CNS650-M ADVANCEDENERGY | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 11
Technical content
©2022 Advanced Energy Industries, Inc. ARTESYN CNS650-M SERIES
650 W AC-DC Power Supplies
Total Power: 650 W Input Voltage: 90 to 264 VAC # of Outputs: Single AT A GLANCEAdvanced Energy's Artesyn CNS650-MU series of single output open-frame AC-DC power supplies are offered 12 V, 24 V, or 48 V outputs with +15% trim range. Each power supply comes with a 12 V fan output and 5 V standby. All models feature ITE and medical safety approvals and accept a universal input of 90 to 264 VAC. Depending on operating conditions, its 4'' x 6'' x 1.54'' compact and high density "U-Channel" construction delivers up to 400 W of output power with free air convection cooling and up to 650 W with 400 LFM of forced air. These power supplies are ideal for industrial systems as well as for medical applications. SPECIAL FEATURES Designed for forced air and natural convection cooling Medical and ITE safety approvals, 2x MOPP PMBus® interface Active current share with OR-ing FET Dual fused Type BF ready Active Power Factor Correction, 61000-3-2 compliant Built-in Class B EMI filter Less than 1U high 4" x 6" U-channel construction (open-frame or end-fan variants available for 12 V) <500 mW no-load power consumption 80 PLUS® certified (-ME model) Three year warranty (consult factory for extended terms) SAFETY UL+CUL ES 60601-1 UL 60601-1 UL 62368-1 TÜV EN 60601-1 DEMKO EN 62368-1 CB IEC 60950-1 IEC 60601-1 IEC 62368-1 CCC GB4943.1/GB9254 GB17625.1 CE LVD, RoHS UKCA Mark ** CNS650-M tested according to the medical standard IEC 60601-1-2 4th Edition.
2 advancedenergy.com CNS650-M ELECTRICAL SPECIFICATIONS ENVIRONMENTAL SPECIFICATIONS Input Input voltage ra nge 90 to 264 VAC or 127 to 350 VDC Frequency 47 to 63 Hz (360 to 440 Hz with higher leakage) Inrush current 50 Apk, cold start Leakage current <300 µA (using UL test method) No load power < 500 mW Output Maximum power 650 W, forced-air cooling (750 W peak)
400 W, free-air natural convection cooling (650 W peak)
Adjustment range -0% to +15% Holdup time 20 ms @ 400 W Fan output 12 V @ 1.0 A (forced air) 12 V @ 0.5 A (natural convection) Standby output 5 V @ 2.0 A (forced air) 5 V @ 1.0 A (natural convection) Control and Protection Serial bus interface PMBus® Current share Active Remote sense 2-wire (+ and -) Remote inhibit Pull inhibit low = main & fan output OFF (5 V standby is ON) Pull inhibit high (or floating) = all outputs ON AC OK Active high when normal AC input is present (with internal 10 kOhm pull up to 3.3 V) DC OK Active high when main O/P is within regulation (with internal 10 kOhm pull up to 3.3 V) Smart fan control Monitor, control and override Overvoltage protection Latch (AC recyle or inhibit toggle required for PSU restart) Overload protection Auto-recovery (constant current mode down to 50% Vout) Overtemperature protection Auto-recovery with hysteresis Operating temperature -20 °C to +80 °C (derate at 50 °C), startup at -40 °C Storage temperature -40 °C to +85 °C Operating humidity 5% to 95% (non-condensing) Non-operating humidity 5% to 95% (non-condensing) Maximum altitude 5000 m (3000 m for medical), derating may apply
advancedenergy.com 3 CNS650-M Isolation 4000 VAC (input to output)
1500 VAC (input to PE, output to PE)
