E-E30DR-A CP1E-E40DR-A CP1E-E10D@-@ CP1E-E14DR-A CP1E-E20DR-A Support Software CX-Programmer IBM PC/AT or equivalent CP1E CPU Unit Expansion I/O Units Expansion Units 20 or 40 I/O Points 8 inputs 8 outputs 16 outputs 32 outputs Up to 3 Units can be connected CP1W-CN811 CP1E CPU Unit Expansion Units and Expansion I/O Units I/O Connecting Cable /circle6When a two level layout is created by expansion and distance is required DIN Track Analog I/O Analog inputs Analog outputs Temperature sensors CompoBus/S I/O Link Unit
■Application Model Basic System Configuration Using an N/NA@@S(1)-type CPU Unit Basic System Configuration Using an N/NA-type CPU Unit Expansion I/O Units Expansion Units 8 inputs 8 outputs 16 outputs 32 outputs Analog I/O Analog inputs Analog outputs Temperature sensors CompoBus/S I/O Link Unit Up to 3 Units can be connected DIN Track CP1W-CN811 CP1E CPU Unit Expansion Units and Expansion I/O Units I/O Connecting Cable /g122When a two level layout is created by expansion and distance is required 20 or 40 I/O Points (NT Link/Host Link) General component (No-protocol mode) (Modbus-RTU) CP-series PLC or CJ2M PLC (Serial PLC Link) Host computer (Host Link) Programmable Terminal (PT) Inverter Personal computer Support Software CX-Programmer IBM PC/AT or equivalent Battery CP1W-BAT01 CP1E-N30S(1)D/g133-/g133 CP1E-N40S(1)D/g133-/g133 CP1E-N60S(1)D/g133-/g133 CP1E-N30D/g133-/g133 CP1E-N40D/g133-/g133 CP1E-N60D/g133-/g133 CP1E-NA20D/g133-/g133 CP1E-N14D/g133-/g133 CP1E-N20D/g133-/g133 CP1E CPU Unit Expansion I/O Units Expansion Units 20 or 40 I/O Points 8 inputs 8 outputs 16 outputs 32 outputs Analog I/O Analog inputs Analog outputs Temperature sensors CompoBus/S I/O Link Unit Up to 3 Units can be connected DIN Track CP1W-CN811 CP1E CPU Unit Expansion Units and Expansion I/O Units I/O Connecting Cable Personal computer IBM PC/AT or equivalent Built in RS-232C Battery CP1W-BAT01 /g122When a two level layout is created by expansion and distance is required (NT Link/HOST Link) General component (No-protocol mode) (Modbus-RTU) CP-series PLC or CJ2M PLC (Serial PLC Link) Host computer (Host Link) Programmable Terminal (PT) Inverter Support Software CX-Programmer COMM RS-232C Option Board CP1W-CIF01 COMM RS-422A/485 Option Board CP1W-CIF11 CP1W-CIF12-V1 IP ADDRESS: SUBNET MASK: COMM ERR 10BASE-T 100BASE-TX Ethernet Option Board CP1W-CIF41 (version 2.0 or higher) r Or O Analog Option Board CP1W-ADB21 CP1W-DAB21V CP1W-MAB221 Or Note Neither the CP1W-DAM01 LCD Option Board nor the CP1W-CIF41 Ethernet Option Board version 1.0 can be used. * Analog Option Board can be mounted only to N30/40/60 or NA20 CPU Units version 1.2 or higher.
■ Model Number Legend (Not all models that can be represented with the model number legend can necessarily be produced.) Difference between E/N/NA@@-type and E/N@@S(1)-type ■Basic Model E@@(S)-type CPU Units Difference in Characteristics and Functions Product Lineup 1. Class E : Basic model N : Application model NA :Application model with built-in analog 3. Unit type S : Renewal None : Normal 6. Output type R : Relays outputs T : Transistor outputs, sinking T1 : Transistor outputs, sourcing 2. I/O capacity 10 : 10 I/O points (6 inputs, 4 outputs) 14 : 14 I/O points (8 inputs, 6 outputs) 20 : 20 I/O points (12 inputs, 8 outputs) 30 : 30 I/O points (18 inputs, 12 outputs) 40 : 40 I/O points (24 inputs, 16 outputs) 60 : 60 I/O points (36 inputs, 24 outputs) 4. Built-in RS-485 port 1 : RS-485 None : - 7. Power supply A : AC power supply D : DC power supply 5. Input type D : DC inputs Normal-type E@@-type Renewal-type E@@S-type Function E@@-type (Normal) E@@S-type (Renewal) Analog adjusters 2 adjusters (Setting range: 0 to 255) None The analog adjuster PV in A642/A643 is fixed on 0000. E@@ CPU Unit (Normal) E@@S CPU Unit (Renewal) Relay outputs Transistor outputs (sinking/sourcing) Relay outputs Transistor outputs (sinking/sourcing) Power supply AC DC AC DC AC DC AC DC
10 I/O points ❍❍❍❍ -- -- -- --
■Application Model N/NA@@(S)-type CPU Units Difference in Characteristics and Functions Product Lineup * 30, 40 and 60 I/O points only. Normal-type N@@-/NA-type Renewal-type N@@S1-type Renewal-type N@@S-type Function N/NA@@-type (Normal) N@@S(1)-type (Renewal) Analog adjusters 2 adjusters (Setting range: 0 to 255) None The analog adjuster PV in A642/A643 is fixed on 0000. Built-in RS-232C port 6 signals are supported: SD, RD, RS, CS, DR and ER. 4 signals are supported: SD, RD, RS and CS. DR (pin 7) and ER (pin 8) are not supported. Option board 1 port (N30/40/60, NA20 CPU Unit only) Cannot be mounted There is no slot for an option board. Built-in RS-485 port None 1 port (N30/40/60S1 CPU Unit only) With 2-wire connections, it can only communicate in half duplex. Terminating resistance ON/OFF can be set by DIP switch. Terminal Arrangements (Transistor outputs only) COM allocation CIO 100.00 and CIO 100.01 correspond with different common terminals. CIO 100.00 and CIO 100.01 correspond with the same common terminal. Power supply for transistor outputs Not needed Do not connect an external power supply. Needed It is necessary to connect a DC24V external power supply when using terminals 00 and 01 on terminal block CIO 100. Do not connect the external power supply to the terminals except 00 and 01 on terminal block CIO 100. Normal-type Renewal-type N@@ CPU Unit RS-232C+1 option slot (*) N@@S CPU Unit Built-in RS-232C N@@S1 CPU Unit Built-in RS-232C+RS-485 Relay outputs Transistor outputs (sinking/sourcing) Relay outputs Transistor outputs (sinking/sourcing) Relay outputs Transistor outputs (sinking/sourcing) Power supply AC DC AC DC AC DC AC DC AC DC AC DC
20 I/O points
(Built-in analog) ❍ -- -- ❍ -- -- -- -- -- -- -- -- Peripheral USB Port Built-in RS-232C port Option Board slot Analog input terminal (NA-type only) Analog output terminals (NA-type only) Built-in RS-232C port Built-in RS-485 port Peripheral USB Port Peripheral USB Port Built-in RS-232C port NC0 00 10 2 NC COM COM COM 03 CIO 100.00 and CIO 100.01 are different COM. V+0 00 10 2 V- COM(V -) COM 03 CIO 100.00 and CIO 100.01 are the same COM.
Ordering Information
Refer to the OMRON website (www.ia.omron.com) or ask your OMRON representative for the most recent applicable standards for each model.
- Renewal-type ■E@@S-type CP1E CPU Units (Built-in USB port) * Product no longer available to order. Basic Model Product name Specifications External power supply (24 VDC) (A) Current consumption (A) Model Power Supply Inputs Outputs Output type Program capacity Data memory capacity
5 V 24 V
E@@S-type CPU Units with 14 I/O Points 100 to 240 VAC 8 6 Relay 2K steps 2K words -- 0.16 0.07 CP1E-E14SDR-A * E@@S-type CPU Units with 20 I/O Points 100 to 240 VAC 12 8 Relay 2K steps 2K words -- 0.17 0.08 CP1E-E20SDR-A * E@@S-type CPU Units with 30 I/O Points 100 to 240 VAC 18 12 Relay 2K steps 2K words 0.30 0.17 0.07 CP1E-E30SDR-A * E@@S-type CPU Units with 40 I/O Points 100 to 240 VAC 24 16 Relay 2K steps 2K words 0.30 0.17 0.09 CP1E-E40SDR-A * E@@S-type CPU Units with 60 I/O Points 100 to 240 VAC 36 24 Relay 2K steps 2K words 0.30 0.17 0.13 CP1E-E60SDR-A *
- Normal-type ■E@@-type CP1E CPU Units (Built-in USB port) * Product no longer available to order. Product name Specifications External power supply (24 VDC) (A) Current consumption (A) Model Power Supply Inputs Outputs Output type Program capacity Data memory capacity
E@@-type CPU Units with 10 I/O Points 100 to 240 VAC Relay steps words -- 0.08 0.04 CP1E-E10DR-A Transistor (sinking) -- 0.11 -- CP1E-E10DT-A Transistor (sourcing) -- 0.11 -- CP1E-E10DT1-A
24 VDC
Relay -- 0.08 0.04 CP1E-E10DR-D Transistor (sinking) -- 0.11 -- CP1E-E10DT-D Transistor (sourcing) -- 0.11 -- CP1E-E10DT1-D E@@-type CPU Units with 14 I/O Points 100 to 240 VAC 8 6 Relay 2K steps 2K words -- 0.16 0.07 CP1E-E14DR-A * E@@-type CPU Units with 20 I/O Points 100 to 240 VAC 12 8 Relay 2K steps 2K words -- 0.17 0.08 CP1E-E20DR-A * E@@-type CPU Units with 30 I/O Points 100 to 240 VAC 18 12 Relay 2K steps 2K words 0.30 0.17 0.07 CP1E-E30DR-A * E@@-type CPU Units with 40 I/O Points 100 to 240 VAC 24 16 Relay 2K steps 2K words 0.30 0.17 0.09 CP1E-E40DR-A *
- Renewal-type ■N@@S1-type CP1E CPU Units (Built-in RS-232C, RS-485, USB ports) * Product no longer available to order. ■N@@S-type CP1E CPU Units (Built-in RS-232C, USB ports) * Product no longer available to order. Application Model Product name Specifications External power supply (24 VDC) (A) Current consumption (A) ModelPower Supply Inputs Outputs Output type Program capacity Data memory capacity
N@@S1-type CPU Units with 30 I/O Points 100 to 240 VAC 18 12 Relay 8K steps 8K words 0.30 0.21 0.07 CP1E-N30S1DR-A * DC24V Transistor (sinking) -- 0.27 0.02 CP1E-N30S1DT-D * Transistor (sourcing) -- 0.27 0.02 CP1E-N30S1DT1-D * N@@S1-type CPU Units with 40 I/O Points 100 to 240 VAC 24 16 Relay 8K steps 8K words 0.30 0.21 0.09 CP1E-N40S1DR-A * DC24V Transistor (sinking) -- 0.31 0.02 CP1E-N40S1DT-D * Transistor (sourcing) -- 0.31 0.02 CP1E-N40S1DT1-D * N@@S1-type CPU Units with 60 I/O Points 100 to 240 VAC 36 24 Relay 8K steps 8K words 0.30 0.21 0.13 CP1E-N60S1DR-A * DC24V Transistor (sinking) -- 0.31 0.02 CP1E-N60S1DT-D * Transistor (sourcing) -- 0.31 0.02 CP1E-N60S1DT1-D * Product name Specifications External power supply (24 VDC) (A) Current consumption (A) Model Power Supply Inputs Outputs Output type Program capacity Data memory capacity N@@S-type CPU Units with 30 I/O Points 100 to 240 VAC 18 12 Relay 8K steps 8K words 0.30 0.21 0.07 CP1E-N30SDR-A * DC24V Transistor (sinking) -- 0.27 0.02 CP1E-N30SDT-D * Transistor (sourcing) -- 0.27 0.02 CP1E-N30SDT1-D * N@@S-type CPU Units with 40 I/O Points 100 to 240 VAC 24 16 Relay 8K steps 8K words 0.30 0.21 0.09 CP1E-N40SDR-A * DC24V Transistor (sinking) -- 0.31 0.02 CP1E-N40SDT-D * Transistor (sourcing) -- 0.31 0.02 CP1E-N40SDT1-D * N@@S-type CPU Units with 60 I/O Points 100 to 240 VAC 36 24 Relay 8K steps 8K words 0.30 0.21 0.13 CP1E-N60SDR-A * DC24V Transistor (sinking) -- 0.31 0.02 CP1E-N60SDT-D * Transistor (sourcing) -- 0.31 0.02 CP1E-N60SDT1-D *
- Normal-type ■N/NA@@-type CP1E CPU Units (Built-in RS-232C, USB ports) Product name Specifications External power supply (24 VDC) (A) Current consumption (A) ModelPower Supply Inputs Outputs Output type Program capacity Data memory capacity
N@@-type CPU Units with 14 I/O Points 100 to 240 VAC Relay steps words -- 0.17 0.07 CP1E-N14DR-A * Transistor (sinking) -- 0.22 0.02 CP1E-N14DT-A * Transistor (sourcing) -- 0.22 0.02 CP1E-N14DT1-A * Relay -- 0.17 0.07 CP1E-N14DR-D * Transistor (sinking) -- 0.22 0.02 CP1E-N14DT-D * Transistor (sourcing) -- 0.22 0.02 CP1E-N14DT1-D * N@@-type CPU Units with 20 I/O Points 100 to 240 VAC 12 8 Relay 8K steps 8K words -- 0.18 0.08 CP1E-N20DR-A * Transistor (sinking) -- 0.23 0.02 CP1E-N20DT-A * Transistor (sourcing) -- 0.23 0.02 CP1E-N20DT1-A * Relay -- 0.18 0.08 CP1E-N20DR-D * Transistor (sinking) -- 0.23 0.02 CP1E-N20DT-D * Transistor (sourcing) -- 0.23 0.02 CP1E-N20DT1-D * N@@-type CPU Units with 30 I/O Points 100 to 240 VAC 18 12 Relay 8K steps 8K words 0.30 0.21 0.07 CP1E-N30DR-A * Transistor (sinking) 0.30 0.27 0.02 CP1E-N30DT-A * Transistor (sourcing) 0.30 0.27 0.02 CP1E-N30DT1-A * Relay -- 0.21 0.07 CP1E-N30DR-D * Transistor (sinking) -- 0.27 0.02 CP1E-N30DT-D * Transistor (sourcing) -- 0.27 0.02 CP1E-N30DT1-D * N@@-type CPU Units with 40 I/O Points 100 to 240 VAC 24 16 Relay 8K steps 8K words 0.30 0.21 0.09 CP1E-N40DR-A * Transistor (sinking) 0.30 0.31 0.02 CP1E-N40DT-A * Transistor (sourcing) 0.30 0.31 0.02 CP1E-N40DT1-A * Relay -- 0.21 0.09 CP1E-N40DR-D * Transistor (sinking) -- 0.31 0.02 CP1E-N40DT-D * Transistor (sourcing) -- 0.31 0.02 CP1E-N40DT1-D * * Product no longer available to order.
