CCP EATON | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 12

Technical content

1-, 2- and 3-pole — Class CC, Midget, 10x38mm 1-, 2- and 3-pole — Class CF Auxiliary contacts PLC fuse monitor

Contents

Description Page Description Page Compact Circuit Protector (CCP) UL Class CC, CF (CUBEFuse™), midget and IEC 10x38mm DIN-Rail fused disconnect switches 2011/65/EU Technical Data 1 157 Effective March 2018 Supersedes March 2017 BUSSMANN SERIES

Compact Circuit Protector (CCP) UL Class CC, CF (CUBEFuse), midget and IEC 10x38mm fused disconnect switches Eaton.com/bussmannseries 1-, 2- and 3-pole — Class CC, midget, 10x38mm Description: The revolutionary Bussmann series Compact Circuit Protector (CCP) fused disconnect switch is 2/3 the footprint of a traditional fusible switch and can provide up to a high 200 kA SCCR that can help improve assembly SCCR . Specifications: Ratings

  • Volts
  • 600 Vac (Class CC)
  • 240 Vac (midget UL®)
  • 400 Vac (midget International Electrotechnical Commission (IEC)
  • 80Vdc (DC Class CC/UL, DC midget/IEC)
  • Amps
  • 30A (UL)
  • 32A (IEC)
  • SCCR
  • 200 kA (Class CC)
  • 10 kA (midget UL)
  • 120 kA (midget IEC max)
  • 20 kA (DC Class CC/UL)
  • 10 kA (DC midget/IEC) Poles
  • 1-, 2- and 3-pole versions Agency information
  • CE
  • RoHS compliant
  • For Class CC fuse versions
  • UL 98 Listed, File E302370, Guide WHTY
  • cULus to CSA Standard 22 .2 No . 4-04, File 302370, Guide WHTY7
  • For UL midget and 10X38 IEC fuse versions
  • UL 508 Listed, File E320230, Guide NRNT
  • cULus Certified 22 .2 No . 14-05
  • IEC 60947-3 AC23A
  • IEC 60947-3 DC23A Conductors 75°C Cu or higher
  • Single/dual 18-6AWG solid or stranded
  • Single 4AWG solid or stranded T erminals
  • Single/dual conductor box lug or fork terminal suitable for line, load or accessory connection T orque
  • 18-10AWG 20 Lb-In
  • 8-4AWG 35 Lb-In Storage and operating temperature
  • -20°C to 75°C* * For fuse performance under or above 25°C, consult fuse performance derating charts in the Bussmann Division publication titled Selecting Protective Devices (SPD), data sheet No . 3002 . Flammability rating
  • UL 94V0 Lockout/tagout provisions
  • 4mm shank lock or Brady pin-out device part number 90850 Mounting
  • 35mm DIN-Rail Local open fuse indication minimum voltage**
  • 90 Vac for AC versions
  • 12Vdc for DC versions ** Open fuse indication requires an open fuse to be in the CCP and the switch in the ON position . Accessories
  • Auxiliary contacts
  • PLC wired remote fuse indication Shipping weight
  • 2 .84 lbs (1 .29 kg) per carton Carton quantity
  • 12 poles Features:
  • Extremely compact design at 17 .5mm wide per pole
  • High Short-Circuit Current Ratings (SCCR) up to 200 kA (UL) and 120 kA (IEC)
  • Disconnect rated to provide means for load isolation
  • Full voltage rated up to 600 Vac or 80Vdc
  • Class CC version is UL 98 Listed and horsepower rated, and suitable for branch circuit disconnect and branch circuit protection
  • IEC 10x38 version complies with IEC 60947-3 and suitable for branch circuit disconnect and branch circuit protection
  • Suitable for global installations, the units comply with UL, cULus, and IEC standards accepting UL Class CC, midget or IEC aM and gG/gL fuses
  • Open fuse indication:
  • Local fuse indication lights are standard
  • Optional wired remote open fuse indication can be utilized to signal a PLC and open a contactor to de-energize all phases, if required
  • IP20 finger-safe with 10AWG (6mm2) or larger wire
  • Built-in switch interlock prohibits removing the fuse under load
  • Padlockable handle for lockout/tagout procedures - recommend using Brady pin-out device part number 90850 1-Pole DC CCP