Line harmonics 61000-3-2, Class A ESD immunity 61000-4-2, ±15kV (air) / ±8kV (contact) - Criterion A Conducted EMI Level B, CISPR 22 and FCC Part 15 Radiated EMI Level B, CISPR 22 and FCC Part 15 (with cover) Surge immunity 61000-4-5, Level 3 - Criterion A, Level 4 - Criterion C Medical EMC 60601-1-2, Edition 4 (cover maybe required for some tests) MTBF (Telcordia, Issue 3, Method 1, Case 3) > 950 KHrs, 25 °C, 410 W natural convection > 1.3 MHrs, 25 °C, 650 W forced air Model Number Output Voltage Vout Adjust Range (-0% / +15%) Minimum Load Max. Continuous Load (Free Air) Max. Peak Load (Free Air) Max. Continuous Load (Forced Air) Max. Peak Load (Forced Air) Regulation Ripple (p-p) CNS653-ME 5, 6 12 V 12 - 13.8 V 0 A 54.2 A 62.5 A NA NA ±2% 120 mV CNS653-MF 1 Peak load current not to exceed 10 seconds, Ta = 50 °C. 2 Requires at least 400 LFM of airflow. 3 At 25 °C including factory setpoint, line voltage and load current variations. 4 Peak-to-peak ripple measured at the output terminal with 20 MHz bandwidth and 10 µF (tantalum capacitor) in parallel with 0.1 µF capacitor across the output. 5 Optional suffix “-ME” (end-fan) and “-MF: (open-frame) available on the 12 V output. 6 80 PLUS certified. OTHER SPECIFICATIONS
ORDERING INFORMATION
4 advancedenergy.com CNS650-M INPUT CONNECTIONS (-MU AND -MF SUFFIX) INPUT CONNECTIONS (-ME SUFFIX) OUTPUT CONNECTIONS Pin Function Power Supply Side System Side TB1 PE Dinkle EHK762V-03P Max Torque: 4kgf-cm Recommended Wire Size: AWG #22 to #14TB2 L2/Neutral TB3 L1/Line Pin Function Power Supply Side System Side BAR1 -Vout Output Terminal Screw: M4X8 (4X) Max Torque: 10kgf-cm Molex 19099-0032 or 19141-0063 for AWG #16 to #14 Molex 19099-0048 or 19141-0083 for AWG #12 to #10 BAR2 -Vout BAR3 +Vout BAR4 +Vout Pin Function Power Supply Side System Side IEC Inlet Input AC IEC 60320 C14 (Male) IEC Cord C13 (Female)
advancedenergy.com 5 CNS650-M OTHER OUTPUT AND CONTROL CONNECTIONS (CONNECTOR J304) FAN OUTPUT CONNECTOR FOR -MU, -MF SUFFIX (CONNECTOR J306) Pin Designation Description 1 5VSB +5 V Standby Output J304 20-Pin Connector (PSU Side): 2 5VSB +5 V Standby Output Landwin: 2052P20008T or 3 5VSB_GND +5 V Standby Output Return/Ground CviLux: CI0120P1HD0-LF
4 SCL Serial Clock Signal (I2C)
5 A0 EEPROM Address Recommended Mating Connectors:
6 SDA Serial Data Signal (I2C) CviLux: CI0120SD000 (housing)
7 I_SHARE Active Current Share CI01TD21PE0 (contact pins)
8 SYS_GND Return Ground for Signals and I2C Landwin: 2050S2000 (housing)
9 12VFAN 12 V Fan Output 2053T021V (contact pins)
10 REMOTE INHIBIT Output Inhibit Pin (Main Output) JST: PHDR-20VS (housing)
11 FAN_RTN 12 V Fan Output Return/Ground SPHD-001T-P0.5 (contact pins)
12 VIN_GOOD Input Line OK Signal
13 FAN_PWM1 FAN PWM
14 PWOK Output Power OK Signal See ACCESSORIES Section
15 FAN_TACH1 Fan1 Tacho Signal
16 FAN_OVERRIDE External Fan Sensor for Override
17 FAN_FAIL Fain Fail Signal
18 FAN_FAULT_EN FAN Fault Enable Due to Low RPM
19 REMOTE_SENSE+ Positive Remote Sense
20 REMOTE_SENSE- Remote Sense Return
1 12VFAN 12 V fan output J306 4-Pin Connector (PSU Side):
2 FAN_RTN 12 V fan return CviLux: CI0104P1HK0-LF
3 FAN_PWM1 Fan PWM Landwin: 2003P0401V
4 FAN_TACH1 Fan1 tacho signal Recommended Mating Connectors:
CviLux: CI0104S0000 (housing) CviLux: CI01T01MPP0 (contact pins) Landwin: 2001S0400 (housing) Landwin: 2005T011R (contact pins)
6 advancedenergy.com CNS650-M MECHANICAL DRAWINGS (“-MU” SUFFIX FOR U-BASE CONSTRUCTION/12 V, 24 V AND 48 V) INPUT CONNECTOR DINKLE EHK762V-03P TORQUE: 4kgf-cm MAX. PEM F-M3-1 (2X) 2.5 mm max penetration depth from face of side chassis J304 OUTPUT TERMINALS SCREW M4X8 (4X) TORQUE: 10kgf-cm MAX. 20-WAY SIGNAL CONNECTOR MODEL LABEL PEM F-M3-1 (2X) PEM F-M3-1 (4X) 120 30 (2X) 39.2 16.2 16.2 120 30 (2X) 39.2 0.5 26.2 100 (2X) 152.4 0.5 75 (2X) 13.3 101.6 0.5
1.9 REF
L N J306 FAN CONNECTOR L-0P VR408 TRIMPOT FOR OUTPUT ADJUSTABILITY COUNTER-CLOCKWISE: INCREASE OUTPUT VOLTAGE
