CCPB-1-15CF ETC1 | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 6
Technical content
CUBEFuse™ Compact Circuit Protector Base (CCPB) 2011/65/EU Product description: The revolutionary Bussmann™ series Compact Circuit Protector Base (CCPB) with CUBEFuse™ is designed as a fused branch circuit disconnect switch for the Bussmann series Quik-Spec™ Coordination Panelboard. The CCPB with CUBEFuse simplifies selective coordination and lockout/tagout provisions allow for isolation of individual branch circuit loads for safe work practices. Features and benefits:
- Uses finger-safe, current-limiting Class CF CUBEFuse with Class J performance available, time-delay or fast-acting versions from 1 to 100 amps*
- Patented ampacity rejection feature helps prevent overfusing
- High 200kA short-circuit current ratings
- Disconnect rated to provide means for load isolation
- All versions are full voltage rated at 600Vac
- 125Vdc rated for 80A and below
- UL 98 Listed and suitable for branch circuit disconnect
- 1-, 2- and 3-pole versions are horsepower rated
- Listed to UL and cULus
- Open fuse indication light per pole
- Additional open fuse indication can be provided by using the time-delay indicating CUBEFuse version
- Built-in switch/fuse interlock prohibits fuse removal while energized
- Permanent lockout/tagout provisions
- Lock-On provision available when used in the Bussmann series Quik-Spec Coordination Panelboard (QSCP) * See data sheet 9000 for time-delay CUBEFuse and data sheet 2147 for fast-acting CUBEFuse specifications. Technical Data 1 161 Effective April 2017 Supersedes April 2016 BUSSMANN SERIES
CUBEFuse Compact Circuit Protector Base (CCPB) for Quik–Spec™ Coordination Panelboards Eaton.com/bussmannseries Specifications: Switch ampacity and rejection breaks
- 15A, 20A, 30A, 40A, 50A, 60A, 70A, 90A and 100A Poles
- 1-, 2- and 3-pole versions Volts
- 600Vac (or less)
- 125Vdc (15, 20, 30, 40, 70 and 90 amp switches with ≤ 80A fuse) Agency information
- UL 98 Listed, File E302370, Guide WHTY
- cULus to CSA Standard 22.2 No. 4, File E302370, Guide WHTY7
- CE compliant
- RoHS compliant T erminals Lineside bolt-on bus connector and torque
- Bolt-mounted design into Quik-Spec Coordination Panelboard bus
- #10-32-UNC Hex flange Phillips screw; 25 Lb-In (2.8 N•m) Loadside box lug terminal and torque
- 15-60A:
- 18 to 10 AWG (1 to 6mm2) single or dual rated (same size wire), solid or stranded – 75°C or higher - Cu only; 20 Lb-In (3.4 N•m)
- 8 to 6 AWG (10 to 16mm2) single or dual rated (same size wire), solid or stranded – 75°C or higher - Cu only; 35 Lb-In (5.8 N•m)
- 4 AWG (25mm2) single – 75°C or higher - Cu only; 35 Lb-In (5.8 N•m)
- 100A:
- 18 to 10 AWG (1 to 6mm2) single, solid or stranded – 75°C or higher - Cu only; 25 Lb-In (2.82 N•m)
- 8 to 1 AWG (10 to 45mm2) single stranded – 75°C or higher - Cu only; 40 Lb-In (4.52 N•m)
- 6 AWG (16mm2) dual stranded (same size wire) – 75°C or higher Cu only; 45 Lb-In (5.08 N•m) Loadside fork terminal
- Max. 30A suitable for use with #8-32UNC screw Lockout/tagout