Compact Circuit Protector (CCP) UL Class CC, CF (CUBEFuse), midget and IEC 10x38mm fused disconnect switches Eaton.com/bussmannseries Switch handle (ganged on 2- and 3-pole versions) Catalog numbers: Amp rating Fuse class No. of poles Volts SCCR Max horsepower rating ( Vac) Wire size/ (torque*) Wire type Catalog no. Agency information120 240 480 600 30 CC 1 600 Vac 200 kA 0 .5 — — — Single/Dual 18-6AWG Sol/Str Single 4AWG Sol/Str Spade Terminal†† 75°C Cu or higher CCP-1-30CC UL 98 Listed, cULus 22 .2, No . 4-04 30 CC 2 600 Vac 200 kA — 2 — — CCP-2-30CC UL 98 Listed, cULus 22 .2, No . 4-04 30 CC 3 600 Vac 200 kA — 3 5 7 .5 CCP-3-30CC UL 98 Listed, cULus 22 .2, No . 4-04

30 UL Midget

240 Vac† 10 kA†

— — — — CCP-1-30M UL 508 Listed, cULus 22 .2, No . 14-05 32** 10x38 IEC 400 Vac† 120 kA† IEC 60947-3, AC-23A — — — — CCP-2-30M UL 508 Listed, cULus 22 .2, No . 14-05 32** 10x38 IEC 400 Vac† 120 kA† IEC 60947-3, AC-23A — — — — CCP-3-30M UL 508 Listed, cULus 22 .2, No . 14-05 32 10x38 IEC 400 Vac† 120 kA† IEC 60947-3, AC-23A 30 CC 1 80Vdc† 20 kA† — — — — CCP-1-DCC UL 98 Listed, CSA 22 .2, No . 4-04 30 UL Midget 1 80Vdc† 10 kA† — — — — CCP-1-DCM UL 508 Listed, cULus 22 .2, No . 14-05 32 10x38 IEC IEC 60947-3, DC-23A * 18-10AWG; 20 Lb-In, 8-4AWG; 35 Lb-In . ** 32A Class aM, 25A Class gG . † SCCR May be lower, refer to installed fuse data sheets . †† Fork terminal with a 4 .3mm gap for a #8-32 stud, 30A max, insulated flange, wire size 12-10AWG . Available Bussmann series fuses: Fuse class T ype/description Volts Data sheet no. CC LP-CC time-delay, current limiting 600 Vac/300Vdc 1023 CC FNQ-R time-delay 600 Vac/300Vdc 1014 CC KTK-R fast-acting 600 Vac 1015 M FNM time-delay 250 Vac 2028 M FNQ time-delay 500 Vac 1012 M KTK fast-acting 600 Vac 1011 M BAF fast-acting 250 Vac 2 011 M KLM fast-acting 600 Vac/dc 2020 gG/gL C10G 500V (400V@32A) 7201 15 aM C10M 500V (400V@20@25A) 7201 15 Dimensions – mm (in) Class CC, UL midget and I0x38 IEC Recommended lockout device: CCP version Brady pin-out device P/N Class CC, midget, IEC 10x38 90850 92.7 (3.7) 17.5 (0.7) (1.8) (1.4) 79.8 (3.1) 52.5 (2.1) 49.2 (1.9) Fuse access door Circuit marking area Fork terminal Box lug terminal Open fuse indicating light Lockout/ tagout provision

Compact Circuit Protector (CCP) UL Class CC, CF (CUBEFuse), midget and IEC 10x38mm fused disconnect switches Eaton.com/bussmannseries Motor sizing table: LP-CC time-delay Class CC fuses Voltage Motor size (Hp) Motor FLA (amps) Min (amps) Code max (amps) Heavy start (amps) 1 15 Vac, 1-phase 0 .167 4 .4 9 15 15 0 .25 5 .8 12 20 20 0 .33 7 .2 15 25 25 0 .50 9 .8 30 30 30

