MODEL: CB2 CB2 SPECIFICATIONS ES-2630 Rev.6 Page 1/7 http://www.m-system.co.jp/ Plug-in Signal Conditioners M-UNIT COMPUTER BACKUP STATION Functions & Features

  • Holding and manipulating control signals in case of computer or DCS failure
  • Ramp rate adjustable
  • High-density mounting Typical Applications
  • Computer and DCS backup applications
  • Used as manual-auto controller (1.97) 136 (5.35) (3.15) mm (inch) MODEL: CB2–[1]–[2][3]

ORDERING INFORMATION

  • Code number: CB2-[1]-[2][3] Specify a code from below for each of [1] through [3]. (e.g. CB2-A-B/Q)
  • Special output range (For codes Z & 0)
  • Specify the specification for option code /Q (e.g. /C01/S01) [1] OUTPUT Current A: 4 – 20 mA DC (Load resistance 750 Ω max.) B: 2 – 10 mA DC (Load resistance 1500 Ω max.) C: 1 – 5 mA DC (Load resistance 3000 Ω max.) D: 0 – 20 mA DC (Load resistance 750 Ω max.) E: 0 – 16 mA DC (Load resistance 900 Ω max.) F: 0 – 10 mA DC (Load resistance 1500 Ω max.) G: 0 – 1 mA DC (Load resistance 15 kΩ max.) Z: Specify current (See OUTPUT SPECIFICATIONS) Voltage 1: 0 – 10 mV DC (Load resistance 10 kΩ min.) 2: 0 – 100 mV DC (Load resistance 100 kΩ min.) 3: 0 – 1 V DC (Load resistance 100 Ω min.) 4: 0 – 10 V DC (Load resistance 1000 Ω min.) 5: 0 – 5 V DC (Load resistance 500 Ω min.) 6: 1 – 5 V DC (Load resistance 500 Ω min.) 4W: -10 – +10 V DC (Load resistance 2000 Ω min.) 0: Specify voltage (See OUTPUT SPECIFICATIONS) [2] POWER INPUT AC Power B: 100 V AC C: 110 V AC D: 115 V AC F: 120 V AC G: 200 V AC H: 220 V AC J: 240 V AC DC Power S: 12 V DC R: 24 V DC [3] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q (multiple selections) COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating TERMINAL SCREW MATERIAL /S01: Stainless steel

RELATED PRODUCTS

  • Soft-Terminal (model: ST/STL) GENERAL SPECIFICATIONS Construction: Plug-in Connection: M3.5 screw terminals Screw terminal: Chromated steel (standard) or stainless steel Housing material: Flame-resistant resin (black) Isolation: Input to output to power Overrange output: 0 to 100 % Ramp rate adjustment: Approx. 5 – 30 sec. (front) Zero adjustment: -5 to +5 % (front) Span adjustment: 95 to 105 % (front) INPUT SPECIFICATIONS ■ Contact Input: TTL level (5V-CMOS level) or open collector/dry contact (saturation voltage ≤1 V, sink current 0.5 mA)
  • Input signal from the computer UP: The output increases with UP signal ON. DOWN: The output decreases with DOWN signal

MODEL: CB2 CB2 SPECIFICATIONS ES-2630 Rev.6 Page 2/7 http://www.m-system.co.jp/ ON. STOP: The CB2 tracks the computer input with the STOP signal ON; holds the value just before the OFF signal with OFF.

  • Soft-terminal input in manual mode UP: The output increases with UP signal ON. DOWN: The output decreases with DOWN signal ON. OUTPUT SPECIFICATIONS ■ DC Current: 0 – 20 mA DC Minimum span: 1 mA Offset: Max. 1.5 times span Load resistance: Output drive 15 V max. ■ DC Voltage: -10 – +12 V DC Minimum span: 5 mV Offset: Max. 1.5 times span Load resistance: Output drive 10 mA max.; 5 mA for negative voltage output; at ≥ 0.5 V INSTALLATION Power input
  • AC: Rating ±10 %, 50/60 ±2 Hz, approx. 5 VA at 100 V approx. 7 VA at 200 V approx. 10 VA at 240 V
  • DC: Rating ±10 % (ripple 10 %p-p max.) approx. 3.5 W (150 mA at 24 V) Operating temperature: -5 to +55°C (23 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Mounting: Surface or DIN rail Weight: 450 g (0.99 lb) PERFORMANCE in percentage of span Temp. coefficient: ±0.02 %/°C (±0.01 %/°F) Response time: Approx. 5 – 30 sec. variable (0 – 100 %) Output memory at power failure: The output value is stored in memory. Line voltage effect: ±0.1 % over voltage range Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 1000 V AC @1 minute (input to output to power)

2000 V AC @1 minute

(input or output or power to ground)

