Features
- Listed under ANSI/UL ® Standard 864 9th Edition.
- IBC Seismic Certified.
- 120 or 240 VAC (optional) input line voltage.
- Front panel programming with day/night sensitivity adjustments.
- 80-character alpha-numeric display.
- One Style 4 (Class “B”) signaling line circuit. Style 6 (Class “A”) with optional CAOM Module.
- Two Style Y (Class “B”) regulated notification appliance circuits rated for 1.5 amp each. Style Z (Class “A”) with optional CAOM Module.
- F M / U L ® Listed for Pre-action/Deluge with optional MCOM Module.
- Periodic trouble reminder.
- Individual sensor drift compensation.
- Dual-stage maintenance alerts (“dirty” and “very dirty”).
- Multilevel sensor sensitivit y adjustments (front panel programmable).
- Alarm verification per individual sensor.
- Positive alarm sequence for sensors or monitor modules. continued on the next page
7100 Series
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9020-0466 Rev. N page 2 of 3 www.gamewell-fci.com Optional Accessories LCD-7100 The LCD-7100 remote serial display offers an 80-character alphanumeric readout for the remote display of all system events. It duplicates all the information on the 7100 Series panel display and provides ke y switch protected functions such as System Reset, Alarm Acknowledge, Trouble Acknowledge, Signal Silence, and Drill Test. LEDs on the LCD-7100 indicate Alarm, Supervisory, Sys- tem Trouble, Power Fault, Systems Silenced, NAC#1, and NAC#2 Silenced conditions. The LCD-7100 can be surface or semi-flush mounted on a standard four-gang electrical box. It can be installed up to 3,000 feet (914.4 m) from the main control panel. The 7100 Series fire alarm control panel supports up to five remote LCD-7100 annunciators using one pair of twisted, non- shielded 18 AWG min. wire or serial communication and uses another pair of 16 AWG min. for operating voltage. (For additional information, refer to the LCD-7100 data sheet, Part Number: 9020-0486). RAN-7100 The RAN-7100 maintains the same character display as the 7100 Series. The RAN-7100 is mounted in a RAN2-BB backbox for surface or flush mounting retrofits. (For additional information, refer to the Gamewell Retrofit Kits Data Sheet, P/N: 9020-60678). CAOM The Class “A” Optional Module (CAOM) allows Style Y and Z (Class “B” and “A”) operation for both Notification Appli- ance Circuits and allows Style 4 and 6 (Class “B” and “A”) for the Signaling Line Circuit. It also provides a disconnect switch for the signaling line circuit and a common discon- nect switch for both notification appliance circuits. MCOM The Municipal Connection Option Module (MCOM) pro- vides three choices of outputs. It can be configured as a Municipal Circuit (City Box) output. It may also be set to serve as a Reverse Polarity output with a nominal voltage output of 24 VDC at 0.012 amp maximum alarm and supervisory current. The MCOM’s third option provides a releasing solenoid output rated at:
- 24 VDC nominal voltage.
- 0.005 amp supervisory current.
- 0.710 amp maximum alarm current.
- 2 ohms maximum line resistance. PTRM The Printer Transient Module (PTRM) provides RS-232 Isolator/Transient protection for the 7100’s RS-232 port (BSM connector J2). It is used in conjunction with a serial printer applied to the RS-232 port for permanent record keeping. INI-7100 The Intelligent Network Interface Module allows the 7100 Series fire alarm control panel to become the platform of a peer-to-peer, token ring, self-regenerative network com- prised of up to 64, 7100 panels. Features (Continued)
- Four levels of system access using six digit passwords with up to five user passwords per Level.
- Duplicate and extra address indications.
- March time (60 or 120 BPM)/temporal pattern/coded fours/California Code/user-defined zone coding.
- Cross zoning.
- System configuration prog ramming and 280 event log stored in non-volatile memory.
- Fan restart with sequential restart delay.
- Upload/download of panel configuration between panel and CAMWorks program (password protected feature).
- Up to 64, 7100 panels in the E3 Broadband network with an optional INI-7100 Module. Specifications Primary Input Power 120 VAC, 50/60 Hz @ 2.0 amps. or 240 VAC, 50/60 Hz @ 1.0 amp Output Power 3.335 amps. @ 24 VDC (total) Non-resettable Power: 1.0 amp max. Resettable Power: 1.0 amp max. 1.0 amp max. from both power circuits Two Notification Appliance Circuits: 1.5 amp each @ 24 VDC Current: Supervisory Alarm 7100-1 (One SLC) 0.065 amp 0.085 amp 7100-1D (One SLC w/DACT) 0.075 amp 0.095 amp LCD-7100 0.050 amp 0.075 amp INI-7100-UTP,-FO 0.040 amp 0.040 amp Operating Temperature: 32° - 120° F (0° - 49° C) Relative Humidity: 93 % (non-condensing) Battery Charger Capacity: 31 A/H (Cabinet accommodates
12 A/H size batteries)
Alarm & Trouble Relay Contacts: Form “C”, 2 amps. @ 24 VDC (resistive)
www.gamewell-fci.com 9020-0466 Rev. N page 3 of 3
Ordering Information
7100-1-PNL 7100 Addressable FACP, 1 SLC mounted in the 7100-CAB enclosure, red 7100-1D-PNL 7100 Addressable FACP w/DACT, One SLC mounted in 7100-CAB enclosure, red Basic Kits 1100-1313 Basic System Kit, 2 SLC, 240 VAC Optional Modules LCD-7100 Remote Serial Annunciator, LCD Display (80-character). Dimensions: 4.25” H x 8.25” W x 1.90” (43 H x 37 W x 7.7 D cm) RAN-7100 Remote Series Annunciator, LCD Display (80-character). Dimensions: 10” W x 5 1/4” H x 2 7/16” D (25 1/4 W x 13 1/3 H x 6 9/10 D cm) CAOM Class A Option Combination Module with disconnect switches for both signaling line circuits and notification appliance circuits. MCOM Municipal Connection Option Module for local energy city box reverse polarity sig- naling, or releasing solenoid. PTRM Printer Transient Module. INI-7100-FO Intelligent Network Interface Module, Fiber-Optic. INI-7100-UTP Intelligent Network Interface Module, Unshielded, Twisted-Pair. Ordering Information (Continued) Replacement Parts Part Number Description BSM-7100-1 Replacement board for 7100-1 BSM-7100-1D Replacement board for 7100-1D BSM-7100-2 Replacement board for 7100-2 BSM-7100-2D Replacement board for 7100-2D Seismic Battery Bracket Kits 90516 7100-Slim 7 A/H Seismic Battery Bracket kit E3 B-Slim 7 A/H Seismic Battery Bracket Kit 90517 7100-Slim 12 A/H Seismic Battery Bracket Kit E3 B-Slim 12 A/H Seismic Battery Bracket Kit
90518 NetSOLO 7100 7 A/H Seismic Battery
For additional information on the Seismic Battery Brackets, refer to the following documents:
- Seismic Battery Bracket Installation Guide, P/N: 53839
- E3 Series Cabinets Data Sheet, P/N: 9020-0649