230 Vac, 1-phase

0 .17 2 .2 4 .5 10 10 0 .25 2 .9 6 10 10 0 .33 3 .6 7 15 15 0 .50 4 .9 10 15 15 0 .75 6 .9 15 25 25 1 8 25 25 30 1 .5 10 30 30 30

200 Vac, 3-phase

0 .50 2 .5 5 10 10 0 .75 3 .7 7 .5 15 15 1 4 .8 10 15 15 1 .5 6 .9 15 25 25 2 7 .8 25 25 30

208 Vac, 3-phase

0 .50 2 .4 5 10 10 0 .75 3 .5 7 15 15 1 4 .6 10 15 15 1 .5 6 .6 15 20 25 2 7 .5 15 25 30

230 Vac, 3-phase

0 .50 2 .2 4 .5 10 10 0 .75 3 .2 7 10 12 1 4 .2 9 15 15 1 .5 6 12 20 20 2 6 .8 15 25 25 3 9 .6 30 30 30

460 Vac, 3-phase

0 .50 1 .1 2 .25 6 6 0 .75 1 .6 3 .2 6 6 .25 1 2 .1 4 .5 10 10 1 .5 3 6 10 12 2 3 .4 7 15 15 3 .00 4 .8 10 15 15 5 .00 7 .6 25 25 30

575 Vac, 3-phase

0 .50 0 .9 1 .8 3 3 .5 0 .75 1 .3 2 .8 6 6 1 1 .7 3 .5 6 6 .25 1 .5 2 .4 5 10 10 2 2 .7 5 .6 10 10 3 .00 3 .9 8 15 15 5 .00 6 .1 15 20 20 7 .50 9 30 30 30 Note: NEMA motors only (no IEC or design B energy efficient) . Minimum size if no more than 1 start/hour . Code max if low to moderate reverse/jog/plug applications . Heavy start permitted only if code max does not allow motor start-up . For high reverse/jog/plug applications or larger horsepower motors, Bussmann series Class CF (Class J electrical performance) fuses are recommended . See CCP_CF with CUBEFuse™ .

Compact Circuit Protector (CCP) UL Class CC, CF (CUBEFuse), midget and IEC 10x38mm fused disconnect switches Eaton.com/bussmannseries 1-, 2- and 3-Pole — Class CF Description: The revolutionary Bussmann series Compact Circuit Protector (CCP) fused disconnect switch with CUBEFuse™is 2/3 the footprint of a traditional fusible switch and provides a high 200 kA SCCR that can help increase assembly SCCR . Specifications: Ratings Volts

