DESCRIPTION

The Fire Control Instruments 7200 Series Analog/ FCINET ®/Hardwire Fire Alarm Control is multiprocessor-based and designed for commercial, indus - trial, proprietary, central station and institutional applica - tions. The 7200 Series may be configured as an analog/addressable, point identified system where individ - ual identification of initiating devices and control points are required, a conventional hard-wired, zone-identified system, or combination of both. It meets the requirements of NFPA Standard 72, and is suitable for releasing device service. The 7200 Series is field programmable to perform a wide variety of functions. Inherently power limited, it can accom- modate 15 units of one type with a maximum total combina- tion of 30 units. Units are available in a wide range of configurations. Designed around multiprocessors that provide and control all system functions, the 7200 Series has a powerful software structure that affords true “distributed processing” of all sys- tem components. The system can accommodate module placement at either a central location, or up to fifteen (15) re- mote locations via the FCINET ® communications to provide multiplex system features. The FCI Listed Integrated Sensitivity Testing (LIST) pro- gram meets all NFPA 72 requirements for testing and moni- toring of sensor sensitivity. The 7200 Series control has been tested for extraordinary ambient conditions with 6,000 volt transient immunity cir- cuits. OPTIONAL FEATURES FireVac®7200 Distributed Fire Alarm/ Voice Evacuation System Operation 80-Character Alpha-numeric Display Listed Integral Sensitivity Testing meets NFPA 72 Testing Requirements Drift Compensation Overcomes Effects of Aging or Environment on Sensor Sensitivity “Dirty” and “Very Dirty” Sensor Indications Day/Night Sensor Sensitivity Setting Class A, Style 6/7 or Class B, Style 4 Signaling Line Circuits Selectable Analog Sensor Alarm Verification Individually Programmable Control and Power Relays Switching Technology Power Supply Interface with FireVac ®III Emergency Voice Evacuation System Releasing Device Unit with Abort Timer

7200 SERIES

ANALOG/FCINET®/HARD-WIRE FIRE ALARM CONTROL

FEATURES

UL Listed to Standard 864, Category UOJZ FCINET ® (FCI Communication Network) Control/Remote Signaling Line Circuits Inherently Power Limited per UL 864 ADAC ® Degrade Operation Suitable for Releasing Device Service Two Field Programmable Modes: Front Panel/Auto-configuration Computer Programming Diagnostic Center Non-volatile Data Storage Distributed Processing RS-232 Serial Output Walk Test Feature

500 Event History Log

Class A, Style D or Class B, Style B Initiating Zone Circuits Class A, Style Z or Class B, Style Y Individually Programmable Notification Appliance Circuits Alarm Verification Dual Rate Charger Enhanced Transient Protection Field Expandable