- Product no longer available to order. ■Battery Set ■Option Board (for CP1E N30/40/60 or NA20 CPU Units) The Options cannot be used for CP1E N14/20, N30/40/60S(1), E10/14/20/30/40/60(S) CPU Units. Note: It is not possible to use a CP-series Ethernet Option Board version 1.0 (CP1W-CIF41), LCD Option Board (CP1W-DAM01), or Memory Card (CP1W-ME05M) with a CP1E CPU Unit. * Support is provided with CP1E CPU Unit version 1.2 and later. N@@-type CPU Units with 60 I/O Points 100 to 240 VAC 36 24 Relay steps words 0.30 0.21 0.13 CP1E-N60DR-A * Transistor (sinking) 0.30 0.31 0.02 CP1E-N60DT-A * Transistor (sourcing) 0.30 0.31 0.02 CP1E-N60DT1-A *
Relay -- 0.21 0.13 CP1E-N60DR-D * Transistor (sinking) -- 0.31 0.02 CP1E-N60DT-D * Transistor (sourcing) -- 0.31 0.02 CP1E-N60DT1-D * NA-type CPU Units with 20 I/O Points (Built-in analog) 100 to 240 VAC (Built-in analog inputs: 2) (Built-in analog outputs: 1) Relay steps words 0.30 0.18 0.11 CP1E-NA20DR-A (sinking) -- 0.23 0.09 CP1E-NA20DT-D Transistor (sourcing) -- 0.23 0.09 CP1E-NA20DT1-D Optional Products Product name Specifications Model Battery Set For N/NA@@(S@)-type CP1E CPU Units Note: Mount a Battery to an N/NA@@(S@)-type CPU Unit if the data in the following areas must be backed up for power interruptions.
- DM Area (D) (except backed up words in the DM Area), Holding Area (H), Counter Completion Flags (C), Counter Present Values (C), Auxiliary Area (A), and Clock Function (Use batteries within two years of manufacture.) CP1W-BAT01 Product name Specifications Model RS-232C Option Board One RS-232C Option Board can be mounted to the Option Board slot. CP1W-CIF01 RS-422A/485 Option Board One RS-422A/485 Option Board can be mounted to the Option Board slot. CP1W-CIF11 RS-422A/485 Isolated-type Option Board CP1W-CIF12-V1 Ethernet Option Board One Ethernet Option Board can be mounted to the Option Board slot. CP1E CPU Units are supported by CP1W-CIF41 version 2.0 or higher. When using CP1W-CIF41, CX-Programmer version 9.12 or higher is required. CP1W-CIF41 Analog Input Option Board Can be mounted in CPU Unit Option Board slot. 2 analog inputs. 0-10V(Resolution:1/4000), 0-20mA (Resolution:1/2000). CP1W-ADB21 * Analog Output Option Board Can be mounted in CPU Unit Option Board slot. 2 analog outputs. 0-10V (Resolution:1/4000). CP1W-DAB21V * Analog I/O Option Board Can be mounted in CPU Unit Option Board slot. 2 analog inputs. 0-10V(Resolution:1/4000), 0-20mA(Resolution:1/2000). 2 analog outputs. 0-10V (Resolution:1/4000). CP1W-MAB221 * Product name Specifications External power supply (24 VDC) (A) Current consumption (A) ModelPower Supply Inputs Outputs Output type Program capacity Data memory capacity
■Expansion I/O Units and Expansion Units (for CP1E E30/40/60(S), N30/40/60(S@), or NA20 CPU Units) CP1E E10/14/20(S) or N14/20 CPU Units do not support Expansion I/O Units and Expansion Units. ■I/O Connecting Cable Note: An I/O Connecting Cable (approx. 6 cm) for horizontal connection is provided with CP1W Expansion I/O Units and Expansion Units. Unit type Product name Specifications Current consumption (A) Model Inputs Outputs Output type 5 V 24 V CP1W Expansion I/O Units Input Unit 8 -- 24 VDC Input 0.018 -- CP1W-8ED Output Units -- 8 Relay 0.026 0.044 CP1W-8ER Transistor (sinking) 0.075 -- CP1W-8ET Transistor (sourcing) 0.075 -- CP1W-8ET1 -- 16 Relay 0.042 0.090 CP1W-16ER Transistor (sinking) 0.076 -- CP1W-16ET Transistor (sourcing) 0.076 -- CP1W-16ET1 -- 32 Relay 0.049 0.131 CP1W-32ER Transistor (sinking) 0.113 -- CP1W-32ET Transistor (sourcing) 0.113 -- CP1W-32ET1 I/O Units 12 8 Relay 0.103 0.044 CP1W-20EDR1 Transistor (sinking) 0.130 -- CP1W-20EDT Transistor (sourcing) 0.130 -- CP1W-20EDT1 24 16 Relay 0.080 0.090 CP1W-40EDR Transistor (sinking) 0.160 -- CP1W-40EDT Transistor (sourcing) 0.160 -- CP1W-40EDT1 CP1W Expansion Units Analog Input Unit 4CH -- Input range: 0 to 5 V, 1 to 5 V, 0 to 10 V, ±10 V, 0 to 20 mA, or 4 to 20 mA. Resolution: 1/6000 0.100 0.090 CP1W-AD041 Resolution: 1/12000 0.100 0.050 CP1W-AD042 Analog Output Unit -- 2CH Output range: 1 to 5 V, 0 to 10 V, ±10 V, 0 to 20 mA, or 4 to 20 mA. Resolution: 1/6000 0.040 0.095 CP1W-DA021 -- 4CH Resolution: 1/6000 0.080 0.124 CP1W-DA041 Resolution: 1/12000 0.070 0.160 CP1W-DA042 Analog I/O Unit 4CH 4CH Input range: 0 to 5 V, 1 to 5 V, 0 to 10 V, ±10 V, 0 to 20 mA, or 4 to 20 mA. Output range: 1 to 5 V, 0 to 10 V, ±10 V, 0 to 20 mA, or 4 to 20 mA. Resolution: 1/12000 0.120 0.170 CP1W-MAD44 4CH 2CH Resolution: 1/12000 0.120 0.120 CP1W-MAD42 2CH 1CH Resolution: 1/6000 0.083 0.110 CP1W-MAD11 Temperature Sensor Unit 2CH -- Sensor type: Thermocouple (J or K) 0.040 0.059 CP1W-TS001 4CH -- Sensor type: Thermocouple (J or K) 0.040 0.059 CP1W-TS002 2CH -- Sensor type: Platinum resistance thermometer (Pt100 or JPt100) 0.054 0.073 CP1W-TS101 4CH -- Sensor type: Platinum resistance thermometer (Pt100 or JPt100) 0.054 0.073 CP1W-TS102 4CH -- Sensor type: Thermocouple (J or K) 2channels can be used as analog input. Input range: 1 to 5 V, 0 to 10 V, 4-20 mA Resolution: 1/12000 0.070 0.030 CP1W-TS003 12CH -- Sensor type: Thermocouple (J or K) 0.080 0.050 CP1W-TS004 CompoBus/S I/O Link Unit 8 8 CompoBus/S slave 0.029 -- CP1W-SRT21 Product name Specifications Model I/O Connecting Cable 80 cm (for CP1W Expansion I/O Units and Expansion Units) Only one I/O Connecting Cable can be used in each PLC. CP1W-CN811
■DIN Track Accessories Name Specifications Model DIN Track Length: 0.5 m; Height: 7.3 mm PFP-50N Length: 1 m; Height: 7.3 mm PFP-100N Length: 1 m; Height: 16 mm PFP-100N2 End Plate A stopper to secure the Units on the DIN Track. PFP-M
■Software Note: 1. The E20/30/40(S), N20/N30/N40(S) CPU Units are supported by CX-Programmer version 8.2 or higher. The E10, E14, N14, N60, and NA20 CPU Units are supported by CX-Programmer version 9.03 or higher. When Micro PLC Edition CX- Programmer is used, you need version 9.03 or higher. The E60S CPU Units are supported by CX-Programmer version 9.42 or higher. When Micro PLC Edition CX-Programmer is used, you need version 9.42 or higher. 2. The CX-One and CX-One Lite cannot be simultaneously installed on the same computer. * Multi licenses (3, 10, 30, or 50 licenses) and DVD media without licenses are also available for the CX-One. The following tables lists the Support Software that can be installed from CX-One Note: For details, refer to the CX-One Catalog (Cat. No. R134). Unit Versions Unit Versions and Programming Devices The following tables show the relationship between unit versions and CX-Programmer versions. Note: 1. To update the CX-Programmer, the CX-One version 3/version 4 auto-update must be installed. 2. Use the CX-Programmer version 9.12 or higher, when the CP1W-CIF41 is applied. * 1 A Programming Console cannot be used. * 2 Supports Smart Input function. * 3 Does not support Smart Input function. Programming Devices Product name Specifications ModelNumber of licenses Media FA Integrated Tool Package CX-One Lite Ver.4.@ CX-One Lite is a subset of the complete CX-One package that provides only the Support Software required for micro PLC applications. CX-One Lite runs on the following OS. OS: Windows 7 (32-bit/64-bit version) / Windows 8 (32-bit/64-bit version) / Windows 8.1 (32- bit/64-bit version) / Windows 10 (32-bit/64-bit version) 1 license DVD CXONE-LT01D-V4 FA Integrated Tool Package CX-One Package Ver. 4.@ CX-One is a comprehensive software package that integrates Support Software for OMRON PLCs and components. CX-One runs on the following OS. OS: Windows 7 (32-bit/64-bit version) / Windows 8 (32-bit/64-bit version) / Windows 8.1 (32- bit/64-bit version) / Windows 10 (32-bit/64-bit version) 1 license * DVD CXONE-AL01D-V4 Support Software in CX-One CX-One Lite Ver.4.@ CX-One Ver.4.@ Support Software in CX-One CX-One Lite Ver.4.@ CX-One Ver.4.@ Micro PLC Edition CX-Programmer Ver.9. @ Yes No CX-Drive Ver.1.@ Yes Yes CX-Programmer Ver.9.@ No Yes CX-Process Tool Ver.5.@ No Yes CX-Integrator Ver.2.@ Yes Yes Faceplate Auto-Builder for NS Ver.3. @ No Yes Switch Box Utility Ver.1.@ Yes Yes CX-Designer Ver.3.@ Yes Yes CX-Protocol Ver.1.@ No Yes NV-Designer Ver.1.@ Yes Yes CX-Simulator Ver.1.@ Yes Yes CX-Thermo Ver.4.@ Yes Yes CX-Position Ver.2.@ No Yes CX-ConfiguratorFDT Ver.1.@ Yes Yes CX-Motion-NCF Ver.1.@ No Yes CX-FLnet Ver.1.@ No Yes CX-Motion-MCH Ver.2.@ No Yes Network Configurator Ver.3.@ Yes Yes CX-Motion Ver.2.@ No Yes CX-Server Ver.4.@ Yes Yes Units Model numbers Unit version CP1E CPU Units CP1E-E@@SDR-A CP1E-E@@D@-@ CP1E-N@@D@-@ CP1E-NA@@D@-@ Unit version 1.@ CPU Unit Functions Required Programming Device *1 CX-Programmer Micro PLC Edition CX-Programmer CX- Programmer for CP1E Ver.8.2 or higher Ver.9.03 or higher Ver.9.42 or higher Ver.8.2 or higher Ver.9.03 or higher Ver.9.42 or higher Ver.1.0 CP1E-E20/30/40(S)D@-A CP1E-N20/30/40(S@)D@-@ Unit version 1.@ functions Yes Yes Yes Yes Yes Yes Yes CP1E-E10D@-@ CP1E-@14(S)D@-@ CP1E-N60(S@)D@-@ CP1E-NA20D@-@ Unit version 1.@ functions No Yes Yes *2 No Yes Yes *2 No CP1E-E60SDR-A Unit version 1.@ functions No No Yes *2 No No Yes *2 No
- 1 Total of 110 mm with mounting brackets. * 2 Excluding cables. * 3 Use the external power supply to power input devices. Do not use it to drive output devices. * 4 This is the rated value for the maximum system configuration. Use the following formula to calculate power consumption for CPU Units with DC power. Formula: DC power consumption = (5V current consumption ✕ 5 V/70% (internal power efficiency) + 24V current consumption) ✕ 1.1(current fluctuation factor) The above calculation results show that a DC power supply with a greater capacity is required. Type AC power supply models DC power supply models CP1E-@@@D@-A CP1E-@@@D@-D Enclosure Mounted in a panel Dimensions (H × D × W) E/N/NA@@-type CPU Unit with 10 I/O points (CP1E-E10D@-@): 90mm *1 × 85mm *2 × 66 mm CPU Unit with 14 or 20 I/O points (CP1E-@14D@-@/@20D@-@): 90mm *1 × 85mm *2 × 86 mm CPU Unit with 30 I/O points (CP1E-@30D@-@): 90mm *1 × 85mm *2 × 130 mm CPU Unit with 40 I/O points (CP1E-@40D@-@): 90mm *1 × 85mm *2 × 150 mm CPU Unit with 60 I/O points (CP1E-N60D@-@): 90mm *1 × 85mm *2 × 195 mm CPU Unit with 20 I/O points and built-in analog (CP1E-NA20D@-@): 90mm *1 × 85mm *2 × 130 mm E/N/@@S(1)-type CPU Unit with 14 or 20 I/O points (CP1E-@14SD@-@/@20SD@-@): 90mm *1 × 79mm *2 × 86 mm CPU Unit with 30 I/O points (CP1E-@30S(1)D@-@): 90mm *1 × 79mm *2 × 130 mm CPU Unit with 40 I/O points (CP1E-@40S(1)D@-@): 90mm *1 × 79mm *2 × 150 mm CPU Unit with 60 I/O points (CP1E-@60S(1)D@-@): 90mm *1 × 79mm *2 × 195 mm Weight CPU Unit with 10 I/O points (CP1E-E10D@-@): 300g max. CPU Unit with 14 I/O points (CP1E-@14(S)D@-@): 360g max. CPU Unit with 20 I/O points (CP1E-@20(S)D@-@): 370g max. CPU Unit with 30 I/O points (CP1E-@30(S@)D@-@): 600g max. CPU Unit with 40 I/O points (CP1E-@40(S@)D@-@): 660g max. CPU Unit with 60 I/O points (CP1E-@60(S@)D@-@): 850g max. CPU Unit with 20 I/O points and built-in analog (CP1E-NA20D@-@): 680g max. Electrical specifications Supply voltage 100 to 240 VAC 50/60 Hz 24 VDC Operating voltage range 85 to 264 VAC 20.4 to 26.4 VDC Power consumption 15 VA/100 VAC max. 25 VA/240 VAC max. (CP1E-E10D@-A/@14(S)D@-A/@20(S)D@-A) 9 W max. (CP1E-E10D@-D) 13 W max. (CP1E-N14D@-D/N20D@-D) 50 VA/100 VAC max. 70 VA/240 VAC max. (CP1E-NA20D@-A/@30(S@)D@-A/@40(S@)D@-A/ N60(S@)D@-A) 20 W max. (CP1E-NA20D@-D/N30(S@)D@-D/N40(S@)D@-D/ N60(S@)D@-D) *4 Inrush current 120 VAC, 20 A for 8 ms max. for cold start at room temperature 240 VAC, 40 A for 8 ms max. for cold start at room temperature 24 VDC, 30 A for 20 ms max. for cold start at room temperature External power supply Not provided. (CP1E-E10D@-A/@14(S)D@-A/@20(S)D@-A)
24 VDC, 300 mA
(CP1E-NA20D@-A/@30D@-A/@40D@-A/@60D@-A/ @30SDR-A/@40SDR-A/@60SDR-A) Not provided Insulation resistance 20 MΩ min. (at 500 VDC) between the external AC terminals and GR terminals Except between DC primary current and DC secondary current Dielectric strength 2,300 VAC 50/60Hz for 1 min between AC external and GR terminals Leakage current: 5 mA max. Except between DC primary current and DC secondary current Power OFF detection time 10 ms min. 2 ms min. Application environment Ambient operating temperature 0 to 55 °C Ambient humidity 10% to 90% Atmosphere No corrosive gas. Ambient storage temperature -20 to 75 °C (excluding battery) Altitude 2,000 m max. Pollution degree 2 or less: Meets IEC 61010-2-201. Noise resistance 2 kV on power supply line (Conforms to IEC61000-4-4.) Overvoltage category Category II: Meets IEC 61010-2-201. EMC Immunity Level Zone B Vibration resistance Conforms to JIS 60068-2-6. 5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz Acceleration of 9.8 m/s2 for 100 min in X, Y, and Z directions (10 sweeps of 10 min each = 100 min total) Shock resistance Conforms to JIS 60068-2-27. 147 m/s 2, 3 times in X, Y, and Z directions Terminal block Fixed (not removable) Terminal screw size M3 Applicable standards Conforms to EC Directive Grounding method Ground to 100 Ω or less.