  • 600 Vac
  • 125Vdc (up to 80A max) Amps
  • 30, 60, 100A SCCR
  • 200 kA AC
  • 100 kA DC (up to 80A max) Poles
  • 1-, 2-, 3-pole Agency information
  • UL 98 Listed, File E302370, Guide WHTY
  • cULus to CSA Standard 22 .2 No . 4-04, File 302370, Guide WHTY7
  • CE
  • RoHS compliant Conductors 75°C Cu or higher
  • 30 to 60A CCPs: - Single/dual 18-6AWG solid or stranded - Single 4AWG solid or stranded
  • 100A CCPs - Single 10-8AWG solid - Single 8-1AWG stranded - Dual 6AWG stranded T erminals
  • Single/dual conductor box lug or fork terminal suitable for line, load or accessory connection
  • Torque: 0-60A: - 18-10AWG 20 Lb-In - 8-6AWG 35Lb-In - 4AWG 35 Lb-In 70-100A: - 18-10AWG single 25 Lb-In - 8-1AWG single 40 Lb-In - 6AWG dual 45 Lb-In Fuses
  • Uses finger-safe Class CF Bussmann series CUBEFuse with Class J performance
  • Bussmann series Low-Peak™ dual-element, time-delay*
  • Non-indicating 1-100A
  • Indicating 6-100A
  • Fast-acting, non-indicating 1-100A** * See data sheet No . 9000 . **See data sheet No . 2147 . Storage and operating temperature
  • -20°C to 75°C* * For fuse performance under or above 25°C, consult fuse performance derating charts in the Bussmann Division publication titled Selecting Protective Devices (SPD) No . 3002 . Flammability rating
  • UL 94V0 Lockout/tagout provisions
  • 4mm shank lock Mounting
  • 35mm DIN-Rail Local open fuse indication minimum voltage†
  • 90V † Open fuse indication requires an open fuse to be in the CCP and the switch in the ON position . Accessories
  • Auxiliary contacts
  • PLC wired remote fuse indication
  • Bussmann series CUBEFuse fuse pullers (P/Ns: CFP-30, CFP-60, CFP-100) Shipping weight
  • 2 .03 lbs (0 .92kg) per carton Carton quantity
  • Six (6) poles Features:
  • Uses Class CF finger-safe fast-acting and time-delay CUBEFuse with Class J electrical performance
  • Extremely compact design at 25 .4mm (1 inch) wide per pole
  • Ampacity rejecting disconnects will not accept Bussmann series CUBEFuse amp ratings greater than switch rating
  • High Short-Circuit Current Ratings at 200 kA
  • Disconnect rated to provide means for load isolation
  • Full voltage rated at 600 Vac
  • 125Vdc rated up to 80A max
  • UL 98 Listed and suitable for branch circuit disconnect and branch circuit protection
  • 1-, 2- and 3-pole versions are horsepower rated
  • Complies with UL and CSA
  • Open fuse indication:
  • Local fuse indication lights are standard
  • Optional wired remote open fuse indication can be utilized to signal a PLC and open a contactor to de-energize all phases, if required
  • Additional open fuse indication can be provided by the Bussmann series CUBEFuse
  • IP20 finger-safe construction with 10AWG (6mm2) wire or larger
  • Built-in switch interlock capability prohibits removing the fuse under load
  • Padlockable handle for lockout/tagout procedures

Compact Circuit Protector (CCP) UL Class CC, CF (CUBEFuse), midget and IEC 10x38mm fused disconnect switches Eaton.com/bussmannseries Catalog numbers: Amp rating UL fuse class No. of poles Volts SCCR Max horsepower rating ( Vac)* Wire size/ torque** Wire type Catalog number Agency information120 240 480 600 30 CF 1 600 Vac 200 kA 1 .5 — — — Single/Dual 18-6AWG Sol/Str Single 4AWG Sol/Str Spade Terminal† 75°C Cu or higher CCP-1-30CF UL 98 Listed, cULus 22 .2, No . 4-04125Vdc 100 kA 30 CF 2 600 Vac 200 kA — 3 — — CCP-2-30CF UL 98 Listed, cULus 22 .2, No . 4-04125Vdc 100 kA 30 CF 3 600 Vac 200 kA — 5 15 10 CCP-3-30CF UL 98 Listed, cULus 22 .2, No . 4-04 60 CF 1 600 Vac 200 kA 3 — — — CCP-1-60CF UL 98 Listed, cULus 22 .2, No . 4-04125Vdc†† 100 kA 60 CF 2 600 Vac 200 kA — 7 .5 — — CCP-2-60CF UL 98 Listed, cULus 22 .2, No . 4-04125Vdc†† 100 kA 60 CF 3 600 Vac 200 kA — 7 .5 20 15 CCP-3-60CF UL 98 Listed, cULus 22 .2, No . 4-04

