Features

 Analog/addressable and conventional input circuits.  SmartScan™ protocol up to 99 detectors and 99 devices per loop.  SmartStart™ self-programming logic.  Fully modular.  160-character, four-line display.  One to eight Signal Line Circuits (SLC) for up to 1584 addressable points.  Automatic default response for increased survivability.  1000-event history log.  Digital SLC protocol.  PC or front-panel programming.  Password protected.  Serial annunciator, remote display, and remote printer options.  One-man, selectable-input walk test.  Automatic drift compensation.  Coded signaling.  Day/night mode settings.  Approved for Supervisory Service.  Optional UDACT.  Adjustable sensor sensitivity and temperature settings.  Operates as either a stand-alone panel or a network node using SmartLink™. IF632SS g2001ph1.jpg An ISO 9000-2000 Company SIGNALING S521 APPROVED FM

12 Clintonville Road, Northford, CT 06472-1610 USA  Tel: (203) 484-7161  Fax: (203) 484-7118

CS-2492 Rev. A page 2 of 3 www.gamewell-fci.com Operator’s Display (Continued) The Reset key returns the control panel to idle mode after an alarm condition has been cleared. Trouble conditions that have been cleared will automatically return the control panel to idle mode when the problem has been corrected. Trouble conditions that have been acknowledged will resound the internal sounder if the condition is not cor- rected within a programmed time period. The Signal Silence key deactivates notification appliances. This function can be modified by user programming to operate only after a specified time period. There are three additional programmable switches avail- able to control application-specific operations. Keys for programming and bypass functions, along with LEDs for active and trouble conditions, are provided for the City Connection, and two signal circuits which are part of the Common Control section. Other Panel/System Components The IF632 COMMON CONTROL SECTION comprises the heart of the system. The common control section houses the main CPU and all system memory as well as providing local and remote communications and supervision. The common control contains the common system relays, two signal circuits, city tie, and optional EIA-232 port. All inter- action with the common control section is through the oper- ator’s display panel. Four relay circuits control auxiliary functions. The relays, rated at 10 Amps, are controlled by the main CPU. Two 24 VDC notification appliance circuits (NAC) are provided. The NACs can provide a steady or coded output. All circuits are power-limited per NEC 760 and UL 864. The IF632 SmartScan™ ANALOG INTERFACE MODULE (SSM-2/2E and SSM-4) occupies one bay and has from two to four SLC circuits that can monitor and control up to 198 addressable/analog devices each for a total of 792 points per bay or 1584 points total. The analog interface module has a dedicated microprocessor which simulta- neously communicates with the connected field devices and the main CPU. This feature allows the IF632 to main- tain maximum communications speed throughout the sys- tem. Analog/addressable circuits can be wired as non- polarized in Style 4, 6, or 7. The communications protocol provides for alarm verification per detector, detector adjust- ability and compensation, adjustable analog heat detector range (131°F to 194°F/55°C to 90°C), circuit isolation, and priority interrupts. Priority interrupts allow contact-type devices such as manual fire alarm stations to interrupt the polling cycle and transmit their addresses at any time dur- ing a polling sequence. The digital protocol allows the IF632 to operate on most types of field wiring, greatly expanding its use in retrofit applications (consult the SLC manual or Gamewell-FCI Technical Support for specific wiring requirements). The CONVENTIONAL INPUT MODULE (CIM-8) occupies one bay and provides eight hard-wired input circuits for monitoring conventional detectors and contact-type devices. The CIM-8 monitors and reports each circuit’s analog status to the CPU as it distinguishes between detectors and contact devices and determines if two or more detectors are in alarm. Each input module uses one slot in the MPU bus and is supplied with its own display module. The display module provides LED annunciation of alarm and trouble conditions and has a switch (per circuit) for programming and bypass functions. The display has space for user-defined custom labels for each circuit. Beyond normal alarm and supervisory functions, the input circuits can be programmed for Remote Acknowledge, Reset, Signal Silence, and Release Abort switches. Cir- cuits can be wired for Style B, D, and E service and are capable of monitoring normally-closed devices. The 600 Series UNIVERSAL SIGNAL MODULE (USM-8) occupies one bay and is a multifunctional eight-circuit out- put module. USM-8 modules communicate via the MPU bus and require one expansion slot each. The USM can be configured as 24 VDC signaling circuits. Modules are pro- grammed in two-circuit increments, making it possible to perform all four functions with a single module. Signal cir- cuits provide steady or coded outputs. All circuits are power-limited per NEC 760 and UL 864. Signal circuits can be wired in either Style Y or Z. Signal modules are supplied with their own display that provides LED annunciation of activation and trouble conditions and has a switch (per cir- cuit) for programming and bypass functions. The display has space for user-defined custom labels for each circuit. The 600 Series POWER SUPPLY (MPS-8) furnishes sys- tem operating and signaling power. The supply is equipped with a battery charger for maintaining the secondary power source. The power supply is monitored by the main CPU to ensure that adequate power levels are maintained. The power supply design allows for high efficiency while provid- ing precise power output. The battery charger is capable of operating with lead-acid batteries and maintaining up to 50 AH batteries. The 600 Series RELAY MODULE (RM-8) supplies eight NO/NC relays for control of auxiliary functions. The relays are controlled by the main CPU and are fully programma- ble. Each position on the MPU bus can accommodate a relay module. The relays are rated at 10 Amp and each is provided with a feedback point for positive confirmation of activation. Like all 600 Series expansion modules, the relay module reports activation. The 600 Series BUILDING CONTROL MODULE (BCM-8) provides an interface between the fire alarm and HVAC systems. Relays (rated at 10 A) are accompanied by feed- back points for positive confirmation of the programmed action. The BCM is available in eight-circuit modules that

