Carling Technologies, Inc.
60 Johnson Avenue, Plainville, CT 06062
Email: sales@carlingtech.com Application Support: team2@carlingtech.com Phone: 860.793.9281 Fax: 860.793.9231 www.carlingtech.com C-SeriesC-Series CIRCUIT BREAKER The C-Series hydraulic-magnetic circuit breakers are ideal for applications that require higher amperage and voltage handling capability in a smaller package. They are available in 1-6 poles, 0.02-100amps, UL Recognized up to 480VAC or 150VDC, UL489 Listed up to 240VAC or 125VDC, with choice of time delays, terminal options, actuator styles and colors. The C-Series employs a unique arc chute design which allows for higher interrupting capacities of up to 10,000 amps. New thermoset glass filled polyester half shell construction provides for increased mechanical and electrical strength. The wiping contacts, mechanical linkage with two step actuaction, clean contacts providing high, positive contact pressure and longer contact life. Available with American Standard or Metric Threaded Stud terminals , or Saddle Clamp screw terminals. The optional mid-trip handle style actuator allows a visual indication of electrical overload with or without alarm feature. Product Highlights: Extensive list of Agency Approvals Available with Standard or Metric Stud terminals, or Saddle Clamp screw terminals Optional mid-trip handle style actuator Unique arc chute design which allows for higher interrupting capacities of up to 10,000 amps Exclusive Rockerguard and Push-To-Reset bezel Available with new solid color and two-color Visi- rocker® actuators New thermoset glass filled polyester half shell construction Typical Applications: Marine Telecom/Datacom Military Renewable Energy Generators & Welders Eco-Friendly Resources: Download 3D CAD Files IGS STP
Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
48 DC --- 110 - 150 --- --- 5000 TC1, OL1, U2 TC1, OL1, U2
0.02 - 70 --- --- 10,000 TC1,2, OL1,U1 TC1,2, OL1,U1 Must Have Agency Code "L" --- 71 -100 --- 10,000 TC1,2, OL0,U1 TC1,2, OL0,U1 Must Have Agency Code "L" 125 DC --- 0.02 - 50 --- 5000 TC1,2,OL1,U1 TC1,2,OL1,U1 Must Have Agency Code "L" 125 / 250 DC --- 0.02 - 50 --- 5000 TC1,2,OL1,U1 TC1,2,OL1,U1 Must Have Agency Code "L" 250 DC --- 0.02 - 50 --- 5000 TC1,2,OL1,U1 TC1,2,OL1,U1 Must Have Agency Code "L". 2 Pole Break Required for 250 Volts 0.02 - 100 --- --- 3000 TC1, OL1, U2 TC1, OL1, U2 Per Pole Rating 0.02 - 100 --- --- 5000 TC1,2,OL1,U1 TC1,2,OL1,U1 Must Have Agency Code "L"
150 DC --- --- 80 - 100 --- 5000 TC1, OL0, U3 --- Must Have Agency Code "L"
150 DC --- --- 101 - 175 --- 5000 TC1, OL0, U3 --- Must Have Agency Code "L" Parallel Pole
0.02 - 100 --- --- 3500 TC1, OL1, U2 TC1, OL1, U2 0.02 - 50 --- --- 3000 TC1,2,OL1,U1 TC1,2,OL1,U1 2 or 3 poles breaking single phase 51 - 100 --- --- 1000 TC1,2,OL1,U1 TC1,2,OL1,U1 2 or 3 poles breaking single phase 0.02 - 100 --- --- 5000 TC1,2,OL1,U2 TC1,2,OL1,U2 2 or 3 poles breaking single phase, "L" Agency Code 0.02 - 50 --- --- 3500 TC1, OL1, U2 TC1, OL1, U2 Per Pole Rating 0.02 - 100 --- --- 5000 TC1,2,OL1,U1 TC1,2,OL1,U1 Must Have Agency Code "L" --- 0.02 - 100 --- 3000 TC1, OL0, U2 TC1, OL0, U2 0.02 - 70 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 3 poles breaking 3 phase --- 0.02 - 90 --- 5000 TC1,2,OL0,U1 TC1,2,OL0,U1 Must Have Agency Code "L" 277 50 / 60 1 0.02 - 50 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 0.02 - 30 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 3 poles breaking 3 phase 0.02 - 30 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 2 poles breaking 1 phase 125 50 / 60 1 0.02 - 50 --- --- 3000 TC1, OL1, U2 TC1, OL1, U2 Per Pole Rating 0.02 - 50 --- --- 3500 TC1, OL1, U2 TC1, OL1, U2 2 or 3 poles breaking single phase 0.02 - 50 --- --- 3000 TC1,2,OL1,U1 TC1,2,OL1,U1 2 or 3 poles breaking single phase 1 0.02 - 50 --- --- 3500 TC1, OL1, U2 TC1, OL1, U2 0.02 - 50 --- --- 3000 TC1, OL0, U2 TC1, OL0, U2 Per Pole Rating 277 50 / 60 1 0.02 - 50 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 3 poles breaking 3 phase 277 50 / 60 1 0.02 - 50 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 250 50 / 60 3 0.02 - 50 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 3 poles breaking 3 phase 0.02 - 30 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 3 poles breaking 3 phase 0.02 - 30 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 2 poles breaking 1 phase 277 50 / 60 1 0.02 - 50 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 250 50 / 60 3 0.02 - 50 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 3 poles breaking 3 phase 125 / 250 50 / 60 1 0.02 - 100 --- --- --- --- --- 2 or 3 poles breaking single phase 0.02 - 30 --- --- --- --- --- 3 poles breaking 3 phase 125 / 250 50 / 60 1 DUAL COIL C-SERIES TABLE A: COMPONENT SUPPLEMENTARY PROTECTORS FULL LOAD AMPS SERIES CIRCUIT CONFIGURATION MAX. RATING FREQUENCY 250 50 / 60 480 50 / 60 1 480 / 277 50 / 60 480 50 / 60 1 480 / 277 50 / 60 GENERAL PURPOSE AMPS DC VOLTAGE ---80 80 DC SHORT CIRCUIT CAPACITY (AMPS) WITHOUT BACKUP FUSE WITH BACKUP FUSE 1 SWITCH ONLY 480 / 277 50 / 60 250 50 / 60 DC CURRENT RATING RELAY SHUNT 65 DC 250 50 / 60 --- --- 125 50 / 60 1 NOTES UL CSA APPLICATION CODES --- PHASE UL/CSA 2 | C-Series – General Specifications Electrical Tables Table A: Lists UL Recognized & CSA Accepted configurations and performance capabilities as a Component Supplementary Protector Notes for Table A: 1 Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse rated 15A minimum and no more than 4 times full load amps not to exceed 125A for 50 Amp or less rating and not to exceed 175 for 51 through 100 Amp rating *Manufacturer reserves the right to change product specification without prior notice.
Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com | 3 C-Series – General Specifications Electrical Tables Table B: Lists UL Recognized and CSA Accepted configurations and performance capabilities as a Manual Motor Controller. Table C: Lists UL Recognized, CSA Accepted , VDE and TUV Certified configurations and performance capabilities as a Component Supplementary Protector. Notes for Table B: 1 UL recognized and CSA Accepted at 480V refers to 3 & 4 pole versions used in a 3Ø, wye connected circuit or 2-pole version connected with 2 poles breaking. 1Ø and backed up with series fusing as stated above in note 1. *Series, Shunt and Relay Trip - Voltage Coil Construction not current coils Notes for Table C: 1 General Purpose ratings for UL/CSA only. 2 Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse rated 15A minimum and no more than 4 times full load amps not to exceed 125A for 50 Amp or less rating and not to exceed 175 for 51 through 100 Amp rating. RELAY
Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com 4 | C-Series – General Specifications Electrical Tables Table D: Lists UL Listed (489), CSA Certified (C22.2 No. 5.1-M) configuration and performance capabilities as a Molded Case Circuit Breaker. Table E: Lists UL Recognized, CSA Accepted configurations and performance capabilities as Protectors, Supplementary for Marine Electrical and Fuel Systems (Guide PEQZ2, File E75596). Ignition Protected per UL 1500. UL Classified Small Craft Table F: Lists UL Listed configurations and performance capabilities as Circuit Breakers for use in Communications Equipment (Guide DITT, File E189195), under UL489A. Notes from Table D: 1 Special catalog number required. Consult factory. CURRENT RATING INTERRUPTING CAPACITY (AMPS) 50,000 1 Limited to 2 Poles Max from 71 - 100 Amps. 10,000 Limited to 2 Poles Max from 71 - 100 Amps. 125 DC --- 0.10 - 100 5,000 1 - 3 Poles 125 / 250 DC --- 0.10 - 50 5,000 1 or 2 Poles (2 Poles Required for 250 Volts) 0.10 - 50 10,000 1 - 3 Poles 51 - 70 5,000 1 - 3 Poles 0.10 - 50 5,000 2 or 3 Poles. 1 Pole of a 3 Pole Unit is Neutral 0.10 - 50 10000 1 2 or 3 Poles. 1 Pole of a 3 Pole Unit is Neutral 240 50 / 60 1 0.10 - 30 5,000 1Pole 240 50 / 60 1 0.10 - 20 5,000 2 Pole 277 50 / 60 1 0.10 - 20 10,000 1Pole DUAL COIL 120 50 / 60 1 0.10 - 30 10,000 --- CIRCUIT CONFIGURATION FULL LOAD AMPSPHASE VOLTAGE 0.10 - 100 50 / 60 1120 / 240 DC CONSTRUCTION NOTES C SERIES TABLE D : UL489 LISTED BRANCH CIRCUIT BREAKERS SERIES 120 WITHOUT BACKUP FUSE MAX. RATING FREQUENCY ---
Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com | 5 C-Series – General Specifications Mechanical Physical Environmental Electrical 0.1 0.10.01 0.001 0.01 100 1000 15% 25% 35% 1 10010 TOLERANCE (%) O H M S CURRENT (AMPS) FIGURE 1 0.100 - 5.0 5.1 - 20.0 20.1 - 100 RESISTANCE, IMPEDANCE VALUES from Line to Load Terminals (Values Based on Series Trip Circuit Breaker) AMPERE RATING Time Delay Curves 42, 44 & 46 (50 Amps Max.) 16.67 t Multiple of Rated Current rI 4.165 8.33 25x 12x 20.0 Time Delay Curves 22, 24 (100 Amps Max.) 26 (70 Amps Max.) Time in Milliseconds t Time Delay Curves 22, 24 (100 Amps Max.) 26 (70 Amps Max.)
60 Hz 1/2 Cycle
50 Hz 1/2 Cycle
10.0 Time Delay Curves 42, 44 & 46 (50 Amps Max.) 22x 10x Multiple of Rated Current 5.0 rI Time Delay Curves 42, 44 & 46 (50 Amps Max.) 16.67 t Multiple of Rated Current rI 4.165 8.33 25x 12x 20.0 Time Delay Curves 22, 24 (100 Amps Max.) 26 (70 Amps Max.) Time in Milliseconds t Time Delay Curves 22, 24 (100 Amps Max.) 26 (70 Amps Max.) 10.0 Time Delay Curves 42, 44 & 46 (50 Amps Max.) 22x 10x Multiple of Rated Current 5.0 rI CURRENT (AMPS) 0.10 - 5.0 5.1 - 20.0 15% 25% TOLERANCE (%) 20.1 - 100.0 35% Maximum Voltage AC, 480 WYE/277 VAC, 50/60 Hz (see Table A.) UL489: AC,240 VAC. (See Table D), 50/60 Hz, 125 VDC Current Rating Standard current coils: 0.100, 90.0 and 100 amps. Other ratings available, see Ordering Scheme. Standard Voltage Coils DC - 6V, 12V; AC - 120V; other ratings available, see Ordering Scheme. Auxiliary Switch Rating SPDT; 10.1 amps-250VAC, DC Aux. Switch 1.0A, 65 VDC. 0.5A, 80VDC,1/4 HP, 125VAC,VDE & TUV 1.0 125 VAC. Insulation Resistance Minimum of 100 Megohms at 500 VDC. Dielectric Strength UL, CSA: 1960 V 50/60 Hz for one minute between all electrically isolated terminals. C-Series Circuit Breakers comply with the 8mm spacing and 3750V 50/60 Hz dielectric requirements from hazardous voltage to operator accessible surfaces, between adjacent poles and from main circuits to auxiliary circuits per Publications EN 60950 and VDE 0805. Resistance, Impedance Values from Line to Load Terminal - based on Series Trip Circuit Breaker. Endurance 10,000 ON-OFF operations @ 6 per minute; with rated current & voltage. Trip Free All C-Series circuit breakers will trip on overload, even when actuator is forcibly held in the ON position. Trip Indication The operating actuator moves positively to the OFF position when an overload causes the breaker to trip. With mid-trip, handle moves to the mid position on electrical trip of the circuit breaker. With mid trip handle with alarm switch, handle moves to the mid position and the alarm switch actuates when the circuit breaker is electrically tripped. Number of Poles 1-6 poles ≤ 50A; 1-4 poles @ 51- 70A; 1-2 poles 71-100A. UL489 Handle: 1 pole ≤ 100A, 2 pole ≤ 50A; Rocker: 1 pole ≤ 100A. Internal Circuit Config. Series (with or without auxiliary switch, mid trip & mid trip with alarm switch) Shunt & Relay with current or voltage trip coils, Dual Coil, Switch Only (with or without aux. switch). UL489: Series (with or without auxiliary switch, mid-trip & midtrip with alarm switch). Weight Approx.112 grams/pole ( 3.95 oz). Standard Colors Housing: Black Designed and tested in accordance with requirements of specification MIL-PRF-55629 & MIL-STD-202 as follows: Shock Withstands 100 Gs, 6ms sawtooth while carrying rated current per Method 213, Test Condition “I”. Instantaneous and ultrashort curves tested @ 90% of rated current. Vibration Withstands 0.060” excursion from 10-55 Hz & 10 Gs 55-500 Hz, @ rated current per Method 204C, Test Cond. A. Instantaneous & ultrashort curves tested @ 90% of rated current. Moisture Resistance Method 106D, i.e., ten 24-hour cycles @ +25°C to +65°C, 80-98% RH. Salt Spray Method 101, Condition A (90-95% RH @ 5% NaCl Solution, 96 hrs). Thermal Shock Method 107D, Condition A (five cycles @ -55°C to +25°C to +85°C to +25°C). Operating Temperature -40°C to +85°C Pulse Tolerance Curves
Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com 6 | C-Series - Agency Certifications Agency Certifications: UL Recognized UL Standard 1077 Component Recognition Program as Protectors, Supplementary (Guide CCN/QVNU2, File E75596) UL Standard 508 Motor Controllers, Manual (Guide CCN/NLRV2, File E135367) UL Standard 1500 Protectors, Supplementary for Marine Electrical & Fuel Systems (Guide PEQZ2, File E75596) Ignition Protection UL Listed UL Standard 489 Circuit Breakers, Molded Case, (Guide DIVQ, File E129899) UL Standard 489A Communications Equipment (Guide CCN/DITT, File E189195) CSA Accepted Component Supplementary Protector under Class 3215 30, File 047848 0 000 CSA Standard C22.2 No. 235 CSA Certified Circuit Breaker Model Case (Class 1432 01, File 093910), CSA Standard C22.2 No. 5.1 - M TUV Certified EN60934, under License No. R72041016 VDE Certified EN60934, VDE 0642 under File No. 10537
Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com | 7 C-Series Handle UL Recognized – Ordering Scheme Series Actuator Poles Aux/Alarm Switch Frequency & Delay Current Rating Terminal Actuator Color Mounting Bezel/Barrier Agency Approval Circuit C A B 1 13 0 2 C10 450
1 SERIES
C
2 ACTUATOR1
A Handle, one per pole B Handle, one per multipole unit S Mid-Trip Handle, one per pole T Mid-Trip, one per pole & Alarm Switch
8 TERMINAL15
110 Stud 10-32
211 Screw 10-32
312 Stud 1/4-20
411 Stud M5 x 0.8 511 Screw M5 x 0.8
612 Stud M6
713,15 0.250 Double Click Connect 915 7/16” Clip Terminal A14 Plug-In Stud C11,15 5/16” Clip Terminal
3 POLES2
1 One
2 Two
3 Three
4 Four
5 Five
6 Six
4 CIRCUIT3
A3 Switch Only (no coil) B Series Trip (current) C Series Trip (voltage) D4 Shunt Trip (current) E4 Shunt Trip (voltage) F4 Relay Trip (current) G4 Relay Trip (voltage) H4,5 Dual Coil with Shunt Trip Voltage Coil K4,5 Dual Coil with Relay Trip Voltage Coil
5 AUXILIARY/ALARM SWITCH
(Gold Contacts)
6 FREQUENCY & DELAY
033 DC 50/60Hz, Switch Only
107 DC Instantaneous
11 DC Ultra Short
12 DC Short
14 DC Medium
16 DC Long
30 DC 50/60Hz Instantaneous
31 DC 50/60Hz Ultra Short
32 DC 50/60Hz Short
34 DC 50/60Hz Medium
36 DC 50/60Hz Long
428 50/60Hz Short, Hi-Inrush 448 50/60Hz Medium, Hi-Inrush 468 50/60Hz Long, Hi-Inrush
528 DC Short, Hi-Inrush
548 DC Medium, Hi-Inrush
56 DC Long, Hi-Inrush
7 CURRENT RATING (AMPERES)
020 0.020 025 0.025 030 0.030 035 0.035 040 0.040 045 0.045 050 0.050 055 0.055 060 0.060 065 0.065 070 0.070 075 0.075 080 0.080 085 0.085 090 0.090 095 0.095 210 0.100 215 0.150 220 0.200 225 0.250 230 0.300 235 0.350 240 0.400 245 0.450 250 0.500 255 0.550 260 0.600 265 0.650 270 0.700 275 0.750 280 0.800 285 0.850 290 0.900 295 0.950 410 1.000 512 1.250 415 1.500 517 1.750 420 2.000 522 2.250 425 2.500 527 2.750 430 3.000 435 3.500 440 4.000 445 4.500 450 5.000 455 5.500 460 6.000 465 6.500 470 7.000 475 7.500 480 8.000 485 8.500 490 9.000 495 9.500 610 10.000 710 10.500 611 11.000 711 11.500 612 12.000 712 12.500 613 13.000 614 14.000 615 15.000 616 16.000 617 17.000 618 18.000 620 20.000 622 22.000 624 24.000 625 25.000 630 30.000 635 35.000 640 40.000 650 50.000 6609 60.000 6709 70.000 6809 80.000 6859 85.000 6909 90.000 6959 95.000 8109 100.000 CODE AMPERES A06 6DC A12 12DC A18 18DC A24 24DC A32 32DC A48 48DC A65 65DC J06 6AC J12 12AC J18 18AC J24 24AC J48 48AC J65 65AC K20 120AC L40 240AC CODE RATING VOLTAGE COIL (NOMINAL RATED VOLTAGE)7
9 ACTUATOR COLOR & LEGEND16
Actuator Color I-O ON-OFF Dual Legend Color White A B 1 Black Black C D 2 White Red F G 3 White Green H J 4 White Blue K L 5 White Yellow M N 6 Black Gray P Q 7 Black Orange R S 8 Black Black (short handle)17 T U 9 White
10 MOUNTING/BARRIERS
MOUNTING STYLE BARRIERS VOLTAGE Threaded Insert 1 6-32 x 0.195 inches no < 300 A 6-32 X 0.195 inches yes < 300 C18 6-32 X 0.195 inches yes ≥ 300
2 ISO M3 x 5mm no < 300
B ISO M3 x 5mm yes < 300 D18 ISO M3 x 5mm yes ≥ 300 Front panel Snap-In, 1.00” [25.4mm] wide bezel E17 with Handleguard no < 300
11 AGENCY APPROVAL
C UL Recognized, CSA Accepted D VDE Certified, UL Recognized, CSA Accepted E TUV Certified, UL Recognized, CSA Accepted H UL489 Construction: VDE Certified, UL Recognized, CSA Accepted I UL Rec. STD 1077, UL Rec. 1500 (ignition protected), CSA Accepted L UL489 Construction: UL Recognized, CSA Accepted R UL489 Construction: TUV Certified, UL Recognized, CSA Accepted Notes:
1 Actuator Code:
A: Handle tie pin spacer(s) and retainers provided assembled with multi-pole units. B: Handle location as viewed from front of breaker: 2 pole - left pole 3 pole - center pole 4 pole - two handles at center poles 5 pole - three handles at center poles 6 pole - four handles at center poles S: Handle moves to mid-position only upon electrical trip of the breaker. Available with circuit codes B, C, D, E, F, G, H and K. T: Handle moves to mid-position and alarm switch activates only upon electrical trip of the breaker. Available with circuit codes B & C.
2 Standard multipole units have all poles identical except when specifying auxiliary
switch and/or mixed poles. 4 pole max w/VDE. 5th pole available as Series Trip w/ Voltage Coil only.
3 Switch Only circuits, rated up to 50 amps and 6 poles, and only available with VDE
Certification when tied to a protected pole (Circuit Code B, C, D or H.). For .02 to 30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650. For 55-70 amps, select Current Code 670. For 75-100 amps, select Current Code 810. 4 Circuit Codes D,E,F,G,H & K available with Terminal Codes 1,2,4 & 5 only. Circuit Codes D, F, H & K available up to 50 amps maximum Current Rating.
5 Consult factory for available Dual Coil options, as special catalog number is
required. Dual Coil Voltage Coils with Shunt Trip Construction trip instantaneously on line voltage. Dual Coil Voltage Coils require 30VA minimum power to trip instantaneously and are rated for intermittent duty only. 6 Auxiliary Switch available with Series Trip and Switch Only circuits. On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right pole. 7 Voltage coils not rated for continuous duty. Available only with delay codes 10 & 20. 8 Available with Circuit Codes B & D only, and up to 50 amps maximum. 9 Current Ratings 60 - 70 are available up to four poles maximum. Ratings 71 - 100 are available up to two poles maximum. 10 Terminal Code 1 available to 60 amps maximum. 11 Terminal Codes 2, 4, 5 and C available to 50 amps maximum. 12 Terminal Codes 3, 6 & 9 available to 100 amps maximum. 13 Terminal Code 7 available to 25 amps maximum. 14 Terminal Code A available to 100 amps maximum. 15 Terminal Codes 7, 9 & C are not VDE approved. 16 No marking available. Consult factory. VDE/TUV Approval requires dual (I-O, ON-OFF) or I-O markings on all handles. 17 Single pole only. 18 VDE/TUV: 30 amps max.; UL/CSA: 50 amps max.; Available in 2 - 4 poles only and limited to AC Delays. “General Purpose amps” not rated for “full load amps” or to be used in applications with a motor.
Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com 8 | C-Series Handle UL489A Listed / Parallel Pole – Ordering Scheme
9 ACTUATOR COLOR2
10 MOUNTING
1 6-32 x 0.195 inches
2 ISO M3 x 5mm
12 AGENCY APPROVAL8
J UL489A Listed, TUV Certified T UL489A Listed K UL489A Listed, VDE Certified (up to 200 amps)
7 UL489A Listed, TUV Certified (up to 250 amps)
& Delay Current Rating Terminal Actuator Color Mounting Max. App. Rating Agency Approval Circuit C A P 3 12 0 2 M TD4 820 C A Handle, one per pole S Mid-Trip Handle, one per pole T Mid-Trip, one per pole & Alarm Switch
8 TERMINAL6
3 Stud 1/4-20
6 Stud M6
3 POLES4
1 One 2 Two 3 Three
4 CIRCUIT5
B Series Trip P Series Trip (parallel pole)
6 FREQUENCY & DELAY7
810 100.00 811 110.00 812 120.00 912 125.00 813 130.00 814 140.00 815 150.00 816 160.00 817 170.00 917 175.00 818 180.00 819 190.00 820 200.00 9224 225.00 8254 250.00 CODE AMPERES
11 MAXIMUM APPLICATION RATING
Notes:
1 Handle moves to Mid-Position only upon electrical trip of C/B when Actuator S is
specified. When Actuator Code T is specified, handle moves to Mid Position and Alarm Switch actuates only upon electrical trip of C/B. 2 Standard Handle colors are White, Black, Red & Yellow.