3.0 MM MAX
Thermal Hot Spot Reference Component Temperature Limit (-MU) D1 (AC bridge diode) 105 °C L1 (PFC choke) 115 °C C40 (output cap) 100 °C L-output (output choke) 125 °C Do not exceed indicated temperature limits to ensure operation is within the component thermal derating limits. Measure the component temperatures using K type thermocouples. Unit weight (-MU suffix): 800 g
advancedenergy.com 7 CNS650-M MECHANICAL DRAWINGS (“-MF” SUFFIX FOR OPEN-FRAME CONSTRUCTION/12 V ONLY) Thermal Hot Spot Reference Component Temperature Limit (-MF) D1 (AC bridge diode) 120 °C L1 (PFC choke) 120°C C40 (output cap) 100 °C L-output (output choke) 125 °C Do not exceed indicated temperature limits to ensure operation is within the component thermal derating limits. Measure the component temperatures using K type thermocouples. Unit weight (-MF suffix): 650 g INPUT CONNECTOR DINKLE EHK762V-03P TORQUE: 4kgf-cm MAX. RoHS LABEL MODEL LABEL OUTPUT TERMINALS SCREW M4X8 (4X) TORQUE: 10kgf-cm MAX. 20-WAY SIGNAL CONNECTOR 4.5 141.9 152.4 0.5 43.9 1 12.7 1 88.8 4.5 143.4 4 88.3 96.8 0.5 34.1 0.5
2.5 REF
0.5 REF
TRIMPOT FOR OUTPUT ADJUSTABILITY COUNTER-CLOCKWISE: INCREASE OUTPUT VOLTAGE J306 FAN CONNECTOR J304 C40 PE L N
8 advancedenergy.com CNS650-M MECHANICAL DRAWINGS (“-ME” SUFFIX FOR END-FAN CONSTRUCTION/12 V ONLY) PEM F-M3-1 (2X) MODEL LABEL PEM F-M3-1 (2X) PEM F-M3-1 (4X) AC INLET OUTPUT TERMINALS SCREW M4X8 (4X) TORQUE: 10kgf-cm MAX. 20-WAY SIGNAL CONNECTOR 152.4 177.8 0.5 101.6 0.5
4.8 REF
(2X) 30 16.2120 16.2120 1.9 REF (2X) 30 40 0.5 13.3(2X) 75 26.2(2X) 100 55.8 J304 VR408 TRIMPOT FOR OUTPUT ADJUSTABILITY COUNTER-CLOCKWISE: INCREASE OUTPUT VOLTAGE
Figure 1. Output Power vs. Ambient Temperature at Natural Convection and Figure 2. Output Power vs. Input Line at Natural Convection and Forced Air Figure 3. Typical Efficiency for 12 V Output Figure 4. Typical Efficiency for 24 V Output Figure 5. Typical Efficiency for 48 V Output
400 LFM (MF/MU)
200 LFM (MF/MU)
115 VAC
230 VAC
Figure 6. Estimated Product Useful Life Based on C40 Case Temperature Figure 7. CNS653-ME (End Fan) Typical Audible Noise Level vs. Output Load at
10 advancedenergy.com CNS650-M ACCESSORIES Orderable Part Number Description Description 73-788-001 J304 (20 Pin) Mating Connector with 0.3 m wires attached PIN 20 PIN 2 PIN 19 PIN 1 PIN 3 300 ± 5 mm CNS-BBAR-KIT Output Bussbar Extension Kit for Vertical Wire Interface 73-769-002 USB to I C Adaptor for PMBus Communication
ENG-CNS650-M-235-01 4.20 For international contact information, visit advancedenergy .com. powersales@aei.com (Sales Support) productsupport.ep@aei.com (Technical Support) +1 888 412 7832 ABOUT ADVANCED ENERGY Advanced Energy (AE) has devoted more than three decades to perfecting power for its global customers. AE designs and manufactures highly engineered, precision power conversion, measurement and control solutions for mission-critical applications and processes. Our products enable customer innovation in complex applications for a wide range of industries including semiconductor equipment, industrial, manufacturing, telecommunications, data center computing, and medical. With deep applications know-how and responsive service and support across the globe, we build collaborative partnerships to meet rapid technological developments, propel growth for our customers, and innovate the future of power. Specifications are subject to change without notice. Not responsible for errors or omissions. ©2022 Advanced Energy Industries, Inc. All rights reserved. Advanced Energy®, AE® and Artesyn™ are U.S. trademarks of Advanced Energy Industries, Inc.