Edition • 2023-07-21T16:15:23+02:00 BL67 electronic module 8 Digital Outputs, PNP, 0.5 A BL67-8DO-0.5A-P Type BL67-8DO-0.5A-P ID 6827172 Number of channels 8 Supply voltage 24 VDC Nominal voltage Vo 24 VDC Nominal current from field supply ð 100 mA Nominal current from module bus ð 30 mA Max. sensor supply Isens 4 A electronically limited current supply via gateway or power feed max. load current Io 10 A via gateway or power feed Power dissipation, typical ð 1.5 W Output connectivity M8, M12, M23 Output type PNP Output voltage 24 VDC Output current per channel 0.5 A Output delay 3 ms Load type resistive, inductive, lamp load Load resistance, resistive > 48 ò Load resistance, inductive < 1.2 H Lamp load < 3 W Switching frequency, resistive < 200 Hz Switching frequency, inductive < 2 Hz Switching frequency, lamp load < 20 Hz Short-circuit protection yes Simultaneity factor 1 Electrical isolation electronics for the field level Number of diagnostic bits 8 ■ Independent of the fieldbus and connection technology used ■ Protection class IP67 ■ LEDs indicate status and diagnostic ■ Electronics galvanically separated from the field level via optocouplers ■ 8 digital outputs, 24 VDC ■ Max. 0.5 A ■ PNP switching ■ From version VN 01-07 and higher, the module supports accelerated start-up for applications with Fast Start-Up (FSU) and QuickConnect (QC). Functional principle BL67 electronic modules are plugged on the purely passive base modules which in turn are connected to the field devices. The separa- tion of connection level and electronics sim- plifies maintenance considerably. Flexibility is enhanced because the user can choose be- tween base modules with different connection technologies. The electronic modules are completely inde- pendent of the higher level fieldbus through the use of gateways.

Edition • 2023-07-21T16:15:23+02:00 Dimensions (W x L x H) 32 x 91 x 59 mm Approvals CE, cULus Ambient temperature -40…+70 °C Temperature derating < 0 °C Ambient temperature Support for version VN 01-03 and higher, no limita- tion > 55 °C Steady ambient air Simultaneity factor 0.5 Storage temperature -40…+85 °C Relative humidity 5…95 % (internal), level RH-2, no condensation (when stored at 45 °C) Vibration test Acc. to EN 61131 - up to 5 g (at 10 to 150 Hz) for mounting on DIN rail no drilling according to EN 60715, with end bracket - up to 20 g (at 10 up to 150 Hz) for mounting on base plate or machinery Therefore every second module has to be mounted with two screws each. Shock test Acc. to IEC 60068-2-27 Drop and topple acc. to IEC 68-2-31 and free fall to IEC 68-2-32 Electromagnetic compatibility Acc. to EN 61131-2 Protection class IP67 Tightening torque fixing screw 0.9…1.2 Nm

Edition • 2023-07-21T16:15:23+02:00 Compatible base modules Dimension drawing Type Pin configuration BL67-B-8M8 6827188 8 x M8, 3-pole, female Comments Matching connection cable (for example): PKG3M-2-PSW3M/TXL Ident-No. 6625668 Pin Assignment Wiring Diagram BL67-B-4M12 6827187 4 x M12, 5-pole, female Comments Matching connection cable (for example): RKC4.4T-2-RSC4.4T/TXL Ident-No. 6625608 BL67-B-4M12-P 6827195 4 x M12, 5-pole, female, paired Comments Matching connection cable (for example): RKC4.4T-2-RSC4.4T/TXL Ident-No. 6625608 Pin Assignment Wiring Diagram BL67-B-1M23 6827213 1 x M23, 12-pole, female Comments field-wireable connector (for example): FW-M23ST12Q-G-LT-ME-XX-10 Ident-No. 6604070 Pin Assignment

Edition • 2023-07-21T16:15:23+02:00 LED display LED Color Status Meaning D OFF No error message or diagnostics active. RED ON Failure of module bus communication. Check if more than 2 adja- cent electronic modules are pulled. Relevant modules are located between gateway and this module. RED FLASHING (0.5 Hz) Upcoming module diagnostics DO channel OFF Status of channel x = „0“ (OFF), no diagnostics active 0...7 GREEN ON Status of channel x = „1“ (ON) RED ON Short circuit / overload on channel x

Edition • 2023-07-21T16:15:23+02:00 Data mapping DATA BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Output m DO 7 DO 6 DO 5 DO 4 DO 3 DO 2 DO 1 DO 0 n = Offset of input data; depending on extension of station and the corresponding fieldbus. m = Offset of output data; depending on extension of station and the corresponding fieldbus. With PROFIBUS, PROFINET and CANopen, the I/O data of this module is localized within the process data of the whole station via the hardware configuration tool of the fieldbus master. With DeviceNet™, EtherNet/IP™ and Modbus TCP a detailed mapping table can be created with the TURCK configuration tool I/O-ASSISTANT. Pin assignment at corresponding base module: DATA BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 BL67-B-8M8 Output m C7 P4 C6 P4 C5 P4 C4 P4 C3 P4 C2 P4 C1 P4 C0 P4 BL67-B-4M12 Output m C3 P2 C2 P2 C1 P2 C0 P2 C3 P4 C2 P4 C1 P4 C0 P4 BL67-B-4M12-P Output m C3 P2 C3 P4 C2 P2 C2 P4 C1 P2 C1 P4 C0 P2 C0 P4 BL67-B-1M23(-VI) Output m C0 P8 C0 P7 C0 P6 C0 P5 C0 P4 C0 P3 C0 P2 C0 P1 C… = slot no., P… = pin no.