Performance Specifications Item CP1E-E@@SD@-@ CP1E-@@D@-@ CP1E-N@@D@-@ CP1E-NA@@D@-@ Program capacity 2 K steps (8 Kbytes) including the symbol table, comments, and program indices of the CX-Programmer
8 K steps (32 Kbytes) including the symbol table,
comments, and program indices of the CX-Programmer Control method Stored program method I/O control method Cyclic scan with immediate refreshing Program language Ladder diagram Instructions Approximately 200 Processing speed Overhead processing time 0.4 ms Instruction execution times Basic instructions (LD): 1.19 µs min. Special instructions (MOV): 7.9 µs min. Number of CP1W-series Expansion Units connected CP1E-E10D@-@/@14(S)D@-@/@20(S)D@-@: None Maximum number of I/O points CP1E-E10D@-@ : 10 CP1E-@14(S)D@-@: 14 CP1E-@20(S)D@-@: 20 CP1E-@30(S@)D@-@: 150 (30 built in, 40 × 3 expansion) CP1E-@40(S@)D@-@: 160 (40 built in, 40 × 3 expansion) CP1E-@60(S@)D@-@: 180 (60 built in, 40 × 3 expansion) CP1E-NA20D@-@: 140 (20 built in, 40 × 3 expansion) Built-in I/O CP1E-E10D@-@ : 10 (6 inputs, 4 outputs) CP1E-@14(S)D@-@: 14 (8 inputs, 6 outputs) CP1E-@20(S)D@-@: 20 (12 inputs, 8 outputs) CP1E-@30(S@)D@-@: 30 (18 inputs, 12 outputs) CP1E-@40(S@)D@-@: 40 (24 inputs, 16 outputs) CP1E-@60(S@)D@-@: 60 (36 inputs, 24 outputs) CP1E-NA20D@-@: 20 (12 inputs, 8 outputs) Built-in input functions High-speed counters High-speed counter mode/ maximum frequency Incremental Pulse Inputs 10 kHz: 6 counters 5 counters (only for 10 I/O points) Up/Down Inputs 10 kHz: 2 counters Pulse + Direction Inputs 10 kHz: 2 counters Differential Phase Inputs (4x) 5 kHz: 2 counters Incremental Pulse Inputs 100 kHz: 2 counters,10 kHz: 4 counters Up/Down Inputs 100 kHz: 1 counters,10 kHz: 1 counters Pulse + Direction Inputs 100 kHz: 2 counters Differential Phase Inputs (4x) 50 kHz: 1 counter, 5 kHz: 1 counter Counting mode Linear mode Ring mode Count value 32 bits Counter reset modes Phase Z and software reset (excluding increment pulse input) Software reset Control method Target Matching Range Comparison Input interrupts 6 inputs (4 inputs only for 10 I/O points) Interrupt input pulse width: 50 µs min. Quick-response Inputs 6 inputs (4 inputs only for 10 I/O points) Input pulse width: 50 µs min. Normal input Input constants Delays can be set in the PLC Setup (0 to 32 ms, default: 8 ms). Set values: 0, 1, 2, 4, 8, 16, or 32 ms Built-in output functions Pulse outputs (Models with transistor outputs only) Pulse output method and output frequency Pulse output function not included Pulse + Direction Mode
1 Hz to 100 kHz: 2 outputs
Output mode Continuous mode (for speed control) Independent mode (for position control) Number of output pulses Relative coordinates: 0000 0000 to 7FFF FFFF hex (0 to 2147483647) Absolute coordinates: 8000 0000 to 7FFF FFFF hex (-2147483647 to 2147483647) Acceleration/ deceleration curves Trapezoidal acceleration and deceleration (Cannot perform S-curve acceleration and deceleration.) Changing SVs during instruction execution Only target position can be changed. Origin searches Included Pulse outputs (Models with transistor outputs only) Frequency PWM output function not included 2.0 to 6,553.5 Hz (in increments of 0.1 Hz) with 1 output or 2 Hz to 32,000 Hz (in increments of 1 Hz) with 1 output Duty factor 0.0% to 100.0% (in increments of 0.1%) Accuracy: +1%/-0% at 2 Hz to 10,000 Hz and +5%/-0% at 10,000 Hz to 32,000 kHz Output mode Continuous Mode Built-in analog Analog input Analog function not included Setting range: 0 to 6,000 (2 channels only for NA-type) Analog output Setting range: 0 to 6,000 (1 channels only for NA-type) Analog adjusters E/N/NA@@-type: 2 adjusters (Setting range: 0 to 255) E/N@@S(1)-type: None
Item CP1E-E@@SD@-@ CP1E-E@@D@-@ CP1E-N@@D@-@ CP1E-NA@@D@-@ Communications B-type Peripheral USB Port Conforming to USB 2.0 B type connector Transmission distance 5 m max. Built-in RS-232C port No built-in RS-232C port Interface: Conforms to EIA RS-232C. Communications method Half duplex synchronization Start-stop Transmission distance 15 m max. Supported protocol
- Host Link
- 1:N NT Link
- No-protocol mode
- Serial PLC Links (master, slave)
- Modbus-RTU Easy Master Built-in RS-485 port No built-in RS-485 port N30/40/60S1-type only Interface: Conforms to EIA RS-485. 2-wire sensors No isolation Communications method Half duplex synchronization Start-stop Transmission distance 50 m max. Supported protocol
- Host Link
- 1:N NT Link
- No-protocol mode
- Serial PLC Links (master, slave)
- Modbus-RTU Easy Master Serial Option port Option Board cannot be mounted. N30/40/60 and NA20-type only 1 port Mountable Option Boards
- One RS-232C port: CP1W-CIF01
- One RS-422A/485 port (not isolated): CP1W-CIF11
- One RS-422A/485 port (isolated): CP1W-CIF12-V1
- One Ethernet port: CP1W-CIF41 Communications method Depends on Option Board. synchronization Depends on Option Board. Compatible protocols
- Host Link
- 1:N NT Link
- No-protocol mode
- Serial PLC Links (master, slave)
- Modbus-RTU Easy Master Number of tasks
- One cyclic execution task
- One scheduled interrupt task (always interrupt task 1)
- Six input interrupt tasks (interrupt tasks 2 to 7)
- Sixteen high-speed counter interrupt tasks (interrupt tasks 1 to 16) Maximum subroutine number 128 Maximum jump number 128 Scheduled interrupt tasks 1 interrupt task Clock Clock function not included. The time of error occurrence displays 01-01-01 01:01:01 Sunday Included. Accuracy (monthly deviation): -4.5 min to -0.5 min at ambient temperature of 55 oC, -2.0 min to +2.0 min at ambient temperature of 25oC, -2.5 min to +1.5 min at ambient temperature of 0oC Memory backup Built-in EEPROM Ladder programs and parameters are automatically saved to built-in EEPROM A section of the Data Memory Area can be saved to the built-in EEPROM. Battery backup With CP1W-BAT01 Battery (Sold separately) Battery cannot be mounted. CP1W-BAT01 can be used. Maximum battery service life: 5 years Backup Time Guaranteed value (ambient temperature: 55 oC): 13,000 hours (approx. 1.5 years) Effective value (ambient temperature: 25 oC): 43,000 hours (approx. 5 years) CIO Area Input Bits 1,600 bits (100 words): CIO 0.00 to CIO 99.15 (CIO 00 to CIO 99) Output Bits 1,600 bits (100 words): CIO 100.00 to CIO 199.15 (CIO 100 to CIO 199) Serial PLC Link Words 1,440 bits (90 words): CIO 200.00 to CIO 289.15 (words CIO 200 to CIO 289) Work Area (W) 1,600 bits (100 words): W0.00 to W99.15 (W0 to W99) Holding Area (H) 800 bits (50 words): H0.00 to H49.15 (H0 to H49) Bits in this area maintain their ON/OFF status when operating mode is changed. Auxiliary Area (A) Read-only: 7,168 bits (448 words) A0 to A447 Read/write: 4,896 bits (306 words) in words A448 to A753 Temporary Relay Area (TR) (TR Area) 16 bits: TR0 to TR15 Timer Area (T) 256 timer numbers (T0 to T255 (separate from counters)) Counter Area (C) 256 counter numbers (C0 to C255 (separate from timers))
Data Memory Area (D)
2 Kwords: D0 to D2047
Of these, 1,500 words can be saved to the backup memory (built-in EEPROM) using settings in the Auxiliary Area.
8 Kwords: D0 to D8191
Of these, 7,000 words can be saved to the backup memory (built-in EEP-ROM) using settings in the Auxiliary Area Operating modes PROGRAM mode: Program execution is stopped. Preparations can be executed prior to program execution in this mode. MONITOR mode: Programs are executed. Some operations, such as online editing, and changes to present values in I/O memory, are enabled in this mode. RUN mode: Programs are executed. This is the normal operating mode. Item CP1E-E@@SD@-@ CP1E-E@@D@-@ CP1E-N@@D@-@ CP1E-NA@@D@-@
Internal Memory in the CPU Units CPU Unit Memory Backup Structure The internal memory in the CPU Unit consists of built-in RAM and built-in EEPROM. The built-in RAM is used as execution memory and the built- in EEPROM is used as backup memory.
- Precautions for Correct Use Create a system and write the ladder programs so that problems will not occur in the system if the data in these area may be unstable.
- Data in areas such as the DM area (D), Holding Area (H), the Counter Present Values (C) and the status of Counter Completion Flags (C), which is retained by the battery, may be unstable when the power supply is turned off (Except for the DM area that are retained by the built-in EEP- ROM using the Auxilliary Area bit.)