16 Southwest Park, Westwood, MA 02090 USA TEL: (781) 471-3000 FAX: (781) 471-3099

An ISO 9001 Certified Company 9020-0271 Rev. H

The operating system resides in an EPROM (Eras - able Programmable Read Only Memory). The system’s functional program, which is defined by the user, is stored in an EEPROM (Electrically Erasable And Pro- grammable Read Only Memory), and may be pro - grammed by either front panel switches or via a uniquely “User Friendly” computer program. Both forms of storage are non-volatile. The system features a 500-event History Log. SYSTEM CONTROL UNIT The main System Control Unit (SCU) serves as a ba- sic information and control center for standard operator functions. A self-contained Programming Diagnostic Center with a two-digit, 7-segment LED digital display pro - vides system operation, programming and internal trouble shooting features. An RS-232 port provides su- pervised output to a remote printer or video terminal. The power supply contains a dual rate charger. The transformerless Switching Power Supply Unit (SPSU/V) can maintain sealed lead-acid batteries up to 55 amp/hr capacity. AUXILIARY DEGRADE ALARM CIRCUIT (ADAC®) The 7200 Series control features Auxiliary Degrade Alarm Circuit (ADAC®) degrade operation. In the event of main processor failure, the “DEGRADE” LED will light. In the event an alarm is received, each subor- dinate processor is capable of operating a general alarm program. In the event of multiple or all processor failure, the ADAC ® mode will operate the system in a general alarm configuration. ALARM VERIFICATION The Alarm Verification feature is programmable for all smoke sensors, analog or conventional. This allows smoke sensors that are installed in environments prone to nuisance or unwanted alarms to operate as follows: In the event the sensor alarms, a distinctive alarm veri- fication message will be displayed for 25 seconds. The circuit or device will then automatically reset. The sys- tem will then remain in the verification mode for a pe- riod of approximately 85 seconds. If the sensor or any other sensor on the same circuit alarms within this pe- riod, a system alarm will occur. If no alarm occurs within this period, the system will return to normal con- dition. WALK TEST The Walk Test feature is performed on a signaling line circuit, or zone basis and enables testing of the system by a single individual. During this test, the act of plac- ing a device in alarm will cause four pulses on the noti- fication appliance circuits, operation of a supervisory switch will cause three pulses, while removal or dis - connection of an initiating device will cause two pulses. The events will be recorded on a printer, if one is installed. SELECTIVE ALARM SOUNDING The notification appliance circuits on the SCU, DSU and DIU units can be individually programmed to acti- vate on alarm, trouble, or supervisory signal from a spe- cific addressable module/sensor, hardwired zone or zones, and sound non-code, temporal pattern, march time or fixed code signals. Cross-zoning and “Ring by Zone” operation are readily accomplished. 2o f4 9020-0271

The optional Keyboard Display Unit (KDU) features an 80-character alphanumeric display and 12-key keypad to en- hance and simplify system operation by the user. It may be remotely located. The Keyboard Display Unit, Local, (KDU-L) is intended for mounting in the control cabinet only, and also provides an interface for remote units. The Analog Loop Unit (ALU) provides two (2) signaling line circuits, wired Class A or B, Styles 4, 6 or 7. Each circuit can address 197 points (99 analog sensors or modules; 98 monitor and/or control points. ALU units configured with the Field Configuration Program 5.2 or later do not require twisted pair wire and will operate on “straight lay” wire. The Distributed Intelligent Unit (DIU) is remotely located and duplicates many of the functions of the System Control Unit (SCU). DRIFT COMPENSATION The 7200 Series continuously monitors the sensitivity of all installed analog smoke sensors to measure any change in their sensitivity due to the environment. The drift compensa- tion software overcomes effects of aging or environment on sensor sensitivity giving a dependable alarm threshold. “Dirty” and “Very Dirty” indicators are activated when a sen- sor drifts beyond acceptable limits. Sensors can automati - cally change sensitivity with time of day to be “matched” to their real-life environment. Drift compensation also meets the sensitivity testing re- quirements of NFPA 72. LISTED INTEGRATED SENSITIVITY TEST (L.I.S.T) Each analog smoke sensor is automatically tested by the system software a minimum of three (3) times per day. The test is a recognized functional test of the ion sensor chamber and photocell of the photoelectronic sensor and meets the sensitivity and maintenance testing requirements of NFPA 72. This test will give a “Test Failed” indication and identify the individual sensor if it fails the test. OPTIONAL UNITS-HARDWIRED Optional hardwired units include a Quad Zone Unit (QZU), with four (4) Style D (Class “A”) or Style B (Class “B”) initiating zone circuits, an Eight Zone Unit (EZU), with eight Style B (Class “B”) initiating zone circuits, an Eight Zone Daughter board (EZD) which gives Style D (Class “A”) capability and LED annunciator output to the EZU, and an Eight Zone Annunciator board (EZA) which gives LED annunciator output to the EZU unit. Alarm verification is available in the QZU and EZU units via software programming. OPTIONAL AUXILIARY UNITS Additional optional units include a Quad Relay Unit (QRU) and High Current Relay Unit (HRU), each containing four (4) individually programmable relays, each relay equipped with “OFF-AUTO-ON” user switch and status LED. The relays in these units can also be individually pro- grammed to energize either on alarm, trouble, or supervisory output from specific addresses/zones. A Dual Signal Unit (DSU) is available with a self-con - tained auxiliary power supply and two individually program- mable notification appliance circuits. AZone Coder Unit (ZCU) provides Positive, Non-interfer- ing and Successive (PNIS) coding output and offers a choice of optional relay operation upon completion of various rounds of the first code. The Remote Annunciator Unit (RAU) offers thirty two (32) supervised LED or incandescent lamp annunciator points and provision for remote switches. The RAU mounts inside the remote annunciator. The RAU-FV unit is designed to interface with the FireVac ®III Emergency V oice Evacua- tion System. The Panel Bus Adapter, (PBA) provides transient protec- tion for any remotely located units. Only one adapter is re- quired per 7200 Series system. APPROV ALS UL S1869 per UL864 FM 0W6A5.AY CSFM 7165-0694:174 NYC MEA 62-93-E 9020-0271 3o f4 OPERATING CHARACTERISTICS Operating temperature 32 to 120 o F( 0 t o 4 9o C) Relative humidity 85% (non-condensing) DIMENSIONS CAB-A‡ 19 3/8" High, 15" Wide, 4" Deep (49.23 x 38.1 x 10.16 cm) CAB-B 28" High, 21" Wide, 4" Deep (71.12 x 53.34 x 10.16 cm) CAB-C 38" High, 21" Wide, 4" Deep 96.52 x 53.34 x 10.16 cm) CAB-D 38" High, 30" Wide, 6" Deep (96.52 x 76.2 x 15.24 cm) NOTE: ‡ CAB-A (Not ULC Listed) is intended for use only with SPSU, KDU/KDU-L, and ALU or DIU units. Remote Keyboard Display Unit (KDU)

Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice. © 1997 All Rights Reserved

ORDERING INFORMATION

TR-1B TR-1R Semi-Flush Trim Ring (CAB-A) TR-2B TR-2R Semi-Flush Trim Ring, (CAB-B) TR-3B TR-3R Semi-Flush Trim Ring, (CAB-C) RHBS RHRS Remote KDU housing, surface mount RHBF RHRF Remote KDU housing, flush mount TECHNICAL AND ORDERING INFORMATION Model Supv. Alarm Description Current Current SPSU-V .010 A .015 A Switching Power Supply Unit, Vertical SPSU‡ .010 A .015 A Switching Power Supply Unit SCU .050 A .260 A System Control Unit QZU-L .027 A .062 A Quad Zone Unit EZU-L .045 A .086 A Eight Zone Unit EZD-L .002 A .009 A Eight Zone Daughter board, (For Class A wiring) EZA-L .002 A .009 A Eight Zone Annunciator board ALU .065 A .085 A Analog Loop Unit DIU .017 A .072 A Distributed Intelligent Unit KDU .060 A .065 A Keyboard Display Unit KDU-L .060 A .065 A Keyboard Display Unit, Local (For replacement only) QRU-EOL .004 A .023 A Quad Relay Unit/FCINET ® Style 6 EOL HRU .004 A .034 A High-current Relay Unit DSU .025 A .075 A Dual Signal Unit with two (2) notification appliance circuits and auxiliary power supply. (Order XFMR transformer separately) ZCU .001 A .037 A Zone Coder Unit RAU .018 A .007 A* .075 A** Remote Annunciator Unit RAU-FV .018 A .040 A † FireVac ®III/7200 Series Interface Unit ATU .014 A .030 A Abort Timer Unit RDU .065 A .085 A Releasing Device Unit PBA —— —— Panel Bus Adapter * per LED ** per incandescent lamp † add .002 amp./ckt. ‡ For use in CAB-A only. FireVac®7200, FCINET®, FireVac® and ADAC® are registered trademarks of Fire Control Instruments, Inc.