PEL100 CHAUVINARNOUX | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 8

Technical content

67 WIFI 3G

y Ideal for all types of electrical cabinets and Low Voltage installations y Implementation without cutting off the mains power supply y Recording duration up to several months or years y Breakdown of energy losses PEL100, the loggers for efficient consumption! Power and energy loggers, simultaneously PEL 100 SERIES

100 SERIES100 SERIES

For sustainable, economical buildings, improve your energy efficiency In the context of a worldwide approach for protection of the environment, Europe has set itself the goal of reducing consumption by approximately 30%. Today, more than 50% of energy consumption occurs in the industrial sector and buildings. Optimization of energy consumption is therefore crucial to fulfil the regulatory requirements. The PEL100 models are power and energy measurement loggers for all electrical installations. The measurements are made by means of current sensors and voltage inputs. They can be used to view all the electrical parameters and take advantage of the measuring, energy metering and communication functions. They offer users all the measurements needed to carry out successful energy efficiency projects and ensure supervision of the electrical distribution system. The PEL100 family of energy meters makes it easy to add metering and measuring points in electrical cabinets affected by strong integration constraints. They are magnetized, so they are easy to position in any electrical cabinet without causing any difficulties once the cabinet is closed. The monitoring performed by the PEL100s provides the recordings to be compared with the period of reference. Monitoring and mapping of the consumption on a site PEL100 loggers catch every detail of the electrical consumption in a factory, workshop, building, agency, etc. They can be used simultaneously for real-time monitoring and comparative, historical consumption analysis. PEL Transfer software The PEL Transfer software can also provide a breakdown of the types of energy and their losses. Users have access to all the elements needed to establish the priority of their operations. y Useful energy y Active unbalance energy y Active harmonic energy y Non-active energy y Reactive energy y Distorting energy y Apparent energy Use in networks & centralized consumption management By setting up several PEL100s on a general electrical distribution system, for example, local authorities can control the different allocations of consumption, which is very practical for facilitating consumption management across a town district: street lighting network, lighting network for common areas, general single-phase distribution, three-phase distribution. Measuring the savings The recordings made with the PEL100 measuring instruments are time/date-stamped. This makes it very simple to measure the gain achieved by comparing the recordings before and after modifications to an installation. The analysis of the recording made with the PEL100s before the modifications corresponds to the period of reference. Various operations such as maintenance or improvement of the electrical network or equipment can then be carried out. A correctly-positioned PEL100 will help you quickly pinpoint the areas where work is required, without wasting any time. A period of monitoring will help to show whether the solutions applied are sufficient and above all to measure the savings achieved. The monitoring performed by the PEL100s provides the recordings to be compared with the period of reference.

APPLICATIONSAPPLICATIONS APPLICATIONSAPPLICATIONS Analogue measurements The PEL106 can be used to identify each of the dysfunctions by recording external parameters such as the pressure, temperature etc. Via its Bluetooth wireless link, it communicates with remote L452 dataloggers. The PEL106’s recording function can integrate up to 2 x 4 analogue channels. The analogue channels complement the voltage, current and power measurements. Energy consumption of a transformer station, etc. When used with remote L452 loggers, the PEL106 records analogue measurements (external parameters, up to 2 x 4 channels) such as the temperature, pressure, etc. It used to analyse for example electrical transformer station. Renewable energy The PEL106’s analogue measurement function offers the possibility of linking electricity generation to a wind speed or a hydro-electric current to a flow-rate. It meets the requirements of the applications in the renewable energies sector, such as metering the energy linked to the strength of the wind, for example. The PEL106 accurately measures the energy efficiency of wind turbines, which depend on the wind speed, or hydro-electric dams, which depend on the water flow-rate, etc. Advantages of the ANDROID application Users can view the measurement results in real time on their ANDROID devices. The application is multilingual. Available for download free of charge.