3 Breakers with Terminal Codes 3 & 6 are supplied with bus bars connecting the Line
and Load Terminals. For Terminal Code A, Line and Load Terminals must be connected to a copper bus bar having a minimum cross-section of 0.078 square inches. Terminal code A not available on the single pole unit. 4 Rating for 101 to 125 amps are available in 1 pole size. Ratings from 110 to 200 amps are available in 2-pole size. For ratings from 225-250 amps, specify 3-pole size. 5 Circuit code B only available with 1 pole. 6 1 pole only available with terminal codes 3 and 6. 7 Delays 11, 12, 14, and 16 are only available with 1 pole. 8 Agency code K and 7 not available with 1 pole. Agency code J only available with 1 pole. (Gold Contacts)
Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com | 9 C-Series Rocker UL489A Listed / Parallel Pole – Ordering Scheme
9 ACTUATOR COLOR
ROCKER / MOUNTING INSERT STYLE A Standard Rocker Bezel - 6-32 Inserts B Standard Rocker Bezel - M3 Inserts C Rocker Guard Bezel - 6-32 Inserts D Rocker Guard Bezel - M3 Inserts E Standard Bezel with recessed Off Side Flat Rocker - 6-32 Inserts F Standard Bezel with recessed Off Side Flat Rocker - M3 Inserts G Push to Reset Bezel - 6-32 Inserts H Push to Reset Bezel - M3 Inserts
12 AGENCY APPROVAL6
J UL489A Listed, TUV Certified T UL489A Listed
7 UL489A Listed, TUV Certified
& Delay Current Rating Terminal Actuator Color Mounting Max. App. Rating Agency Approval Circuit C 1 P 3 A2 0 1 M TD4 820 C
2 ACTUATOR
C Curved Rocker, Two Color Visi, Indicate On, Vertical Legend D Curved Rocker, Two Color Visi, Indicate On, Horizontal Legend F Curved Rocker, Two Color Visi, Indicate Off, Vertical Legend G Curved Rocker, Two Color Visi, Indicate Off, Horizontal Legend J Curved Rocker, Single Color, Vertical Legend K Curved Rocker, Single Color, Horizontal Legend
1 Flat Rocker, Two Color Visi, Vertical Legend
2 Flat Rocker, Two Color Visi, Horizontal Legend
3 Flat Rocker, Single Color, Vertical Legend
4 Flat Rocker, Single Color, Horizontal Legend
5 Flat Rocker, Push To Reset, Two Color Visi, Vertical Legend
6 Flat Rocker, Push To Reset, Two Color Visi, Horizontal Legend
7 Flat Rocker, Push To Reset, Single Color, Vertical Legend
8 Flat Rocker, Push To Reset, Single Color, Horizontal Legend
8 TERMINAL4
B Series Trip P Series Trip (parallel pole)
6 FREQUENCY & DELAY5
7 CURRENT RATING (AMPERES)2
810 100.00 811 110.00 812 120.00 912 125.00 813 130.00 814 140.00 815 150.00 816 160.00 817 170.00 917 175.00 818 180.00 819 190.00 820 200.00 922 225.00 825 250.00 CODE AMPERES Notes:
1 Breakers with Terminal Codes 3 & 6 are supplied with bus bars connecting the Line
and Load Terminals. For Terminal Code A, Line and Load Terminals must be connected to a copper bus bar having a minimum cross-section of 0.078 square inches. Terminal code A not available on the single pole unit. 2 Ratings for 101 to 125 amps are availabe in 1-pole size. Ratings from 110 to 200 amps are available in 2-pole size. For ratings from 225-250 amps, specify 3-pole size. 3 Circuit code B only available with 1-pole. 4 1 pole only available with terminal codes 3 and 6. 5 Delays 11, 12, 14, and 16 are only available with 1 pole. 6 Agency code K and 7 not available with 1 pole. Agency code J only available with 1 pole. (Gold Contacts)
Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com 10 | C-Series Handle UL489 Listed – Ordering Scheme Series Actuator Poles Aux/Alarm Switch Frequency & Delay Current Rating Terminal Actuator Color Mounting/ Barriers Max. App. Rating Agency Approval Circuit C A B 1 13 0 2 K G14 450 C A Handle, one per pole B Handle, one per multipole unit S Mid-Trip Handle, one per pole T Mid-Trip, one per pole & Alarm Switch
17 Stud 10-32
28 Screw 10-32
39 Stud 1/4-20
48 Stud M5 x 0.8 58 Screw M5 x 0.8
69 Stud M6
99 7/16” Clip Terminal A10 Plug-In Stud C8 5/16” Clip Terminal
4 CIRCUIT
B Series Trip (current) 424 50/60Hz Short, Hi-Inrush 444 50/60Hz Medium, Hi-Inrush 464 50/60Hz Long, Hi-Inrush
524 DC Short, Hi-Inrush
544 DC Medium, Hi-Inrush
564 DC Long, Hi-Inrush
7 CURRENT RATING (AMPERES)5
210 0.100 215 0.150 220 0.200 225 0.250 230 0.300 235 0.350 240 0.400 245 0.450 250 0.500 255 0.550 260 0.600 265 0.650 270 0.700 275 0.750 280 0.800 285 0.850 290 0.900 295 0.950 410 1.000 512 1.250 415 1.500 517 1.750 420 2.000 522 2.250 425 2.500 527 2.750 430 3.000 435 3.500 440 4.000 445 4.500 450 5.000 455 5.500 460 6.000 465 6.500 470 7.000 475 7.500 480 8.000 485 8.500 490 9.000 495 9.500 610 10.000 710 10.500 611 11.000 711 11.500 612 12.000 712 12.500 613 13.000 614 14.000 615 15.000 616 16.000 617 17.000 618 18.000 620 20.000 622 22.000 624 24.000 625 25.000 630 30.000 635 35.000 640 40.000 660 60.000 670 70.000 680 80.000 685 85.000 690 90.000 695 95.000 810 100.000 CODE AMPERES Notes: A: Handle tie pin spacer(s) and retainers provided assembled with multi-pole units. B: Handle located, as viewed from front of breaker in left pole. 2 pole maximum. S: Handle moves to mid-position only upon electrical trip of the breaker. T: Handle moves to mid-position and alarm switch activates only upon electrical trip of the breaker. switch and/or mixed poles. 2 & 3 pole circuit breakers required for 120/240 VAC (Maximum application rating code C) applications, have all poles identical except when specifying auxiliary / alarm switch which is normally supplied in extreme right pole per figure B. Terminal barriers are required on all multipole breakers. Third pole is for 120/240 VAC applications requiring neutral disconnect. The 3rd pole has the same construction as poles 1 & 2. 3 On multi-pole breakers, one auxiliary. switch is supplied, mounted in the extreme right pole. VDE approval on auxiliary switch codes 2, 3 & 4 only. Auxiliary / Alarm Switch with Independent Circuit ie: separate from breaker circuit, only available with circuit breakers rated 50 amp maximum at 80 VDC, 125 VDC, and 120 VAC. Auxiliary / Alarm Switch with Dependent Circuit ie: same as circuit breaker, is supplied from factory with common terminal of auxiliary / alarm switch connected to line terminal on 120/240 and 240 VAC ratings. Circuit breakers rated
120 VAC 50 amp maximum can be supplied with Auxiliary/Alarm switch common
terminal connected to breaker line terminal. Consult factory for special catalog number. 4 Available up to 50 amps maximum.
5 Current ratings 71 - 100 with VDE approvals are available up to two poles
maximum. 6 Terminal Codes 9 & C are not VDE approved. 7 Terminal Code 1 available to 60 amps maximum. 8 Terminal Codes 2, 4, 5 & C available to 50 amps maximum. 9 Terminal Codes 3, 6 & 9 available to 100 amps maximum. 10 Terminal Code A available to 100 amps maximum. 11 VDE and TUV approvals require Dual (I-O, ON-OFF) markings on all handles. 12 Barriers supplied on multi-pole units only.
