Edition • 2023-07-21T16:03:46+02:00 BL Compact Fieldbus Station for EtherCAT Interface for Connection of 2 BL ident Read/Write Heads (HF/ UHF) BLCEC-2M12MT-2RFID-S Type BLCEC-2M12MT-2RFID-S ID 6811630 Nominal system voltage 24 VDC System power supply Via auxiliary power Voltage supply connection 2 x M12, 5-pin Admissible range Vi 18…30 VDC Nominal current Vi 125 mA Max. current Vi 1 A Admissible range Vo 18…30 VDC Max. current Vo 4 A Fieldbus transmission rate 100 Mbps Fieldbus address range 0 × 00 (automatic assignment) 0 × 01…0 × FF (fixed assignment) Fieldbus addressing 2 hexadecimally coded rotary switches Fieldbus connection technology 2 × M12 4-pole, D-coded Service interface Ethernet Technology Signal type Simple RFID interface Number of channels 2 Sensor supply 0.5 A per channel, short-circuit proof Simultaneity factor 1 Transmission rate 115.2 kbps Cable length 50 m Electrical isolation isolation of electronics and field level via optocou- plers ■ On-machine Compact fieldbus I/O block ■ EtherCAT™ slave ■ Integrated Ethernet Switch ■ Two 4-pole M12, D-coded, connectors for fieldbus connection ■ Auto and Fixed addressing ■ IP67, IP69K ■ M12 I/O connectors ■ LEDs indicating status and diagnostics ■ Electronics galvanically separated from the field level via optocouplers ■ Simple RFID interface ■ Connection of 2 BL ident® read/write heads ■ Max cable length of 50 m

Edition • 2023-07-21T16:03:46+02:00 Dimensions 113 x 71 x 32.5 mm Mounting 2 × 5.4 mm diameter holes, 1.7 Nm torque Weight 360 ± 20 g Housing material Glass-filled nylon, nickel plated brass connectors Housing color Black Material screw Nickel-plated brass Material label Polyester with polycarbonate overlay Ground label material Nickel plated brass Protection class IP67 IP69K Ambient temperature -40…+70 °C Storage temperature -40…+85 °C Relative humidity 15 to 95% (non-condensing) Vibration test Acc. to IEC 61131-2 - up to 20 g (at 10 up to 150 Hz) For mounting on base plate or machinery Shock test according to IEC 61131-2 Electromagnetic compatibility Acc. to IEC 61131-2 MTTF 110 years MTTF note acc. to SN 29500 (Ed. 99) 20 °C Approvals and certificates CE, cULus

Edition • 2023-07-21T16:03:46+02:00 Pinning and wiring diagram EtherCAT Fieldbus cable (IP67 example): RSSD RSSD 441-2M ID number U-02482 or RSSD-RSSD-441-2M/S2174 ID number 6914218 Pin assignment (M12, D-coded) RFID Channels Extension cable (example): RK 4.5T-2-RS 4.5T/S2501 ident-no. U3-01243 or RK4.5T-2-RS4.5T/S2500 ident-no. 6699200 …/S2500 Connectors …/S2501 Connectors Auxiliary Power Extension cable (example): RKC 4.4T-2-RSC 4.4T ident-no. U5264 or RKC4.4T-2-RSC4.4T/TEL ident-no. 6625208 Pin Assignment

Edition • 2023-07-21T16:03:46+02:00 Station LED status LED Color Status Description IOs OFF No power RED ON Low power or station error RED FLASHING (1 Hz) I/O module configuration error RED FLASHING (4 Hz) No I/O module bus communication GREEN ON Station ok GREEN FLASHING Force mode active OFF Port Closed, No Link, No Activity GREEN ON Port Open, Link Established, No Activity LNK/ACT GREEN FLICKERING Port Open, Link Established, Activity Present OFF Device is in state INIT GREEN BLINKING Device is in state PRE-OPERATIONAL GREEN SINGLE FLASH Device is in state SAFE-OPERATIONAL GREEN ON Device is in state OPERATIONAL RUN GREEN FLICKERING Device is in state BOOTSTRAP RED DOUBLE FLASH Sync Manager Watchdog timeout RED SINGLE FLASH State changes from Op to SafeOpError (synchronization error) RED BLINKING State change not possible (invalid register/object settings/hardware config.) ERR RED OFF No EtherCAT comm errors I/O LED status LED Color Status Description D * OFF No diagnostics active RED ON Station error/ module bus communication failure RED FLASHING (0.5Hz) Diagnostics active RW0 / RW1 OFF No tag present, no diagnostics active GREEN ON Tag present GREEN FLASHING (2 Hz) Data communication from / to tag active RED ON Error in the R/W head RED FLASHING (2 Hz) Short circuit in the transceiver supply * D LED also indicates gateway diagnostics

Edition • 2023-07-21T16:03:46+02:00 I/O Data Map INPUT BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 Done Busy Error Trans. Conn. Trans. On TP TFR - 1 Error Cat. (Category Code) 2 Error Desc. (Description Code) 3 - - - - - - - - RFID 10 4…11 Read Data (8 Byte) 12 Done Busy Error Trans. Conn Trans. On TP TFR - 13 Error Cat. (Category Code) 14 Error Desc. (Description Code) 15 - - - - - - - - RFID 11 16…23 Read Data (8 Byte) OUTPUT BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 Transceiver Next Tag ID Read Write Tag Info. Trans. Info. Reset 1 - - - - - Byte Count 2 Byte Count 1 Byte Count 0

2 Address High Byte (MSB)

3 Address Low Byte (LSB)

4…11 Write Data (8 Byte) 12 Transceiver Next Tag ID Read Write Tag Info. Trans. Info. Reset 13 - - - - - Byte Count 2 Byte Count 1 Byte Count 0

14 Address High Byte (MSB)

15 Address Low Byte (LSB)

16…23 Write Data (8 Byte)