100 CF 1 600 Vac 200 kA 5 — — — Single

Spade Terminal† CCP-1-100CF UL 98 Listed, cULus 22 .2, No . 4-04125Vdc††† 100 kA

100 CF 2

600 Vac 200 kA

— 10 — — CCP-2-100CF UL 98 Listed, cULus 22 .2, No . 4-04 125Vdc††† 100 kA 100 CF 3 600 Vac 200 kA — 20 50 40 CCP-3-100CF UL 98 Listed, cULus 22 .2, No . 4-04 * With time-delay Bussmann series Low-Peak CUBEFuse . ** 30-60A: 18-10AWG 20 Lb-In, 8-6AWG 35 Lb-In, 4AWG 35 Lb-In, 70-100A: 18-10AWG Single 25 Lb-In, 8-1AWG Single 35 Lb-In, 6AWG Dual 45 Lb-In † Fork terminal with a 4 .3mm gap for a #8-32 stud, 30A max, insulated flange, wire size 12-10AWG . †† Up to 40A max . ††† Up to 80A max . Available Bussmann series fuses: Fuse class T ype/description Data sheet No. CF Low-Peak time-delay, current limiting 600 Vac/300Vdc 9000 CF UPS/fast-acting 600 Vac/dc 2147 Dimensions – mm (in) 30 and 60A CUBEFuse CCP 100A CUBEFuse CCP 50.4 (2.0) 25.1 (1.0) 75.7 (3.0) 9.1 (0.4) 7.6 (0.3) 60.3 (2.4) 113.9 (4.5) 49.2 (1.9) 75.1 (3.0) 30A CUBEFuse 83.3 (3.3) 60A CUBEFuse 89.1 (3.5) 79.5 (3.0) 147.1 (5.8) 50.5 (2.0)25.15 (1.0) 91.2 (3.6)56.6 (2.2) 100.0 (3.9) 67.7 (2.7) Switch handle (ganged on 2- and 3-pole versions) Fuse holder Circuit marking area Fork terminal Box lug terminal Open fuse indicating light Lockout/ tagout provision

Compact Circuit Protector (CCP) UL Class CC, CF (CUBEFuse), midget and IEC 10x38mm fused disconnect switches Eaton.com/bussmannseries Motor sizing table: Bussmann series TCF Low-Peak™ time-delay Class CF fuses Voltage Motor size (Hp) Motor FLA (amps) Optimal protection (amps) Code max (amps) Heavy start (amps) 1 15 Vac, 1-phase 0 .167 4 .4 10 10 10 0 .25 5 .8 10 15 15 0 .333 7 .2 15 15 15 0 .5 9 .8 15 20 20 0 .75 13 .8 25 25 30 1 16 25 30 35 1 .5 20 30 35 45 2 24 40 45 50 3 34 50 60 N/A 5** 56 90 100 N/A

230 Vac,1-phase

0 .167 2 .2 6 6 6 0 .25 2 .9 6 6 6 0 .333 3 .6 6 10 10 0 .5 4 .9 10 10 10 0 .75 6 .9 15 15 15 1 8 15 15 1 7 .5 1 .5 10 15 20 20 2 12 20 25 25 3 17 25 30 35 5 28 45 50 60 7 .5 40 60 N/A N/A 10** 50 80 90 N/A 0 .5 2 .5 6 6 6 0 .75 3 .7 6 10 10 1 4 .8 10 10 10 1 .5 6 .9 15 15 15 2 7 .8 15 15 1 7 .5 3 11 1 7 .5 20 20 5 1 7 .5 30 35 35 7 .5 25 .3 40 45 50 20** 62 .1 100 N/A N/A 0 .5 2 .4 6 6 6 0 .75 3 .5 6 10 10 1 4 .6 10 10 10 1 .5 6 .6 10 15 15 2 7 .5 15 15 15 3 10 .6 1 7 .5 20 20 5 16 .7 25 30 35 7 .5 24 .2 40 45 50 20** 59 .4 90 N/A N/A Voltage Motor size (Hp) Motor FLA (amps) Optimal protection (amps) Code max (amps) Heavy start (amps) 0 .5 2 .2 6 6 6 0 .75 3 .2 6 6 6 1 4 .2 10 10 10 1 .5 6 10 15 15 2 6 .8 15 15 15 3 9 .6 15 20 20 5 15 .2 25 30 30 7 .5 22 35 40 45 20** 54 90 100 N/A 0 .5 1 .1 3 3 3 0 .75 1 .6 3 3 3 1 2 .1 6 6 6 1 .5 3 6 6 6 2 3 .4 6 6 6 3 4 .8 10 10 10 5 7 .6 15 15 15 7 .5 11 1 7 .5 20 20 10 14 25 25 30 15 21 35 40 45 20 27 40 50 60 50** 65 100 N/A N/A 0 .5 0 .9 3 3 3 0 .75 1 .3 3 3 3 1 1 .7 3 3 3 1 .5 2 .4 6 6 6 2 2 .7 6 6 6 3 3 .9 6 10 10 5 6 .1 10 15 15 7 .5 9 15 20 20 10 11 1 7 .5 20 20 40** 41 70 80 80 Note: Use Code Max column for low to moderate reverse/jog/plug applications . *Heavy Start permitted only if Code Max does not allow motor start-up . Based on motor FLA from NEC® tables 430 .248 and 430 .250 .