- The error log, and clock data (N/NA@@(S@)-type CPU Unit only) in the Auxiliary Area will become unstable. Other words and bits in the Auxiliary Area will be cleared to their default values. The built-in capacitor’s backup time varies with the ambient temperature as shown in the following graph. CPU Unit Built-in EEPROM Built-in RAM Backup memory User Program Area (Backup) PLC Setup PLC Setup DM Area DM Area User Program Area I/O Memory Areas Data is retained even if the power supply is interrupted for longer than the backup time of the built-in capacitor. Execution Memory Automatic backup Read at startup Automatic backup Read at startup Backup using bit in Auxiliary Area DM Area data read at startup If a CP1W-BAT01 Battery (sold separately) is mounted to an N/NA@@(S@)-type CPU Unit, which is normally backed up by a built-in capacitor, data will be backed up by the battery. Area where data is backed up even if the power supply is interrupted for longer than the back-up time of the built-in capacitor. Area where data is cleared if the power supply is interrupted for longer than the back-up time of the built-in capacitor. Backup time of built-in capacitor 50 hours 40 hours 25 hours 20 hours 9 hours 7 hours CP1E E@@(S)-type CPU Unit CP1E N/NA@@(S@)-type CPU Unit Ambient temperature 25 40 60
Data can be read and written to I/O memory from the ladder programs. I/O memory consists of an area for I/O with external devices, user areas, and system areas. I/O Memory Areas Name No. of bits Word addresses Remarks CIO Area Input Bits 1,600 bits (100 words) CIO 0 to CIO 99 For NA-t ype, CIO90, CIO91 is occupied by analog input 0, 1. Output Bits 1,600 bits (100 words) CIO 100 to CIO 199 For NA-type, CIO190 is occupied by analog output 0. Serial PLC Link Words 1,440 bits (90 words) CIO 200 to CIO 289 -- Work Area (W) 1,600 bits (100 words) W0 to W99 -- Holding Area (H) 800 bits (50 words) H0 to H49 Data in this area is retained during power interruptions if a Battery Set (sold separately) is mounted to an N/NA@@(S@)- type CPU Unit. Data Memory Area (D) E@@(S)-type CPU Unit 2K words D0 to D2047 Data in specified words of the DM Area can be retained in the built-in EEPROM in the backup memory by using a bit in the Auxiliary Area. Applicable words: D0 to D1499 (One word can be specified at a time.) N/NA@@(S@)-type CPU Unit 8K words D0 to D8191 Data in specified words of the DM Area can be retained in the built-in EEPROM in the backup memory by using a bit in the Auxiliary Area. Applicable words: D0 to D6999 (One word can be specified at a time.) Timer Area (T) Present values 256 T0 to T255 Timer Completion Flags 256 -- Counter Area (C) Present values 256 C0 to C255 Data in this area is retained during power interruptions if a Battery Set (sold separately) is mounted to an N/NA@@(S@)- type CPU Unit. Counter Completion Flags 256 -- Auxiliary Area (A) Read only 7168 bits (448 words) A0 to A447 Data in this area is retained during power interruptions if a Battery Set (sold separately) is mounted to an N/NA@@(S@)- type CPU Unit.Read-write 4,896 bits (306 words) A448 to A753 Input bits (starting from CIO 0) User Areas Holding Area (H) DM Area (D) Timer Area (T) Counter Area (C) Output bits (starting from CIO 100) Work Area (W) System Areas Auxiliary Area (A) Condition Flags Clock Pulses
Backing Up and Restoring DM Area Data The contents of the DM Area (D) will become unstable if the power supply is interrupted for longer than the backup time of the built-in capacitor (50 hours for an E@@(S)-type CPU Unit, 40 hours for an N/NA@@(S@)-type CPU Unit without a Battery). The contents of the specified words in the DM Area data can be backed up from RAM to the built-in EEPROM backup memory during operation by turning ON a bit in the Auxiliary Area. The number of DM Area words to back up is specified in the Number of CH of DM for backup Box in the PLC Setup. If the Restore D0- from backup memory Check Box is selected in the PLC Setup, the backup data will automatically be restored to RAM when the power is turned back ON so that data is not lost even if power is interrupted. Conditions for Executing Backup Specified words starting from D0 in the RAM can be saved to the built-in EEPROM backup memory by turning ON A751.15. (These words are called the DM backup words and the data is called the DM backup data.) A751.15 (DM Backup Save Start Bit) can be used in any operating mode (RUN, MONITOR, or PROGRAM mode). Words That Can Be Backed Up
- E@@(S)-type CP1E CPU Units: D0 to D1499
- N/NA@@(S@)-type CP1E CPU Units: D0 to D6999 Number of Words To Back Up The number of words to back up starting from D0 is set in the Number of CH of DM for backup Box in the Startup Data Read Area in the PLC Setup. Restoring DM Backup Data to RAM When Power Is Turned ON The DM backup data can be restored to RAM when power is turned ON by selecting the Restore D0- from backup memory Check Box in the Startup Data Read Area in the PLC Setup. The DM backup data will be read from the backup memory even if the Clear retained memory area (HR/DM/CNT) Check Box is selected in the PLC Setup. D(n-1) Built-in RAM CP1E CPU Unit A751.15 (DM Backup Save Start Bit) turned ON DM Area (D) Data backed up Built-in EEPROM Backup Memory DM backup data Specified number of words Specify the number of words starting from D0 in the Number of CH of DM for backup Box in the Startup Data Read Area in PLC Setup. DM backup data is restored to the RAM when power supply is turned ON again if the Restore D0- from backup memory Check Box is selected in the Startup Data Read Area in the PLC Setup. Data restored
- Input Terminal Arrangement for CPU Unit with 10 I/O Points AC power supply models DC power supply models
- Input Terminal Arrangement for CPU Unit with 14 I/O Points AC power supply models DC power supply models
- Input Terminal Arrangement for CPU Unit with 20 I/O Points AC power supply models DC power supply models
- Input Terminal Arrangement for CPU Unit with 30 I/O Points AC power supply models DC power supply models CIO 0 L1 L2/N COM 01 03 05 00 02 04NC + − COM 01 03 05 00 02 04NC CIO 0 CIO 0 L1 L2/N COM 01 03 05 07 NC NC 00 02 04 06 NC NCNC + − COM 01 03 05 07 NC NC 00 02 04 06 NC NCNC CIO 0 CIO 0 L1 L2/N COM 01 03 05 07 09 11 00 02 04 06 08 10NC CIO 0 +− COM 01 03 05 07 09 11 00 02 04 06 08 10NC L1 L2/N COM NC 01 03 05 07 09 11 00 02 04 06 08 10 01 03 05 00 02 04 CIO 0 CIO 1 +− COM NC NC 01 03 05 07 09 11 00 02 04 06 08 10 01 03 05 00 02 04 CIO 0 CIO 1
- Input Terminal Arrangement for CPU Unit with 40 I/O Points AC power supply models DC power supply models
- Input Terminal Arrangement for CPU Unit with 60 I/O Points AC power supply models DC power supply models
- Input Terminal Arrangement for CPU Unit with 20 I/O Points and Built-in Analog AC power supply models DC power supply models L1 L2/N COM 01 03 05 00 02 04 07 09 11 06 08 10 01 03 05 00 02 04 07 09 11 06 08 10 CIO 0 CIO 1 +− COM NC 01 03 05 00 02 04 07 09 11 06 08 10 01 03 05 00 02 04 07 09 11 06 08 10 CIO 0 CIO 1 L1 L2/N COM 01 03 05 00 02 04 07 09 11 06 08 10 01 03 05 00 02 04 07 09 11 06 08 10 01 03 05 00 02 04 07 09 11 06 08 10 CIO 0 CIO 1 CIO 2 CIO 0 CIO 1 CIO 2 01 03 05 07 09 11 04 08 01 03 05 07 09 11 00 0000 02 04 06 08 10 01 03 05 07 09 11 02 04 06 08 10NC + − COM 06 10 L1 L2/N COM COM1 01 03 05 07 09 11 00 02 04 06 08 10 I IN0 AG I IN1 VIN0 COM0 VIN1 CIO 0 CIO 90 CIO 91 CIO 0 CIO 90 CIO 91 + - COM COM1 01 03 05 07 09 11 00NC 02 04 06 08 10 I IN0 AG I IN1 VIN0 COM0 VIN1
Allocating Built-in Inputs to Functions Input terminals are allocated functions by setting parameters in the PLC Setup. Set the PLC Setup so that each terminal is used for only one function. CPU Unit with I/O Points Input terminal block Settings in PLC Setup Interrupt input setting on Built-in Input Tab Page High-speed counter 0 to 3 setting on Built-in Input Tab Page Origin search settings on Pulse Output 0/1 Tab Page Terminal block label Terminal number Normal Interrupt Quick Single-phase (increment pulse input) Two-phase (differential phase x4 or up/down) Two-phase (pulse/ direction) CPU Unit with 20 to 60 points CPU Unit with
14 I/O pointsNormal
00 Normal
input 0 -- -- Counter 0, increment input Counter 0, phase A or up input Counter 0, pulse input -- --
01 Normal
Counter 1, increment input Counter 0, phase B or down input Counter 1, pulse input -- --
02 Normal
Counter 2, increment input Counter 1, phase A or up input Counter 0, direction -- --
03 Normal
-- Counter 1, phase B or down input Counter 1, direction -- Pulse 0, Origin proximity input signal
04 Normal
Counter 3, increment input Counter 0, phase Z or reset input Counter 0, reset input -- --
05 Normal
Counter 4, increment input Counter 1, phase Z or reset input Counter 1, reset input -- Pulse 1, Origin proximity input signal
06 Normal
Counter 5, increment input -- -- Pulse 0: Origin input signal Pulse 0, Origin input signal
07 Normal
-- -- -- Pulse 1: Origin input signal Pulse 1, Origin input signal
08 Normal
09 Normal
10 Normal
Pulse 0: Origin proximity input signal
11 Normal
Pulse 1: Origin proximity input signal CIO 1 00 to 05 Normal input 12 to17 40 06 to 11 Normal input 18 to 23
60 CIO 2 00 to 11
These functions are supported only by N/NA@@(S@)-type CPU Units with transistor outputs.
- Output Terminal Arrangement for CPU Unit with 10 I/O Points AC power supply model DC power supply model
- Output Terminal Arrangement for CPU Unit with 14 I/O Points AC power supply model DC power supply model
- Output Terminal Arrangement for CPU Unit with 20 I/O Points AC power supply model DC power supply model
- Output Terminal Arrangement for CPU Unit with 30 I/O Points AC power supply model E/N30(S@)D@-A DC power supply model N30D@-D N30S(1)DT-D Note: V- and COM(V-) are internally connected. N30S(1)DT1-D Note: V+ and COM(V+) are internally connected. 00 01 02 03 COM COM NC COM NC CIO 100 00 01 02 03 COM COM NC COM 04 05 NC NCCOM NC CIO 100 00 01 02 03 COM COM NC COM 04 05 07 06COM NC CIO 100 00 01 02 04 05 07 00 03 06 01 03 - COM COM COM COM COM CIO 100 CIO 101 00 01 02 04 05 07 00 03 06 01 03 NC NC COM COM COM COM COM CIO 100 CIO 101
100 CH 101 CH
V- COM(V -) COM COM COM V- COM(V+) COM COM COM
- Output Terminal Arrangement for CPU Unit with 40 I/O Points AC power supply model E/N40(S@)D@-A DC power supply model N40D@-D N40S(1)DT-D Note: V- and COM(V-) are internally connected. N40S(1)DT1-D Note: V+ and COM(V+) are internally connected.
- Output Terminal Arrangement for CPU Unit with 60 I/O Points AC power supply model E/N60(S@)D@-A DC power supply model N60D@-D N60S(1)DT-D Note: V- and COM(V-) are internally connected. N60S(1)DT1-D Note: V+ and COM(V+) are internally connected. +0 0 0 1 02 03 04 06 00 01 COM COM 05 07 COM 03 04 06 02 05COMCOMCOM - CIO 100 CIO 101 CIO 100 CIO 101 NC 00 01 02 03 04 06 00 01 COM COM 05 07 COM 03 04 06 02 05COMCOMCOM NC
02 05 COM COM COM(V-)V- 02 05 COM COM COM(V+)V- CIO 101 CIO 100 CIO 102 + 0 00 10 20 40 50 70 00 20 40 50 7 COM COM -COM 03 COM 06 COM 01 03 COM 06 COM COM CIO 101 CIO 100 CIO 102 NC 00 01 02 04 05 07 00 02 04 05 07 COM COM NCCOM 03 COM 06 COM 01 03 COM 06 COM COM
01 COM03
01 COM0303
COM(V-)V-
01 COM0303COM(V+)V-
- Output Terminal Arrangement for CPU Unit with 20 I/O Points and Built-in Analog AC power supply model DC power supply model Allocating Built-in Output Terminals to Functions Output terminals are allocated functions by setting parameters in the PLC Setup. Set the PLC Setup so that each terminal is used for only one function. CIO 100 CIO 190 00 01 02 04 05 07 NC 03 06 IOUT0 VOUT0 COM0 − COM COM COM COM NC CIO 100 CIO 190 0201 04 05 07 NC IOUT000 COM COM COM COM NCNC NC 03 06 VOUT0 COM0 CPU Unit with I/O points Output terminal block Other than those shown right When a pulse output instruction (SPED, ACC, PLS2, or ORG) is executed Setting in PLC Setup When the PWM instruction is executedOrigin search setting on Pulse Output 0/1 Tab Page Terminal block label Terminal number Normal output Fixed duty ratio pulse output Variable duty ratio pulse output Pulse + direction Use PWM output CIO 100
00 Normal output 0 Pulse output 0 (pulse) -- --
01 Normal output 1 Pulse output 1 (pulse) -- PWM output 0
02 Normal output 2 Pulse output 0 (direction) -- --
03 Normal output 3 Pulse output 1 (direction) -- --
04 Normal output 4 -- Pulse 0: Error counter reset
05 Normal output 5 -- Pulse 1: Error counter reset
06 Normal output 6 -- -- --
07 Normal output 7 -- -- --
00 to 03 Normal output 8 to 11 -- -- -- 40 04 to 07 Normal output 12 to 15 -- -- --
60 CIO 102 00 to 07 Normal output 16 to 23 -- -- --
These functions are supported only by N/NA@@(S@)-type CPU Units with transistor outputs.
