embedded control, data logging, and network connectivity. backup power supply connections to protect against primary power failure. well as take advantage of the built-in Web (HTTP) and file (FTP) servers. solid backplane and controls a wide variety of hot-swappable I/O modules. pulse-width modulation (PWM), and 24 V digital I/O.

  • Execution target for NI LabVIEW Real-Time applications
  • 400 MHz real-time processor with up to 256 MB of SDRAM
  • Up to 512 MB of nonvolatile storage, removable CompactFlash and USB ports
  • Up to 2 Ethernet ports for communication for distributed real-time systems
  • Dual redundant 11 to 30 VDC power supply inputs, low power
  • Up to 4 serial ports (3 RS232 and

1 RS485) for communication

  • Industrial certifications, -40 to 70 °C operating temperature range Operating Systems
  • LabVIEW Real-Time (VxWorks) Recommended Software
  • LabVIEW Real-Time Module 8.5.1 or later
  • NI-FieldPoint driver 6.0.1 or later NI cFP-2220, NI cFP-2210, NI cFP-2200 Controller DRAM Memory (MB) Internal Nonvolatile Storage (MB) Removable CompactFlash Removable USB Ethernet Ports RS232 Ports RS485 Ports cFP-2220 256 256 2 3 1 cFP-2210 256 128 – – 1 2 0 cFP-2200 128 128 – – 1 1 0

Table 1. NI cFP-22xx Selection Guide

Expansion I/O with NI cFP-1808 For systems that require more than eight Compact FieldPoint modules, the cFP-1808 expansion chassis provides an easy way to add expansion I/O over Ethernet or serial. A single cFP-22xx controller can connect to as many additional cFP-1808 network interface systems as the Ethernet network allows. Compact FieldPoint Real-Time Controllers BUY ONLINE at ni.com or CALL 800 813 3693 (U.S.)

Ordering Information

Recommended Compact FieldPoint System Products BUY NOW! For complete product specifications, pricing, and accessory information, call 800 813 3693 (U.S.) or go toni.com/compactfieldpoint. Figure 1. Expansion I/O for Compact FieldPoint Controllers with NI cFP-1808

Specifications subject to change without notice. The following specifications are typical for the range -40 to 70 °C unless otherwise noted. Memory

128 MB DRAM

256 MB DRAM

RS232 (DTE) Ports RS485 (DTE) Port port to earth ground USB Port (cFP-2220 only) Power Requirements Caution: You must use a National Electric Code (NEC) UL-listed Class 2 power supply with cFP-22xx controllers. Recommended power supply power requirements) Physical Characteristics If you need to clean the controller, wipe it with a dry towel. 10 mm (0.39 in.) of insulation stripped from the end Environmental The cFP-22xx controllers are intended for indoor use only, but they may be used outdoors if mounted in a suitably sealed enclosure. Operating temperature Storage temperature Operating humidity Shock and Vibration To meet these specifications, you must panel mount the Compact FieldPoint system and affix ferrules to the ends of the power terminal wires. 3 ms half sine; 18 shocks at 6 orientations Operating vibration, random Operating vibration, sinusoidal Safety Voltages Connect only voltages that are within these limits Caution: Do not connect the system to signals or use for measurements within Measurement Category II, III, or IV. Compact FieldPoint Real-Time Controllers BUY ONLINE at ni.com or CALL 800 813 3693 (U.S.)

This product is designed to meet the requirements of the following standards of safety for electrical equipment for measurement, control, and laboratory use:

  • IEC 61010-1, EN 61010-1
  • UL 61010-1, CSA 61010-1 Note: For UL and other safety certifications, refer to the product label or visit ni.com/certification, search by model number or product line, and click the appropriate link in the Certification column. Electromagnetic Compatibility This product is designed to meet the requirements of the following standards of EMC for electrical equipment for measurement, control, and laboratory use:
  • EN 61326 EMC requirements; Industrial Immunity
  • EN 55011 Emissions; Group 1, Class A
  • CE, C-Tick, ICES, and FCC Part 15 Emissions; Class A Note: For EMC compliance, operate this device according to product documentation. CE Compliance This product meets the essential requirements of applicable European Directives, as amended for CE marking, as follows:
  • 2006/95/EC; Low-Voltage Directive (safety)
  • 2004/108/EC; Electromagnetic Compatibility Directive (EMC) Note: Refer to the Declaration of Conformity (DoC) for this product for any additional regulatory compliance information. To obtain the DoC for this product, visit ni.com/certification, search by model number or product line, and click the appropriate link in the Certification column. Waste Electrical and Electronic Equipment (WEEE) EU Customers: At the end of their life cycle, all products must be sent to a WEEE recycling center. For more information about WEEE recycling centers and National Instruments WEEE initiatives, visit ni.com/environment/weee.htm. Compact FieldPoint Real-Time Controllers BUY ONLINE at ni.com or CALL 800 813 3693 (U.S.)

NI has the services and support to meet your needs around the globe and through the application life cycle – from planning and development through deployment and ongoing maintenance. We offer services and service levels to meet customer requirements in research, design, validation, and manufacturing. Visit ni.com/services. Training and Certification NI training is the fastest, most certain route to productivity with our products. NI training can shorten your learning curve, save development time, and reduce maintenance costs over the application life cycle. We schedule instructor-led courses in cities worldwide, or we can hold a course at your facility. We also offer a professional certification program that identifies individuals who have high levels of skill and knowledge on using NI products. Visit ni.com/training. Professional Services Our NI Professional Services team is composed of NI applications and systems engineers and a worldwide National Instruments Alliance Partner program of more than 600 independent consultants and integrators. Services range from start-up assistance to turnkey system integration. Visit ni.com/alliance. OEM Support We offer design-in consulting and product integration assistance if you want to use our products for OEM applications. For information about special pricing and services for OEM customers, visit ni.com/oem. Local Sales and Technical Support In offices worldwide, our staff is local to the country, giving you access to engineers who speak your language. NI delivers industry-leading technical support through online knowledge bases, our applications engineers, and access to 14,000 measurement and automation professionals within NI Developer Exchange forums. Find immediate answers to your questions at ni.com/support. We also offer service programs that provide automatic upgrades to your application development environment and higher levels of technical support. Visit ni.com/ssp. Hardware Services NI Factory Installation Services NI Factory Installation Services (FIS) is the fastest and easiest way to use your Compact FieldPoint systems right out of the box. Trained NI technicians install the software and hardware and configure the system to your specifications. NI extends the standard warranty by one year on hardware components (controllers, chassis, modules) purchased with FIS. To use FIS, simply configure your system online with http://ohm.ni.com/advisors/cfp. Calibration Services NI recognizes the need to maintain properly calibrated devices for high-accuracy measurements. We provide manual calibration procedures, services to recalibrate your products, and automated calibration software specifically designed for use by metrology laboratories. Visit ni.com/calibration. Repair and Extended Warranty NI provides complete repair services for our products. Express repair and advance replacement services are also available. We offer extended warranties to help you meet project life-cycle requirements. Visit ni.com/services. SERVICE NEEDS M AINTAIN PLAN DEVELOPDEPLOY ©2008 National Instruments Corporation. All rights reserved. FieldPoint, LabVIEW, National Instruments, National Instruments Alliance Partner, NI, ni.com, and SCXI are trademarks of National Instr uments. Other pr oduct and company names listed are trademarks or trade names of their respective companies. A National Instruments Alliance Partner is a business entity independent fr om NI and has no agency , partnership, or joint-ventur e relationship with NI. National Instruments • info@ni.com ni.com • 800 813 3693 *351585A-01* 351585A-01 2008-9213-161-101-D