- 4mm shank lock Local open fuse indication
- Light illumination requires closed circuit and minimum 90V operating voltage Shipping weight
- 2.03 lbs per carton Carton quantity
- 6 poles Environmental data Storage and operating temperature -20°C to 75°C For fuse performance under or above 25°C, consult fuse performance derating charts. Switch handle Lockout/tagout provision Loadside fork terminal Loadside box lug terminal Local open fuse indication light Lineside bolt-on bus connector Switch ON and OFF symbols CUBEFuse base 1-Pole 2-Pole 3-pole CCPB-1-_CF CCPB-2-_CF CCPB-3-_CF
CUBEFuse Compact Circuit Protector Base (CCPB) for Quik–Spec™ Coordination Panelboards Eaton.com/bussmannseries Catalog numbers: CCPB part numbers Poles Voltage rating Accepts CUBEFuse amp range Typical installed fuse amp range Max. fuse amps† SCCR Hp ratings (Vac)†† Time-delay non-indicating Time-delay indicating* Fast-acting non-indicating** CCPB-1-15CF 1 600Vac, 125Vdc 1 to 15 TCF1RN, TCF3RN, TCF6RN, TCF10RN, TCF15RN TCF6, TCF10, TCF15 FCF1RN, FCF3RN, FCF6RN, FCF10RN, FCF15RN 15A 200kA AC 100kA DC 0.5Hp@120V CCPB-2-15CF 2 1 .5Hp@240V CCPB-3-15CF 3 600Vac 3Hp@240V 5Hp@480V 7 .5Hp@600V CCPB-1-20CF 1 600Vac, 125Vdc 1 to 20 TCF17-1/2RN, TCF20RN TCF17-1/2, TCF20 FCF20RN 20A 200kA AC 100kA DC 0.75Hp@120V CCPB-2-20CF 2 2Hp@240V CCPB-3-20CF 3 600Vac 3Hp@240V 7 .5Hp@480V 10Hp@600V CCPB-1-30CF 1 600Vac, 125Vdc 1 to 30 TCF25RN, TCF30RN TCF25, TCF30 FCF25RN, FCF30RN 30A 200kA AC 100kA DC 1 .5Hp@120V CCPB-2-30CF 2 3Hp@240V CCPB-3-30CF 3 600Vac 5Hp@240V 15Hp@480V 10Hp@600V CCPB-1-40CF 1 600Vac, 125Vdc 1 to 40 TCF35RN, TCF40RN TCF35, TCF40 FCF35RN, FCF40RN 40A 200kA AC 100kA DC 2.0Hp@120V CCPB-2-40CF 2 3Hp@240V CCPB-3-40CF 3 600Vac 7 .5Hp@240V 20Hp@480V 10Hp@600V CCPB-1-50CF 1 600Vac, 125Vdc 1 to 50 TCF45RN, TCF50RN TCF45, TCF50 FCF45RN, FCF50RN 50A 200kA AC 100kA DC 3.0Hp@120V CCPB-2-50CF 2 5Hp@240V CCPB-3-50CF 3 600Vac 7 .5Hp@240V 20Hp@480V 10Hp@600V CCPB-1-60CF 1 600Vac, 125Vdc 1 to 60 TCF60RN TCF60 FCF60RN 60A 200kA AC 100kA DC 3.0Hp@120V CCPB-2-60CF 2 7 .5Hp@240V CCPB-3-60CF 3 600Vac 7 .5Hp@240V 20Hp@480V 10Hp@600V CCPB-1-70CF 1 600Vac, 125Vdc 1 to 70 TCF70RN TCF70 FCF70RN 70A 200kA AC 100kA DC 3.0Hp@120V CCPB-2-70CF 2 7 .5Hp@240V CCPB-3-70CF 3 600Vac 15Hp@240V 30Hp@480V 40Hp@600V CCPB-1-90CF 1 600Vac, 125Vdc 1 to 90 TCF90RN TCF90 FCF80RN, FCF90RN 90A 200kA AC 100kA DC 5.0Hp@120V CCPB-2-90CF 2 10Hp@240V CCPB-3-90CF 3 600Vac 20Hp@240V 50Hp@480V 40Hp@600V CCPB-1-100CF 1 600Vac, 125Vdc ††† 1 to 100 TCF100RN TCF100 FCF100RN 100A 200kA AC 5.0Hp@120V CCPB-2-100CF 2 10Hp@240V CCPB-3-100CF 3 600Vac 20Hp@240V 50Hp@480V 40Hp@600V * 1A and 3A indicating CUBEFuse not available. Correct fit with CCPB disconnect requires indicating CUBEFuse with date code R38 or later. ** Do not use UPS/Critical Application fast-acting FCF with motors. † Any fuse with an amp rating less than or equal to the max fuse rating may be used. E.g., TCF15 may be used with CCPB-1-20CF . †† Indiacting or non-indicating time-delay CUBEFuse only. ††† 125Vdc only applies up to 80A.