I/O Specifications for CPU Units Input Specifications * 1 The bits that can be used depend on the model of CPU Unit. * 2 The response time is the delay caused by hardware. The delay set in the PLC Setup (0 to 32 ms, default: 8 ms) for a normal input must be added to this value. Item Specification Input type High-speed counter inputs or Normal Inputs High-speed counter inputs, interrupt input, quick-response inputs, or Normal Inputs Normal inputs Input bits CIO 0.00 to CIO 0.01 CIO 0.02 to CIO 0.07 *1 CIO 0.08 to CIO 0.11, CIO 1.00 to CIO 1.11 and CIO 2.00 to CIO 2.11 *1 Input voltage 24 VDC, +10%, -15% Applicable sensors 2-wire and 3-wire sensors Input Impedance 3.3 kΩ 3.3 kΩ 4.8 kΩ Input current 7.5 mA typical 7.5 mA typical 5 mA typical ON response time *2 E@@(S)-type CPU Unit: 50 µs min. N/NA@@(S@)-type CPU Unit: 2.5 µs min. 50 µs max. 1 ms max. OFF response time *2 E@@(S)-type CPU Unit: 50 µs min. N/NA@@(S@)-type CPU Unit: 2.5 µs min. 50 µs max. 1 ms max. Circuit configuration E@@(S)-type CPU Unit N/NA@@(S@)-type CPU Unit Input 0.00 to 0.07 Input 0.08 to 0.11, 1.00 to 1.11 Input 0.00 to 0.01 Input 0.02 to 0.07 Inputs CIO 0.08 to CIO 0.11, CIO 1.00 to CIO 1.11 and CIO 2.00 to CIO 2.11 Input indicator IN IN COM 3.3kΩ 910Ω 1000pF Internal circuits Internal circuits IN IN COM 4.8kΩ 750Ω Input indicator IN IN COM 3.3kΩ 4.3kΩ 1000pF Input indicator Internal circuits IN IN COM 910Ω 1000pF 3.3kΩ Input indicator Internal circuits IN IN COM 750Ω 4.8kΩ Internal circuits Input indicator ON OFF ON OFF ON OFF T1 T2 T3 T4 T1, T2, T3, T4: 2.5 μs min. 90% 50% 10% 90% 50% 10% 90% 50% 10% 2.5 μs min. 2.5 μs min. 20.0 μs min. 10.0 μs min. Up/down input mode Differential phase mode Pulse plus direction input mode, Increment mode N/NA@@(S@)-type: 0.00/0.01 N/NA@@(S@)-type: 0.00/0.01 ON OFF ON OFF ON OFF T1 T2 T3 T4 T1, T2, T3, T4: 50 μs min. 90% 50% 10% 90% 50% 10% 90% 50% 10% 50 μs min. 50 μs min. 200 μs min. 100 μs min. E@@(S)-type: 0.00 to 0.07 N/NA@@(S@)-type: 0.02 to 0.07 E@@(S)-type: 0.00 to 0.03 N/NA@@(S@)-type: 0.02/0.03
- Output Specifications for Relay Outputs Estimating the Service Life of Relays Under normal conditions, the service life of output contacts is as shown above. The service life of relays is as shown in the following diagram as a guideline Relationship between Continuous Simultaneous ON Rate and Ambient Temperature There are restrictions on the power supply voltage and output load current imposed by the ambient temperature. Make sure that the power supply voltage and output load current are within the following ranges. Note: The above restrictions apply to the relay output load current from the CPU Unit even if Expansion I/O Units are not connected. Item Specification Maximum switching capacity 250 VAC/2 A (cosφ = 1)
2 A, 24 VDC (4 A/common)
Minimum switching capacity 5 VDC, 10 mA Service life of relay Electrical Resistive load 200,000 operations (24 VDC) Inductive load 70,000 operations (250 VAC, cosφ = 0.4) Mechanical 20,000,000 operations ON delay 15 ms max. OFF response time 15 ms max. Circuit configuration CP1E-@@DR-@ CP1E-N20DR-D CP1E-N30DR-D CP1E-N40DR-D CP1E-@20@DR-A/N20DT@-@ CP1E-NA20DR-A CP1E-N60DR-D Output indicator Internal circuits COM OUT OUT
250 VAC, 2A,
24 VDC, 2 A
max. 30-VDC/250-VAC resistive load 125-VAC resistive load 125 VAC cosφ= 0.4 250 VAC cosφ= 0.4/
30 VDC, τ = 7ms
Contact current (A) Life (x 10 300 500 700 1000 200 100 50% 100% 55˚C45 Power voltage
21.6 VDC
20.4 VDC
50% 100% 35 45 55˚C Power voltage 50% 100% 55˚C0% Power voltage 50% 100% 55˚C50 Ambient temperature 80% 100% 55°C Ambient temperature 50% 100% 55˚C45 Power voltage
- Output Specifications for Transistor Outputs (Sinking or Sourcing) Normal Outputs Note: Do not connect a load to an output terminal or apply a voltage in excess of the maximum switching capacity. * 2 The bits that can be used depend on the model of CPU Unit. Pulse Outputs (CIO 100.00 and CIO 100.01) Note: 1. The load for the above values is assumed to be the resistance load, and does not take into account the impedance for the connecting cable to the load. 2. Due to distortions in pulse waveforms resulting from connecting cable impedance, the pulse widths in actual operation may be smaller than the values shown above. 3. The OFF and ON refer to the output transistor. The output transistor is ON at level “L”. Item Specification N@@(S@)-type 100.00, 100.01 N@@(S@)-type 100.02 to 102.07 *2 E10-type 100.00 to 100.03N@@S(1)-type N@@-type Maximum switching capacity 0.3 A/output, 0.9 A/common *1 4.5 to 30 VDC CP1E-E10D@-@: 0.9 A/Unit CP1E-N40(S@)D@-@: 3.6 A/Unit CP1E-N14D@-@: 1.5 A/Unit CP1E-N60(S@)D@-@: 5.4 A/Unit CP1E-N20D@-@: 1.8 A/Unit CP1E-NA20D@-@: 1.8 A/Unit CP1E-N30(S@)D@-@: 2.7 A/Unit Minimum switching capacity 1 mA 4.5 to 30 VDC Leakage current 0.1mA max. Residual voltage 0.6 V max. 1.5V max. ON response time 0.1 ms max. 0.1 ms max. OFF response time 0.1 ms max. 1 ms max. Fuse Not provided. External Power Supply 20.4 to 26.4V VDC 30mA max. None None Circuit configuration N@@S (1)-type sinking sourcing sinking sourcing N/NA@@-type sinking sourcing Item Specification Maximum switching capacity 100 mA/4.5 to 26.4 VDC Minimum switching capacity 7 mA/4.5 to 26.4 VDC Maximum output frequency 100 kHz Output waveform OUT OUT COM (V-) L L 4.5 to 30 VDC 20.4 to 26.4 VDC Internal circuits Internal circuits ~OUT OUT COM (V+) L L Internal circuits Internal circuits 20.4 to 26.4 VDC 4.5 to 30 VDC OUT OUT COM(–) L L
24 VDC,
4.5 to 30 VDC Internal circuits OUT OUT COM(+) L L 4.5 to 30 VDC Internal circuits OUT OUT COM(–) L L Internal circuits Internal circuits 4.5 to 30 VDC Internal circuits Internal circuits 4.5 to 30 VDC OUT OUT L L COM(+) 4µs min. 2µs min. OFF 90% ON 10%
PWM Output (CIO 100.01) Note: The OFF and ON refer to the output transistor. The output transistor is ON at level “L”. Built-in Analog I/O (NA-type CPU Units)
- Analog Input Specifications
- Analog Output Specifications * In 0 to 20 mA mode, accuracy cannot be ensured at 0.2 mA or less.
- Shared I/O Specifications Item Specification Maximum switching capacity 30 mA/4.5 to 26.4 VDC Maximum output frequency 32 kHz PWM output accuracy For ON duty +1%, .0%:10 kHz output For ON duty +5%, .0%: 0 to 32 kHz output Output waveform Item Voltage input Current input Number of inputs 2 inputs (Allocated 2 words: CIO 90 to CIO 91.) Input signal range 0 to 5 V, 1 to 5 V, 0 to 10 V, or -10 to 10 V 0 to 20 mA or 4 to 20 mA Max. rated input ±15 V ±30 mA External input impedance 1 MΩ min. Approx. 250Ω Resolution 1/6000 Overall accuracy At 25°C ±0.3% full scale ±0.4% full scale 0 to 55°C ±0.6% full scale ±0.8% full scale A/D conversion data -10 to +10 V F448 to 0BB8 hex Full Scale Other ranges 0000 to 1770 hex Full Scale Averaging function Supported (Set for individual inputs in the PLC Setup.) Open-circuit detection function Supported (Value when disconnected: 8000 hex) Item Voltage output Current output Number of outputs 1 output (Allocated 1 word: CIO 190.) Output signal range 0 to 5 V, 1 to 5 V, 0 to 10 V, or -10 to 10 V 0 to 20 mA or 4 to 20 mA Allowable external output load resistance 1 kΩ min. 600Ω max. External input impedance 0.5Ωmax. --- Resolution 1/6000 Overall accuracy At 25°C ±0.4% full scale * 0 to 55°C ±0.8% full scale * D/A conversion data -10 to +10 V F448 to 0BB8 hex Full Scale Other ranges 0000 to 1770 hex Full Scale Item Specification Conversion time 2 ms/point (6 ms total for 2 analog inputs and 1 analog output.) Isolation method Photocoupler isolation between analog I/O terminals and internal circuits. No isolation between analog I/O signals. T ON duty= × 100%T tON tON OFF ON
Specifications of Expansion I/O Units and Expansion Units Expandable CPU Units
- Expansion I/O Units and Expansion Units cannot be connected to E10/14/20(S) or N14/20 CPU Units.
- A total of up to three Expansion I/O Units and Expansion Units can be connected to an E30/40/60(S), N30/40/60(S@), NA20 CPU Unit.
- CP1E E10/14/20(S) or N14/20CPU Unit
- CP1E E30/40(S), N30/40/60(S@) or NA20 CPU Unit Connection Methods Connection cables for the Expansion I/O Units and Expansion Units are used to connect the Units. The length can be extended by using a CP1W- CN811 I/O Connection Cable (length: 800 m). Maximum Number of I/O Points for an Expanded System Restrictions on External Power Supply Capacity The following restrictions apply when using the CPU Unit’s external power supply.
- AC-power-supply E30/40(S), N30/40/60(S@) or NA20 CPU Unit The power supply capacity is restricted for AC-power-supplyE30/40/60(S), N30/40/60(S@), NA20 CPU Units. It may not be possible to use the full 300 mA of the external power supply, though a CPU Unit can connect any CP-series Expansion I/O Unit or Expansion Unit. The entire 300 mA from the external power supply can be used if Expansion Units and Expansion I/O Units are not connected. Refer to the CP1E CPU Unit Hardware Manual (Cat. No. W479) for details.
- AC-power-supply or DC-power-supply E10/14/20(S), N14/20(S) CPU Unit There is no external power supply on AC-power-supply or DC-power-supply E10/14/20, N14/20 CPU Units. CPU Unit Built-in I/O on CPU Unit Built-in Analog Total number of Expansion I/O Units and Expansion Units that can be connected Number of inputs: 24 Number of outputs: 16 Total number of I/O points when three CP1W-40ED @ Expansion I/O Units are connected Total Number of inputs Number of outputs AD DA Total Number of inputs Number of outputs CP1E-E10D@-@ 10 6 4 None None Not possible. 10 6 4 CP1E-@14@D@-@ 14 8 6 14 8 6 CP1E-@20@D@-@ 20 12 8 20 12 8
3 Units maximum
CP1E-@40@D@-@ 40 24 16 160 96 64 CP1E-@60@D@-@ 60 36 24 180 108 72 CP1E-NA20D@-@ 20 12 8 2 1 140 84 56 CP-series Expansion Units and Expansion I/O Units cannot be connected. A total of up to three CP-series Expansion I/O Units and Expansion Units can be connected. CH NC NC NC NC NC NC COM COM COM COM COM COM COM03 06 01 03 06 00 02 04 06 08 10 00 01 02 04 05 07 00 02 04 05 07 00 02 04 06 08 10 01 03 05 07 09 11 01 03 05 07 09 11 IN 40EDR OUT CH CH CH CH EXP CH CH CH 11 10 09 0807 06 05 04 03 02 01 00 11 10 09 0807 06 05 04 03 02 01 00 07 06 05 04 03 02 01 00 07 06 05 04 03 02 01 00 CH NC NC NC NC NC NC COM COM COM COM COM COM COM03 06 01 03 06 00 02 04 06 08 10 00 01 02 04 05 07 00 02 04 05 07 00 02 04 06 08 10 01 03 05 07 09 11 01 03 05 07 09 11 IN 40EDR OUT CH CH CH CH EXP CH CH CH 11 10 09 0807 06 05 04 03 02 01 00 11 10 09 0807 06 05 04 03 02 01 00 07 06 05 04 03 02 01 00 07 06 05 04 03 02 01 00 CH NC NC NC NC NC NC COM COM COM COM COM COM COM03 06 01 03 06 00 02 04 06 08 10 00 01 02 04 05 07 00 02 04 05 07 00 02 04 06 08 10 01 03 05 07 09 11 01 03 05 07 09 11 IN 40EDR OUT CH CH CH CH EXP CH CH CH 111009080706 05 0403020100 111009080706 05 0403020100 0706 05 0403020100 0706 05 0403020100
Specifications of Expansion I/O Units
- Input Specifications (CP1W-40EDR/40EDT/40EDT1/20EDR1/20EDT/20EDT1/8ED) Note: Do not apply voltage in excess of the rated voltage to the input terminal. * The response time is the hardware delay value. The delay set in the PLC Setup (0 to 32 ms, default: 8 ms) must be added to this value. For the CP1W-40EDR/EDT/EDT1, a fixed value of 16 ms must be added.
