EXCELSYS COOLX® MODULES INTELLIGENT MODULAR POWER SUPPLIES Advanced Energy's CoolX® modules are designed to be used with the Advanced Energy's CoolX series, part of our Excelsys product line of intelligent modular power supplies. CoolX modules can be used with the fanless, convection cooled CoolX1000 or CoolX600 U-Channel designs, or the fan cooled CoolX1800 to deliver up to 1800 W in a compact 1U high package. The CoolX® series also offers increased flexibility by allowing system designers to monitor and control power supply performance — essential for staving off process disruption — using either analog or digital communica - tions (PMBus™). Power Standard modules deliver up to
300 W in fan cooled chassis, 200 W
in convection cooled chassis High Power Modules deliver
900 W in fan cooled chassis, 600 W
in convection cooled chassis Cooling Fan Cooled or Convection Cooled options Certifications Medical IEC60601-1 3rd edition, IEC60601-1-2 4th edition (EMC) 2 MOPP Dual fused ISO 9001:2015 Industrial IEC60950, IEC62368-1 SEMI F47* AT A GLANCE PRODUCT HIGHLIGHTS Reliability High-input surge protection — 4 kV line to PE for harsh environments Reverse energy protection — no blocking diodes required Safety approved to 5000 m altitude 93% efficiency Five-year warranty Flexibility Analog and digital management — PMBus™ monitoring and control capability Field-configurable — plug and play power Series and parallel outputs — higher voltages/currents Mounting options — base/side and DIN-Rail mounting TYPICAL APPLICATIONS Medical Clinical diagnostic equipment, medical lasers, dialysis equipment, radiological imaging, clinical chemistry Industrial Test and measurement, industrial machines, automation equipment, printing, telecommunications, audio equipment Hi Rel Harsh industrial electronics, radar (naval- and ground-based), communications, test and measurement
2 advancedenergy.com COOLX SERIES MODULES MODULES CoolX CoolMods Single Output Modules (1 Slot) Vnom (V) Set Point Adjust Range (V) Imax (A) (CX600 & CX1000) Power (W) – Convection Cooled (CX600 & CX1000) Imax (A) (CX1800) Power (W) – Fan Cooled (CX1800) CmA 5 2.5-6.0 21.0 105 30.0 150 CmB 12 6.0-15.0 15.0 180 23.3 280 CmC 24 15.0-28.0 8.3 200 12.5 300 CmD 48 28.0-58.0 4.17 200 6.25 300 High Power Modules (3 Slot) CmE 24 24-25.2 25.0 600 37.5 900 CmF 48 48-50.4 12.50 600 18.75 900 Dual Output Modules (1 Slot) CmG V1 24 3.0-30.0 3.0 90 4.0 120 V2 24 3.0-30.0 3.0 90 4.0 120 CmH V1 5 3.0-6.0 6.0 36 10.0 60 V2 24 3.0-30.0 3.0 90 4.0 120 Wide Trim Modules (1 Slot) CmA-W01 5 1.0-6.0 21 105 30.0 150 CmB-W01 12 1.0-15.0 15 180 23.3 280 CmC-W01 24 2.0-28.0 8.33 200 12.5 300 CmD-W01 48 3.0-58.0 4.17 200 6.25 300 * SEMI F47 compliant at input voltages > 180 VAC. Consult Advanced Energy for details. Full dynamic specifications may not be met at full load when output voltage is trimmed by above 13 V Max trim 14 V when used with high power module Max trim 56 V when used with high power module 4 a) Only one high power module (CmE or CmF) can be used per CoolPac. b) During load transients starting from 0% load on the High Power modules, other modules in the CoolPac may experience an output voltage dynamic during the load change. Contact applications support for details or support. For the CmG module, the max combined power of both outputs is 120 W (Convection Cooled) or 200 W (Fan Cooled) 6 For the CmH module, the max combined power of both outputs is 100 W (Convection Cooled) or 180 W (Fan Cooled)
advancedenergy.com 3 COOLX SERIES MODULES ELECTRICAL SPECIFICATIONS Output Parameter Conditions/Description Min Nom Max Units Minimum Load 0 — — A Line Regulation For ±10% change from nominal line — — ±0.1 % CmE, CmF , CmG, CmH — — ±0.5 % Load and Cross Regulation For 25% to 75% load change — — ±0.2 % Transient Response For 25% to 75% load change 0.5 A/uS: Voltage deviation — — 4 (4) % *CmE and CmF , figures in () settling time — — 500 (1000) µS Ripple and Noise 100 mV or 1.0% pk-pk. 20 MHz BW — — 1 % CmE, CmF — — 3 % Overvoltage Protection Tracking OVP Level (N/A in CmE and CmF , CmG, CmH) 105 — 125 % Non-latching OVP 110 — 160 % Remote Sense Max. line drop compensation. (N/A in CmG, CmH) — — 0.5 VDC Overshoot — — 1 % Rise Time Monotonic CmG, CmH figures in () — — 10 (20) ms Turn-On Delay From AC — — 800 ms From global enable — — 12 (20) ms From CoolMod enable — — 12 (20) ms Hold-Up Time For nominal output voltages at full load 16 — — ms CoolMod Power As per CoolMod table — — — — Output Adjustment Range Manual: Multi-turn potentiometer. As per CoolMod table Vtrim: As per CoolMod table — — — — Overcurrent Protection Straight line with hiccup activation @ 35% Vo nom CmE, CmF , CmG, CmH: Current limit hiccup autorecovery 110 130 150 % Short Circuit Protection Yes, autorecovery — — — — OverTemperature Protection Yes, autorecovery (CmG, CmH latch off ) Capacitive Load Nominal output voltages at full load CmG CmH CmE CmF — — 270 270 2.5 uF uF mF mF ECIFICATIONS (CONTINUED)