9 ACTUATOR COLOR & LEGEND11
Actuator Color ON-OFF Dual Legend Color White B 1 Black Black D 2 White Red G 3 White Green J 4 White Blue L 5 White Yellow N 6 Black Gray Q 7 Black Orange S 8 Black 1 6-32 x 0.195 inches yes
2 ISO M3 x 5mm yes
12 AGENCY APPROVAL11
F UL489 Listed, CSA Certified & VDE Certified G UL489 Listed & CSA Certified J UL489 Listed, CSA Certified & TUV Certified
5 AUXILIARY/ALARM SWITCH3
(Gold Contacts)
Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com | 11 C-Series Sealed Toggle UL Recognized – Ordering Scheme Series Actuator Poles Aux/Alarm Switch Frequency & Delay Current Rating Terminal Legend Plate Mounting Bezel/Barrier Agency Approval Circuit C M B 1 13 0 0 C10 450 C M Sealed Toggle, one per pole
8 TERMINAL
19 Stud 10-32
210 Screw 10-32
311 Stud 1/4-20
410 Stud M5 x 0.8 510 Screw M5 x 0.8
611 Stud M6
712 0.250 Double Click Connect 911 7/16” Clip Terminal A13 Plug-In Stud C10 5/16” Clip Terminal
3 POLES
A2 Switch Only (no coil) B Series Trip (current) C Series Trip (voltage) D3 Shunt Trip (current) E3 Shunt Trip (voltage) F3 Relay Trip (current) G3 Relay Trip (voltage) H3,4 Dual Coil with Shunt Trip Voltage Coil K3,4 Dual Coil with Relay Trip Voltage Coil
032 DC 50/60Hz, Switch Only
106 DC Instantaneous
427 50/60Hz Short, Hi-Inrush 447 50/60Hz Medium, Hi-Inrush 467 50/60Hz Long, Hi-Inrush
527 DC Short, Hi-Inrush
547 DC Medium, Hi-Inrush
7 CURRENT RATING (AMPERES)9
020 0.020 025 0.025 030 0.030 035 0.035 040 0.040 045 0.045 050 0.050 055 0.055 060 0.060 065 0.065 070 0.070 075 0.075 080 0.080 085 0.085 090 0.090 095 0.095 210 0.100 215 0.150 220 0.200 225 0.250 230 0.300 235 0.350 240 0.400 245 0.450 250 0.500 255 0.550 260 0.600 265 0.650 270 0.700 275 0.750 280 0.800 285 0.850 290 0.900 295 0.950 410 1.000 512 1.250 415 1.500 517 1.750 420 2.000 522 2.250 425 2.500 527 2.750 430 3.000 435 3.500 440 4.000 445 4.500 450 5.000 455 5.500 460 6.000 465 6.500 470 7.000 475 7.500 480 8.000 485 8.500 490 9.000 495 9.500 610 10.000 710 10.500 611 11.000 711 11.500 612 12.000 712 12.500 613 13.000 614 14.000 615 15.000 616 16.000 617 17.000 618 18.000 620 20.000 622 22.000 624 24.000 625 25.000 630 30.000 635 35.000 640 40.000 650 50.000 660 9 60.000 6709 70.000 6809 80.000 6859 85.000 6909 90.000 6959 95.000 8109 100.000 CODE AMPERES A06 6DC A12 12DC A18 18DC A24 24DC A32 32DC A48 48DC A65 65DC J06 6AC J12 12AC J18 18AC J24 24AC J48 48AC J65 65AC K20 120AC L40 240AC CODE RATING VOLTAGE COIL (NOMINAL RATED VOLTAGE)7
9 LEGEND PLATE
0 No Legend
Notes:
1 Actuator Code M: Handle location as viewed from front of breaker:
2 pole - right pole 3 pole - center pole 2 Switch Only circuits, rated up to 50 amps and 3 poles, and only available with VDE. For .02 to 30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650. For 55-70 amps, select Current Code 670. For 75-100 amps, select Current Code 810. 3 Circuit Codes D,E,F,G,H & K available with Terminal Codes 1,2,4 & 5 only.
4 Consult factory for available Dual Coil options, as special catalog number is
required. Dual Coil Voltage Coils with Shunt Trip Construction trip instantaneously on line voltage. Dual Coil Voltage Coils require 30VA minimum power to trip instantaneously and are rated for intermittent duty only. 5 Auxiliary Switch available with Series Trip and Switch Only circuits. On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right pole. 6 Voltage coils not rated for continuous duty. Available only with delay codes 10 & 20. 7 Available with Circuit Codes B & D only, and up to 50 amps maximum.
8 Consult factory for current ratings 71-100, in three pole units, available as special
catalog number only. 9 Terminal Code 1 available to 60 amps maximum. 10 Terminal Codes 2, 4, 5 and C available to 50 amps maximum. 11 Terminal Codes 3, 6 & 9 available to 100 amps maximum. 12 Terminal Code 7 available to 25 amps maximum. 13 Terminal Code A available to 100 amps maximum.
1 Standard Hex Nut no
A Standard Hex Nut (multi-pole units only) yes C UL Recognized & CSA Accepted L UL Recognized & CSA Accepted with listed construction T UL Recognized & CSA Accepted, UL1500 ignition protection (Gold Contacts)
Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com 12 | C-Series Rocker UL Recognized – Ordering Scheme C Indicate ON, vertical legend D Indicate ON, horizontal legend E Indicate ON, no legend F Indicate OFF, vertical legend G Indicate OFF, horizontal legend H Indicate OFF, no legend Push-To-Reset, Visi-Rocker N Indicate OFF, vertical legend O Indicate OFF, horizontal legend P Indicate OFF, no legend Single color J Vertical legend K Horizontal legend L No legend Push-To-Reset, Single color R Vertical legend U Horizontal legend V No legend Series Actuator Poles Aux/Alarm Switch Frequency & Delay Current Rating Terminal Actuator Color Mounting/ Barriers Agency Approval Circuit C C B 1 13 0 2 D14 450 C 411 Stud M5 x 0.8 511 Screw M5 x 0.8 713 0.250 Double Quick Connect 9 7/16” Clip Terminal A14 Plug-In Stud C 5/16” Clip Terminal A3 Switch Only (No Coil) B Series Trip (Current) C Series Trip (Voltage) D4 Shunt Trip (Current) E4 Shunt Trip (Voltage) F4 Relay Trip (Current) G4 Relay Trip (Voltage) H4,5 Dual Coil with Shunt Trip Voltage Coil K4,5 Dual Coil with Relay Trip Voltage Coil
9 ACTUATOR COLOR & LEGEND16,17,18
Color: I-O ON-OFF Dual/None Rocker/Handle Visi-Rocker White A B 1 Black White Black C D 2 White n/a Red F G 3 White Red Green H J 4 White Green Blue K L 5 White Blue Yellow M N 6 Black Yellow Gray P Q 7 Black Gray Orange R S 8 Black Orange Actuator or Visi-Color Marking: Marking Color: 020 0.020 025 0.025 030 0.030 035 0.035 040 0.040 045 0.045 050 0.050 055 0.055 060 0.060 065 0.065 070 0.070 075 0.075 080 0.080 085 0.085 090 0.090 095 0.095 210 0.100 215 0.150 220 0.200 225 0.250 230 0.300 235 0.350 240 0.400 245 0.450 250 0.500 255 0.550 260 0.600 265 0.650 270 0.700 275 0.750 280 0.800 285 0.850 290 0.900 295 0.950 410 1.000 512 1.250 415 1.500 517 1.750 420 2.000 522 2.250 425 2.500 527 2.750 430 3.000 435 3.500 440 4.000 445 4.500 450 5.000 455 5.500 460 6.000 465 6.500 470 7.000 475 7.500 480 8.000 485 8.500 490 9.000 495 9.500 610 10.000 710 10.500 611 11.000 711 11.500 612 12.000 712 12.500 613 13.000 614 14.000 615 15.000 616 16.000 617 17.000 618 18.000 620 20.000 622 22.000 624 24.000 625 25.000 630 30.000 635 35.000 640 40.000 650 50.000 660 9 60.000 6709 70.000 6809 80.000 6859 85.000 6909 90.000 6959 95.000 8109 100.000 CODE AMPERES A06 6DC A12 12DC A18 18DC A24 24DC A32 32DC A48 48DC A65 65DC J06 6AC J12 12AC J18 18AC J24 24AC J48 48AC J65 65AC K20 120AC L40 240AC CODE RATING VOLTAGE COIL (NOMINAL RATED VOLTAGE)7
03 DC 50/60Hz, Switch Only
428 50/60Hz Short, Hi-Inrush 448 50/60Hz Medium, Hi-Inrush 468 50/60Hz Long, Hi-Inrush
568 DC Long, Hi-Inrush
Notes: 1 Push-To-Reset actuators have OFF portion of rocker shrouded. 2 Multi-pole breakers have all poles identical except when specifying Aux. switch and/ or mixed poles, and have one rocker per breaker. Rocker location as viewed from front panel: 2 pole – left pole; 3 pole – center pole.