- Output Specifications Relay Outputs (CP1W-40EDR/32ER/20EDR1/16ER/8ER) Note: 1. Estimating the Service Life of Relays The service life of output contacts is as shown in the following diagram. Item Specification Input voltage 24 VDC +10%/-15% Input impedance 4.7 kΩ Input current 5 mA typical ON voltage 14.4 VDC min. OFF voltage 5.0 VDC max. ON delay 1 ms max. * OFF delay 1 ms max. * Circuit configuration Item Specification Max. switching capacity 2 A, 250 VAC (cosφ = 1),
Min. switching capacity 5 VDC, 10 mA Service life of relay (See note.) Electrical Resistive load 150,000 operations (24 VDC) Inductive load 100,000 operations (240 VAC, cosφ = 0.4) Mechanical 20,000,000 operations ON delay 15 ms max. OFF delay 15 ms max. Circuit configuration v IN IN CO M 4.7 kΩ 750 Ω Input LED Internal circuits COM OUT OUT Output LED Internal circuits Maximum
250 VAC: 2 A
24 VDC: 2 A
Life (× 104) Contact current (A)
120 VAC resistive load
24 VDC τ = 7 ms
120 VAC cosφ = 0.4 240 VAC cosφ = 0.4
24 VDC/240 VAC resistive load
Switching rate: 1,800 operations/hour
- Restrictions of CP1W-16ER/32ER Limit the output load current to satisfy the following derating curve. 3. CP1W-32ER’s maximum number of simultaneously ON output points is 24 (75%). Relation between Number of ON Outputs and Ambient Temperature (CP1W-32ER) 4. According to the ambient temperature, there are restrictions on power supply voltage and output load current for the CPU Units connected with the Expansion I/O Units (CP1W-8ER/16ER/20EDR1/32ER/40EDR). Use the PLC in the range of the power supply voltage and output load current as show below. The ambient temperature is restricted for the power-supply CPU Units (CP1E-N/NA@@@@-@). Derating curve of the output load current for Expansion I/O Units (CP1W-8ER/16ER/20EDR1/32ER/40EDR). Connected to CP1E-N30DR-D Connected to CP1E-N40DR-D Connected to CP1E-N30(S@)DT@-D Connected to CP1E-N40(S @)DT@-D Connected to CP1E-N60DR-D/ CP1E-N60(S@)DT@-D Connected to CP1E-NA20DT@-D Connected to CP1E-NA20DR-A 100 5543 Ambient temperature(˚C) Output load current(%) Ambient temperature (˚C) Number of inputs ON simultaneously (%) 50% 100% 55°C45350% Power voltage:
Power voltage: 50% 100% 55°C45 Power voltage: voltage: 50% 100% 55°C45 350% Power voltage: Power voltage: 50% 100% 55°C45 350% Power voltage: voltage: 50% 100% 55°C45 Power voltage: Power voltage: 50% 100% 55°C45 Power voltage: Power voltage: 80% 100% 55°C Ambient temperature
- Transistor Outputs (Sinking or Sourcing) *1 If the ambient temperature is maintained below 50°C, up to 0.9 A/common can be used. *2 The fuse cannot be replaced by the user. Replace the Unit if the fuse breaks due to an short-circuit or overcurrent. *3 Do not connect a load to an output terminal or apply a voltage in excess of the maximum switching capacity. Item Specification CP1W-40EDT CP1W-40EDT1 CP1W-32ET CP1W-32ET1 CP1W-20EDT CP1W-20EDT1 CP1W-16ET CP1W-16ET1 CP1W-8ET CP1W-8ET1 Max. switching capacity 4.5 to 30 VDC
0.3 A/output
4.5 to 30 VDC
24 VDC +10%/-5%
4.5 to 30 VDC 4.5 to 30 VDC
0.9 A/common
3.6 A/Unit
7.2 A/Unit
1.8 A/Unit
1 ms max. 1 ms max. 1 ms max. 1 ms max. 1 ms max. Max. number of Simultaneously ON Points of Output 16 pts (100%) 24 pts (75%) 8 pts (100%) 16 pts (100%) 8 pts (100%) Fuse *2 1 fuse/common Circuit configuration COM (−) OUT OUT L L COM (+) OUT OUT L L Sinking Outputs Sourcing Outputs Output LED Output LED Internal circuits Internal circuits24 VDC/4.5 to 30 VDC 24 VDC/4.5 to 30 VDC 0.9 0.8 (A) 0 (°C)50 55 Ambient temperature Total current for common
Specifications of Expansion Units
- Analog Input Units
- Analog Output Units Model CP1W-AD041 CP1W-AD042 Item Voltage Input Current Input Voltage Input Current Input Number of inputs 4 inputs (4 words allocated) Input signal range 0 to 5 VDC, 1 to 5 VDC, 0 to 10 VDC, or –10 to 10 VDC 0 to 20 mA or 4 to 20 mA 0 to 5 VDC, 1 to 5 VDC, 0 to 10 VDC, or -10 to 10 VDC 0 to 20 mA or 4 to 20 mA Max. rated input ±15 V ±30 mA ±15 V ±30 mA External input impedance 1 MΩ min. Approx. 250 Ω 1 MΩ min. Approx. 250 Ω Resolution 1/6000 (full scale) 1/12000 (full scale) Overall accuracy 25°C 0.3% full scale 0.4% full scale 0.2% full scale 0.3% full scale 0 to 55°C 0.6% full scale 0.8% full scale 0.5% full scale 0.7% full scale A/D conversion data 16-bit binary (4-digit hexadecimal) Full scale for –10 to 10 V: F448 to 0BB8 Hex Full scale for other ranges: 0000 to 1770 Hex 16-bit binary (4-digit hexadecimal) Full scale for –10 to 10 V: E890 to 1770 Hex Full scale for other ranges: 0000 to 2EE0 Hex Averaging function Supported (Set in output words n+1 and n+2.) Open-circuit detection function Supported Conversion time 2 ms/point (8 ms/all points) 1 ms/point (4 ms/all points) Isolation method Photocoupler isolation between analog I/O terminals and internal circuits. No isolation between analog I/O signals. Current consumption 5 VDC: 100 mA max.; 24 VDC: 90 mA max. 5 VDC: 100 mA max.; 24 VDC: 50 mA max. Model CP1W-DA021/CP1W-DA041 CP1W-DA042 Item Voltage Output Current Output Voltage Input Current Input Analog output section Number of outputs CP1W-DA021: 2 outputs (2 words allocated) CP1W-DA041: 4 outputs (4 words allocated) 4 outputs (4 words allocated) Output signal range 1 to 5 VDC, 0 to 10 VDC, or –10 to 10 VDC 0 to 20 mA or 4 to 20 mA 1 to 5 VDC, 0 to 10 VDC, or –10 to 10 VDC 0 to 20 mA or 4 to 20 mA External output allowable load resistance 2 kΩ min. 350 Ω max. 2 kΩ min. 350 Ω max. External output impedance 0.5 Ω max. --- 0.5 Ω max. --- Resolution 1/6000 (full scale) 1/12000 (full scale) Overall accuracy 25°C 0.4% full scale 0.3% full scale 0 to 55°C 0.8% full scale 0.7% full scale D/A conversion data 16-bit binary (4-digit hexadecimal) Full scale for –10 to 10 V: F448 to 0BB8 Hex Full scale for other ranges: 0000 to 1770 Hex 16-bit binary (4-digit hexadecimal) Full scale for –10 to 10 V: E890 to 1770 Hex Full scale for other ranges: 0000 to 2EE0 Hex Conversion time CP1W-DA021: 2 ms/point (4 ms/all points) CP1W-DA041: 2 ms/point (8 ms/all points) 1 ms/point (4 ms/all points) Isolation method Photocoupler isolation between analog I/O terminals and internal circuits. No isolation between analog I/O signals. Current consumption CP1W-DA021: 5 VDC: 40 mA max.; 24 VDC: 95 mA max. CP1W-DA041: 5 VDC: 80 mA max.; 24 VDC: 124 mA max. 5 VDC: 70 mA max.; 24 VDC: 160 mA max.
- Analog I/O Units
- Temperature Sensors Units * Accuracy for a K-type sensor at -100°C or less is ±4°C ±1 digit max. The rotary switch is used to set the temperature range. Model CP1W-MAD42/CP1W-MAD44 CP1W-MAD11 Item Voltage I/O Current I/O Voltage I/O Current I/O Analog Input Section Number of inputs 4 inputs (4 words allocated) 2 inputs (2 words allocated) Input signal range 0 to 5 VDC, 1 to 5 VDC, 0 to 10 VDC, or –10 to 10 VDC 0 to 20 mA or 4 to 20 mA 0 to 5 VDC, 1 to 5 VDC, 0 to 10 VDC, or −10 to 10 VDC 0 to 20 mA or 4 to 20 mA Max. rated input ±15 V ±30 mA ±15 V ±30 mA External input impedance 1 MΩ min. Approx. 250 Ω 1 MΩ min. Approx. 250 Ω Resolution 1/12000 (full scale) 1/6000 (full scale) Overall accuracy 25°C 0.2% full scale 0.3% full scale 0.3% full scale 0.4% full scale 0 to 55°C 0.5% full scale 0.7% full scale 0.6% full scale 0.8% full scale A/D conversion data 16-bit binary (4-digit hexadecimal) Full scale for –10 to 10 V: E890 to 1770 hex Full scale for other ranges: 0000 to 2EE0 hex 16-bit binary (4-digit hexadecimal) Full scale for −10 to 10 V: F448 to 0BB8 hex Full scale for other ranges: 0000 to 1770 hex Averaging function Supported Supported (Settable for individual inputs via DIP switch) Open-circuit detection function Supported Analog Output Section Number of outputs CP1W-MAD42: 2 outputs (2 words allocated) CP1W-MAD44: 4 outputs (4 words allocated) 1 output (1 word allocated) Output signal range 1 to 5 VDC, 0 to 10 VDC, or −10 to 10 VDC 0 to 20 mA or 4 to 20 mA 1 to 5 VDC, 0 to 10 VDC, or −10 to 10 VDC, 0 to 20 mA or 4 to 20 mA Allowable external output load resistance 2 kΩ min. 350 Ω max. 1 kΩ min. 600 Ω max. External output impedance 0.5 Ω max. --- 0.5 Ω max. --- Resolution 1/12000 (full scale) 1/6000 (full scale) Overall accuracy 25°C 0.3% full scale 0.4% full scale 0 to 55°C 0.7% full scale 0.8% full scale Set data (D/A conversion) 16-bit binary (4-digit hexadecimal) Full scale for −10 to 10 V: E890 to 1770 hex Full scale for other ranges: 0000 to 2EE0 hex 16-bit binary (4-digit hexadecimal) Full scale for −10 to 10 V: F448 to 0BB8 hex Full scale for other ranges: 0000 to 1770 hex Conversion time CP1W-MAD42: 1 ms/point (6 ms/all points) CP1W-MAD44: 1 ms/point (8 ms/all points) 2 ms/point (6 ms/all points) Isolation method Photocoupler isolation between analog I/O terminals and internal circuits. No isolation between analog I/O signals. Current consumption CP1W-MAD42: 5 VDC: 120 mA max., 24 VDC: 120 mA max. CP1W-MAD44: 5 VDC: 120 mA max., 24 VDC: 170 mA max. 5 VDC: 83 mA max., 24 VDC: 110 mA max.Item CP1W-TS001 CP1W-TS002 CP1W-TS101 CP1W-TS102 Temperature sensors Thermocouples Platinum resistance thermometer Switchable between K and J, but same type must be used for all inputs. Switchable between Pt100 and JPt100, but same type must be used for all inputs. Number of inputs 2424 Allocated input words 2424 Accuracy (The larger of ±0.5% of converted value or ±2°C) ±1 digit max. * (The larger of ±0.5% of converted value or ±1°C) ±1 digit max. Conversion time 250 ms for 2 or 4 input points Converted temperature data 16-bit binary data (4-digit hexadecimal) Isolation Photocouplers between all temperature input signals Current consumption 5 VDC: 40 mA max., 24 VDC: 59 mA max. 5 VDC: 54 mA max., 24 VDC: 73 mA max. Setting CP1W-TS001/TS002 CP1W-TS101/TS102 Input type Range (°C) Range (°F) Input type Range (°C) Range (°F) K −200 to 1,300 −300 to 2,300 Pt100 −200.0 to 650.0 −300.0 to 1,200.0 J −100 to 850 −100 to 1,500 --- 4 to F --- Cannot be set. ---
- Main Specifications * 1 Accuracy for a K-type sensor at -100°C or less is ±4°C ±1 digit max. * 2 Accuracy for a K-type sensor at -100°C or less is ±10°C ±1 digit max. DIP Switch Settings The DIP switch is used to set the input type (temperature or analog input), the input thermocouple type (K or J) and the temperature unit (°C or °F). Note: Set the temperature range according to the type of temperature sensor connected to the Unit. Temperature data will not be converted correctly if the temperature range does not match the sensor. Item CP1W-TS003 Temperature sensors Thermocouples or analog input Switchable between K and J, but same type must be used for all inputs. Number of inputs Thermocouples inputs :4 , Analog inputs :2 Two analog inputs can be shared with thermocouples inputs. Accuracy at 25°C Thermocouple inputs (The larger of ±0.5% of converted value or ±2°C) ±1 digit max. *1 Analog voltage inputs 0.5% full scale Analog inputs 0.6% full scale Accuracy at 0 to 55°C Thermocouple inputs (The larger of ±1% of converted value or ±4°C) ±1 digit max. *2 Analog voltage inputs 1.0 % full scale Analog inputs 1.2 % full scale Input signal range Analog voltage inputs 0 to 10V/1 to 5V Analog inputs 4 to 20mA Resolution Thermocouple inputs 0.1°C or 0.1°F Analog inputs 1/12000 (full scale) Max. rated input Analog voltage inputs ±15V Analog inputs ±30mA External input impedance Analog voltage inputs 1MΩ min. Analog inputs Approx. 250Ω Open-circuit detection function Supported Averaging function Unsupported Conversion time 250 ms for 4 input points Converted temperature data 16-bit binary data (4-digit hexadecimal) Converted AD data 16-bit binary data (4-digit hexadecimal) Isolation Photocouplers between any two input signals Current consumption 5 VDC: 70 mA max., 24 VDC: 30 mA max. SW Setting
1 Thermocouple type of temperature
2 Temperature unit
ON °F OFF °C 3N C
4 Input type selection for the third input
(Input 2) ON Analog input OFF Thermocouple
5 Input type selection for the fourth
input (Input 3) ON Analog input OFF Thermocouple
6 Analog input signal range
Input type Range (°C) Range (°F) K -200.0 to 1300.0 -300 to 2300 J -100.0 to 850.0 -100.0 to 1500 ON 1 2 3 4 5 6 OFF SW
- Main Specifications * 1 Accuracy for a K-type sensor at -100°C or less is ±4°C ±1 digit max. * 2 Accuracy for a K-type sensor at -100°C or less is ±10°C ±1 digit max. DIP Switch Settings The DIP switch is used to set the temperature unit and to set the temperature input range. Note: Set the temperature range according to the type of temperature sensor connected to the Unit. Temperature data will not be converted correctly if the temperature range does not match the sensor.