ALL THE PEL100 MODELS ARE EQUIPPED WITH MULTIPLE COMMUNICATION MODES: ETHERNET AND USB PORTS, AS WELL AS BLUETOOTH. The PEL104 and PEL106 also offer Wifi communication and 3G/GPRS. The 3G/GPRS mode allows users to insert a SIM card in the PEL for remote connection via a GPRS-3G link. It is also possible to access a PEL104 or PEL106 via an IRD server. In this way, when an alarm is triggered, the user can automatically receive an email for real-time notifications. WiFi The PEL104 and PEL106 are equipped with a Wifi interface. This means they are accessible from any PC by means of the PEL Transfer software. The PEL104 and PEL106 can be configured as a Wifi access point operating on the 2.4 GHz radio frequency band, allowing you to monitor the measurements in real time with a PC, smartphone, tablet, ... GPRS As measurement campaigns are usually spread over a period of several days or weeks, it is important to check that the measurements are proceeding correctly. With their SIM card, the PEL104 and PEL106 communicate remotely, saving you time because you no longer have to go from one logger to the next to check each one. This makes it easy to recover the 10-minute consumption data on an electrical feeder. IRD Server By positioning PEL100s on the different electrical feeders, it is possible and even simple to size the relative weight of each line in terms of overall consumption, define a load profile for the installation and thus determine the priorities for the improvements to be made. When access to the PEL100 is complex because of the protective systems on today’s IT systems, and when you’re far from the logger, our solution lets you view the measurements remotely, via internet, without endangering the existing protective IT systems. PC & PEL Transfer software IRD SERVER PEL 104/106 GPRS IP ULTRA-COMMUNICATINGULTRA-COMMUNICATING

ALL THE PEL100 MODELS ARE EQUIPPED WITH MULTIPLE COMMUNICATION MODES: ETHERNET AND USB PORTS, AS WELL AS BLUETOOTH. The PEL104 and PEL106 also offer Wifi communication and 3G/GPRS. The 3G/GPRS mode allows users to insert a SIM card in the PEL for remote connection via a GPRS-3G link. It is also possible to access a PEL104 or PEL106 via an IRD server. In this way, when an alarm is triggered, the user can automatically receive an email for real-time notifications. Bluetooth Bluetooth enables the PEL100 models to communicate with a smartphone or gain access to the analogue channels. Ethernet When possible, the PEL100 models can be connected together by means of an Ethernet-type wire link. Android Verification of the connections and real-time display of the measurements LAN GPRS WIFI ULTRA-COMMUNICATINGULTRA-COMMUNICATING LAN

Current sensors compatible with the PEL 100 models Measurements & functions The PEL100 power and energy loggers perform the following measurements: y RMS and DC measurements with 128 samples/cycle – simultaneously on each phase y AC and/or DC voltages up to 1,000 V y Analogue measurements y Measurements on motors y Self-powering via the phase y Current up to 10 kA AC or 5 kA DC (depending on the current sensor). y The PEL100 models offer a wider measurement range by using voltage and current ratios (up to 650,000 V / 25,000 A) y Power values from 10 W/var/VA to 10 GW/Gvar/GVA y Energy values up to 4 EWh / 4 EVAh / 4 Evarh & total energy (4 quadrants) y Breakdown of energy losses y Phase data: cos φ, tan Φ, power factor (PF) y Crest factor y THD calculation for currents and voltages y Harmonics up to the 50th order for currents and voltages y DC, 50 Hz, 60 Hz and 400 Hz measurements y Recording of the measurements and calculation results on the SD card y Automatic recognition of the type of sensors connected y Numerous network types supported: split-phase, three-phase with or without neutral, etc. y Communications: USB, Bluetooth, Ethernet, Wifi, GSM 3G, GPRS y Software for data transfer, real-time communication with a PC and report generation Voltage Current Power/P.F THD Power/Tan Partial energyTotal energy Configure your preferred communication mode directly in the instrument. Setup

E3N PAC93 A193-450 A193-800 C193 J93 MA196 A196-610 Measurement range 500 mA to 200 Aac 0,005 Aac to 5 Aac 0,2 Aac to 100 Aac 200mA to 10kAac 50 mA to 10 Aac/dc 100 mA to 100 Aac/dc

1 A to 1000 Aac

1 A to 1300 Adc

50 A to 3500 Aac

50 A to 5000 Adc

Clamping Ø / length 20 mm 20 mm Ø 70/250 mm Ø 100/350 mm Ø 300/1000 mm 11.8 mm 1 x Ø 39 mm 2 x Ø 25 mm Ø 140 mm / 450 mm Ø 70/250 mm / 800 mm 52 mm 72 mm Ø 100 mm / 350 mm Ø190mm/ 610mm IEC 61010 600 V caT III /