www.gamewell-fci.com CS-2492 Rev. A page 3 of 3 are monitored and controlled by the MPU bus which can monitor and control one expanded (i.e., eight-circuit) BCM per position. The display for the BCM provides LEDs for annunciation of relay state or feedback, and windows for user-defined custom labeling. In addition, the display for the BCM comes with a three position ON/OFF/AUTO switch per circuit for manual override of the programmed automatic functions. Although the common control module is equipped with a city tie circuit which is suitable for most applications, an optional four-circuit CITY TIE MODULE (CTX-4) has been developed for applications that require multiple connec- tions. The city tie module connects to the MPU bus and is supplied with a display module. The CTX-4 can also be used for applications requiring a polarity-reversal output. The SYSTEM HOUSING CONFIGURATION for the IF632 control panel is a two-bay cabinet and will accommodate: two of the 600 Series modules, device control display (BCD, RCD, SCD) over the analog module, the common control, power supply, and batteries.

Applications

The Gamewell-FCI IdentiFlex 632 Analog Addressable Control Panel is ideal for any project that require state-of- the-art life safety systems. The embedded CPU offers users unrivaled reliability with flexibility and value. The IF632 control panel is designed to incorporate the ana- log addressable sensors into an integrated life safety sys- tem which will meet today’s most stringent requirements. Addressable input-interface devices provide the means to communicate with cost-effective conventional devices in areas that do not require analog sensors. Addressable control-output devices serve as the interface between the analog circuits and building functions. The outputs are controlled via Control-by-Event software and can be programmed to respond to any event. The control devices can also be used as supervised remote signal cir- cuits. The IF632’s optional EIA-232 output expands the system’s display and control capability. Serial annunciators can be added to display system activity and control. The serial annunciator drivers provide the interface to graphic annunciators. An alphanumeric display (RAN2-RCS) can also be used for remote status and control. The alphanumeric display is designed to communicate over the serial communications network. It features a 160-character display and provides remote reset/acknowledge/silence keys. See RAN/SAN data sheets CS-2025 and CS-2027 for complete annuncia- tor details. The IF632 communicates with an EIA-232 printer either locally or remotely for documentation of system activity. The printer interface accepts serial communications from the control panel and provides a parallel output to the printer. Specifications Common Control: Standby Current: 0.275A Alarm Current: 0.407A plus signaling circuit power, plus 0.002A for master box, or plus 0.022A for reverse-polarity. Input Power: 120 VAC, 2.0A Auxiliary Output: S+/S–, A+/A–: 24 VDC, 2.0A combined maximum Common Relays: 10A @ 30 VDC, or 250A VAC Signaling Circuits: 24 VDC nominal @ 2.0A per circuit Panel Dimensions: Cabinet: 30.0" H x 22.0" W x 5.5" D (76.2 H x 55.9 W x 13.97 D cm) Battery Capacity: 50 AH Battery Storage Dimensions: Standard Cabinet: 10.5" H x 11.0" W x 4.5" D (26.7 H x 27.9 W x 11.43 D cm) Relative Humidity: 93% non-condensing Temperature Rating: 32°F – 120°F (0°C – 49°C)

Ordering Information

IF632 Analog/addressable control panel, with two (2) open module bays available. SSM-2 Two (2) circuit SmartScan™ analog/ addressable SLC cards, 99 detectors and 99 devices per SLC. Note: Must be ordered separately, not included with the IF632. SSM-2RE Two (2) circuit expander modules. Plugs into the SSM-2 to expand the SSM-2 from two (2) to four (4) SmartScan™ SLCs. Note: Must be ordered separately, not included with IF632 or SSM-2. CAB632 Empty cabinet housing with plexi-glass door.

72122 IdentiFlex 632 Installation/Operating