MODEL: CB2 CB2 SPECIFICATIONS ES-2630 Rev.6 Page 3/7 http://www.m-system.co.jp/ CONNECTION EXAMPLES ■CB2 Used Independently AUTO OUTPUT ( ↑) AUTO OUTPUT ( ↓) (–) OUTPUT (+) OUTPUT COMPUTER FAILURE POWER + – + – E/P 4 – 20mA DC COMPUTER BACKUP FIELD CONTROL VALVE FLOWMETER COMPUTER PANEL FRONT BACK UP DOWN FEEDBACK SIGNAL STOP ■CB2 Used in Combination with ST/STL UP DOWN MANUAL CONTROL 6 (+) 7 (–) AUTO-MANUAL SELECTOR SWITCH OUTPUT INDICATOR MONITOR TERMINALS (4 – 20mA DC) 10-pin CONNECTOR MANUAL OUTPUT (↑ ) MANUAL OUTPUT (↓ ) COM. (–) OUTPUT (+) OUTPUT COMPUTER FAILURE POWER + – + – E/P 4 – 20mA DC FEEDBACK SIGNAL ST/STL COMPUTER BACKUP STATION FIELD CONTROL VALVE FLOWMETER COMPUTER PANEL FRONT BACK STOP UP DOWN AUTO OUTPUT (↑ ) AUTO OUTPUT (↓ ) AUTO

MODEL: CB2 CB2 SPECIFICATIONS ES-2630 Rev.6 Page 4/7 http://www.m-system.co.jp/ EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) 5678 2111 10 80 (3.15) 80 (3.15) (.79) 40 (1 .57) 50 (1 .97) 7 .8 (.31) CLAMP (top & bottom) DIN RAIL 35mm wide2–4.5 (.18) dia. MTG HOLE 25 (.98) deep 11 –M3.5 SCREW

  • When mounting, no extra space is needed between units. SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM UP 9 From SOFT-TERMINAL DOWN COM. STOP From COMPUTER UP DOWN COM. Isolation

7 U(+)

V(–)8 POWER OUTPUT Output Driver Control Input Circuit Controller Base Socket SZ RESPONSE ADJ. Enabled only with the STOP input OFF.

MODEL: CB2 CB2 SPECIFICATIONS ES-2630 Rev.6 Page 5/7 http://www.m-system.co.jp/ OPERATION ■ CB2 Used Independently In normal operating mode, the CB2 responds to UP/DOWN signals from the computer in the preset ramp rate. If the computer fails, this will be detected as a "STOP" command and output will be held at the value prior to the breakdown. You can increase the output signal by closing across the terminals 9 – 11, and decrease it by closing 10 – 11. The output responds in the preset ramp rate. ■ CB2 Used in Combination with ST/STL In normal operating mode, the CB2 responds to UP/DOWN signals from the computer in the preset ramp rate. If the computer fails, the "STOP" command will override computer output and put the unit in the manual operation mode by the ST/STL. Using the top-mounted UP-DOWN buttons, output can be increased or decreased in the preset ramp rate. Output signal value can be read on the top-mounted indicator. For more precise control, use the monitor terminals. Also the computer input can be overridden with the AUTO-MANUAL selector on the Soft-Terminal. This is useful when you need to change the output quickly during automatic operation by the computer control. Span Adj. Zero Adj. Ramp Rate (response) Adj. COMMAND TERM. SIGNAL STATUS Computer DOWN 4 – 6 0 1 0 1 – – – – STOP 5 – 6 1 1 1 1 0 0 0 0 UP 9 – 11 – –– – 1 00 1ST/STL DOWN 10 – 11 – – – – 0 1 0 1 Output of the CB2 1 – 2 HH HH [Keys] 1 : ON 0 : OFF – : ON or OFF H: Hold : Increase : Decrease

MODEL: CB2 CB2 SPECIFICATIONS ES-2630 Rev.6 Page 6/7 http://www.m-system.co.jp/ SYSTEM CONFIGURATION EXAMPLES Analog Control Using Contact Closure Outputs from a Computer CB2 Used Independently • CB2 – ST/STL Combination Employing an Analog Controller in a DDC Control Loop

  • CB2 – ST/STL Combination Remote Control of an I/O Positioner with Switches Control Loop with Multiplex Transmission E / P M COMPUTER Control Valve E / P M COMPUTER Control Valve Computer Backup Sta. < CB2 > Computer Backup Sta. < CB2 > Soft-Terminal < ST > E / P M COMPUTER Control Valve Controller Soft-Terminal < STL > Computer Backup Sta. < CB2 > E / P M REMOTE I / O Control Valve Computer Backup Sta. < CB2 > E / P M Control Valve < CB2 > E / P M Control Valve COMPUTER Flowmeter Flowmeter Flowmeter SYSTEM BUS < CB2 > E / P M Control Valve Computer Backup Sta. < CB2 > Indicator CLOSE OPEN I I II

MODEL: CB2 CB2 SPECIFICATIONS ES-2630 Rev.6 Page 7/7 http://www.m-system.co.jp/ Specifications are subject to change without notice.