4 advancedenergy.com COOLX SERIES MODULES Standards & Directives Standard Conditions/Description Safety Agency Approvals EN60601-1 3rd edition, UL60601-1, CSA601, EN60950 2nd edition, CSA C22.2 No. 60950-1, IEC 62368-1 IEC/EN 60950-1, Edition 2 UL 60950-1/CSA 22.2 No 60950-1, Edition 2; 5000 m (16,400 ft) altitude, 100 V to 240 VAC ±10% IEC/EN 60601-1, Edition 3 IEC 60601-1(2005), EN60601-1(2006), ANSI/AAMI ES 60601-1(2005), CAN/CSA C22.2 No. 60601-1 (2008); 5,000 m (16,400 ft) altitude, 100 V to 240 VAC ±10% IEC 62368 Edition 2 IEC 62368-1 (2014) Edition 2 5000 m (16,400 ft) altitude, 100 V to 240 VAC ±10% IEC 60601-1-2 Edition 4 IEC 60601-1-2 (2014) Protection class Class I WEEE Waste Electrical and Electronic Equipment Directive (WEEE) 2002/96/EC ROHS EU DIRECTIVE 2011/65/EC RoHS compliancy REACH Compliant ELECTRICAL SPECIFICATIONS (CONTINUED) Galvanic Isolation Parameter Conditions/Description Min Nom Max Units Input to Output Reinforced (2 x MOPP); contact Advanced Energy for Hi-Pot instructions 4000 — — VAC Output to Case Basic (1 x MOPP) 1850 — — VAC Output to Output Basic (1 x MOPP) 1850 — — VAC Output to Output (Dual) CmG, CmH V1-V2 500 — — VDC LECTRICAL SPECIFICATIONS (CONTINUED) Environmental Parameter Conditions/Description Min Nom Max Units Operating Temperature Operates to specification below -20°C after 10 min warm-up -40 — 85 °C Storage Temperature -40 — 85 °C Derating See derating curves in the Designers Manual — — — — Relative Humidity Non-condensing 5 — 95 %RH Shock and Vibration MIL-STD-810G Method 514.6 — — — — Altitude — — 5000 m EMC Parameter Conditions/Description Criteria Radiated Emissions EN 55011, EN 55022 and FCC, Class B Compliant Conducted Emissions EN 55011, EN 55022 and FCC, Class B Compliant Power Line Harmonics EN 61000-3-2, Class A Compliant Voltage Flicker EN 61000-3-3 Compliant ESD EN 61000-4-2, level 4, 8 kV contact, 15 kV air A Radiated Immunity EN 61000-4-3, level 3, 10V/m 80-2700 MHz A Electrical Fast Transient EN 61000-4-4, level 4, ±4 kV A Surge Immunity EN 61000-4-5, level 4, 2 kV DM, 4 kV CM A Conducted RF Immunity EN 61000-4-6, level 3, 10 Vemf 150 KHz-80 MHz A Power Frequency Magnetic Field EN 61000-4-8, level 4, 30 A/m A Voltage Dips & Interruptions EN 61000-4-11 A & B Compliant Consult AE applications for system level compliance
5 advancedenergy.com COOLX SERIES MODULES Main DC Output Terminal Block (CmG, CmH) Camden - CTB9350/4A — Output Signal Connector (CmG, CmH) Molex - 87833-0831 — System Signal Connector J1007 Molex 87833-0831 8-way Locking Molex 51110-0860; Non Locking Molex 51110-0850; Crimp Terminal: Molex p/n 50394 or Molex 51110-0856 which includes locking tab and polarization keying Output Signal Connectors J1001-1006 Molex 87833-0631 6-way Locking Molex 51110-0660; Non Locking Molex 51110-0650; Crimp Terminal: Molex p/n 50394 or Molex 51110-0656 which includes locking tab and polarization keying Output Sense Connectors J3 JST-S2BPH-K(LF)(SN) JST PHR2. Crimp Terminal JST BPH-002TP .0.5S or SPH-002T-P .05S Auxiliary Output Connector J1 Molex 1041880210 2pin — MECHANICAL SPECIFICATIONS Mechanical Data Connectors Description Mating Connectors (if applicable) AC/DC Input Terminal Block TE 2-1437667-S, DINKLE DT-35-B07W-03 — Main DC Output Terminal Block (CmA-CmF) M4 Screws —
advancedenergy.com 6 COOLX SERIES MODULES INTERFACE Signal Connectors CoolMod Connectors
Advanced Energy (AE) has devoted more than three decades to perfecting power for its global customers. AE designs and manufactures highly engineered, precision power conversion, measurement and control solutions for mission-critical appli- cations and processes. AE’s power solutions enable customer innovation in complex semiconductor and industrial thin film plasma manufacturing processes, demanding high and low voltage applications, and temperature-critical thermal processes. With deep applications know-how and responsive service and support across the globe, AE builds collaborative partnerships to meet rapid technological developments, propel growth for its customers and power the future of technology. Specifications are subject to change without notice. Not responsible for errors or omissions. ©2019 Advanced Energy Industries, Inc. All rights reserved. Advanced Energy® and AE® are U.S. trademarks, and CoolX® is a U.S. and Europe trademark of Advanced Energy Industries, Inc. For international contact information, visit advancedenergy .com ENG-LV-COOLX1000-235-28 10.20