CUBEFuse Compact Circuit Protector Base (CCPB) for Quik–Spec™ Coordination Panelboards Eaton.com/bussmannseries Dimensions — in (mm): 15-60A 70-100A For details on the CCPB and its use in the Quik-Spec Coordination Panelboard, see data sheet 1160. 3.0 (75.8) 1.0 (25.4) 2.0 (50.7) (5.08) Ø.2 2.7 (69.1) 2.9 3.9 (99.4) 0. 5 (12.9) (73.5) 1.0 (25.4) 2.0 (50.7) 3.0 (75.8) Ø0.2 (5.08) 5.3 (133.3) 2.7 (69.6) 0.03 (0.84) 3.4 (86.0) 0.54 (13 72)
CUBEFuse Compact Circuit Protector Base (CCPB) for Quik–Spec™ Coordination Panelboards Eaton.com/bussmannseries Motor sizing table: Low-Peak™ TCF_ and TCT_RN time-delay Class CF fuses Voltage Motor size (Hp) Motor FLA (amps) Optimal protection (amps) Code max (amps) Heavy start (amps) 115Vac, 1-Phase 0.167 4.4 10 10 10 0.25 5.8 10 15 15 0.333 7. 2 15 15 15 0.5 9.8 15 20 20 0.75 13.8 25 25 30 1 16 25 30 35 1. 5 20 30 35 45 2 24 40 45 50 3 34 50 60 N/A 5 56 90 100 N/A 230Vac,1-Phase 0.167 2.2 6 6 6 0.25 2.9 6 6 6 0.333 3.6 6 10 10 0.5 4.9 10 10 10 0.75 6.9 15 15 15 1 8 15 15 1 7. 5 1. 5 10 15 20 20 2 12 20 25 25 3 17 25 30 35 5 28 45 50 60 7. 5 40 60 N/A N/A 10 50 80 90 N/A 200Vac, 3-Phase 0.5 2.5 6 6 6 0.75 3.7 6 10 10 1 4.8 10 10 10 1. 5 6.9 15 15 15 2 7. 8 15 15 1 7. 5 3 11 1 7. 5 20 20 5 1 7. 5 30 35 35 7. 5 25.3 40 45 50 20 62.1 100 N/A N/A 208Vac, 3-Phase 0.5 2.4 6 6 6 0.75 3.5 6 10 10 1 4.6 10 10 10 1. 5 6.6 10 15 15 2 7. 5 15 15 15 3 10.6 1 7. 5 20 20 5 16.7 25 30 35 7. 5 24.2 40 45 50 20 59.4 90 N/A N/A Voltage Motor size (Hp) Motor FLA (amps) Optimal protection (amps) Code max (amps) Heavy start (amps) 230Vac, 3-Phase 0.5 2.2 6 6 6 0.75 3.2 6 6 6 1 4.2 10 10 10 1. 5 6 10 15 15 2 6.8 15 15 15 3 9.6 15 20 20 5 15.2 25 30 30 7. 5 22 35 40 45 20 54 90 100 N/A 460Vac, 3-Phase 0.5 1. 1 3 3 3 0.75 1. 6 3 3 3 1 2.1 6 6 6 1. 5 3 6 6 6 2 3.4 6 6 6 3 4.8 10 10 10 5 7. 6 15 15 15 7. 5 11 1 7. 5 20 20 10 14 25 25 30 15 21 35 40 45 20 27 40 50 60 50 65 100 N/A N/A 575Vac, 3-Phase 0.5 0.9 3 3 3 0.75 1. 3 3 3 3 1 1. 7 3 3 3 1. 5 2.4 6 6 6 2 2.7 6 6 6 3 3.9 6 10 10 5 6.1 10 15 15 7. 5 9 15 20 20 10 11 1 7. 5 20 20 40** 41 70 80 80 Note: Use Code Max column for low to moderate reverse/jog/plug applications. Heavy Start permitted only if Code Max does not allow motor start-up. * Based on motor FLA from NEC ® tables 430.248 and 430.250.
CUBEFuse Compact Circuit Protector Base (CCPB) for Quik–Spec™ Coordination Panelboards Technical Data 1161 Effective April 2017 The only controlled copy of this Data Sheet is the electronic read-only version located on the Eaton Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Eaton reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Eaton also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. Eaton, Bussmann, Quik-Spec and CUBEfuse are valuable trademarks of Eaton in the U.S. and other countries. Y ou are not permitted to use the Eaton trademarks without prior writ- ten consent of Eaton. CSA is a registered trademark of the Canadian Standards Group. NEC is a registered trademark of the National Fire Protection Association, Inc. NEMA is a registered trademark of the National Electrical Manufacturers Association. UL is a registered trademark of the Underwriters Laboratories, Inc. Follow us on social media to get the latest product and support information. Eaton