3 Switch Only circuits, rated up to 50 amps and 3 poles, and only available with VDE
Certification when tied to a protected pole (Circuit Code B, C, D or H.), For .02 to 30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650. For 55-70 amps, select Current Code 670. For 75-100 amps, select Current Code 810. 4 Circuit Codes D,E,F,G,H & K available with Terminal Codes 1,2,4 & 5 only. Circuit Codes D,F,H & K available up to 50 amps maximum Current Rating. required. Dual Coil Voltage Coils with Shunt Trip Construction trip instantaneously on line voltage. Dual Coil Voltage Coils require 30VA minimum power to trip instantaneously and are rated for intermittent duty only. 6 Auxiliary Switch available with Series Trip and Switch Only circuits. On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right pole. Auxiliary switch codes 2, 3 & 4 are VDE approved. 7 Voltage coils not rated for continuous duty. Available only with delay codes 10 & 20. 8 Available with Circuit Codes B & D only, and up to 50 amps maximum. 9 Current Ratings 60-70 are available up to four poles maximum. Ratings 71-100 are available up to two poles maximum. 10 Terminal Code 1 available to 60 amps maximum. 11 Terminal Codes 2,4,5 & C available to 50 amps maximum. 12 Terminal Codes 3,6 & 9 available to 100 amps maximum. 13 Terminal Code 7 available to 25 amps maximum. 14 Terminal Code A available to 100 amps maximum. 15 Terminal Codes 7, 9 & C are not VDE approved.
16 Color shown is visi and legend with remainder of rocker black
17 Legend on Push-to-reset bezel/shroud is white when single color rocker is ordered. Dual = ON-OFF/I-O legend with actuator codes C - G, and J, K, N, O, R, & U. None = no legend with actuator codes H, L, P, V. Rockerguard available with actuator codes C - L. Push-to-reset available with actuator codes N, O, P, R, U, V. 18 VDE/TUV approval requires Dual (I-O, ON-OFF) or I-O markings on rocker. 19 VDE/TUV: 30 amps max.; UL/CSA: 50 amps max.; Available in 2 - 4 poles only and limited to AC Delays. “General Purpose amps” not rated for “full load amps” or to be used in applications with a motor.
10 MOUNTING/BARRIERS 1
STANDARD ROCKER BEZEL BARRIERS VOLTAGE 1 6-32 x 0.195 inches no <300 2 6-32 x 0.195 inches yes <300 319 6-32 x 0.195 inches yes ≥300
4 ISO M3 x 5mm no <300
5 ISO M3 x 5mm yes <300
619 ISO M3 x 5mm yes ≥300
A 6-32 x 0.195 inches no <300 C 6-32 x 0.195 inches yes <300 E19 6-32 x 0.195 inches yes ≥300 G ISO M3 x 5mm no <300 J ISO M3 x 5mm yes <300 L19 ISO M3 x 5mm yes ≥300 PUSH-TO-RESET BEZEL B 6-32 x 0.195 inches no <300 D 6-32 x 0.195 inches yes <300 F19 6-32 x 0.195 inches yes ≥300 H ISO M3 x 5mm no <300 J ISO M3 x 5mm yes <300 M19 ISO M3 x 5mm yes ≥300 C UL Recognized & CSA Accepted D VDE Certified, UL Recognized & CSA Accepted E TUV Certified, UL Recognized & CSA Accepted H UL489 Construction: VDE Certified, UL Recognized & CSA Accepted I UL Rec. STD 1077, UL Rec. 1500 (ignition protected), & CSA Accepted L UL489 Construction: UL Recognized & CSA Accepted R UL489 Construction: TUV Certified, UL Recognized & CSA Accepted
5 AUXILIARY/ALARM SWITCH6
(Gold Contacts)
Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com | 13 C-Series Rocker UL Listed – Ordering Scheme C Indicate ON, vertical legend D Indicate ON, horizontal legend F Indicate OFF, vertical legend G Indicate OFF, horizontal legend Single color J Vertical legend K Horizontal legend Color: ON-OFF Dual10 Rocker/Handle Visi-Rocker White B 1 Black White Black D 2 White n/a Red G 3 White Red Green J 4 White Green Blue L 5 White Blue Yellow N 6 Black Yellow Gray Q 7 Black Gray Orange S 8 Black Orange Actuator or Visi-Color Marking: Marking Color: SINGLE COLOR CODE "J" LINE CODE "K" LINE INDICATE "ON" CODE "C"LINE LINELINE LINE CODE "D" INDICATE COLOR LOCATION HORIZONTAL STYLE VERTICAL STYLE CODE "G" CODE "F" ROCKER STYLE DESCRIPTIONS INDICATE "OFF" Series Actuator Poles Aux/Alarm Switch Frequency & Delay Current Rating Terminal Actuator Color Mounting/ Barriers Max. App. Rating Agency Approval Circuit C C B 1 A3 0 2 K G14 450 C
15 Stud 10-32
26 Screw 10-32 w/saddle &
37 Stud 1/4-20
46 Stud M5 x 0.8 56 Screw M5 x 0.8 w/saddle & washer clamps
67 Stud M6
97,8 7/16” Clip Terminal A7,8 Plug-In Stud C6,8 5/16” Clip Terminal
3 POLES1
B Series Trip (current)
7 CURRENT RATING (AMPERES)4
210 0.100 215 0.150 220 0.200 225 0.250 230 0.300 235 0.350 240 0.400 245 0.450 250 0.500 255 0.550 260 0.600 265 0.650 270 0.700 275 0.750 280 0.800 285 0.850 290 0.900 295 0.950 410 1.000 512 1.250 415 1.500 517 1.750 420 2.000 522 2.250 425 2.500 527 2.750 430 3.000 435 3.500 440 4.000 445 4.500 450 5.000 455 5.500 460 6.000 465 6.500 470 7.000 475 7.500 480 8.000 485 8.500 490 9.000 495 9.500 610 10.000 710 10.500 611 11.000 711 11.500 612 12.000 712 12.500 613 13.000 614 14.000 615 15.000 616 16.000 617 17.000 618 18.000 620 20.000 622 22.000 624 24.000 625 25.000 630 30.000 635 35.000 640 40.000 650 50.000 660 60.000 670 70.000 680 80.000 685 85.000 690 90.000 695 95.000 810 100.000 CODE AMPERES 428 50/60Hz Short, Hi-Inrush 448 50/60Hz Medium, Hi-Inrush 468 50/60Hz Long, Hi-Inrush Notes: 1 Multi-pole breakers have all breakers identical except when specifying Aux. switch and/or mixed poles, and have one rocker per breaker. 2 On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right pole. 3 Available up to 50 amps maximum. 4 Current ratings 71 - 100 with VDE approvals are available up to two poles maximum. 5 Terminal Code 1 available to 60 amps maximum. 6 Terminal Codes 2, 4, 5 & C available to 50 amps maximum. 7 Terminal Codes 3, 6, 9 & A available to 100 amps maximum. 8 Terminal Codes 9 & C are not VDE approved.
9 Color shown is visi and legend with remainder of rocker black
10 Dual = ON-OFF/I-O legend on actuator. 11 VDE and TUV approval requires Dual (I-O, ON-OFF) markings on rocker. 12 Rockerguard available with all actuator codes. 13 Barriers supplied on multi-pole units only. 14 2 & 3 pole circuit breakers required for 120/240 AC rating.