- CompoBus/S I/O Link Unit Item CP1W-TS004 Temperature sensors Thermocouples Switchable between K and J, but same type must be used for all inputs. Number of inputs 12 (2 input words and 1 output word allocated) Accuracy 25°C (The larger of ±0.5% of converted value or ±2°C) ±1 digit max. *1 0 to 55°C (The larger of ±1% of converted value or ±4°C) ±1 digit max. *2 Conversion time 500 ms for 12 input points Converted temperature data 16-bit binary data (4-digit hexadecimal) 2-decimal-place mode is not supported Isolation Photocouplers between any two input signals Current consumption 5 VDC: 80 mA max., 24 VDC: 50 mA max. SW Setting
1 Input type
ON °F OFF °C Temperature input Input type Range (°C) Range (°F) K -200.0 to 1300.0 -300 to 2300 J -100.0 to 850.0 -100.0 to 1500 Model number CP1W-SRT21 Master/slave CompoBus/S Slave Number of I/O points 8 input points, 8 output points Number of words allocated in CPU Unit I/O memory 1 input word, 1 output word Node number setting Set using the DIP switch (Set before turning on the CPU Unit’s power supply.) ON 1 2 OFF SW
An analog option board can be added to the CP1E-N/NA@@. Note: 1. Can be used for the CP1E-N/NA@@ version 1.2 or later. 2. Analog boards can not be used for E@@-type and N@@S(1)-type. Specifications of Analog Option Board
- CP1W-ADB21 ●CP1W-DAB21V
- CP1W-MAB221 CP1E N30/40/60 or NA20 CPU Unit CP1W-DAB21V Analog Output Option Board CP1W-MAB221 Analog Input/Output Option Board CP1W-ADB21 Analog Input Option Board Built-in RS-232C port Item Specifications Voltage Input Current Input Input signal range 0 to 10 VDC 0 to 20 mA Max. rated input 0 to 15 VDC 0 to 30 mA External input impedance 200 kΩ min. Approx. 250 Ω Resolution 1/4000 (full scale) 1/2000 (full scale) Overall accuracy 25°C 0.5% full scale 0.6% full scale 0 to 55°C 1.0% full scale 1.2% full scale A/D conversion data 0000 to 0FA0 Hex 0000 to 07D0 Hex Averaging function None Isolation method No isolation between analog I/O terminals and internal circuits. Current consumption 5 VDC: 20 mA max. Item Specifications Voltage Output Current Output Output signal range 0 to 10 VDC --- External output allowable load resistance 2 kΩ min. --- External output impedance 0.5 Ω max. --- Resolution 1/4000 (full scale) --- Overall accuracy 25°C 0.5% full scale --- 0 to 55°C 1.0% full scale --- Set data (D/A conversion) 0000 to 0FA0 Hex --- Isolation method No isolation between analog I/O terminals and internal circuits. Current consumption 5 VDC: 60 mA max. Item Specifications Voltage I/O Current I/O Analog Input Section Input signal range 0 to 10 VDC 0 to 20 mA Max. rated input 0 to 15 VDC 0 to 30 mA External input impedance 200 kΩ min. Approx. 250 Ω Resolution 1/4000 (full scale) 1/2000 (full scale) Overall accuracy 25°C 0.5% full scale 0.6% full scale 0 to 55°C 1.0% full scale 1.2% full scale A/D conversion data 0000 to 0FA0 Hex 0000 to 07D0 Hex Averaging function None Analog Output Section Output signal range 0 to 10 VDC --- External output allowable load resistance 2 kΩ min. --- External output impedance 0.5 Ω max. --- Resolution 1/4000 (full scale) --- Overall accuracy 25°C 0.5% full scale --- 0 to 55°C 1.0% full scale --- Set data (D/A conversion) 0000 to 0FA0 Hex --- Isolation method No isolation between analog I/O terminals and internal circuits. Current consumption 5 VDC: 80 mA max.
Analog Option Board Refresh Time Analog Opiton Board Cycle time 1 ms 10 ms 20 ms CP1W-ADB21 40 ms ±30% 50 ms ±30% 80 ms ±30% CP1W-DAB21V 30 ms ±40% 40 ms ±50% 70 ms ±40% CP1W-MAB221(AD) 60 ms ±40% 80 ms ±60% 100 ms ±50% CP1W-MAB221(DA) 40 ms ±80% 60 ms ±60% 90 ms ±50%
The CP1E CPU Units provide the following external interfaces. E14/20S CPU Units Note: Terminal Block (Fixed) Note: Terminal Block (Fixed) E30/40/60S CPU Units N30/40/60S(1) CPU Units E@@S-type N @@S(1)-type * N@@S1-type only. E10/14/20 CPU Units N14/20 CPU Units E@@-type N@@-type E30/40 CPU Units N30/40/60 or NA20 CPU Units E@@-type N@@-type/NA-type Output terminal block Input terminals Ground terminal Output indicators Power supply input terminals Output terminals Input indicators Peripheral USB port Operation indicators Input terminal block Output terminal block Ground terminal Output indicators Expansion I/O Unit connector Output terminalsExternal power supply Input terminal block Input indicators Peripheral USB port Operation indicators Power supply input terminals Input terminals Built-in RS-232C communications status indicator Built-in RS-485 communications status indicator * Built-in RS-232C port Built-in RS-485 port Battery cover Input terminal block Output terminal block Power supply input terminals Input terminals Output terminals Ground terminal Input indicators Output indicators Peripheral USB port Analog adjusters Operation indicators Battery cover Built-in RS-232C port Built-in RS-232C communications status indicator Input terminal block Output terminal block Power supply input terminals Input terminals Output terminalsExternal power supply Ground terminal Input indicators Output indicators Peripheral USB port Analog adjusters Operation indicators Expansion I/O Unit connector Serial Option Board slot Built-in RS-232C communications status indicator Battery cover Built-in RS-232C port Analog input terminal (NA-type only) Analog output terminals (NA-type only)
Serial Communications Port for N/NA@@(S@)-type CPU Units The Serial Communication Port can be used for a CP1E N/NA@@(S@)-type CPU Unit. N30/40/60 or NA20 CPU Units One built-in RS-232C port and one Option Board can be used. Note: Option Boards cannot be used for CP1E N14/20 CPU Units. N30/40/60S1 CPU Units N30/40/60S CPU Units Built-in RS-232C, RS-485 ports. Built-in RS-232C port. N14/20 CPU Units Built-in RS-232C ports. Built-in RS-232C Built-in RS-2485 Built-in RS-232C CP1W-CIF11/CIF12-V1 RS-422A/485 Option Board CP1W-CIF01 RS-232C Option Board Built-in RS-232C port CP1W-CIF41 Ethernet Option Board version 2.0 or higher IP ADDRESS: SUBNET MASK: COMM ERR 10BASE-T 100BASE-TX Optional Serial Communication Board Note: The Optional Serial Communication Board cannot be used for CP1E N/NA@@S(1)-type CPU Units and E@@-type CPU Units. Model number Port Maximum transmission distance Connection method CP1W-CIF01 One RS-232C port 15 m Connector (D-sub, 9 pin female) CP1W-CIF11 One RS-422A/485 port (not isolated) 50 m Terminal block (using ferrules) CP1W-CIF12-V1 One RS-422A/485 port (isolated) 500 m Terminal block (using ferrules) CP1W-CIF41 One Ethernet port 100 m Connector (RJ45, 8 pin modular) Built-in RS-232C port
Built-in RS-232C Port and CP1W-CIF01 RS-232C Option Board Built-in RS-232C Port (2-wire sensors) (N@@S1-type only) CP1W-CIF11/CIF12-V1 RS-422A/485 Option Board COMM Front Back Communications Status Indicator RS-232 Connector CPU Unit Connector Pin Abbreviation for signal name Signal name Signal direction N@@-type built-in RS-232C port / CP1W-CIF01 N@@S(1)-type Buit-in RS-232C port
1 FG Frame ground --
2 SD (TXD) Send data Output
3 RD (RXD) Receive data Input
4R S ( R T S ) R e quest to send Output
5 CS (CTS) Clear to send Input
7 DR (DSR) NC * Data set ready Input
8 ER (DTR) NC * Data terminal ready Output
9 SG (0 V) Signal ground --
- Built-in RS-232C port of N@@S(1)-type does not support DR/ER. CJ1W-CIF11 cannot be used for the built-in RS-232C port of N@@S(1)-type.
- RS-232C Connector
- DIP Switch for Terminating Resistance Settings Settings ON ON (both ends) Terminating resistance selection Resistance: Approx. 220ΩOFF OFF
- RS-485 Terminal Block DIP Switch COMM Front Back Communications Status Indicator DIP Switch for Operation Settings RS-422A/485 Connector RDA- RDB+ SDA- SDB+ FG CPU Unit Connector
- RS-422A/485 Terminal Block RDB+ RDA- SDA- SDB+ FG Tighten the terminal block screws to a torque of 0.28 N·m.
CP1W-CIF41 Ethernet Option Board version 2.0 or higher
- Specifications ●FINS Communications Service Specifications Connecting to Support Software Connecting Methods Using commercially available USB cable, connect the CX-Programmer to the peripheral USB port on the CPU Unit. Host link connection can be made with RS-232C port to connect the Programming Device (CX-Programmer). IP ADDRESS: SUBNET MASK: COMM ERR 10BASE-T 100BASE-TX Front Rear Label Attach the label here to show IP address and subnet mask. Ethernet Connector Used to connect the Ethernet twisted-pair cable. LED Indicators Display the operating status of the Option Board. CPU Unit connector Type 100/10Base-TX (Auto-MDIX) Support Software CX-Programmer version 9.12 or higher Transfer Media access method CSMA/CD Modulation method Baseband Transmission paths Star form Baud rate
100 Mbit/s
(100Base-TX)
10 Mbit/s
(10Base-TX)
- Half/full auto-negotiation for each port
- Link speed auto-sensing for each port Transmission media
- Unshielded twisted-pair (UDP) cable Categories: 5, 5e
- Shielded twisted- pair (STP) cable Categories: 100Ω at 5, 5e
- Unshielded twisted-pair (UDP) cable Categories: 3, 4, 5, 5e
- Shielded twisted- pair (STP) cable Categories: 100 Ω at 3, 4, 5, 5e Transmission Distance 100 m (distance between hub and node) Number of cascade connections No restrictions if switching hubs are used. Number of nodes 254 Message Length 552 bytes max. Date Length 540 bytes max. (except for FINS header 10 byte and Command header 2 byte.) Number of buffer 8k byte Protocol name FINS/UDP method FINS/TCP method Protocol used UDP/IP TCP/IP The selection of UDP/IP or TCP/IP is made from the FINS/TCP Tab by the Web browser function. Server/Client Only server (Cannot be used as a client) Number of connections --- 2 Port number 9600 (default) Can be changed. 9600 (default) Can be changed. Protection No Yes (Specification of client IP addresses when unit is used as a server) USB port A connector Commercially available USB cable Peripheral USB port (Conforming to USB 2.0, B connector) B connector CP1E CPU Unit CX-Programmer
Use the following cable to connect the CP1E CPU Unit to the computer running the Support Software. USB port RS-232C Port for N/NA@@(S@)-type CPU Units Note: Connectable with CX-Programmer Ver.9.1 or higher only. * Use the USB-Serial Conversion Cable CS1W-CIF31 together to connect a PLC to a personal computer's USB port. Port at Unit Port at computer Network type (communications mode) Model numbers Length Peripheral USB port (Conforming to USB 2.0, B connector) USB port USB 2.0 (or 1.1) Commercially available USB cable (A connector - B connector) Less than 5 m Port at Unit Port at computer Communications mode Connecting Cable Model Length Remarks RS-232C Port or CP1W-CIF01 (Add this to the option board slot.) RS-232C port * Host Link (SYSWAY) XW2Z-200S-CV 2m With anti-static connectors XW2Z-500S-CV 5m With anti-static connectors XW2Z-200S-V 2m --- XW2Z-500S-V 5m ---
