discrete module X80 - 8 NO/NC Type C - Isolated relays - 125 V DC/250 V AC BMXDRC0805 Main Range of product Modicon X80 Product or component type Relay discrete output module Discrete output number 8 conforming to EN/IEC 61131-2 Discrete output logic Positive or negative Complementary Electrical connection 40 ways terminal block Network frequency 50/60 Hz Network frequency limits 47…63 Hz Sensor power supply 5...150 V 19...264 V [Ith] conventional free air thermal current

4 A 40 °C

3 A 50 °C

2 A 60 °C

Insulation resistance > 10 MOhm 500 V DC Power dissipation in W 3.6 W Response time on output <= 10 ms activation <= 13 ms deactivation Typical current consumption 40 mA at 3.3 V DC 101 mA at 24 V DC MTBF reliability 2683411 H Protection type External short-circuit protection External overload protection External overvoltage protection, inductive AC network External overvoltage protection, inductive DC network Output overload protection Use 1 fast blow fuse per channel or group of channel Output overvoltage protection Use discharge diode on each output DC Use RC circuit on each output AC Use ZNO surge limiter on each output AC Output short-circuit protection Use 1 fast blow fuse per channel or group of channel Minimum switching current 10 mA 5 V DC Electrical durability AC-12: 200000 cycles at 48 VA 24 V at 0…60 °C AC-12: 300000 cycles at 48 VA 48 V at 0…60 °C AC-12: 150000 cycles at 96 VA 48 V at 0…60 °C AC-12: 300000 cycles at 110 VA 100...120 V at 0…60 °C AC-12: 150000 cycles at 220 VA 100...120 V at 0…60 °C Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications Apr 18, 2022

AC-12: 300000 cycles at 220 VA 200...250 V at 0…60 °C AC-12: 150000 cycles at 500 VA 200...250 V at 0…60 °C AC-15: 700000 cycles at 10 VA 24 V at 0…60 °C (load factor 0.4) AC-15: 500000 cycles at 24 VA 24 V at 0…60 °C (load factor 0.4) AC-15: 200000 cycles at 48 VA 24 V at 0…60 °C (load factor 0.4) AC-15: 700000 cycles at 10 VA 48 V at 0…60 °C (load factor 0.4) AC-15: 500000 cycles at 24 VA 48 V at 0…60 °C (load factor 0.4) AC-15: 300000 cycles at 48 VA 48 V at 0…60 °C (load factor 0.4) AC-15: 100000 cycles at 96 VA 48 V at 0…60 °C (load factor 0.4) AC-15: 1000000 cycles at 10 VA 100...120 V at 0…60 °C (load factor 0.4) AC-15: 300000 cycles at 50 VA 100...120 V at 0…60 °C (load factor 0.4) AC-15: 200000 cycles at 110 VA 100...120 V at 0…60 °C (load factor 0.4) AC-15: 70000 cycles at 220 VA 100...120 V at 0…60 °C (load factor 0.4) AC-15: 1000000 cycles at 10 VA 200...250 V at 0…60 °C (load factor 0.4) AC-15: 500000 cycles at 50 VA 200...250 V at 0…60 °C (load factor 0.4) AC-15: 200000 cycles at 110 VA 200...250 V at 0…60 °C (load factor 0.4) AC-15: 150000 cycles at 220 VA 200...250 V at 0…60 °C (load factor 0.4) DC-12: 200000 cycles at 24 W 24 V at 0…60 °C DC-12: 150000 cycles at 48 W 24 V at 0…60 °C DC-12: 150000 cycles at 40 W 48...60 V at 0…60 °C DC-12: 100000 cycles at 45 W 100...125 V at 0…60 °C DC-13: 100000 cycles at 10 W 24 V at 0…60 °C DC-13: 60000 cycles at 24 W 24 V at 0…60 °C DC-13: 40000 cycles at 48 W 24 V at 0…60 °C DC-13: 40000 cycles at 40 W 48...60 V at 0…60 °C DC-13: 100000 cycles at 15 W 100...125 V at 0…60 °C Status LED 1 LED (green)RUN

1 LED per channel (green)channel diagnostic

1 LED (red)ERR

1 LED (red)I/O

Net weight 0.189 kg Environment IP degree of protection IP20 Dielectric strength 1780 V AC at 50/60 Hz 1 min Vibration resistance 3 gn Shock resistance 30 gn Relative humidity 0…95 % at 0…60 °C without condensation Operating altitude 0...2000 m 2000...5000 m with derating factor Packing Units Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Weight 332.0 g Package 1 Height 5.5 cm Package 1 width 18 cm Package 1 Length 26 cm Unit Type of Package 2 S03 Number of Units in Package 2 8 Package 2 Weight 2.656 kg Package 2 Height 30 cm Package 2 width 30 cm Package 2 Length 40 cm Offer Sustainability Sustainable offer status Green Premium product REACh Regulation REACh Declaration EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope) EU RoHS Declaration Apr 18, 2022

RoHS exemption information Yes China RoHS Regulation China RoHS declaration Environmental Disclosure Product Environmental Profile Circularity Profile End of Life Information WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov Apr 18, 2022

(1) Front view (2) Right view (3) Top view Apr 18, 2022

(1) Module (2) Output (3) Command (4) Pre-actuator (5) Power supply NO : Normally open output NC : Normally closed output Module Connection (1) Pre-actuator (3) Fuse : Use appropriate fast-blow fuse for each relay (4) We recommend installing this type of protection on the terminals of each pre-actuator N/C : Not connected Apr 18, 2022