10 MOUNTING/BARRIERS 12
Standard Rocker Bezel BARRIERS13 Threaded Insert, 2 per pole A 6-32 X 0.195 inches yes C ISO M3 x 5mm yes Rockerguard Bezel Threaded Insert, 2 per pole B 6-32 x 0.195 inches yes D ISO M3 x 5mm yes
12 AGENCY APPROVAL
F UL 489 Listed, CSA Certified, & VDE Certified G UL 489 Listed & CSA Certified J UL489 Listed, CSA Certified & TUV Certified
5 AUXILIARY/ALARM SWITCH2
(Gold Contacts)
Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com 14 | C-Series Flat Rocker UL Recognized – Ordering Scheme
1 Indicate OFF, vertical legend
2 Indicate OFF, horizontal legend
3 Vertical legend
4 Horizontal legend
Push-To-Reset, Visi-Rocker
5 Indicate OFF, vertical legend
6 Indicate OFF, horizontal legend
Push-To-Reset , Single color
7 Vertical legend
8 Horizontal legend
& Delay Current Rating Terminal Actuator Color Mounting/ Barriers Agency Approval Circuit C 1 B 1 12 0 2 E10 450 C 411 Stud M5 x 0.8 511 Screw M5 x 0.8 713 0.250 Double Quick Connect 915 7/16” Clip Terminal A14 Plug-In Stud C15 5/16” Clip Terminal A3 Switch Only (No Coil) B Series Trip (Current) C Series Trip (Voltage) D4 Shunt Trip (Current) E4 Shunt Trip (Voltage) F4 Relay Trip (Current) G4 Relay Trip (Voltage) H4,5 Dual Coil with Shunt Trip Voltage Coil K4,5 Dual Coil with Relay Trip Voltage Coil 020 0.020 025 0.025 030 0.030 035 0.035 040 0.040 045 0.045 050 0.050 055 0.055 060 0.060 065 0.065 070 0.070 075 0.075 080 0.080 085 0.085 090 0.090 095 0.095 210 0.100 215 0.150 220 0.200 225 0.250 230 0.300 235 0.350 240 0.400 245 0.450 250 0.500 255 0.550 260 0.600 265 0.650 270 0.700 275 0.750 280 0.800 285 0.850 290 0.900 295 0.950 410 1.000 512 1.250 415 1.500 517 1.750 420 2.000 522 2.250 425 2.500 527 2.750 430 3.000 435 3.500 440 4.000 445 4.500 450 5.000 455 5.500 460 6.000 465 6.500 470 7.000 475 7.500 480 8.000 485 8.500 490 9.000 495 9.500 610 10.000 710 10.500 611 11.000 711 11.500 612 12.000 712 12.500 613 13.000 614 14.000 615 15.000 616 16.000 617 17.000 618 18.000 620 20.000 622 22.000 624 24.000 625 25.000 630 30.000 635 35.000 640 40.000 650 50.000 660 9 60.000 6709 70.000 6809 80.000 6859 85.000 6909 90.000 6959 95.000 8109 100.000 CODE AMPERES A06 6DC A12 12DC A18 18DC A24 24DC A32 32DC A48 48DC A65 65DC J06 6AC J12 12AC J18 18AC J24 24AC J48 48AC J65 65AC K20 120AC L40 240AC CODE RATING VOLTAGE COIL (NOMINAL RATED VOLTAGE)7 428 50/60Hz Short, Hi-Inrush 448 50/60Hz Medium, Hi-Inrush 468 50/60Hz Long, Hi-Inrush Notes: 1 Push-to-reset actuators have OFF portion of rocker shrouded. 2 Multi-pole breakers have all poles identical except when specifying Aux. switch and/or mixed poles, and have one rocker per breaker. Rocker location as viewed from front panel: 2 pole – left pole; 3 pole – center pole. Certification when tied to a protected pole (Circuit Code B, C, D or H.). For .02 to 30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650. For 55-70 amps, select Current Code 670. For 75-100 amps, select Current Code 810. 4 Circuit Codes D,E,F,G,H & K available with Terminal Codes 1,2,4 & 5 only. Circuit Codes D,F,H & K available up to 50 amps maximum Current Rating. 5 Consult factory for available Dual Coil options, as special catalog number is required. Dual Coil Voltage Coils with Shunt Trip Construction trip instantaneously on line voltage. Dual Coil Voltage Coils require 30VA minimum power to trip instantaneously and are rated for intermittent duty only. 6 Auxiliary Switch available with Series Trip and Switch Only circuits. On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right pole. Auxilary switch codes 2, 3 & 4 are VDE approved. 7 Voltage coils not rated for continuous duty. Available only with delay codes 10 and 20. 8 Available with Circuit Codes B & D only, and up to 50 amps maximum. 9 Current ratings 60-70 are available up to four poles maximum. Current ratings 71 - 100 are available up to two poles maximum. 10 Terminal Code 1 available to 60 amps maximum. 11 Terminal Codes 2,4,5 & C available to 50 amps maximum. 12 Terminal Codes 3,6 & 9 available to 100 amps maximum. 13 Terminal Code 7 available to 25 amps maximum. 14 Terminal Code A available to 100 amps maximum. 15 Terminal Codes 7, 9 & C are not VDE approved. 16 Color shown is visi & legend with remainder of rocker black. Dual = ON-OFF/I-O legend.
17 Legend on Push-to-reset bezel/shroud is white with single color actuator codes 7 &
- Legend on Push-to-reset bezel/shroud matches visi-color of rocker with actuator codes 5 & 6. 18 VDE/TUV approval requires Dual (I-O, ON-OFF) or I-O markings on rocker. 19 VDE/TUV: 30 amps max.; UL/CSA: 50 amps max.; Available in 2 & 3 poles only and limited to AC Delays. “General Purpose amps” not rated for “full load amps” or to be used in applications with a motor. 20 Recessed “OFF SIDE” available with actuator codes 1,2,3&4. Legends on rocker are available in ink stamping only.
Color: I-O ON-OFF Dual/None Rocker/Handle Visi-Rocker White A B 1 Black White Black C D 2 White n/a Red F G 3 White Red Green H J 4 White Green Blue K L 5 White Blue Yellow M N 6 Black Yellow Gray P Q 7 Black Gray Orange R S 8 Black Orange Actuator or Visi-Color Marking: Marking Color: STANDARD ROCKER BEZEL BARRIERS VOLTAGE 1 6-32 x 0.195 inches no <300 2 6-32 x 0.195 inches yes <300 319 6-32 x 0.195 inches yes ≥300 7 6-32 x 0.195 inches no <300 8 6-32 x 0.195 inches yes <300 9 6-32 x 0.195 inches yes ≥300 A ISO M3 x 5mm no <300 C ISO M3 x 5mm yes <300 E ISO M3 x 5mm yes ≥300 PUSH-TO-RESET BEZEL B 6-32 x 0.195 inches no <300 D 6-32 x 0.195 inches yes <300 F 19 6-32 x 0.195 inches yes ≥300 H ISO M3 x 5mm no <300 J ISO M3 x 5mm yes <300 M19 ISO M3 x 5mm yes ≥300 C UL Recognized & CSA Accepted E TUV Certified, UL Recognized & CSA Accepted I UL Rec. STD 1077, UL Rec. 1500 (ignition protected), & CSA Accepted L UL489 Construction: UL Recognized & CSA Accepted R UL489 Construction: TUV Certified, UL Recognized & CSA Accepted (Gold Contacts)
Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com | 15 C-Series Flat Rocker UL Listed – Ordering Scheme Push-To-Reset, Visi-Rocker Push-To-Reset , Single color & Delay Current Rating Terminal Actuator Color Mounting/ Barriers Max. App. Rating Agency Approval Circuit C 1 B 1 A2 0 2 K G14 450 C 48 Stud M5 x 0.8 58 Screw M5 x 0.8 99,10 7/16” Clip Terminal A9 Plug-In Stud C8,10 5/16” Clip Terminal B Series Trip (current) 424 50/60Hz Short, Hi-Inrush 444 50/60Hz Medium, Hi-Inrush 464 50/60Hz Long, Hi-Inrush 210 0.100 215 0.150 220 0.200 225 0.250 230 0.300 235 0.350 240 0.400 245 0.450 250 0.500 255 0.550 260 0.600 265 0.650 270 0.700 275 0.750 280 0.800 285 0.850 290 0.900 295 0.950 410 1.000 512 1.250 415 1.500 517 1.750 420 2.000 522 2.250 425 2.500 527 2.750 430 3.000 435 3.500 440 4.000 445 4.500 450 5.000 455 5.500 460 6.000 465 6.500 470 7.000 475 7.500 480 8.000 485 8.500 490 9.000 495 9.500 610 10.000 710 10.500 611 11.000 711 11.500 612 12.000 712 12.500 613 13.000 614 14.000 615 15.000 616 16.000 617 17.000 618 18.000 620 20.000 622 22.000 624 24.000 625 25.000 630 30.000 635 35.000 640 40.000 650 50.000 660 60.000 670 70.000 680 80.000 685 85.000 690 90.000 695 95.000 810 100.000 CODE AMPERES
1 Notes:
2 Push-to-reset actuators have OFF portion of rocker shrouded. 3 Multi-pole breakers have all breakers identical except when specifying Aux. switch and/or mixed poles, and have one rocker per breaker. 4 On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right pole. 5 Available up to 50 amps maximum. 6 Current ratings 71 - 100 with VDE approvals are available up to two poles maximum. 7 Terminal Code 1 available to 60 amps maximum. 8 Terminal Codes 2, 4, 5 & C available to 50 amps maximum. 9 Terminal Codes 3, 6, 9 & A available to 100 amps maximum. 10 Terminal Codes 9 & C are not VDE approved.