Sequence Input Instructions Sequence Output Instructions Sequence Output Instructions Timer and Counter Instructions Comparison Instructions Data Movement Instructions Instruction Mnemonic LOAD LD LOAD NOT LD NOT AND AND AND NOT AND NOT OR OR OR NOT OR NOT AND LOAD AND LD OR LOAD OR LD NOT NOT CONDITION ON UP CONDITION OFF DOWN Instruction Mnemonic OUTPUT OUT OUTPUT NOT OUT NOT KEEP KEEP DIFFERENTIATE UP DIFU DIFFERENTIATE DOWN DIFD SET SET RESET RSET MULTIPLE BIT SET SETA MULTIPLE BIT RESET RSTA SINGLE BIT SET SETB SINGLE BIT RESET RSTB Instruction Mnemonic END END NO OPERATION NOP INTERLOCK IL INTERLOCK CLEAR ILC MULTI-INTERLOCK DIFFERENTIATION HOLD MILH MULTI-INTERLOCK DIFFERENTIATION RELEASE MILR MULTI-INTERLOCK CLEAR MILC JUMP JMP JUMP END JME CONDITIONAL JUMP CJP FOR LOOP FOR BREAK LOOP BREAK NEXT LOOP NEXT Instruction Mnemonic TIMER TIM TIMX COUNTER CNT CNTX HIGH-SPEED TIMER TIMH TIMHX ONE-MS TIMER TMHH TMHHX ACCUMULATIVE TIMER TTIM TTIMX LONG TIMER TIML TIMLX REVERSIBLE COUNTER CNTR CNTRX RESET TIMER/COUNTER CNR CNRX Instruction Mnemonic Input Comparison Instructions (unsigned) LD,AND,OR+= LD,AND,OR+<> LD,AND,OR+< LD,AND,OR+<= LD,AND,OR+> LD,AND,OR+>= Input Comparison Instructions (double, unsigned) LD,AND,OR+=+L LD,AND,OR+<>+L LD,AND,OR+<+L LD,AND,OR+<=+L LD,AND,OR+>+L LD,AND,OR+>=+L Input Comparison Instructions (signed) LD,AND,OR+=+S LD,AND,OR+<>+S LD,AND,OR+<+S LD,AND,OR+<=+S LD,AND,OR+>+S LD,AND,OR+>=+S Input Comparison Instructions (double, signed) LD,AND,OR+=+SL LD,AND,OR+<>+SL LD,AND,OR+<+SL LD,AND,OR+<=+SL LD,AND,OR+>+SL LD,AND,OR+>=+SL Time Comparison Instructions =DT <>DT <DT <=DT >DT >=DT COMPARE CMP DOUBLE COMPARE CMPL SIGNED BINARY COMPARE CPS DOUBLE SIGNED BINARY COMPARE CPSL TABLE COMPARE TCMP UNSIGNED BLOCK COMPARE BCMP AREA RANGE COMPARE ZCP DOUBLE AREA RANGE COMPARE ZCPL Instruction Mnemonic MOVE MOV DOUBLE MOVE MOVL MOVE NOT MVN MOVE BIT MOVB MOVE DIGIT MOVD MULTIPLE BIT TRANSFER XFRB BLOCK TRANSFER XFER BLOCK SET BSET DATA EXCHANGE XCHG SINGLE WORD DISTRIBUTE DIST DATA COLLECT COLL
Increment/Decrement Instructions Symbol Math Instructions Conversion Instructions Logic Instructions Special Math Instructions Floating-point Math Instructions Table Data Processing Instructions Data Control Instructions Instruction Mnemonic SHIFT REGISTER SFT REVERSIBLE SHIFT REGISTER SFTR WORD SHIFT WSFT ARITHMETIC SHIFT LEFT ASL ARITHMETIC SHIFT RIGHT ASR ROTATE LEFT ROL ROTATE RIGHT ROR ONE DIGIT SHIFT LEFT SLD ONE DIGIT SHIFT RIGHT SRD SHIFT N-BITS LEFT NASL DOUBLE SHIFT N-BITS LEFT NSLL SHIFT N-BITS RIGHT NASR DOUBLE SHIFT N-BITS RIGHT NSRL Instruction Mnemonic INCREMENT BINARY ++ DOUBLE INCREMENT BINARY ++L DECREMENT BINARY -- DOUBLE DECREMENT BINARY --L INCREMENT BCD ++B DOUBLE INCREMENT BCD ++BL DECREMENT BCD --B DOUBLE DECREMENT BCD --BL Instruction Mnemonic SIGNED BINARY ADD WITHOUT CARRY + DOUBLE SIGNED BINARY ADD WITHOUT CARRY +L SIGNED BINARY ADD WITH CARRY +C DOUBLE SIGNED BINARY ADD WITH CARRY +CL BCD ADD WITHOUT CARRY +B DOUBLE BCD ADD WITHOUT CARRY +BL BCD ADD WITH CARRY +BC DOUBLE BCD ADD WITH CARRY +BCL SIGNED BINARY SUBTRACT WITHOUT CARRY - DOUBLE SIGNED BINARY SUBTRACT WITHOUT CARRY -L SIGNED BINARY SUBTRACT WITH CARRY -C DOUBLE SIGNED BINARY SUBTRACT WITH CARRY -CL BCD SUBTRACT WITHOUT CARRY -B DOUBLE BCD SUBTRACT WITHOUT CARRY -BL BCD SUBTRACT WITH CARRY -BC DOUBLE BCD SUBTRACT WITH CARRY -BCL SIGNED BINARY MULTIPLY * DOUBLE SIGNED BINARY MULTIPLY *L BCD MULTIPLY *B DOUBLE BCD MULTIPLY *BL SIGNED BINARY DIVIDE / DOUBLE SIGNED BINARY DIVIDE /L BCD DIVIDE /B DOUBLE BCD DIVIDE /BL Instruction Mnemonic BCD-TO-BINARY BIN DOUBLE BCD-TO-DOUBLE BINARY BINL BINARY-TO-BCD BCD DOUBLE BINARY-TO-DOUBLE BCD BCDL 2’S COMPLEMENT NEG DATA DECODER MLPX DATA ENCODER DMPX ASCII CONVERT ASC ASCII TO HEX HEX Instruction Mnemonic LOGICAL AND ANDW DOUBLE LOGICAL AND ANDL LOGICAL OR ORW DOUBLE LOGICAL OR ORWL EXCLUSIVE OR XORW DOUBLE EXCLUSIVE OR XORL COMPLEMENT COM DOUBLE COMPLEMENT COML Instruction Mnemonic ARITHMETIC PROCESS APR BIT COUNTER BCNT Instruction Mnemonic FLOATING TO 16-BIT FIX FLOATING TO 32-BIT FIXL 16-BIT TO FLOATING FLT 32-BIT TO FLOATING FLTL FLOATING-POINT ADD +F FLOATING-POINT SUBTRACT -F FLOATING-POINT DIVIDE /F FLOATING-POINT MULTIPLY *F Floating Symbol Comparison LD, AND, OR+=F LD, AND, OR+<>F LD, AND, OR+<F LD, AND, OR+<=F LD, AND, OR+>F LD, AND, OR+>=F FLOATING- POINT TO ASCII FSTR ASCII TO FLOATING-POINT FVAL Instruction Mnemonic SWAP BYTES SWAP FRAME CHECKSUM FCS Instruction Mnemonic PID CONTROL WITH AUTOTUNING PIDAT TIME-PROPORTIONAL OUTPUT TPO SCALING SCL SCALING 2 SCL2 SCALING 3 SCL3 AVERAGE AVG
Interrupt Control Instructions High-speed Counter and Pulse Output Instructions Step Instructions I/O Unit Instructions Serial Communications Instructions Clock Instructions Failure Diagnosis Instructions Other Instructions Instruction Mnemonic SUBROUTINE CALL SBS SUBROUTINE ENTRY SBN SUBROUTINE RETURN RET Instruction Mnemonic SET INTERRUPT MASK MSKS CLEAR INTERRUPT CLI DISABLE INTERRUPTS DI ENABLE INTERRUPTS EI Instruction Mnemonic MODE CONTROL INI HIGH-SPEED COUNTER PV READ PRV COMPARISON TABLE LOAD CTBL SPEED OUTPUT SPED SET PULSES PULS PULSE OUTPUT PLS2 ACCELERATION CONTROL ACC ORIGIN SEARCH ORG PULSE WITH VARIABLE DUTY FACTOR PWM Instruction Mnemonic STEP DEFINE STEP STEP START SNXT Instruction Mnemonic I/O REFRESH IORF 7-SEGMENT DECODER SDEC DIGITAL SWITCH INPUT DSW MATRIX INPUT MTR 7-SEGMENT DISPLAY OUTPUT 7SEG Instruction Mnemonic TRANSMIT TXD RECEIVE RXD Instruction Mnemonic CALENDAR ADD CADD CALENDAR SUBTRACT CSUB CLOCK ADJUSTMENT DATE Instruction Mnemonic FAILURE ALARM FAL SEVERE FAILURE ALARM FALS Instruction Mnemonic SET CARRY STC CLEAR CARRY CLC EXTEND MAXIMUM CYCLE TIME WDT
Dimensions (Unit: mm) CP1E CPU Unit
- CPU Units with 10 I/O Points
- CPU Units with 14 or 20 I/O Points CP1E-@14/20D@@-@ CP1E-@14/20SD@@-@
- CPU Units with 30 I/O Points CPU Units with 20 I/O Points and Built-in Analog 110 100 90 Two, 4.5 dia. 90100 110 Two, 4.5 dia. 90100 110 78.6 Two, 4.5 dia. 90100 130 120 110 Four, 4.5 dia.
CP1E-@30S(1)D@@-@
- CPU Units with 40 I/O Points CP1E-@40D@@-@ CP1E-@40S(1)D@@-@
- CPU Units with 60 I/O Points CP1E-N60D@-@ 78.6 90100 130 120 110 Four, 4.5 dia. 90100 Four, 4.5 dia. 150 140 110 78.6 90100 150 140 110 Four, 4.5 dia. 110 100 90 185 195 Four, 4.5 dia.
CP1E-@60S(1)D@@-@ Expansion I/O Units and Expansion Units
- CP1W-8E@@/CP1W-SRT21
- CP1W-20ED@/CP1W-16E@@/CP1W-AD04@/CP1W-DA021/CP1W-DA04@/CP1W-MAD@@/
- CP1W-40ED@/CP1W-32E@@/CP1W-TS004 78.6 90100 195 185 110 Four, 4.5 dia. 5066 56±0.2 100±0.2 Two, 4.5 dia. 5086 76±0.2 100±0.2 Two, 4.5 dia. Four, 4.5 dia. 90 100 110 140 150
Manual name Cat. No. Model numbers Application Contents SYSMAC CP Series CP1E CPU Unit Hardware Manual W479 CP1E-E@@SD@-@ CP1E-E@@D@-@ CP1E-N@@D@-@ CP1E-NA@@D@-@ To learn the hardware specifications of the CP1E PLCs Describes the following information for CP1E PLCs.
- Overview and features
- Basic system configuration
- Part names and functions
- Installation and settings
- Troubleshooting Use this manual together with the CP1E CPU Unit Software Manual (Cat. No. W480) and CP1E CPU Unit Instructions Reference Manual (Cat. No. W483). SYSMAC CP Series CP1E CPU Unit Software Manual W480 CP1E-E@@SD@-@ CP1E-E@@D@-@ CP1E-N@@D@-@ CP1E-NA@@D@-@ To learn the software specifications of the CP1E Describes the following information for CP1E PLCs.
- CPU Unit operation
- Internal memory
- Programming
- Settings
- CPU Unit built-in functions
- Interrupts
- High-speed counter inputs
- Pulse outputs
- Se rial communications
- Analog I/O function
- Other functions Use this manual together with the CP1E CPU Unit Hardware Manual (Cat. No. W479) and CP1E CPU Unit Instructions Reference Manual (Cat. No. W483). SYSMAC CP Series CP1E CPU Unit Instructions Reference Manual W483 CP1E-E@@SD@-@ CP1E-E@@D@-@ CP1E-N@@D@-@ CP1E-NA@@D@-@ To learn programming instructions in detail Describes each programming instruction in detail. When programming, use this manual together with the CP1E CPU Unit Hardware Manual (Cat. No. W479) and CP1E CPU Unit Software Manual (Cat. No. W480). CS/CJ/CP/NSJ Series Communications Commands Reference Manual W342 CS1G/H-CPU@@H CS1G/H-CPU@@-V1 CS1D-CPU@@HA CS1D-CPU@@SA CS1D-CPU@@H CS1D-CPU@@S CS1W-SCU@@-V1 CS1W-SCB@@-V1 CJ1G/H-CPU@@H CJ1G-CPU@@P CJ1M-CPU@@ CJ1G-CPU@@ CJ1W-SCU@@-V1 To learn communications commands for CS/CJ/CP/NSJ-series Controllers in detail Describes 1) C-mode commands and 2) FINS commands in detail. Read this manual for details on C-mode and FINS commands addressed to CPU Units. Note: This manual de scribes commands addressed to CPU Units. It does not cover commands addressed to other Units or ports (e.g., serial communications ports on CPU Units, communications ports on Serial Communications Units/Boards, and other Communications Units). SYSMAC CP Series CP1L/CP1E CPU Unit Introduction Manual W461 CP1L-L10D@-@ CP1L-L14D@-@ CP1L-L20D@-@ CP1L-M30D@-@ CP1L-M40D@-@ CP1L-M60D@-@ CP1E-E@@D@-@ CP1E-N@@D@-@ CP1E-NA@@D@-@ To learn the basic setup methods of the CP1L/CP1E PLCs Describes the following information for CP1L/CP1E PLCs.
- Basic configuration and component names
- Mounting and wiring
- Programming, data transfer, and debugging using the CX-Programmer
- Application program examples
Terms and Conditions Agreement Read and understand this catalog. Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranties. (a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron disclaims all other warranties, express or implied. (b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABL Y MEET THE REQUIREMENTS OF THEIR INTENDED USE. Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the non-complying Product, (ii) repair the non-complying Prod uct, or (iii) repay or credit Buyer an amount equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice, recommendations or infor mation given orally or in writing, are not to be construed as an amendment or addition to the above warranty. See http://www.omron.com/global/ or contact your Omron representative for published information. Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY , NEGLIGENCE OR STRICT LIABILITY . Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted. Suitability of Use. Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases. NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMR ON PRODUCT(S) IS PROPERL Y RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. Programmable Products. Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof. Performance Data. Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability. Change in Specifications. Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change part numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to confirm actual specifications of purchased Product. Errors and Omissions. Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical or proofreading errors or omissions.
Authorized Distributor: In the interest of product improvement, specifications are subject to change without notice. OMRON Corporation Industrial Automation Company OMRON ELECTRONICS LLC
2895 Greenspoint Parkway, Suite 200
Hoffman Estates, IL 60169 U.S.A. Regional Headquarters OMRON EUROPE B.V. Wegalaan 67-69, 2132 JD Hoofddorp The Netherlands Contact: www.ia.omron.com Kyoto, JAPAN OMRON ASIA PACIFIC PTE. LTD. 438B Alexandra Road, #08-01/02 Alexandra Technopark, Singapore 119968 Tel: (65) 6835-3011/Fax: (65) 6835-2711 OMRON (CHINA) CO., LTD. Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200 Note: Do not use this document to operate the Unit. Cat. No. P061-E1-13 0422 (0309) © OMRON Corporation 2009-2022 All Rights Reserved. CSM_17_4