300 V caT IV

600 V caT III /

1000 V caT III /

600 V caT IV 600 V caT IV 600 V caT III /

600 V CAT IV

This application software lets you: y Configure the PEL100 y Check the connections before starting to record y Download the measurements recorded in the PEL100 y View the various measurement results and analyses With the comprehensive DataView® processing software, it is also possible to create certified or customized reports. In this way, DataView® helps you to generate your energy consumption reports more easily. Our PEL Transfer software performs mathematical processing on the power measurement campaigns and automatically breaks down all the losses detected. Configuration of alarms Configuration of L452 loggers Configuration of IRD Server Current sensors compatible with the PEL 100 models

Unit 1 Nelson Ct, Flagship Sq, Shaw Cross Business Pk Dewsbury, West Yorkshire - WF12 7TH Tel: +44 1924 460 494 Fax: +44 1924 455 328 info@chauvin-arnoux.co.uk www.chauvin-arnoux.com Middle East Chauvin Arnoux Middle East P .O. BOX 60-154 1241 2020 JAL EL DIB - LEBANON Tel: +961 1 890 425 Fax: +961 1 890 424 camie@chauvin-arnoux.com www.chauvin-arnoux.com FRANCE Chauvin Arnoux 12-16 rue Sarah Bernhardt

92600 Asnières-sur-Seine

Tel: +33 1 44 85 44 38 Fax: +33 1 46 27 95 59 export@chauvin-arnoux.fr www.chauvin-arnoux.com 906211637- Ed. 2 - 02/2021 -Non-contractual document. Please confirm specifications before ordering. REFERENCES TO ORDER: ACCESSORIES: STATE AT DELIVERY: PEL102 or PEL103 delivered with: 1 carrying bag, 4 measurement cables (straight-banana/straight-banana 3 m long - black), 4 crocodile clips (black), 1 set of plugs (for the extremities of the cables and current sensors), 1 mains cable, 1 x 8 GB SD card, 1 USB cable, 1 SD –USB adapter, PC software (PEL Transfer), 1 user’s manual (on CD), 1 safety datasheet, 1 quick start guide. PEL104 with: 1 carrying bag, 4 voltage cables, 4 crocodile clips, 1 set of rings/inserts, 1 x 600 V mains adapter, 1 SD card, 1 SD - USB adapter, 1 USB cable, PC PEL TRANSFER software & user’s manual to download from the website, 1 quick start guide. PEL106 with: 1 bag for the accessories, 5 x IP67 voltage cables, 5 lockable crocodile clips, 1 set of rings/inserts, PC software (PEL Transfer), 1 SD card, 1 SD -USB adapter,

1 USB cable, PC PEL TRANSFER software & user’s manual to download from

the website, 1 quick start guide. Models PEL102 PEL103 PEL104 PEL106 Display None With quadruple digital display Types of installations Single-phase, split-phase, three-phase with or without neutral, and many other specific configurations Number of channels 3 voltage inputs, 3 current inputs (calculated neutral current) 4 voltage inputs, 4 current inputs Measurements Network frequency DC, 50 Hz, 60 Hz and 400 Hz Voltage (measurement ranges) 10.00 -1,000 Vac/dc Current (depending on sensors) (measurement ranges) 5 mAac to 10 kAac / 50 mAdc to 1.4 kAdc Calculated measurements Ratio Up to 650,000 V / up to 25,000 A Power 10 W to 10 GW / 10 var to 10 Gvar / 10 VA to 10 GVA Energy Up to 4 EWh / 4 EVAh / 4 Evarh (E = 10 18) Phase cos φ, tan Φ, PF Harmonics THD Additional functions Phase sequence Yes Min / Max Yes Mounting Magnet Hook (option) Recording Sampling / Acquisition interval / Aggregation 1 measurement/s - from 1 min to 60 min 5 measurements/s - from 1 min to 60 min Memory SD card, 8 GB (SD-HC card up to 32 GB) Communication Ethernet, Bluetooth and USB Ethernet, Bluetooth, USB, Wifi and GPRS Power supply 110 V - 250 V (+10 %, -15 %) @ 50-60 Hz & 400 Hz Power supply via the phase 1,000 V AC/DC Safety IEC 61010 600 V CA T IV and 1 000 V CA T III IEC 61010 1000 V CAT IV Mechanical specifications Dimensions 256 x 125 x 37 mm without sensor 245 x 270 180 mm without sensor Weight 900 g 950 g 900 g <3400 g Casing IP54 IP67 SPECIFICATIONS L452 logger Mains adapter