11 Color shown is visi and legend with remainder of rocker black
12 Dual = ON-OFF/I-O legend on actuator. 13 VDE and TUV approval requires Dual (I-O, ON-OFF) markings on rocker. 14 Legend on push-to-reset bezel/shroud is white when single color rocker is ordered. Legend on push-to-reset bezel/shroud matches visi-color of rocker with actuator codes 15 5 & 6. 16 Recessed “OFF-SIDE” available with actuator codes 1, 2, 3, & 4. Legends on rocker are available in ink stamping only. 17 Barriers supplied on multi-pole units only. 18 2 & 3 pole circuit breakers required for 120/240 AC rating.
9 ACTUATOR COLOR & LEGEND12
Color: ON-OFF Dual11 Rocker/Handle Visi-Rocker White B 1 Black White Black D 2 White n/a Red G 3 White Red Green J 4 White Green Blue L 5 White Blue Yellow N 6 Black Yellow Gray Q 7 Black Gray Orange S 8 Black Orange Actuator or Visi-Color Marking: Marking Color: STANDARD ROCKER BEZEL BARRIERS15 Threaded Insert, 2 per pole A 6-32 X 0.195 inches yes C ISO M3 x 5mm yes RECESSED OFF ROCKER14 Threaded Insert, 2 per pole E 6-32 x 0.195 inches yes F ISO M3 x 5mm yes PUSH-TO-RESET BEZEL13 Threaded Insert, 2 per pole B 6-32 x 0.195 inches yes D ISO M3 x 5mm yes G UL 489 Listed & CSA Certified J UL489 Listed, CSA Certified & TUV Certified (Gold Contacts)
Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com .558 [14.17] .960 [24.38] .311 DIA [Ø7.90] 16 | C-Series Handle – Circuit & Terminal Diagrams Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance ±.020 [.51] unless otherwise specified. 3 Available on Series Trip and Switch Only Circuits when called for on multi-pole units. Only one aux. switch is normally supplied, as viewed in mulit-pole identification scheme.
Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com | 17 C-Series Handle – Circuit & Terminal Diagrams Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance ±.020 [.51] unless otherwise specified. 3 Schematic shown represents current trip circuits. 4 Available only as special catalog number.
Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com 18 | C-Series Handle – Form & Fit Drawings Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance ±.020 [.51] unless otherwise specified.
Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com | 19 C-Series Handleguard – Form & Fit Drawings Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance ±.020 [.51] unless otherwise specified.
Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com 20 | C-Series Arc Chute Barrier UL Recognized/Listed – Form & Fit Drawings Notes: 1 Only 1-pole and 3-pole configurations shown. Arc chute (w/o barrier) and arc chute barrier also available for 2-pole construction. 2 Dimensions apply to all variations shown.
3 Notice that line and load terminal orientation for indicate on and indicate off rocker
circuit breakers are opposite. 4 Screw type terminals shown for Rocker style (CF1, C11, etc) circuit breakers. For other terminal configurations see circuit and terminal diagrams. 5 All dimensions are in inches [millimeters]. 6 Tolerance ± .020 unless otherwise specified. 7 Must be ordered under a special catalog number.
Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com | 21 C-Series Parallel Pole – Form & Fit Drawings Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance ±.020 [.51] unless otherwise specified.
Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com 22 | C-Series Sealed Toggle – Form & Fit Drawings Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance ±.020 [.51] unless otherwise specified.
Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com | 23 C-Series Rocker – Circuit & Terminal Diagrams Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance ±.020 [.51] unless otherwise specified. 3 Schematic shown represents current trip circuit.
Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com 24 | C-Series Rocker – Form & Fit Drawings Notes: 1 Dimensions apply to all variations shown. Notice that circuit breaker line and load terminal orientation on indicate OFF is opposite of indicate ON. 2 For pole orientation with horizontal legend, rotate front view clockwise 90°. 3 All dimensions are in inches [millimeters]. 4 Tolerance ±.020 [.51] unless otherwise specified.
Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com | 25 C-Series Flat Rocker – Form & Fit Drawings Notes: 1 For pole orientation with horizontal legend, rotate front view clockwise 90°. 2 All dimensions are in inches [millimeters]. 3 Tolerance ±.020 [.51] unless otherwise specified.
Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com 26 | Reps & Contact TX NM AZ CA NV UT CO WY MT ID WA OR OK AR LA MS AL GA FL TN NC VA SC DE NJ CT MA VT NH ME NY OH WV KY IN IL MO KS NE SD MN WI MI ND IA PA RI MD TEMCO Northwest Hanna Lind Ltd. Sierra LD. Allen Norris Pacent TSI North TSI DM Assoc EastDy-tronix Inc. Sunbelt Components Pinnacle Marketing Omega Limited Bridge Marketing Alaska, Hawaii Matera W. Canada Luscombe Engineering Signal Enterprises Matera E. Canada DM Michigan DM Mexico Mexico Matrix South America DM Assoc Melody Emery ProRep Solutions Authorized Sales Representatives About Carling Founded in 1920, Carling Technologies is a leading manufacturer of electrical and electronic switches and assemblies, circuit breakers, electronic controls, power distribution units, and multiplexed power distribution systems. With four ISO registered manufacturing facilities and technical sales offices worldwide, Carling Technologies Sales, Service and Engineering teams do much more than manufacture electrical components, they engineer powerful solutions! To learn more about Carling please visit www.carlingtech.com/company-profile. To view all of Carling’s environmental, quality, health & safety certifications please visit www.carlingtech.com/environmental-certifications Click on the group name on the map below to find your local representative or visit www.carlingtech.com/findarep. Americas Europe Middle East Africa Asia-Pacific Oceania MIDWEST NORTHERN SOUTHEAST LATIN AMERICA WEST
Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com Email: sales @carlingtech.com Application Support: team2@carlingtech.com Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com | 27 Notes
Carling Technologies, Inc. Phone: 860.793.9281 Fax: 860.793.9231 Email: sales@carlingtech.com Northern Region Sales Office: nrsm@carlingtech.com Southeast Region Sales Office: sersm@carlingtech.com Midwest Region Sales Office: mrsm@carlingtech.com West Region Sales Office: wrsm@carlingtech.com Latin America Sales Office: larsm@carlingtech.com Asia-Pacific Headquarters Carling Technologies, Asia-Pacific Ltd., Kowloon, Hong Kong Phone: Int + 852-2737-2277 Fax: Int + 852-2736-9332 Email: sales@carlingtech.com.hk Shenzhen, China: shenzhen@carlingtech.com Shanghai, China: shanghai@carlingtech.com Pune, India: india@carlingtech.com Kaohsiung, Taiwan: taiwan @carlingtech.com Yokohama, Japan: japan@carlingtech.com Europe | Middle East | Africa Headquarters Carling Technologies LTD
4 Airport Business Park, Exeter Airport,