Compact Circuit Protector (CCP) UL Class CC, CF (CUBEFuse), midget and IEC 10x38mm fused disconnect switches Eaton.com/bussmannseries 1.8 2.6 3.7 1.9 .190 1.8 2.9 2.2 3.7 .190 33 NO 41 NC 34 NO 42 NC 42 NC

34 NO33 NO

Auxiliary Contacts: Description: NO+NC contact output to indicate the status of the switching mechanism on the CCP . Specifications:

  • Rated ampacity 5 A
  • Rated voltage 240 Vac
  • NC/NO contacts are closed/open when the CCP switch is in the “ON” position (closed)
  • Flammability rating UL 94V0 Agency information
  • UL 98 Recognized, File E155130, Guide WHTY2
  • cULus to CSA, Standard 22 .2 No . 4-04
  • IEC 60947-5-1 Wiring
  • 20-16AWG (0 .5 to 1 .5mm2) wire
  • Torque 5 Lb-In (0.68N•m)
  • For use with only 75°C Cu wire Packaging
  • The CCP-AUX and CCP-AUX-100 are packaged individually
  • A single unit is capable of mounting to a 1-, 2-, or 3-pole CCP Installation technique
  • Mounts on the right side ONL Y of the CCP , and mechanically interlocks with the CCP switch handle with hardware provided IP20 rating — yes Environmental data
  • Storage and operating temperature: -20°C to 75°C Catalog numbers
  • 1-60 A, CCP-AUX
  • 70-100 A, CCP-AUX-100 Description Max per CCP Signal output Agency information Catalog no. Auxiliary Contacts NO+NC for Switch Status up to 60A 1 per CCP (1-, 2- or 3-pole) 5A/240 Vac UL 98 Recognized, cURus 22 .2 No . 4-04, IEC 60947-5-

1 AC-15

(1-, 2- or 3-pole) 5A/240 Vac UL 98 Recognized, CSA C22 .2 No . 4-04 CCP-AUX-100 De-energize all circuits before installing or removing any CCP-AUX devices and follow all prescribed safety procedures . Installed on a CCP-3-xx Up to 60A CCP 70 to 100A CCP Dimensions – mm (in) Up to 60A CCP 70 to 100A CCP

Compact Circuit Protector (CCP) UL Class CC, CF (CUBEFuse), midget and IEC 10x38mm fused disconnect switches Eaton.com/bussmannseries PLC fuse monitor: Description: A resettable three- phase fuse monitor that integrates with the I/O card in a Programmable Logic Controller (PLC) . Specifications:

  • Signal output to PLC:
  • +24Vdc, 10mA max
  • Output signals:
  • Digital 0Vdc (low), 24Vdc max (high)
  • 0Vdc Low – fuse is good
  • 24Vdc High – fuse has opened When the fuse opens, the output signal is sent high and will remain high until the unit is reset . Agency information
  • UL 98 Recognized, File E155130, Guide WHTY2
  • cULus to CSA, Standard 22 .2 No . 4-04 Emissions and immunity testing
  • Electrostatic discharge, IEC 61000-4-2
  • Electrical fast transient/burst, IEC 6100-4-4
  • Surge immunity, IEC 61000-4-5 Rated impulse voltage
  • 8kV Local indication
  • Two distinct LEDs indicate unit power (green) and open fuse (red) . Open fuse LED is resettable upon the replacement of the fuse and the actuation of the reset switch Flammability rating
  • UL 94V0 Wiring
  • For power, signal and ground connections use shielded twisted pair 22-24AWG (0 .34-0 .25mm2) 300V rated wire Packaging
  • The CCP-PLC-IND is packaged individually
  • A single unit monitors up to three phases . Package includes 0 .1 10” (2 .8mm) quick connects for power, signal and ground connections Minimum circuit voltage
  • Minimum circuit voltage required across the CCP is 100 Vac/dc for the remote indication device to operate Installation technique
  • Mounts on the left side ONL Y of the CCP and mechanically interlocks with the CCP switch handle with hardware provided IP20 rating — yes Storage and operating temperature
  • -20°C to 75°C PLC programming
  • The CCP-PLC-IND signal line is designed to provide a digital input to a PLC I/O card . In this case, a Programmable Logic Control program must be written to properly interpret the input signal to the PLC . The PLC program should check for consecutive high signals before taking action on a critical process . Catalog numbers
  • 1-60 A, CCP-PLC-IND
  • 70-100 A, CCP-PLC-100

Description

Min. circuit Volts Agency information Catalog no. Wired remote fuse indication for PLC

applications

(1, 2- or 3-pole) 24Vdc/ 10mA 100 Vac UL 98 Recognized, cURus 22 .2 No . 4-04 CCP-PLC-IND Wired remote fuse indication for PLC De-energize all circuits before installing or removing any CCP-PLC-IND devices and follow all prescribed safety procedures . Installed on a CCP-3-xx Up to 60A CCP 70 to 100A CCP

Compact Circuit Protector (CCP) UL Class CC, CF (CUBEFuse), midget and IEC 10x38mm fused disconnect switches Eaton.com/bussmannseries PLC wiring schematic: Connection from CCP-PLC-IND to CCP Connections for CCP-PLC-IND from a CCP-3-XX to a remote monitoring device Connect leads from CCP-PLC-IND to the terminals as shown . There is a dedicated terminal on the CCP to accept the spade connectors from the CCP-PLC-IND . NOTE: When monitoring a 1-or 2-pole CCP , trim unused leads . PLC power supply CCP-PLC-IND PLC input card +24 Vdc

0 Vdc/Gnd

+24 Vdc +24 Vdc 10 mA max. The CCP-PLC-IND needs to be powered by the same +24 Vdc and ground (0 Vdc/Gnd return) terminals that feed the PLC input card. If it is not, it may improperly signal. If feeding multiple CCP-PLC-INDs from different power supplies, there must be multiple input cards being powered by those same power supplies as well. Circuit monitoring leads from CCP-PLC-IND to CCP (100 Vac – 600 Vac) Circuit monitoring leads from PLC or remote monitoring device .

Compact Circuit Protector (CCP) UL Class CC, CF (CUBEFuse), midget and IEC 10x38mm fused disconnect switches Eaton.com/bussmannseries 2.6 1.8 3.7 1.9 2.0 2.9 2.2 3.7 ON RESET STATUS +24vDC +24vDC GND SIG ON RESET STATUS +24vDC +24vDC GND SIG 5L 3 3L 2 1L 1 6T 3 4T 2 2T 1 6T 3 2T 14T 2 1L 13L 25L 3 Dimensions – mm (in) Up to 60A CCP 70 to 100A CCP

Compact Circuit Protector (CCP) UL Class CC, CF (CUBEFuse), midget and IEC 10x38mm fused disconnect switches Technical Data 1 157 Effective March 2018 The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Eaton reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Eaton also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. Eaton, Bussmann, CUBEFuse and Low-Peak are valuable trademarks of Eaton in the US and other countries. You are not permitted to use the Eaton trademarks without prior written consent of Eaton. CSA is a registered trademark of the Canadian Standards Group UL is a registered trademark of the Underwriters Laboratories, Inc. Eaton

1000 Eaton Boulevard

Cleveland, OH 44122 United States Eaton .com Bussmann Division 1 14 Old State Road Ellisville, MO 63021 United States Eaton .com/bussmannseries © 2018 Eaton All Rights Reserved Printed in USA Publication No . 1 157 – BU-SB15192 March 2018 For Eaton’s Bussmann series product information, call 1-855-287-7626 or visit: Eaton.com/bussmannseries Follow us on social media to get the latest product and support information.